1. Introduction
1.1 Purpose
This manual describes the assembly, installation, operation, and troubleshooting of the Datouboss 48V 11Kw Hybrid Solar Inverter. Please read this manual carefully before installation and operation. Keep this manual for future reference.
1.2 Scope
This manual provides safety and installation guidelines, as well as information on tools and wiring required for the inverter.
1.3 Product Overview
The Datouboss 48V 11Kw Hybrid Solar Inverter is a multi-function inverter/charger, combining the functions of an inverter, solar charger, and battery charger to offer uninterruptible power support. It features a comprehensive LCD display for user-configurable and easy-accessible button operation, allowing settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.

Figure 1: Datouboss 48V 11Kw Hybrid Solar Inverter with key features.
1.4 Features
- Pure sine wave output.
- Configurable input voltage range for home appliances and personal computers via LCD setting.
- Configurable battery charging current based on applications via LCD setting.
- Configurable AC/Solar Charger priority via LCD setting.
- Compatible with mains voltage or generator power.
- Auto restart while AC is recovering.
- Overload/Over temperature/short circuit protection.
- Smart battery charger design for optimized battery performance.
- Cold start function.
- Maximum power of solar panels: 11000W (2×5500W).
- Wide MPPT voltage range: 90-500V DC.
- Optimum MPPT operation range: 300-400V DC.
- Maximum charge current: 150A.
- DC input: 48V battery system.
- Single-phase power supply: 230V, 50/60Hz.
- Max output current: 47.8A.
1.5 Basic System Architecture
The following illustration shows a basic application for this inverter/charger. A complete running system includes the inverter/charger, a generator or utility connection, and PV modules. Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power various appliances in home or environment, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners.

Figure 2: Basic System Architecture.
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION: To reduce risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION: Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Refer to the INSTALLATION section of this manual for details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
3. Setup
3.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items:
- Inverter unit x 1
- User manual x 1
- Parallel connection cable x 1
- Other accessories (e.g., mounting hardware, communication cables).
Video 1: Unboxing and overview of the Datouboss Hybrid Solar Inverter, showing the unit and included accessories.
3.2 Preparation
Before connecting any wires, remove the bottom cover by unscrewing two screws as shown in the manual.
3.3 Mounting the Unit
Consider the following points when selecting where to install the inverter:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the side and approximately 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Be sure to keep other objects and surfaces clear as shown in the diagram to guarantee sufficient heat dissipation and space for removing wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two screws. Use M6*80mm expansion bolts.

Figure 3: Inverter dimensions and included accessories.
3.4 Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to the typical amperage in the table below as required fuse or breaker size.
WARNING! All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable and terminal size as below.
Recommended battery cable and terminal size:
| Model | Typical Amperage | Battery Capacity | Wire Size | Cable (mm²) | Ring Terminal Dimensions (D x L mm) | Torque Value |
|---|---|---|---|---|---|---|
| 1KVA/2KVA | 44A/88A | 100AH | 1*6AWG 2*10AWG | 14 6 | 6.4 x 33.2 6.4 x 23.8 | 2-3 Nm |
| 3KVA | 132A | 100AH 200AH | 1*4AWG 2*8AWG | 22 9 | 6.4 x 33.2 6.4 x 29.2 | 2-3 Nm |
| 5KVA | 109A | 200AH | 1*2AWG 2*6AWG | 38 28 | 6.4 x 39.2 6.4 x 33.2 | 2-3 Nm |
Follow these steps to implement battery connection:
- Assemble battery ring terminal based on recommended battery cable and terminal size.
- Insert the battery wires flatly into battery connectors of the inverter and make sure the bolts are tightened with a torque of 2 Nm in a clockwise direction. Ensure polarity at both the battery and the inverter/charger is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.
WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
3.5 AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between the inverter and AC input power source. This will ensure the inverter can be disconnected during maintenance and fully protected from over current of AC input. The recommended spec of breaker is 32A for 3KW and 50A for 5KW.
CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires:
| Model | Gauge | Torque Value |
|---|---|---|
| 1KVA | 16AWG | 0.5~0.6Nm |
| 2KVA | 14AWG | 0.8-1.0Nm |
| 3KVA | 12AWG | 1.2-1.6Nm |
| 5KVA | 8AWG | 1.4-1.6Nm |
Follow these steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3mm.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (yellow-green) first.
