1. Introduction
This manual describes the assembly, installation, operation, and troubleshooting of the DATOUBOSS 6200W 48V Hybrid Solar Inverter. Please read this manual carefully before installation and operation. Keep this manual for future reference.
This is a multi-function inverter/charger, combining functions of an inverter, solar charger, and battery charger to offer uninterruptible power support with a portable size. Its comprehensive touch screen provides user-configurable and easy-to-operate push-button operations, such as battery charging current, AC/solar charger prioritization, and acceptable input voltages based on different loads.
1.1 Features
- Pure sine wave inverter
- The input voltage range can be configured for household appliances and personal computers via touch screen settings.
- Application-based configurable battery charging current setting via touch screen.
- The AC/solar charger priority can be configured through touch screen settings.
- Compatible with mains voltage or generator power.
- Auto restart while AC is recovering.
- Overload/Over temperature/short circuit protection.
- Smart battery charger design for optimized battery performance.
- Cold start function.
1.2 Basic System Architecture
The following illustration shows the basic application for this inverter/charger. It also includes the following devices to have a complete running system: Generator or Utility, PV modules.
Consult with your system integrator for other possible system architectures depending on your requirements.
This inverter can power all kinds of appliances in home or environment, including motor-type appliances such as tube light, fan, refrigerator, and air conditioner.

2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION - To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION - Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It is very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short-circuited. Do NOT connect to the mains when DC input short circuits.
- Warning! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to a local dealer or service center for maintenance.
3. Product Overview
3.1 Product Dimensions

3.2 Touch Color Screen
The operation and display panel is located on the front panel of the inverter. It includes RGB indicators and an LCD display. The LCD is a touch screen, displaying overall information of the inverter.

3.2.1 Home Screen
The home screen indicates the system's operating status. If a gray icon and characters are displayed, it means the inverter has an alarm. If a red icon and characters are displayed, it means the inverter is faulty. Detailed error information can be viewed in the instruction manual alarm menu.
The main screen displays information including PV, mains, load, and battery. It also shows the direction of energy flow with arrows and equivalent power. When approaching the limit value, the color on the panel will change from green to red, making the system information vividly displayed on the main screen.
3.2.2 LED Indicator Functions
| Code | Machine State | Color | Effect | Breath Light |
|---|---|---|---|---|
| 1 | Stand by/Self-test | Colorful | Gradient color display | NO |
| 2 | Under DC mode | blue | Monochrome display (one light keeps flashing) | NO |
| 3 | Under AC/Full charge under AC mode | green | Monochrome display | NO |
| 4 | Charging under AC mode | green | Monochrome display | YES |
| 5 | Solar charging | yellow | Monochrome display | YES |
| 6 | Full charge under solar power | yellow | Monochrome display | NO |
| 7 | Under the alarm | red | Monochrome display | YES (recoverable) NO (non-recoverable) |
| 8 | Solar energy and AC charging at the same time | half and half | yellow on the top, green at the bottom | YES |
3.3 Back Panel Connections

- AC Input
- AC Output
- Communication Port
- BMS/RS485 Communication Port
- Dry Contact
- Parallel connection
- Battery Input
- Power ON/OFF Switch
- PV Input
- Input Breaker
- Fan
- Battery Terminal Positive
- Battery Terminal Negative
- Solar Panel Input
- AC Main/Second Output
- Output ground wire
- CT Signal port
4. Setup and Installation
4.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of the package:
- The unit x 1
- User manual x 1
- Communication cables and accessories
4.2 Preparation
Before connecting all, please take off the bottom cover by removing two screws as shown below.

4.3 Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level in order to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
- The ambient temperature should be between -10°C and 50°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing three screws:
- Use M6*80mm expansion bolts.
- Use M4 or M5.

