1. Introduction
Thank you for choosing the PowMr MPPT series solar charge controller. This manual provides important safety, installation, operation, and troubleshooting instructions to ensure optimal performance and longevity of your solar system.
The PowMr MPPT solar charge controller utilizes advanced Maximum Power Point Tracking (MPPT) technology, achieving up to 99.9% tracking efficiency and ≥98% conversion efficiency. It is designed for various solar applications including off-grid homes, RVs, and marine systems.
Key features include:
- Built-in DSP controller for high performance.
- Automatic recognition for 12V, 24V, 36V, and 48V battery banks.
- 3-stage charging algorithm (Bulk, Absorption, Float) to optimize battery performance and prolong lifespan.
- Compatibility with various battery types: Sealed Lead-Acid, Flooded Lead-Acid, Gel, LiFePO4 (L04/08/15/16), and user-defined settings.
- Comprehensive electronic protections: Reverse Current, Reverse Polarity, Overload, Short Circuit, Overcharging, Over-Discharging, and Over-Temperature.
- Backlight LCD display with 4 keys for real-time data monitoring and easy configuration.
- Easy wall-mounting installation.
2. Important Safety Instructions
Please read all instructions and cautions carefully before installation and operation. Save these instructions for future reference.
2.1 General Safety Information
- Read all instructions and cautions in this manual before beginning installation.
- There are no serviceable parts for this controller. Do NOT disassemble or attempt to repair the controller.
- Do NOT allow water to enter the controller.
- Ensure all connections going into and from the controller are tight.
2.2 Charge Controller Safety
- WARNING: NEVER connect the solar panel array to the controller without a battery. The battery MUST be connected first.
- Ensure input voltage does not exceed 190 VDC to prevent permanent damage. Use the Open Circuit Voltage (Voc) to ensure the voltage does not exceed this value when connecting panels together.
- WARNING: Do NOT connect any inverters or battery chargers into the load terminal of the charge controller.
- WARNING: Once equalization is active in battery charging, it will not exit this stage unless there is adequate charging current from the solar panel. There should be NO load on the batteries during the equalization charging stage.
2.3 Battery Safety
- Use only sealed lead-acid, flooded, gel, or lithium batteries that are deep cycle.
- Explosive battery gases may be present while charging. Ensure adequate ventilation to release these gases.
- Be careful when working with large lead-acid batteries. Wear eye protection and have fresh water available in case of contact with battery acid.
- Carefully read battery manuals before operation.
- Do NOT let the positive (+) and negative (-) terminals of the battery touch each other.
- Recycle batteries when they are replaced.
- Over-charging and excessive gas precipitation can damage battery plates and cause material shedding. Too high or too long an equalizing charge may cause damage. Review specific requirements of your battery system.
- Equalization is for non-sealed/vented/flooded/wet cell lead-acid batteries only.
- Do NOT equalize VRLA type AGM/Gel/Lithium cell batteries UNLESS permitted by the battery manufacturer.
3. Setup and Installation
This section details the physical installation and wiring of your MPPT solar charge controller.
3.1 Dimensions
The dimensions of the HHJ-60A model are approximately 214mm x 115mm x 50mm (8.43in x 4.53in x 1.97in). Please refer to the specifications section for other models.
3.2 Installation Notes
- Use only the provided screws for mounting. Using other screws may damage the internal PCB.
- Apply proper torque when tightening screws to avoid damaging the internal PCB.
- Ensure a space of approximately 5.91 inches (15 cm) around the controller for proper ventilation.
3.3 Wiring Procedure
IMPORTANT: You must strictly follow the wiring sequence of “connect the battery first, then the PV array, and finally the load.” It is strictly prohibited to connect an inverter directly to the load terminals of the controller; otherwise, permanent damage to the equipment may result.
- Disconnect all circuit breakers and shade the solar panels.
- Step 1: Connect the batteries. Connect the battery connection cable with the correct polarity to the middle pair of terminals on the solar charge controller (marked with the battery symbol). If the system is 12V, ensure your battery voltage is above 12V for the controller to boot up.
