1. Introduction
Thank you for purchasing the SINOTIMER Three Phase 4 Wire Digital Wattmeter. This instrument is designed for accurate measurement of active energy in three-phase four-wire systems. It features a large-screen LCD display and, for certain models (DDS578MR), an RS485 communication interface for remote meter reading. The meter is designed according to national standard GB/T17215.321-2008 and international standard IEC62053-21, utilizing advanced ultra-low power LSI technology and SMT manufacturing processes for high reliability and longevity.
The product's circuit measurement part uses a dedicated measurement chip, ensuring high reliability, high precision, and accurate active energy measurement. It employs a linear power supply, with the metering chip converting electrical energy into pulses. A microprocessor handles power collection, power calculation, pulse output, and LCD display processing. Data security is ensured through redundant design and multiple backups.

2. Safety Instructions
This section provides important information related to your personal safety and to prevent damage to the instrument. Always observe these instructions.
⚠ Dangerous
Failure to observe the relevant regulations will result in serious damage to the instrument, serious personal injury, or death.
⚠ Warning
This symbol indicates the risk of electric shock. Failure to take appropriate safety precautions may result in serious injury to the instrument, serious personal injury, or death.
2.1 Qualified Personnel
Only qualified personnel should perform the procedures described in this manual. Qualified personnel are authorized professional technicians who can correctly install and commission the instrument in accordance with power safety management standards.
2.2 Use Range
The instrument can only be used in the specific areas specified in this manual and catalog, and can only be connected to devices or components recommended or approved by the company.
2.3 Reasonable Operation
- Ensure correct wiring before using the meter.
- To prevent electric shock, do not use hands, metal, etc., to directly contact the meter connection clamp.
- Always install protective covers.
- Only qualified personnel should install, maintain, and service this product.
- Maintain the integrity of the front cover and housing to ensure normal operation and warranty.
- Avoid wrestling or bumping the product, as this may damage internal precision components.
- Use insulation tools during installation and maintenance.
- Do not install or service when electricity is present.
- Place the meter in a dry, ventilated place.
- Do not expose the meter to dusty, mildew, or insects.
- Ensure that the wire current used does not exceed the maximum current of the meter.
3. Product Overview
3.1 Product Structure and Materials
The meter consists of a front panel, meter cover, bottom, and seal. The front panel is made of flame-retardant PC, while the meter cover and bottom are made of flame-retardant ABS or PC.

3.2 Display Types and Indicators
The DDS578 series meters come in different display types:
- DDS578C: Counter Display Type (mechanical counter).
- DDS578: LCD Display Type (digital display).
- DDS578R: With RS485 communication.
- DDS578MR: Multifunctional with RS485 communication.
The front panel features five LED lights:
- A, B, C: Three-phase power indicators.
- Red Pulse Indicator: Indicates energy consumption pulses.
- Reverse Indicator: Indicates reverse power flow.
For S-type meters, there are four LEDs: A, B, C three-phase power indicators, and a red pulse indicator.


4. Specifications
4.1 Technical Parameters
| Parameter | Value |
|---|---|
| Reference voltage (Un) | 3x220/380V |
| Operating voltage | 181/279 - 300 / 500V AC (3 ~) |
| Rated current (Ib) | 1.5A 5A 10A 15A 20A 30A |
| Maximum current (Imax) | 6A 20A 40A 60A 80A 100A |
| Starting current | ≤ 0.004b |
| Tolerance overload current | 30Imax 0.01s |
| Working frequency | 50Hz ± 10% |
| Internal power consumption | <2W / 10VA |
| Pulse constant | 400imp 1600imp |
| RS485 port | 15 (A) and 16 (B) or 2 (A) and 3 (B) |
| Data storage time | > 20 years |
4.2 Environmental Conditions
| Parameter | Value |
|---|---|
| Working humidity | ≤ 75% |
| Storage humidity | ≤ 95% |
| Operating temperature | -10°C to +50°C |
| Storage temperature | -30°C to +70°C |
| International standard | IEC 62053-21 |
| Domestic standard | GB/T17215.321-2008 |
| Accuracy Class | 1 |
| Dustproof and waterproof | IP 51 |
| Protective insulating enclosing instrument type | II |
4.3 Dimensions and Weight
The meter is designed for 35mm DIN rail installation.
| Parameter | Value |
|---|---|
| Length | 100 mm |
| Width | 123 mm |
| High | 65 mm |
| Weight (net) | 0.6 Kg |