- Make sure the wires are securely connected.
CAUTION: Appliances such as air conditioners require at least 2-3 minutes to restart because it's necessary to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this, check the manufacturer of your air conditioner if it's equipped with a time-delay function before installation. Otherwise, this inverter/charger will trigger an overload fault and cut off output to protect your appliance, but sometimes it still causes internal damage to the air conditioner.
3.6 PV Connection (Only for models with solar charger)
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between the inverter and PV modules.
WARNING! All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for PV wires:
| Typical Amperage | Gauge | Torque Value |
|---|---|---|
| 10A | 12AWG | 1.4-1.6Nm |
PV module selection:
When choosing the right PV module, be sure to first consider the following requirements:
- The open circuit voltage (Voc) of the PV modules does not exceed the maximum PV array open circuit voltage of the inverter.
- The maximum supply voltage of the PV modules should be close to the optimal PV access voltage range of the inverter for best performance.
- If one PV module cannot meet this requirement, it is necessary to connect multiple PV modules in series.
Follow these steps to implement PV module connection:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Fix wire cover to the inverter with supplied screws as shown in the below chart.
- Check correct polarity of wire from PV modules and PV input connectors. Then, connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector. Screw two wires tightly in a clockwise direction. Recommended tool: 4mm blade screwdriver.

Figure 4: Rear panel connections and controls.
3.7 Final Assembly
After connecting all wirings, please put the bottom cover back by screwing the two screws as shown below.
3.8 Communication Connection
- Please use the supplied communication cable to connect to the inverter and PC. Insert the bundled CD into a computer and follow on-screen instructions to install the monitoring software. For detailed software operation, please check the user manual of the software inside the CD.
- Wi-Fi cloud communication (option): Please use the supplied communication cable to connect to the inverter and Wi-Fi module. Download the APP and install it from the APP store. Refer to the "Wi-Fi Plug Quick Installation Guideline" to set up the network and register. The inverter status will be shown by the mobile phone APP or webpage of the computer.
- GPRS cloud communication (option): Please use the supplied communication cable to connect to the inverter and GPRS module, and then apply it externally to the GPRS module. Download the APP and install it from the APP store. Refer to the "GPRS RTU Quick Installation Guideline" to set up the network and register. The inverter status will be shown by the mobile phone APP or webpage of the computer.
4. Operating
4.1 Power On/Off
Once the unit has been properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.
Steps to start up:
Connect the battery that meets the requirements (battery voltage needs to be beyond 23V) or AC (AC needs to confirm the suitable input range depending on the output mode), then you can start up the inverter.
- Mains power on: Connect to normal AC power, press the switch, the system will automatically turn on. If you set AC output power priority, after waiting for a period of time, the panel will display AC mode that represents the machine is successfully turned on, then it will enter AC mode.
- Battery boot: Connect to battery, press the power-on button to establish a working power source. The system will automatically turn on. After waiting for a period of time, the panel will display battery mode that represents the machine is successfully turned on, then it will enter battery mode.
Shutdown steps:
When the system is in battery mode or AC mode output, press the switch again, then the system will be turned off.
4.2 Operation and Display Panel
The operation and display panel, shown in the below chart, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.

Figure 5: Front panel with LCD display, LED indicators, and function keys.
LED Indicator
| LED Indicator | Messages |
|---|---|
| AC/INV (Green) | Solid On: Output is powered by utility in Line mode. Flashing: Output is powered by battery or PV in battery mode. |
| CHG (Green) | Solid On: Battery is fully charged. Flashing: Battery is charging. |
| FAULT (Red) | Solid On: Fault occurs in the inverter. Flashing: Warning condition occurs in the inverter. |
Function Keys
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
LCD Display Icons
| Icon | Function Description |
|---|---|
| AC | Indicates the AC input. |
| PV | Indicates the PV input. |
| INPUT/BATT/kW | Indicates input voltage, input frequency, PV voltage, charger current, charger power, battery voltage. |
| OUTPUT/BATT/kW | Indicates output voltage, output frequency, load percent, load in VA, load in Watt and discharging current. |
| CHARGING | Indicates battery level by 0-24%, 25-49%, 50-74% and 75-100% in battery mode and charging status in line mode. |
4.3 LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press the "UP" or "DOWN" button to select setting programs. Then, press the "ENTER" button to confirm the selection or the ESC button to exit.