- Step 2: Connect the solar panel. Ensure the PV modules are protected from incident light. Ensure the solar panel's maximum permissible input current is not exceeded. Connect the PV modules connection cable to the correct polarity of the left pair of terminals on the solar charge controller (marked with the PV modules symbol).
- Step 3: Connect loads. Connect the load cable to the correct polarity of the right pair of terminals on the solar charge controller (marked with the lamp symbol). To avoid voltage on the wires, connect the wire to the load BEFORE connecting to the controller.
- Step 4: Finalize connections. Tighten all cables connected to the controller and remove any debris around the controller.
3.4 Air Circuit Breaker and Wires Requirement
We strongly recommend connecting a fuse directly to the battery to protect against short circuits. Protect solar modules from incident light during installation. Never touch uninsulated cable ends; use only insulated tools. Ensure wire diameter is in accordance with expected currents.
| Models | Copper Wires (Recommended) | Air Circuit Breakers (Recommended) |
|---|---|---|
| HHJ-60A | PV: 6mm² x 2, Battery: 6mm² x 2 | PV: 100A-2P, Battery: 100A |
| HHJ-80A | PV: 10mm² / 8AWG x 2, Battery: 10mm² / 8AWG x 2 | PV: 100A-2P, Battery: 100A-2P |
| HHJ-100A | PV: 10mm² / 8AWG x 2, Battery: 10mm² / 8AWG x 2 | PV: 125A-2P, Battery: 125A-2P |
Load Breaker (Recommended): HHJ-60A: N/A, HHJ-80A: 40A-2P, HHJ-100A: 40A-3P.
3.5 Initial Power-Up
- Install air circuit breakers between the controller and batteries, and between the controller and PV modules. Turn them off initially.
- Connect batteries to the controller with correct polarity.
- Connect wires between PV modules and controller, ensuring correct PV polarity.
- Turn on the air circuit breaker between the controller and batteries.
- Turn on the air circuit breaker between the controller and PV modules.
- The controller will enter self-test mode. The LCD will display parameters if all connections are correct, and the RUN lamp (under the fan) will flash every second. If there is no response, recheck connections or consult the manual.
4. Operation
This section describes how to operate your MPPT solar charge controller, including understanding the LCD display and configuring settings.
4.1 LCD Display
The controller features a backlight LCD screen that displays various parameters and working modes. The main interface shows PV voltage/output power, battery voltage/charging current, working mode/temperature, and fault codes.
Main Interface Items:
- PV voltage / Output power
- Battery voltage / Charging current
- Working mode / Temperature
- Fault code
4.2 Working Modes
- 3.0 Night mode: No charging.
- 4.0 MPPT mode: Maximum Power Point Tracking.
- 7.0 Absorption mode: Constant voltage charging stage.
- 8.0 Floating mode: Constant voltage maintenance charging.
4.3 Battery Charge Voltage Reference
The controller supports various battery types with predefined charging parameters. When selecting SEL, GEL, and FLd battery types, the controller automatically detects the system voltage.
| Battery Type | Float Charging Voltage | Absorption Charging Voltage | Under-voltage Protection |
|---|---|---|---|
| SEL (Sealed Lead-Acid) | 13.8V | 14.4V | 11.0V |
| GEL (Gel Sealed Lead-Acid) | 13.8V | 14.2V | 11.0V |
| FLd (Flooded Lead-Acid) | 13.8V | 14.6V | 11.0V |
| L04 (4-series Lithium Iron Phosphate) | 13.8V | 14.5V | 11.2V |
| L08 (8-series Lithium Iron Phosphate) | 27.6V | 29.0V | 22.4V |
| L15 (15-series Lithium Iron Phosphate) | 51.8V | 54.4V | 42.0V |
| L16 (16-series Lithium Iron Phosphate) | 55.2V | 58.0V | 44.8V |
| USE (User-defined) | Defined by users | ||
4.4 Manual Settings
Caution: All steps must be carried out when the PV modules are disconnected from the controller. The controller will work fine under default settings except for lithium batteries.
