Contents

DATOUBOSS Hybrid Solar Inverter User Manual

Models: DT4862L (6200W 48V) / DT2430 (3000W 24V)

Brand: DATOUBOSS

1. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION - To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION - Only qualified personnel can install this device with battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Refer to the INSTALLATION section of this manual for details.
  10. One piece of 150A fuse is provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

2. Introduction

2.1 Product Overview

The DATOUBOSS Hybrid Solar Inverter is a multi-function inverter/charger that combines the functions of an inverter, solar charger, and battery charger to provide uninterruptible power support. Its comprehensive LCD display offers user-configurable and easy-accessible button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.

2.2 Features

  • Pure sine wave inverter output.
  • Configurable input voltage range for home appliances and personal computers via LCD setting.
  • Configurable battery charging current based on applications via LCD setting.
  • Configurable AC/Solar Charger priority via LCD setting.
  • Compatible with mains voltage or generator power.
  • Auto restart while AC is recovering.
  • Overload, over temperature, and short circuit protection.
  • Smart battery charger design for optimized battery performance.
  • Cold start function.
  • Optional WiFi module for convenient real-time monitoring (purchased separately).
  • CE, FCC, PSE certifications.

2.3 Basic System Architecture

The inverter/charger is designed to work within a complete system that may include a generator or utility power source and PV modules. Consult with your system integrator for specific configurations.

Basic System Architecture Diagram
Figure 1: Basic System Architecture. This diagram illustrates the inverter connected to solar panels (Solar power), a generator or utility, external battery packs, and various home appliances.

This inverter can power various appliances in home or other environments, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners.

3. Setup (Installation)

3.1 Unpacking and Inspection

Before installation, carefully inspect the unit for any damage. The package should contain one inverter unit and one user manual.

3.2 Preparation

Before connecting any wires, remove the bottom cover by unscrewing the two screws as shown in the product diagrams.

3.3 Mounting the Unit

Consider the following points when selecting an installation location:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install the inverter at eye level for easy reading of the LCD display.
  • For proper air circulation and heat dissipation, allow a clearance of approximately 20 cm to the sides and 50 cm above and below the unit.
  • The ambient temperature should be within the optimal operating range.
  • The recommended installation position is vertically on a wall.
  • Ensure sufficient space for heat dissipation and wire removal.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing three screws:

  • Use M6*80mm expansion bolts for points 1 and 2.
  • Use M4 or M5 screws for point 3.
Inverter Mounting Dimensions and Views
Figure 2: Inverter Mounting Dimensions and Various Views. This image shows the front, side, and bottom views of the inverter, along with recommended clearances for installation (20cm side, 50cm top/bottom) and mounting points.

3.4 Battery Connection

CAUTION: For safety and compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. Refer to the table below for recommended fuse or breaker sizes.

WARNING! All wiring must be performed by qualified personnel. Use appropriate cable for battery connection to reduce risk of injury.

Rated Capacity Typical Amperage Battery Capacity Wire Size Cable (mm²) Dimensions D(mm) Dimensions L(mm) Torque value
3KVA132A100AH/200AH1*4AWG / 2*8AWG22 / 96.4 / 6.433.2 / 29.22~3 Nm
3.6KVA165A200AH2*4AWG258.433.25Nm
4KVA165A200AH2*4AWG258.433.25Nm
5.5KVA121A200AH1*2AWG / 2*6AWG34 / 146.4 / 6.439.2 / 33.22~3 Nm
6.2KVA124A200AH1*2AWG / 2*4AWG38 / 258.4 / 8.439.2 / 33.25Nm
11KVA228A250AH1*3/0AWG858.4545Nm

Follow these steps for battery connection:

  1. Assemble battery ring terminals based on recommended cable and terminal size.
  2. Insert battery wires flatly into the inverter's battery connectors. Ensure bolts are tightened to 2 Nm in a clockwise direction. Verify correct polarity at both the battery and inverter/charger.

WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.

CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).