4.4 Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between the battery and inverter. It may not be requested to have a disconnect device in some applications; however, it is still requested to have over-current protection installed. Please refer to typical amperage in the table below for required fuse or breaker size.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable and terminal size as below.
Recommended Battery Cable and Terminal Size:
| Rated Capacity | Typical Amperage | Battery Capacity | Wire Size | Cable (mm²) | Ring Terminal D (mm) | Ring Terminal L (mm) | Torque Value |
|---|---|---|---|---|---|---|---|
| 3KVA | 132A | 100AH | 1*4AWG | 22 | 6.4 | 33.2 | 2~3 Nm |
| 200AH | 2*8AWG | 9 | 6.4 | 29.2 | |||
| 3.6KVA | 165A | 200AH | 2*4AWG | 25 | 8.4 | 33.2 | 5Nm |
| 4KVA | 165A | 200AH | 2*4AWG | 25 | 8.4 | 33.2 | 5Nm |
| 5.5KVA | 121A | 200AH | 1*2AWG | 34 | 6.4 | 39.2 | 2~3 Nm |
| 2*6AWG | 14 | 6.4 | 33.2 | ||||
| 6.2KVA | 124A | 200AH | 1*2AWG | 38 | 8.4 | 39.2 | 5Nm |
| 2*4AWG | 25 | 8.4 | 33.2 | ||||
| 11KVA | 228A | 250AH | 1*3/0AWG | 85 | 8.4 | 54 | 5Nm |
Please follow below steps to implement battery connection:
- Assemble battery ring terminal based on recommended battery cable and terminal size.
- Insert the battery wires flatly into battery connectors of the inverter and make sure the bolts are tightened with a torque of 2 Nm in a clockwise direction. Make sure polarity at both the battery and the inverter/charger is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.
WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
4.5 AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between the inverter and AC input power source. This will ensure the inverter can be disconnected during maintenance and fully protected from over current of AC input. The recommended spec of breaker is 32A for 24V system and 63A for 48V system.
CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested Cable Requirement for AC Wires:
| Rated Capacity | Gauge | Torque Value |
|---|---|---|
| 3KVA | 12AWG | 1.2~1.6Nm |
| 3.6KVA | 12AWG | 1.2~1.6Nm |
| 4KVA | 12AWG | 1.2~1.6Nm |
| 5.5KVA | 10AWG | 1.4~1.6Nm |
| 6.2KVA | 10AWG | 1.4~1.6Nm |
| 11KVA | 8AWG | 1.4~1.6Nm |
Please follow below steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open the DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N3 mm.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (Ground - yellow-green) first. L-LINE (brown or black), N-Neutral (blue).
WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.
- Make sure the wires are securely connected.
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check the manufacturer of the air conditioner if it's equipped with a time-delay function before installation. Otherwise, this inverter/charger will trigger an overload fault and cut off output to protect your appliance, but sometimes it still causes internal damage to the air conditioner.
4.6 PV Connection
(Only applies for models with solar charger)
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between the inverter and PV modules.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested Cable Requirement for PV Wires:
| Typical Amperage | Gauge | Torque Value |
|---|---|---|
| 30A | 12AWG | 1.4~1.6Nm |
PV Module Selection:
When choosing the right PV module, be sure to first consider the following requirements:
The open circuit voltage (Voc) of the PV modules does not exceed the maximum PV array open circuit voltage of the inverter. The maximum supply voltage of the PV modules should be close to the optimal PV access voltage range of the inverter for best performance. If one PV module cannot meet this requirement, it is necessary to connect multiple PV modules in series.
PV Module Wire Connection Steps:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Fix wire cover to the inverter with supplied screws as shown in the diagram.
- Check correct polarity of wire from PV modules and PV input connectors. Then, connect the positive pole (+) of the connection wire to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection wire to the negative pole (-) of the PV input connector. Screw two wires tightly in a clockwise direction. Recommended tool: 4mm blade screwdriver.
4.7 Final Assembly
After connecting all wirings, please put the bottom cover back by screwing two screws as shown below.

5. Operation
5.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the button of the case) to turn on the unit.
5.1.1 Steps to Start Up
Connect the battery that meets the requirements (battery voltage needs to be beyond 23V) or AC (AC needs to confirm the suitable input range depending on the output mode), then you can start up the inverter.
- Mains Power On: Connect to normal AC power, press the switch, the system will automatically turn on. If you set AC output power priority, after waiting for a period of time, the panel will display AC mode that represents the machine successfully turned on, then it will enter AC mode.
- Battery Boot: Connect to battery, press the power-on button to establish a working power source. The system will automatically turn on, after waiting for a period of time, the panel will display battery mode that represents the machine successfully turned on, then it will enter battery mode.
5.1.2 Shutdown Steps
When the system is in battery mode or AC mode output, press the switch again, then the system will be turned off.
5.2 Touch Screen Operation Instructions
The touch screen allows users to navigate through various settings and view real-time data. The main screen provides an overview of the system status, including PV input, battery status, grid power, and load output. Detailed information for each component can be accessed through dedicated screens.
5.2.1 System Settings Menu
The System Settings page allows configuration of various parameters, including battery settings, system working mode, grid settings, charging settings, basic settings, advanced functions, and device information.
5.2.2 LCD Display Icons