- Step 1: D00 (Load Working Time). Press the PRG button until the LCD displays D00. This sets the load working time (default is 24-hour). Press ENT until numbers flash, then use UP/DOWN to set the desired time. Long-press ENT to confirm. This output voltage is the same as the battery. This setting is for small DC loads less than 5A. If no load, leave it.
- Step 2: D01 (Floating Charging Voltage). Press the UP button; the LCD shows 13.8V (default for 12V system). Press ENT until numbers flash, then use UP/DOWN to set the desired voltage. Long-press ENT to confirm. Caution: This value is for a single 12V battery. If multiple batteries are in series, the controller will automatically multiply the voltage proportionally, but the LCD will only display the voltage for one battery.
- Step 3: D02 (Absorption Charging Voltage). Continue pressing the UP button; the LCD shows 14.5V (highest absorption charging voltage for 12V system). Press ENT until numbers flash, then use UP/DOWN to set the desired voltage. Long-press ENT to confirm. Caution: This value is for a single 12V battery. If multiple batteries are in series, the controller will automatically multiply the voltage proportionally, but the LCD will only display the voltage for one battery.
- Step 4: D03 (Under-voltage Disconnect). Continue pressing the UP button; the LCD shows 10.0V (protection value for 12V battery discharge). Press ENT until numbers flash, then use UP/DOWN to set the desired voltage. Long-press ENT to confirm. This means if a 12V battery drops below 10.0V, there will be no output power from OU+ and OU-.
- Step 5: D04 (Battery Voltage Calibration). Continue pressing the UP button; the LCD shows C12.2. This setting is used to calibrate the battery voltage, ensuring the controller's detected voltage matches the actual battery voltage.
- Step 6: D05 (Battery Type Setting). Continue pressing the UP button; the LCD shows the setting program for battery type. The default is USE. Select from SEL, GEL, FLd, L04, L08, L15, L16, or USE. Caution: When selecting SEL, GEL, and FLd battery types, the controller automatically detects the system voltage.
- Step 7: D06 (System Voltage for USE type). If you choose the USE option in D05, you must manually configure the system voltage in D06. The configuration range is 12V/24V/36V/48V.
Press ESC to exit the setting menu.
Reminder: After setting all steps, disconnect the battery and then reconnect it to see if all settings are successful. Once settings are confirmed, connect the PV modules to the controller.
5. Maintenance
Regular maintenance ensures the longevity and optimal performance of your solar charge controller.
- Cleaning: Periodically clean the controller's exterior, especially the fan vents, to prevent dust buildup that could impede cooling. Use a soft, dry cloth. Do not use liquids or abrasive cleaners.
- Connections: Annually inspect all wiring connections to ensure they are tight and free from corrosion. Loose connections can cause overheating and poor performance.
- Ventilation: Ensure the area around the controller remains clear of obstructions to allow for proper airflow and cooling.
- Battery Inspection: Regularly check your batteries according to their manufacturer's guidelines. Ensure terminals are clean and tight. For flooded batteries, check electrolyte levels.
- Firmware: Check the manufacturer's website periodically for any firmware updates, though this model typically does not require user-initiated updates.
6. Troubleshooting and Protections
This section provides guidance on common issues and the controller's built-in protection mechanisms.
6.1 Troubleshooting Guide
| Code | Description | How to Solve |
|---|---|---|
| 18 | Input PV voltage is low | Increase the PV voltage. |
| 60 | Over-temperature protection | Fan will work and temperature will reduce automatically. |
| 63 | Battery voltage is high | Battery high voltage protection; wait for recovery. |
| 65 | Battery voltage is low | Battery over-discharge; wait for recovery. |
| 71 | Input PV voltage is high | Decrease the PV voltage. |
| 73 | Over-charging current | Decrease the PV power. |
6.2 Protection Mechanisms
- PV Over Current: The controller limits charging power to its rated capacity. An oversized PV array will not operate at maximum power point but will not damage the controller.
- PV Short Circuit: If a PV short circuit occurs, the controller stops charging. Remove the short to resume normal operation.
- PV Reverse Polarity: Full protection against PV reverse polarity. No damage to the controller. Correct the connection to start normal operation.