Battery Connection Diagram for 24V and 48V Inverters
Figure 3: Battery Connection Diagram. This diagram shows how to connect 12V batteries in series for 24V and 48V inverter systems.

3.5 AC Input/Output Connection

CAUTION!! Before connecting to AC input power source, install a separate AC breaker between the inverter and the AC input source. This ensures the inverter can be disconnected for maintenance and protected from overcurrent. Recommended breaker: 32A for 24V system, 63A for 48V system.

CAUTION!! There are two terminal blocks: "IN" and "OUT". Do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by qualified personnel. Use appropriate cable for AC input connection to reduce risk of injury.

Rated Capacity Gauge Torque value
3KVA12AWG1.2~1.6Nm
3.6KVA12AWG1.2~1.6Nm
4KVA12AWG1.2~1.6Nm
5.5KVA10AWG1.4~1.6Nm
6.2KVA10AWG1.4~1.6Nm
11KVA8AWG1.4~1.6Nm

Follow these steps to implement AC input/output connection:

  1. Before making AC input/output connection, open the DC protector or disconnector.
  2. Remove 10mm insulation from six conductors. Shorten phase L and neutral conductor N by 3mm.
  3. Insert AC input wires according to polarities (Ground: yellow-green, L-LINE: brown or black, N-Neutral: blue) and tighten terminal screws. Connect PE protective conductor first.
  4. Ensure wires are securely connected.

WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.

CAUTION: Appliances like air conditioners require 2-3 minutes to restart. A power shortage and quick recovery can damage connected appliances. Check if your appliance has a time-delay function.

3.6 PV Connection (For models with solar charger)

CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.

WARNING! All wiring must be performed by qualified personnel. Use appropriate cable for PV module connection to reduce risk of injury.

Typical Amperage Gauge Torque Value
30A12AWG1.4~1.6Nm

PV Module Selection:

  • The open circuit voltage (Voc) of PV modules must not exceed the maximum PV array open circuit voltage of the inverter.
  • The maximum supply voltage of PV modules should be close to the optimal PV access voltage range of the inverter for best performance.
  • If one PV module cannot meet this requirement, connect multiple PV modules in series.

PV Module Wire Connection Steps:

  1. Remove 10mm insulation sleeve for positive and negative conductors.
  2. Suggest putting bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Fix wire cover to the inverter with supplied screws.
  4. Check correct polarity of wires from PV modules and PV input connectors. Connect positive pole (+) to positive pole (+) and negative pole (-) to negative pole (-). Screw two wires tightly (4mm blade screwdriver recommended).

3.7 Final Assembly

After connecting all wirings, replace the bottom cover by screwing the two screws back into place.

4. Operating Instructions

4.1 Power ON/OFF

Once the unit is properly installed and batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

4.1.1 Steps to Start Up

Connect the battery (voltage needs to be beyond 23V) or AC power (ensure suitable input range based on output mode). Then, you can start up the inverter.

  • Mains Power On: Connect to normal AC power, press the switch. The system will automatically turn on. If AC output priority is set, the panel will display 'AC mode' after a period, indicating successful power-on.
  • Battery Boot: Connect to battery, press the power-on button. The system will automatically turn on. The panel will display 'Battery mode' after a period, indicating successful power-on.

4.1.2 Shutdown Steps

When the system is in battery mode or AC mode output, press the switch again to turn off the system.

4.2 Operation and Display Panel

The front panel of the inverter features an LCD display, three indicators (Status, Charging, Fault), and four function keys (ESC, UP, DOWN, ENTER) to show operating status and power information.

Inverter LCD Display and Back Panel Overview
Figure 4: Inverter LCD Display and Back Panel Overview. This image labels the LCD display, status indicators, function keys, and various ports on the back panel including AC input/output, battery input, PV input, communication ports, and power switch.