6. Parallel Function
The DATOUBOSS 6200W 48V Hybrid Solar Inverter supports parallel connection for increased power output and system flexibility. This allows for easy expansion to meet higher power demands.
6.1 Mounting for Parallel Units
When installing multiple units, ensure proper spacing for air circulation: approximately 20 cm to the sides and 50 cm above and below each unit. All units should be installed at the same level.
6.2 Wiring Connection for Parallel Units
NOTICE: It is requested to connect to a battery for parallel operation.
WARNING: Be sure the length of all battery cables is the same. Otherwise, there will be voltage difference between the inverter and battery, causing parallel inverters not to work.
Recommended Battery Capacity for Parallel Inverters:
| Inverter Parallel Numbers | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
|---|---|---|---|---|---|---|---|---|
| Battery Capacity for 6.2KW | 400AH | 600AH | 800AH | 1000AH | 1200AH | 1400AH | 1600AH | 1800AH |
Recommended Breaker Specification for AC Input with Single Phase:
| Rated Capacity | 2 units | 3 units | 4 units | 5 units | 6 units | 7 units | 8 units | 9 units |
|---|---|---|---|---|---|---|---|---|
| 6.2KVA | 80A/230VAC | 120A/230VAC | 160A/230VAC | 200A/230VAC | 240A/230VAC | 280A/230VAC | 320A/230VAC | 360A/230VAC |
Note 1: Also, a circuit breaker should be installed at the AC input of each inverter, and the selection of the circuit breaker should refer to the AC input current of the machine nameplate.
Note 2: Regarding three-phase system, you can use a 4-pole breaker directly and the rating of the breaker should be compatible with the phase current limitation from the phase with maximum units.
6.3 Commissioning for Parallel Operation
Step 1: Check the following requirements before commissioning:
- Correct wire connection.
- Ensure all breakers in Line wires of load side are open and each Neutral wire of each unit are connected together.
Step 2: Turn on each unit and set the output type to "PAL" in the touch screen setting system operating mode of each device. Then shut down all units.
NOTE: It's necessary to turn off the switch when setting the LCD program. Otherwise, the setting cannot be programmed.
Step 3: Turn on each unit.
7. Maintenance
Regular maintenance ensures the longevity and optimal performance of your DATOUBOSS Hybrid Solar Inverter. Always prioritize safety during maintenance procedures.
- Cleaning: To reduce the risk of electric shock, disconnect all wirings before attempting any cleaning. Turning off the unit will not reduce this risk. Use a dry, soft cloth to clean the exterior of the inverter. Do not use liquid cleaners.
- Ventilation: Ensure that the inverter's ventilation openings are clear of dust and debris to maintain proper airflow and prevent overheating. Regularly check for any obstructions.
- Cable Connections: Periodically inspect all cable connections (battery, AC input/output, PV) to ensure they are secure and free from corrosion. Tighten any loose connections.
- Environmental Conditions: Ensure the inverter is operating within its specified temperature range (-10°C to 50°C) and humidity levels. Avoid exposing the unit to excessive moisture or direct sunlight.
- Firmware Updates: Check the manufacturer's website or contact support for any available firmware updates to ensure optimal performance and access to new features.
8. Troubleshooting
This section provides guidance for common issues and fault codes. If the problem persists after following these steps, contact qualified service personnel.
8.1 Fault and Alarm Descriptions
When the inverter enters fault mode, the red LED light is always on and the LCD displays the fault code. For alarms, the red LED flashes, and the LCD displays an alarm code, but the inverter does not enter the failure mode.
Fault Reference Codes:
| Fault Code | Fault Event |
|---|---|
| 01 | Fan is locked when inverter is off. |
| 02 | Over temperature or NTC is not connected well. |
| 03 | Battery voltage is too high. |
| 04 | Battery voltage is too low. |
| 05 | Output short circuited or over temperature is detected by internal converter components. |
| 06 | Output voltage is too high. |
| 07 | Over load time out. |
| 08 | Bus voltage is too high. |
| 09 | Bus soft start failed. |
| 51 | Over currents or surge. |
| 52 | Bus voltage is too low. |
| 53 | Inverter soft start failed. |
| 55 | Over DC voltage in AC output. |
| 57 | Current sensor failed. |
| 58 | Output voltage is too low. |
| 59 | PV voltage is over limitation. |
Alarm Codes:
| Alarm Code | Alarm Event | Audible Alarm |
|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second |
| 02 | Over temperature | None |
| 03 | Battery is over-charged | Beep once every second |
| 04 | Low battery | Beep once every second |
| 07 | Overload | Beep once every 0.5 second |
| 10 | Output power derating | Beep twice every 3 seconds |
| 15 | PV energy is low. | Beep twice every 3 seconds |
| 16 | High AC input (>280VAC) during BUS soft start | None |
| E9 | Battery equalization | None |
| 6P | Battery is not connected | None |