4.4 Basic Error (Accuracy Class 1)
| Load Condition | Power Factor (Cosp) | Error |
|---|---|---|
| Three-phase balanced load | ||
| 0.05Ib | 1 | ±1.5% |
| 0.1Ib | 0.5L | ±1.5% |
| 0.8C | ±1.5% | |
| 0.1Ib - Imax | 1 | ±1.0% |
| 0.2Ib - Imax | 0.5L | ±1.0% |
| 0.8C | ±1.0% | |
| Single-phase unbalanced load | ||
| 0.1Ib - Imax | 1 | ±2.0% |
| 0.2Ib - Imax | 0.5L | ±2.0% |
5. Installation
The meter connection should be selected in accordance with the overload current device in the circuit, the performance of the circuit-breaker, and the relevant local codes. In the selection of external air switches or circuit breakers, they should conform to local standards and current electrical design. The air switch or circuit breaker should be installed in the meter line and used as meter power equipment, positioned near the meter for easy operation.
The meter can be installed either directly indoors or in a waterproof case outdoors, according to relevant local standards. Install a padlock or similar device to prevent tampering. This meter must be installed on a fireproof wall and in a ventilated and dry place. If installing in a dusty or dangerous location, ensure the meter is placed in a protective case.
The meter must be tested, stamped, and affixed with a qualified sign before installation. Place this meter in a convenient location for reading. If the meter is installed in an area with significant interference (e.g., multi-mined areas, welding machines, converters), install an anti-jamming device.
After installation, close the meter to prevent tampering. Please follow the wiring diagrams below to connect the meter circuit. This product is available in two wiring options (Direct Access and CT Access); ensure you use the correct wiring type for your instrument.
5.1 Wiring Diagram (Direct Access)

| Terminal | Notice |
|---|---|
| 1/2 | Ia Input/output |
| 3/4 | Ib Input/output |
| 5/6 | Ic Input/output |
| 7 | Neutral line |
| 15/16 | RS485 port |
| 17/18 | Pulse port |
5.2 Wiring Diagram (CT Access)