4.2.1 LED Indicators

Indicator Color Status Message
AC/INVGreenSolid On
Flashing
Output powered by utility (Line mode)
Output powered by battery or PV (Battery mode)
CHGYellowSolid On
Flashing
Battery fully charged
Battery is charging
FAULTRedSolid On
Flashing
Fault occurs in inverter
Warning condition occurs in inverter

4.2.2 Function Keys

Function Key Description
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm selection in setting mode or enter setting mode

4.2.3 LCD Display Icons

The LCD displays various information using icons and numerical values. These include input source information (AC, PV1, PV2), left digital display (input voltage, frequency, battery voltage, PV voltage, charger current), middle digital display (setting programs, warning/fault codes), right digital display (output voltage, frequency, load percent, load VA, load W, PV charger power, DC discharging current), battery information (level, type), load information (overload, load level), mode operation information (utility connection, PV connection, solar charger, DC/AC inverter), and mute operation status.

4.3 Display Setting

Pressing "UP" or "DOWN" keys cycles through various display screens, showing information such as input voltage, output voltage, input/output frequency, battery voltage, load percentage, load in Watt/VA, PV charger power, DC discharging current, and firmware versions.

4.4 Operating Mode Description

The inverter operates in different modes, each with specific behaviors and LCD indications:

  • Standby Mode: Inverter is not turned on, but can charge batteries from solar or utility.
  • Line Mode: Output power from utility, charger available. Utility charges battery and provides power to load.
  • Battery Mode: Output power from battery or PV.
  • Only PV Mode: Output power from PV only.

4.5 LCD Setting Programs

To enter setting mode, press and hold the ENTER button for 3 seconds. Use "UP" or "DOWN" to select programs, then "ENTER" to confirm or "ESC" to exit.

Key configurable settings include:

  • Program 01: Output source priority selection (Solar first, SBU priority, Utility first).
  • Program 02: Maximum charging current (10A increments).
  • Program 03: AC input voltage range (Appliances: 90-280VAC, UPS: 170-280VAC).
  • Program 05: Battery type (AGM, Flooded, User-Defined, LiA-protocol, Pylontech, Techfine, Growatt, LIB-protocol, 3rd party lithium).
  • Program 06: Auto restart when overload occurs (Enable/Disable).
  • Program 07: Auto restart when over temperature occurs (Enable/Disable).
  • Program 08: ECO function (Enable/Disable system stop at low load in battery mode).
  • Program 09: Output frequency (50Hz/60Hz).
  • Program 10: Output voltage (220V/230V/240V).
  • Program 11: Maximum utility charging current (2A-max AC charging current).
  • Program 12: Setting voltage point back to utility source (22V-25.5V for 24V, 44V-51V for 48V).
  • Program 13: Setting voltage point back to battery mode (24V-29V for 24V, 48V-58V for 48V).
  • Program 16: Charger source priority (Solar first, Solar and Utility, Only Solar).
  • Program 18: Alarm control (On/Off).
  • Program 19: Auto return to default display screen (Enable/Disable).
  • Program 20: Backlight control (On/Off).
  • Program 22: Beeps while primary source is interrupted (On/Off).
  • Program 23: Overload bypass (Enable/Disable).
  • Program 24: Battery low voltage (20.0V-27.0V for 24V, 40.0V-54.0V for 48V).
  • Program 25: Record fault code (Enable/Disable).
  • Program 26: Bulk charging voltage (C.V voltage) (24.0V-30.0V for 24V, 48.0V-60.0V for 48V).
  • Program 27: Floating charging voltage (Default 27.0V for 24V, 54.0V for 48V).
  • Program 28: Reset factory setting.
  • Program 29: Low DC cut-off voltage (20.0V-26.0V for 24V, 40.0V-52.0V for 48V).
  • Program 30: Battery equalization (Enable/Disable).
  • Program 31: Battery equalization voltage (24.0V-30.0V for 24V, 48.0V-60.0V for 48V).
  • Program 33: Battery equalized time (5min-900min).
  • Program 34: Battery equalized timeout (5min-900min).
  • Program 35: Equalization interval (0-90 days).
  • Program 36: Equalization activated immediately (Enable/Disable).
  • Program 37: BMS Function Switch (On/Off).
  • Program 38: Bat Soc Under Lock (Lithium battery SOC value for shutdown).
  • Program 39: Bat Soc Turn To Ac (Lithium battery SOC value for AC charging).
  • Program 40: Bat Soc Turn To Dc (Lithium battery SOC value for DC working mode).
  • Program 41: Bat Restart Soc (Lithium battery SOC value for restart).
  • Program 43: Solar supply priority (Solar first, Load first).
  • Program 44: Solar energy feed to grid configuration (Enable/Disable).
  • Program 45: Reset PV energy storage.
  • Program 46: Start charging time for AC charger (00:00-23:00).
  • Program 47: Stop charging time for AC charger (00:00-23:00).
  • Program 48: Scheduled time for AC output on (00:00-23:00).
  • Program 49: Scheduled time for AC output off (00:00-23:00).
  • Program 50: Set country customized regulations (Mode 1-4 for grid feed-in voltage/frequency).
  • Programs 51-55: Time setting (Minute, Hour, Day, Month, Year).
  • Program 56: GRID-tie current (1A increments).
  • Program 60: Dual output (Enable/Disable).
  • Program 61: Enter the dual output functional voltage point.
  • Program 62: Enter the dual output functional SOC point.
  • Program 63: Dual battery voltage receiver.
  • Program 64: Dual battery SOC Receiver.
  • Program 65: Setting discharge time on the second output.
  • Program 66: Dual Recover Delay Time.
  • Program 67: Output Open Time.
  • Program 68: Output Stop Time.