- Battery Over Voltage: If the battery voltage exceeds 15.5V (for 12V system), 31.0V (for 24V system), 46.5V (for 36V system), or 62.0V (for 48V system), the controller stops charging to protect the battery from overcharging.
- Battery Over Discharge: When battery voltage drops to the set low voltage disconnect point, the controller stops discharging to protect the battery from over-discharging.
- Load Over Current Protection: If the load current exceeds 1.25 times the maximum rated load current, the controller disconnects the load.
- Load Short Circuit Protection: If a load short circuit occurs, the protection activates automatically.
- Over Temperature Protection: The built-in smart thermostatic fan activates at 45°C and above to cool the unit, allowing continuous operation in hot environments.
7. Specifications
Detailed technical specifications for the PowMr MPPT Solar Charge Controller.
| Parameter | HHJ-60A | HHJ-80A | HHJ-100A | |
|---|---|---|---|---|
| Charging Mode | 3-stage | |||
| Solar Input | Rated Charging Current | 60A | 80A | 100A |
| Max. PV Input Power (12V) | 720W | 960W | 1200W | |
| Max. PV Input Power (24V) | 1440W | 1920W | 2400W | |
| Max. PV Input Power (36V) | 2100W | 2880W | 3600W | |
| Max. PV Input Power (48V) | 2800W | 3840W | 4800W | |
| PV Input Voltage Range | 12V system | 20V ~ 80V | ||
| 24V system | 37V ~ 105V | |||
| 36V system | 50V ~ 160V | |||
| 48V system | 72V ~ 160V | |||
| Battery Voltage Auto Recognition | 12V system | DC9V ~ DC15V | ||
| 24V system | DC18V ~ DC29V | |||
| 36V system | DC30V ~ DC39V | |||
| 48V system | DC40V ~ DC60V | |||
| Overcharging Protection Voltage | 60V | |||
| Limited Current Protection | 61A | |||
| Max Efficiency | ≥98.1% | |||
| PV Utilization | ≥99% | |||
| Protection Function | Temperature Protection | 75°C / 167°F | ||
| Fan-on Temperature | >45°C / 104°F | |||
| Fan-off Temperature | <40°C / 95°F | |||
| Properties | Size (mm)/(in) | 214x115x50mm / 8.43x4.53x1.97in | 150x80x260mm / 5.9x3.15x10.24in | 170x80x280mm / 6.7x3.15x11.02in |
| Net Weight (Kg)/(lb) | 1.1 / 2.43 | 2.1 / 4.63 | 2.7 / 5.95 | |
| Gross Weight (Kg)/(lb) | 1.2 / 2.65 | 2.2 / 4.85 | 2.8 / 6.17 | |
| Electromagnetic Compatibility | EN61000, EN55022, EN55024 | |||
| Enclosure | IP21 | |||
| Environmental Temperature | -20°C ~ +55°C | |||
| Storage Temperature | -40°C ~ +75°C | |||
8. User Tips
- When the PV or battery data readings are constantly changing, it indicates the controller is actively searching for the Maximum Power Point (MPP). This is normal behavior, especially if your PV input power or voltage is fluctuating.
- For optimal performance, ensure your solar panel array is correctly sized for your controller model and battery bank voltage.
- Always double-check polarity before making any connections to prevent damage to the controller or batteries.
- Consider installing appropriate circuit breakers or fuses on both the PV and battery sides for additional system protection.
9. Warranty and Support
9.1 Warranty Regulations
- Within 30 days from the date of purchase, a faulty controller will be replaced free of charge under normal use (with authorization from company technical personnel).
- Within 2 years from the date of purchase, a faulty controller will be repaired free of charge.
- Note: Disassembling the unit privately voids the warranty.
9.2 Liability Disclaimer
The manufacturer is not liable for damages, especially to the battery, caused by use other than as intended or as mentioned in this manual, or if the recommendations of the battery manufacturer are neglected. The manufacturer is not liable if service or repair is carried out by unauthorized personnel, or due to unusual use, wrong installation, or bad system design.