Setting Programs:
| Program | Description | Selectable Option |
|---|---|---|
| 00 | Exit setting mode | Escape |
| 01 | Output source priority: To configure load power source priority | Utility first (default): Utility will provide power to the loads as first priority. Solar and battery energy will provide power to the loads only when utility power is not available. Solar first: Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, Utility energy will supply power to the loads at the same time. BU priority: Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time. Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or the setting point in program 12. |
| 02 | Maximum charging current: To configure total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current) | 60A (default). Setting range is from 10A to 100A. Increment of each click is 10A. |
| 03 | AC input voltage range | Appliances (default): If selected, acceptable AC input voltage range will be within 90-280VAC. UPS: If selected, acceptable AC input voltage range will be within 170-280VAC. |
| 05 | Battery type | AGM (default) Flooded User-Defined: If "User-Defined" is selected, battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29. |
| 06 | Auto restart when overload occurs | Restart disable (default) Restart enable |
| 07 | Auto restart when over temperature occurs | Restart disable (default) Restart enable |
| 08 | ECO function: System will temporarily stop when the load is low in battery mode. | Disable (default) Enable |
| 09 | Output frequency | 50Hz (default) 60Hz |
| 10 | Output voltage | 220V 230V (default) 240V |
| 11 | Maximum utility charging current | 30A (default). Setting range is 2A, then from 10A to 60A. Increment of each click is 10A. |
| 12 | Setting voltage point back to utility source when selecting "SBU priority" in program 01. | Available options in 3KVA model: 23.0V (default). Setting range is from 22V to 25.5V. Increment of each click is 0.5V. Available options in 5KVA model: 46V (default). Setting range is from 44V to 51V. Increment of each click is 1V. |
| 13 | Setting voltage point back to battery mode when selecting "SBU priority" in program 01. | Available options in 3KVA model: Battery fully charged. 27V (default). Setting range is from 24V to 29V. Increment of each click is 0.5V. |
| 23 | Overload bypass: When enabled, the unit will transfer to line mode if overload occurs in battery mode. | Bypass disable (default) Bypass enable |
| 25 | Record Fault code | Record enable (default) Record disable |
| 26 | Bulk charging voltage (C.V voltage) | 3KVA default setting: 28.2V 5KVA default setting: 56.4V. If self-defined is selected in program 5, this program can be set up. Setting range is from 25.0V to 31.5V for 3KVA model and 48.0V to 61.0V for 5KVA model. Increment of each click is 0.1V. |
| 27 | Floating charging voltage | 3KVA default setting: 27.0V 5KVA default setting: 54.0V Default: 28 OFF |
| 28 | Reset factory setting | 00 82 935 |
| 29 | Low DC cut-off voltage: If battery power is only power source available, inverter will shut down. If PV energy and battery power are available, inverter will charge battery without AC output. | If self-defined is selected in program 5, this program can be set up. Setting range is from 21.0V to 24.0V for 3KVA model and 42.0V to 48.0V for 5KVA model. Increment of each click is 0.1V. Low DC cut-off voltage will be fixed to setting value no matter what percentage of load is connected. |
| 30 | Battery equalization | Battery equalization disable (default). If "Flooded" or "User Defined" is selected in program 05, this program can be set up. |
| 31 | Battery equalization voltage | 3KVA default setting: 29.2V 5KVA default setting: 58.4V. Setting range is from 25.0V to 31.5V for 3KVA mode and 48.0V to 61.0V for 5KVA model. Increment of each click is 0.1V. |
| 33 | Battery equalized time | 60min (default). Setting range is from 5min to 900min. Increment of each click is 5min. |
| 34 | Battery equalized timeout | 120min (default). Setting range is from 5min to 900min. Increment of each click is 5min. |
| 35 | Equalization interval | 30days (default). Setting range is from 0 to 90 days. Increment of each click is 1 day. |
| 36 | Equalization activated immediately | Enable: If equalization function is enabled in program 30, this program can be set up. If "Enable" is selected in this program, it's to activate battery equalization immediately and LCD main page will show "69". Disable (default): If "Disable" is selected, it will cancel equalization function until next activated equalization time arrives based on program 35 setting. At this time, "E9" will not be shown in LCD main page. |
| 37 | BMS Function Switch | Off (default): Whether to enable the BMS communication function. On |
| 38 | Bat Soc Under Lock | BMS low voltage SOC value, if the BMS SOC value is lower than the set value, the inverter will shut down to protect the battery. |
| 39 | Bat Soc Turn To Ac | When the working mode of the inverter is set to the battery priority mode, the inverter will be forced to enter the mains charging when the SOC of the BMS is lower than the set value. |
| 40 | Bat Soc Turn To Dc | When the working mode of the inverter is set to the battery priority mode, the inverter resumes the DC working mode when the SOC of the BMS is higher than the set value. |
| 41 | Bat Restart Soc | When the inverter is turned on, the SOC must be higher than the set value to work normally. |
5. Maintenance
5.1 Battery Equalization
Equalization function is added into the charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize the battery periodically.