5. Maintenance

5.1 Battery Equalization

The equalization function helps reverse the buildup of negative chemical effects like stratification and sulfation in batteries, which can reduce overall battery capacity. It is recommended to equalize batteries periodically.

5.1.1 How to Apply Equalization Function

Enable battery equalization in LCD setting program 30. Then, you can apply this function by:

  1. Setting the equalization interval in program 35.
  2. Activating equalization immediately in program 36.

5.1.2 When to Equalize

The controller enters the Equalize stage when the set equalization interval is reached or equalization is actively initiated.

5.1.3 Equalize Charging Time and Timeout

During the Equalize stage, the controller charges the battery until its voltage reaches the equalization voltage. Constant-voltage regulation maintains this level until the set battery equalized time is reached. If the battery voltage doesn't rise to the equalization point within the set time, the controller extends the time. If the voltage is still low after the equalization timeout, the controller stops equalization and returns to the float stage.

6. Troubleshooting

6.1 Fault and Alarm Descriptions

The inverter provides fault codes (red LED solid on) and alarm codes (red LED flashing) to indicate issues.

6.1.1 Fault Reference Code

Fault Code Fault Event
01Fan is locked when inverter is off.
02Over temperature or NTC is not connected well.
03Battery voltage is too high.
04Battery voltage is too low.
05Output short circuited or over temperature is detected by internal converter components.
06Output voltage is too high.
07Over load time out.
08Bus voltage is too high.
09Bus soft start failed.
51Over currents or surge.
52Bus voltage is too low.
53Inverter soft start failed.
55Over DC voltage in AC output.
57Current sensor failed.
58Output voltage is too low.
59PV voltage is over limitation.

6.1.2 Alarm Descriptions

Alarm Code Alarm Event Audible Alarm
01Fan is locked when inverter is on.Beep three times every second
02Over temperatureNone
03Battery is over-chargedBeep once every second
04Low batteryBeep once every second
07OverloadBeep once every 0.5 second
10Output power deratingBeep twice every 3 seconds
15PV energy is low.Beep twice every 3 seconds
16High AC input (>280VAC) during BUS soft startNone
E9Battery equalizationNone
bPBattery is not connectedNone

6.1.3 Code Reference (Communication Status)

Code Description
60 ▲If battery status is not allowed to charge and discharge after successful inverter-battery communication, code 60 will show to stop charging/discharging.
61 ▲Communication lost. Buzzer will beep if signal is not detected for 1 minute after battery connection, or immediately if communication is lost after successful connection.
69 ▲If battery status is not allowed to charge after successful inverter-battery communication, code 69 will show to stop charging.
70 ▲If battery status must charge after successful inverter-battery communication, code 70 will show to charge battery.
71 ▲If battery status is not allowed to discharge after successful inverter-battery communication, code 71 will show to stop discharge battery.