| Terminal | Note |
|---|---|
| L1/L1 | Ia Input/output |
| L2/L2 | Ib Input/output |
| L3/L3 | Ic Input/output |
| N | Neutral line |
| 2/3 | RS485 Port |
| 4/5 | Pulse port |
For CT Access wiring, ensure current transformers are correctly installed on each phase (L1, L2, L3) and connected to the corresponding terminals. The neutral line (N) is connected directly.
6. Operation
6.1 Electricity Indication
The LED indicators on the front panel provide visual feedback on the meter's status:
- A, B, C LEDs: Indicate the presence of power in each phase.
- Red Pulse LED: Flashes to indicate active energy consumption. A faster flash rate means higher consumption.
- Reverse Indicator: Illuminates if reverse power flow is detected.
6.2 Key Operation Instructions (for models with keys)
This section applies to models equipped with 'TURN' and 'SET' buttons.
- Normal State: When not in the setting state, a short press of the 'TURN' button cycles through display parameters. A short press of the 'SET' button has no action.
- Entering Setting State: Press and hold the 'SET' button to enter the password interface. The password is a 4-digit number. Use short presses of the 'TURN' button to increment the flashing digit and short presses of the 'SET' button to move to the next digit. After entering the correct password, long press the 'SET' button to enter the parameter setting mode.
- Navigating Setting Mode: In parameter setting mode, use short presses of the 'TURN' button to toggle between setting items. To set a specific item, press the 'SET' button to enter its parameter. The parameter will flash, and you can adjust it similarly to password entry.
- Saving Settings: After adjusting a parameter, press the 'SET' button to save. A successful save will display 'GOOD'; an unsuccessful save will display 'ERR'.
- Exiting Setting Mode: When in the setting state, press the 'TURN' button to exit or cancel, returning to the previous menu.
Setup Key Display Description
| Display | Value | Description |
|---|---|---|
| PASS | 0000 | Login password |
| Addr | 001 | Meter address |
| bd | 9600 | Baud rate |
| PrEY | E | Check Digit |
| ScrL | E | Circle show |
| SEE | PASS | Modify password |
6.3 Pulse Output and RS485 Output
The three-phase four-wire power meter has a pulse output independent of the internal circuit. For U-type meters, terminal 17 is connected to the positive terminal and terminal 18 to the negative terminal. For S-type meters, terminal 4 connects to the positive and terminal 5 to the negative. The voltage is 5 ~ 27V DC with a maximum current of 27 mA DC.
For RS485 communication, U-type Meter terminal 15 (A) is the positive side of RS485, and terminal 16 (B) is the negative RS485 terminal.
6.4 RS485 Communication Meter Reading Application (MODBUS-RTU)
The energy meter uses its RS485 interface for long-range data acquisition, such as electricity energy data. It also supports infrared communication for close-up data reading with a handheld computer. The encoding format, parity (even parity), and data transmission (eight data bits, one stop bit) comply with MODBUS-RTU standards. Default communication baud rates are 1200bps, 2400bps, 4800bps, and 9600bps.
6.4.1 Data Format
Address + Function Code + Data + CRC Check Code
6.4.2 Register Types
The meter uses two types of registers:
- Data Register: Read-only, accessed using command code 0x04.
- Parameter Register: Readable and writable, accessed using command code 0x03 for reading and 0x10 for writing.
6.4.3 Data Format (Floating Point)
Float type data: Internal data within the meter conforms to the IEEE-754 standard, using a 32-bit 4-byte single-precision floating-point data format.
6.4.4 Data Register List
| Data Register Address | Register Description | ||||
|---|---|---|---|---|---|
| HI Byte | LO Byte | Description | Unit | Format | Mode |
| 00 | 00 | A phase voltage | V | Floating point | Read-only |
| 00 | 02 | B phase voltage | V | Floating point | Read-only |
| 00 | 04 | C phase voltage | V | Floating point | Read-only |
| 00 | 08 | A line current | A | Floating point | Read-only |
| 00 | 0A | B line current | A | Floating point | Read-only |
| 00 | 0C | C line current | A | Floating point | Read-only |
| 00 | 10 | Total active power | KWh | Floating point | Read-only |
| 00 | 12 | A phase active power | KWh | Floating point | Read-only |
| 00 | 14 | B phase active power | KWh | Floating point | Read-only |
| 00 | 16 | C phase active power | KWh | Floating point | Read-only |
| 00 | 18 | Total reactive power | KWh | Floating point | Read-only |
| 00 | 1A | A phase reactive power | Var | Floating point | Read-only |
| 00 | 1C | B phase reactive power | Var | Floating point | Read-only |
| 00 | 1E | C phase reactive power | Var | Floating point | Read-only |
| 00 | 2A | A phase power factor | Floating point | Read-only | |
| 00 | 2C | B phase power factor | Floating point | Read-only | |
| 00 | 2E | C phase power factor | Floating point | Read-only | |
| 00 | 36 | Frequency | Hz | Floating point | Read-only |
| 01 | 00 | Total active electricity power | KWh | Floating point | Read-only |
| 04 | 00 | Total reactive electricity power | Kvarh | Floating point | Read-only |
6.4.5 Parameters Register List
| Parameter Register Address | Register Description | |||
|---|---|---|---|---|
| HI Byte | LO Byte | Description | Format | Mode |
| 00 | 00 | Baud rate (1200 2400 4800 9600) | Floating point | Read & write |
| 00 | 02 | Check Digit (0:Even 1:odd 2:none) | Floating point | Read & write |
| 00 | 08 | Communications Address (Meter NO:1-247) | Floating point | Read & write |
| 00 | 10 | Relay control (1:switch on 2:switch out) | Floating point | Read & write |
7. Troubleshooting
Before attempting any troubleshooting, ensure the power supply to the meter is disconnected. Only qualified personnel familiar with the operation and procedures should perform maintenance. Use insulating tools and ensure the protective cover is restored after repairs. Do not damage the meter seal.
| Fault Condition | Examination | Solution |
|---|---|---|
| Communication No Indication | Whether the meter has power supply | Check the internal power supply. |
| Whether or not connected to communications equipment | The LED will blink only when an external device is connected to the RS485 or far-infrared port. Please contact your technical support staff for a meter change. | |
| RS485 No Transmission | Meter ID is correct | Check the ID number of the meter (factory setting is NO. Of meter front panel). |
| Whether the baud rate of the meter is wrong | Verify that the meter baud rate matches the baud rate of the other devices it communicates with. | |
| Whether the distance too far / Bus on the table is too much | Transmission distance cannot exceed 1200m. There cannot be more than 247 meters in bus. | |
| Wiring is correct | Make sure that the A and B signal cables of RS485 are connected correctly. | |
| LCD Does Not Display Correctly | Whether the power meter connected to the power consumption is too low | Detection of the pulse signal is not flashing. |
| There may be a problem with the internal circuit | When the power is too low, the LCD screen may take a long time to change numbers. Please contact your technical support for the meter. | |
| No Pulse Output | Whether connected to the DC power supply 5,6 or 1,2-terminal connection is correct | Check that the external voltage is 5-27V DC. Tighten again to ensure that terminal 5 (terminal 1) is connected to the positive terminal and terminal 6 (terminal 2) is connected to the negative terminal. |
| There may be a problem with the internal circuit | Please contact your technical support staff for a meter. | |
| Pulse Output Error | There may be a problem with the internal circuit | Please contact your technical support staff for a meter. |
8. Technical Support
For any technical assistance or inquiries not covered in this manual, please contact your supplier or the SINOTIMER Official Store directly.
9. User Tips
- Verify Wiring Carefully: Double-check all phase and neutral connections according to the provided diagrams before powering on the meter to prevent damage and ensure accurate readings.
- Monitor Indicators: Pay attention to the A, B, C, and Pulse LEDs. Consistent flashing of the Pulse LED indicates normal operation and energy consumption.
- Secure Installation: Ensure the meter is securely mounted on a 35mm DIN rail in a dry, well-ventilated area to maximize its lifespan and performance.