How to Apply Equalization Function
You must enable the battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in the device by either one of the following methods:
- Setting equalization interval in program 35.
- Active equalization immediately in program 36.
When to Equalize
In stage, when the setting equalization interval (battery equalization cycle) is reached, or equalization is active immediately, the controller will start to enter the Equalize stage.
Equalize Charging Time and Timeout
In the Equalize stage, the controller will supply power to charge the battery as much as possible until the battery voltage raises to the battery equalization voltage. Then, constant-voltage regulation is applied to maintain the battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until the set battery equalized time is reached.
However, if in the Equalize stage, the battery equalized time is expired and the battery voltage doesn't rise to the battery equalization voltage point, the charge controller will extend the battery equalized time until the battery voltage achieves the battery equalization voltage. If the battery voltage is still lower than the battery equalization voltage when the battery equalized timeout setting is over, the charge controller will stop equalization and return to the float stage.
5.2 General Maintenance Tips
- Regularly check all connections for tightness and corrosion.
- Keep the inverter's ventilation openings clear of dust and debris to ensure proper airflow and prevent overheating.
- Periodically inspect the unit for any signs of damage or wear.
- Ensure the operating environment is within the specified temperature and humidity ranges.
6. Troubleshooting
6.1 Warning Descriptions
Alarm: The red LED flashes, and the LCD displays an alarm code. The inverter does not enter the failure mode.
Warning Indicator
| Warning Code | Warning Event | Audible Alarm | Icon Flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second | DIA |
| 02 | Over temperature | None | UCΔ |
| 03 | Battery is over-charged | Beep once every second | 03 |
| 04 | Low battery | Beep once every second | 04 |
| 07 | Overload | Beep once every 0.5 second | OVER LOAD |
| 10 | Output power derating | Beep twice every 3 seconds | 10 |
| 15 | PV energy is low. | Beep twice every 3 seconds | 15 |
| 16 | High AC input (>280VAC) during BUS soft start | None | 16 |
| 49 | Battery equalization | None | ERA |
| 6P | Battery is not connected | None | БРА |
6.2 Fault Descriptions
Fault: The inverter enters the fault mode, the red LED light is always on and the LCD displays the fault code.