6.2 Trouble Removal

Problem LCD/LED/Buzzer Explanation/Possible Cause What to do
Unit shuts down automatically during startup process.LCD/LEDs and buzzer active for 3s then off.Battery voltage is too low (<1.91V/Cell).1. Re-charge battery.
2. Replace battery.
No response after power on.No indication.1. Battery voltage is far too low (<1.4V/Cell).
2. Internal fuse tripped.
1. Contact repair center for fuse replacement.
2. Re-charge battery.
3. Replace battery.
Input voltage displayed as 0 on LCD, green LED flashing.Input protector is tripped.Check if AC breaker is tripped and AC wiring is connected well.
Mains exist but unit works in battery mode.Green LED is flashing.Insufficient quality of AC power (Shore or Generator).1. Check if AC wires are too thin/long.
2. Check generator (if applied) is working well or if input voltage range setting is correct.
Green LED is flashing.Set "Solar First" as priority of output source.Change output source priority to Utility first.
When unit is turned on, internal relay switches on/off repeatedly.LCD display and LEDs are flashing.Battery is disconnected.Check if battery wires are connected well.
Buzzer beeps continuously and red LED is on.Fault code 07Overload error. Inverter is overloaded 105% and time is up.Reduce the connected load by switching off some equipment.
If PV input voltage is higher than specification, output power will be derated. If connected load is higher than derated output power, it will cause overload.Reduce the number of PV modules in series or the connected load.
Fault code 05Output short circuited.Check if wiring is connected well and remove abnormal load.
Fault code 02Internal converter component over 120°C. Internal inverter temperature over 100°C.Check whether air flow is blocked or ambient temperature is too high.
Fault code 03Battery is over-charged. Battery voltage is too high.Return to repair center. Check if battery specs and quantity meet requirements.
Fault code 01Fan fault.Replace the fan.
Fault code 06/58Output abnormal (Inverter voltage below 190Vac or higher than 260Vac).1. Reduce the connected load.
2. Return to repair center.
Fault code 08/09/53/57Internal components failed.Return to repair center.
Fault code 51Over current or surge.Restart the unit. If error persists, return to repair center.
Fault code 52Bus voltage is too low.
Fault code 55Output voltage is unbalanced.
Fault code 59PV input voltage is beyond the specification.Reduce the number of PV modules in series.

7. Specifications

7.1 General Product Properties

  • Voltage: 50V AC / 75V DC and above
  • High-concerned chemical: none
  • Socket Type: Europe
  • Conversion Efficiency: 0.9
  • Rated Power: 6200W (DT4862L), 3000W (DT2430)
  • Output Frequency: 60 Hz
  • Output Voltage: AC 220V±10%
  • Input Voltage: 220V-250V
  • Origin: Mainland China
  • Certification: CE, FCC, RoHS, pse, weee
  • Max PV Input Power: 8500W
  • Battery Voltage: 48V (42-64VDC) for DT4862L, 24V for DT2430

7.2 Model-Specific Specifications

DT2430 (24V/3000W)

  • Input voltage: 24V
  • Output voltage: 220V/230V/240V±5%
  • Rated power: 3000W
  • Charging current: Max 100A
  • Solar Voltage: Max 500VDC
  • Solar Voltage Range: 40-500VDC
  • Optimum voltage range: 300-400VDC

DT4862L (48V/6200W)

  • Input voltage: 48V (Battery voltage range: 42-64VDC)
  • Output voltage: 230VAC±5%, 50/60Hz
  • Rated power: 6200VA/6200W (PV&DC/AC: 6500VA/6500W)
  • Charging current: Max 120A (Solar mode); 100A (AC charger)
  • Solar Voltage: Max 500VDC
  • Solar voltage range: 60-500VDC (Vmp)
  • Optimum voltage range: 360-430VDC (Full load MPPT range)

7.3 Physical Dimensions

Inverter Dimensions
Figure 5: Inverter Dimensions. The image shows two inverter units with dimensions: 39cm (15.4in) height, 11cm (4.3in) depth, 30.5cm (12in) width for one, and 46.7cm (18.5in) height, 13.5cm (5.5in) depth, 31cm (12.2in) width for the other.