8.1.1 Common Troubleshooting Scenarios:
| Problem | LCD/LED/Buzzer | Explanation/Possible Cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD/LEDs and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low (<1.91V/Cell). | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. The battery voltage is far too low (<1.4V/Cell). 2. Internal fuse tripped. | 1. Contact repair center for replacing the fuse. 2. Re-charge battery. 3. Replace battery. |
| Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped. | Check if AC breaker is tripped and AC wiring is connected well. | |
| Mains exist but the unit works in battery mode. | Green LED is flashing. | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UP-->appliance) |
| Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. | |
| When the unit is turned on, internal relay is switched on and off repeatedly. | LCD display and LEDs are flashing. | Battery is disconnected. | Check if battery wires are connected well. |
| Buzzer beeps continuously and red LED is on. | Fault code 07 | Overload error. The inverter is overloaded 105% and time is up. | Reduce the connected load by switching off some equipment. |
| Fault code 05 | If PV input voltage is higher than specification, the output power will be derated. At this time, if the connected load is higher than derated output power, it will cause overload. | Reduce the number of PV modules in series or the connected load. | |
| Fault code 02 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Fault code 03 | Temperature internal converter component is over 120°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Fault code 01 | Internal temperature of inverter component is over 100°C. | Return to repair center. | |
| Fault code 06/58 | Battery is over-charged. The battery voltage is too high. | Check if spec and quantity of batteries are meet requirements. | |
| Fault code 08/09/53/57 | Fan fault. Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac). | Replace the fan. 1. Reduce the connected load. 2. Return to repair center. | |
| Fault code 51 | Internal components failed. | Return to repair center. | |
| Fault code 52 | Over current or surge. | Restart the unit. If the error happens again, please return to repair center. | |
| Fault code 55 | Bus voltage is too low. | ||
| Fault code 59 | Output voltage is unbalanced. PV input voltage is beyond the specification. | Reduce the number of PV modules in series. |
9. Specifications
| Attribute | Value |
|---|---|
| Model Number | DT-48V6.2KW-BF-A |
| Size | 52.88X41.15X15.88 cm |
| Weight | 20.27kg |
| Brand Name | DATOUBOSS |
| EU LVD Voltage | Low voltage: Below 50Vac or 75Vdc |
| Output Frequency | 50/60Hz |
| Is Smart Device | Yes |
| Origin | Mainland China |
| Rated Output Power | 6200W |
| Peak Output Power | 8500W (10 seconds duration) |
| Output Waveform | Pure sine wave |
| Conversion Efficiency | ≥ 93% (at full load) |
| Max PV Charging Current | 120A |
| MPPT Operating Range | 60-500VDC |
| Optimal MPPT Range at Full Load | 360-430VDC |
| Max PV Input Current | 36A |
| Rated PV Input Current | 27A |
| MPPT Tracking Efficiency | > 99.5% |
| Battery System Voltage | 48VDC |
| Operating Voltage Range | 42-64VDC |
| Float Charge Voltage | 54VDC |
| Equalization Charge Voltage | 56.4VDC |
| Low Voltage Disconnect | 44VDC (adequate) |
| Low Voltage Reconnect | 52VDC (adequate) |
| Max Charging Current | 120A (PV + Grid) |
| Max AC Charging Current | 100A |
| AC Input Current | 40A |
| Parallel Function | Yes |
| Protection Rating | IP54 Dust & Water Protection |
| Wide Temp Range | -10 ~ 50 °C |
10. User Tips
- Battery-Free Operation: This inverter supports battery-free operation, allowing the load to be powered directly from photovoltaic power generation without batteries, and even from the grid in some cases. This provides greater flexibility in system design and is particularly suitable for users who want to reduce initial investment or battery use.
- Optimal MPPT Range: For best performance, ensure your PV modules' maximum power point voltage (Vmp) is within the inverter's optimal MPPT range of 360-430VDC.
- Parallel Connection: Utilize the parallel connection capability to scale your system up to 9 units for higher power output, making it suitable for larger homes or commercial applications.
- IP54 Protection: The IP54 rating ensures dust and water protection, making the inverter suitable for various environments. However, always ensure proper installation and maintenance to preserve this rating.
- Touch Screen Interface: Take advantage of the intuitive color touch screen for easy monitoring and configuration of system parameters.
11. Support
For technical assistance, warranty claims, or service inquiries, please contact your DATOUBOSS dealer or the manufacturer's customer support. Refer to your purchase documentation for specific contact details.
User Manual (PDF): A detailed user manual in PDF format is available for download. Please refer to the official product page or contact customer support for the link: View User Manual (PDF)