Fault Reference Code
| Fault Code | Fault Event | Icon on |
|---|---|---|
| 01 | Fan is locked when inverter is off. | 0 |
| 02 | Over temperature or NTC is not connected well. | 02- |
| 03 | Battery voltage is too high. | 03- |
| 04 | Battery voltage is too low. | 04- |
| 05 | Output short circuited or over temperature is detected by internal converter components. | 05- |
| 06 | Output voltage is too high. | 06- |
| 07 | Over load time out. | 07- |
| 08 | Bus voltage is too high | 08- |
| 09 | Bus soft start failed | 09 |
| 51 | Over currents or surge | 5 |
| 52 | Bus voltage is too low | 52 |
| 53 | Inverter soft start failed | 53- |
| 55 | Over DC voltage in AC output | 55- |
| 57 | Current sensor failed | 57- |
| 58 | Output voltage is too low | 58- |
| 59 | PV voltage is over limitation | 59 |
6.3 Trouble Removal
| Problem | LCD/LED/Buzzer | Explanation/Possible Cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD/LEDs and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication | 1. The battery voltage is far too low (<1.4V/Cell) 2. Internal fuse tripped. | 1. Contact repair center for replacing the fuse. 2. Re-charge battery. |
| Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped | 3. Replace battery. Check if AC breaker is tripped and AC wiring is connected well. | |
| Mains exist but the unit works in battery mode. | Green LED is flashing | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UP-->sppliance) |
| Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. | |
| When the unit is turned on, internal relay is switched on and off repeatedly. | LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. |
| Buzzer beeps continuously and red LED is on. | Fault code 07 | Overload error. The inverter is overload 105% and time is up. If PV input voltage is higher than specification, the output power will be derated. At this time, if connected loads is higher than derated output power, it will cause overload. | Reduce the connected load by switching off some equipment. Reduce the number of PV modules in series or the connected load. |
| Fault code 05 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Fault code 02 | Temperature internal converter component is over 120°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Fault code 03 | Battery is over-charged. The battery voltage is too high. | Return to repair center. Check if spec and quantity of batteries are meet requirements. | |
| Fault code 01 | Fan fault | Replace the fan. | |
| Fault code 06/58 | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center. | |
| Fault code 08/09/53/57 | Internal components failed. | Return to repair center. | |
| Fault code 51 | Over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
| Fault code 52 | Bus voltage is too low. | ||
| Fault code 55 | Output voltage is unbalanced. | ||
| Fault code 59 | PV input voltage is beyond the specification. | Reduce the number of PV modules in series. |
7. Specifications
7.1 Technical Datasheet (Model DT4811B)
| Category | Parameter | Value |
|---|---|---|
| Input | Input Sources | L+N+PE |
| Rated Input Voltage | 220/230/240VAC | |
| Voltage Range | 90-280VAC±3V (APL Mode) / 170-280VAC±3V (UPS Mode) | |
| Output | Rated Capacity | 11000W |
| Output Voltage | 220/230/240VAC±5% | |
| Output Frequency | 50/60Hz±0.1% | |
| Waveform | Pure Sine Wave | |
| Peak Power | 22000VA | |
| Battery | Battery Voltage | 48Vdc |
| Constant Charging Voltage (Adjustable) | 56.4Vdc | |
| Chargers | PV Charging Mode | MPPT Dual MPPT |
| Max PV Input Power | 2*5500W | |
| MPPT Tracking Range | 90-500Vdc | |
| Max PV Input Voltage | 500Vdc | |
| Max PV Charging Current | 150A | |
| Max AC Charging Current | 150A | |
| Max Charging Current | 150A | |
| Interface | Communication Port | Lithium Battery BMS Communication Card, WifiCard, Dry Contact |
| Parallel Connect Interface | With parallel function | |
| Environments | Operating Temperature | -10-50°C |
| Storage Temperature | -15-60°C | |
| Humidity | 20%-95% (Non-condensing) | |
| Noise | ≤50dB |

Figure 6: Detailed Technical Datasheet for DT4811B.
7.2 Physical Specifications
- Size: 70.80 x 57.00 x 24.10 cm
- Weight: 21.94 kg
- Protection Degree: IP21
8. User Tips
- Check for correct version: Verify the model number (e.g., DT-4811B-C-EU) upon delivery to ensure it matches your order, especially regarding power specifications.
- Inspect packaging: Always check the packaging for any damage upon arrival. The product is typically well-packaged.
- Verify contents: Ensure all listed accessories, including the user manual and parallel connection cable, are present.
- Consult the manual for wiring: Pay close attention to the wiring diagrams and instructions for battery, AC, and PV connections to ensure correct polarity and cable sizing.
- Parallel operation: The inverter supports parallel connection. Refer to the manual for detailed instructions on setting up multiple units.
9. Support
For any technical assistance, warranty claims, or service inquiries, please contact your local dealer or the authorized service center. Ensure to provide your product model number and serial number for efficient support.
A user manual in PDF format is available for download: Download User Manual (PDF)