7.4 Technical Datasheet

Parameter DT2430 DT2436 DT2440 DT4855 DT4862L DT4811B
PV Charging ModeMPPTMPPTMPPTMPPTMPPTMPPT Dual MPPT
MAX.PV Input Power5000W6500W6500W8500W8500W2*5500W
MPPT Tracking Range60~500Vdc90-500Vdc
Best voltage300~400V300~400V300~400V360~430V360~430V300~400V
MAX.PV Input Voltage500Vdc500Vdc500Vdc500Vdc500Vdc500Vdc
PV max input current18A27A27A27A27A18A/18A
MAX.PV Charging Current100A120A120A100A120A150A
MAX.AC Charging Current60A100A100A100A100A150A
MAX.Charging Current100A120A120A100A120A150A

8. Parallel Function (Appendix I)

This section applies to models that support parallel operation.

8.1 Mounting the Unit for Parallel Operation

NOTE: For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below each unit. Ensure all units are installed at the same level.

Parallel Inverter Mounting
Figure 6: Parallel Inverter Mounting. This image shows multiple inverter units mounted side-by-side with recommended clearances (20cm between units, 50cm top/bottom).

8.2 Wiring Connection for Parallel Operation

NOTICE: It's required to connect to battery for parallel operation.

WARNING! Be sure the length of all battery cables is the same. Otherwise, there will be voltage difference between inverter and battery to cause parallel inverters not working.

The cable size for each inverter is shown in the table below. For multiple inverters, connect their battery cables together using a connector or bus-bar, then connect to the battery terminal. The cable size from the joint to the battery should be X times the cable size in the table, where X is the number of inverters connected in parallel.

Rated Capacity Wire Size Cable mm² Dimensions D (mm) Dimensions L (mm) Torque value
3KW1*4AWG226.433.22~3Nm
3.6KW2*4AWG258.433.25Nm
4KW2*4AWG258.433.25Nm
5.5KW1*2AWG386.439.22~3Nm
6.2KW1*2AWG388.439.22~3Nm
11KW1*3/0AWG858.4545Nm

WARNING!! Make sure all output N wires of each inverter must be connected all the time. Otherwise, it will cause inverter fault in error code #72.

CAUTION!! Install the breaker at the battery and AC input side. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of battery or AC input.

Rated Capacity 1 unit*
3KW150A/70VDC
3.6KW200A/70VDC
4KW200A/70VDC
5.5KW150A/70VDC
6.2KW150A/70VDC
11KW300A/70VDC

*If you want to use only one breaker at the battery side for the whole system, the rating of the breaker should be X times current of 1 unit. 'X' indicates the number of inverters connected in parallel.

Rated Capacity 2 units 3 units 4 units 5 units 6 units 7 units 8 units 9 units
3KW80A/230VAC120A/230VAC160A/230VAC200A/230VAC240A/230VAC280A/230VAC320A/230VAC360A/230VAC
3.6KW80A/230VAC120A/230VAC160A/230VAC200A/230VAC240A/230VAC280A/230VAC320A/230VAC360A/230VAC
4KW80A/230VAC120A/230VAC160A/230VAC200A/230VAC240A/230VAC280A/230VAC320A/230VAC360A/230VAC
5.5KW80A/230VAC120A/230VAC160A/230VAC200A/230VAC240A/230VAC280A/230VAC320A/230VAC360A/230VAC
6.2KW80A/230VAC120A/230VAC160A/230VAC200A/230VAC240A/230VAC280A/230VAC320A/230VAC360A/230VAC
11KW120A/230VAC180A/230VAC240A/230VAC300A/230VAC360A/230VAC///

Note 1: A circuit breaker should also be installed at the AC input of each inverter, with selection based on the AC input current of the machine nameplate.

Note 2: For three-phase systems, use a 4-pole breaker directly. Its rating should be compatible with the phase current limitation from the phase with maximum units.

Inverter parallel numbers 2 3 4 5 6 7 8 9
Battery Capacity for 3KW400AH600AH800AH1000AH1200AH1400AH1600AH1800AH
Battery Capacity for 3.6KW400AH600AH800AH1000AH1200AH1400AH1600AH1800AH
Battery Capacity for 4KW400AH600AH800AH1000AH1200AH1400AH1600AH1800AH
Battery Capacity for 5.5KW400AH600AH800AH1000AH1200AH1400AH1600AH1800AH
Battery Capacity for 6.2KW400AH600AH800AH1000AH1200AH1400AH1600AH1800AH
Battery Capacity for 11KW500AH750AH1000AH1250AH1500AH///

WARNING! Be sure that all inverters will share the same battery bank. Otherwise, the inverters will transfer to fault mode.

8.2.4 Parallel Operation in Single Phase

Power Connection (Each photovoltaic panel needs to be connected to an independent system)

Two Inverters in Parallel - Single Phase
Figure 7: Two Inverters in Parallel - Single Phase. This diagram shows the wiring for two inverters connected in parallel to a shared battery bank, utility, load, and individual PV inputs.

8.2.5 Support 3-Phase Equipment

WARNING: Do not connect the current sharing cable between inverters which are in different phases. Otherwise, it may damage the inverters.

Various configurations for 3-phase equipment are possible, including three inverters in each phase, or mixed configurations. Refer to the detailed diagrams in the PDF manual for specific wiring instructions.

8.3 PV Connection for Parallel Operation

CAUTION: Each inverter should connect to PV modules separately.

Refer to the user manual of the single unit for PV Connection details.

8.4 LCD Setting and Display for Parallel Operation

When units are used in parallel with single phase, select "PAL" in program 04. For 3-phase equipment, select "3P1", "3P2", "3P3" for L1, L2, L3 phases respectively in program 04. Ensure current sharing cables are connected to units on the same phase. Do NOT connect current sharing cables between units on different phases. Power saving function will be automatically disabled.

8.4.1 Fault Code Display for Parallel Operation

Fault Code Fault Event
60Power feedback protection
71Firmware version inconsistent
72Current sharing fault
73Inconsistent output voltage settings in parallel-connected systems
80CAN fault
81Host loss
82Synchronization loss
83Battery voltage detected different
84AC input voltage and frequency detected different
85AC output current unbalance
86AC output mode setting is different

8.5 Commissioning for Parallel Operation

  1. Step 1: Check Requirements
    Ensure correct wire connection. Ensure all breakers in Line wires of the load side are open and each Neutral wire of each unit is connected together.
  2. Step 2: Configure LCD Setting
    Turn on each unit and set "PAL" in LCD setting program 04 of each unit. Then shut down all units. NOTE: It's necessary to turn off the switch when setting the LCD program; otherwise, the setting cannot be programmed.
  3. Step 3: Turn on each unit.

NOTE: Master and slave units are randomly defined.

9. User Tips

  • The optional WiFi module for remote monitoring must be purchased separately. It is not included with the inverter.
  • Always ensure proper ventilation around the inverter to prevent overheating, especially during high load operation.
  • When connecting batteries, double-check polarity and ensure all connections are tight to prevent faults and ensure efficient operation.
  • For optimal performance and longevity, adhere to the recommended cable sizes for battery, AC, and PV connections.
  • If you experience persistent errors after consulting the troubleshooting guide, contact your local dealer or service center for maintenance.

10. Warranty and Support

For any technical support, service, or warranty inquiries, please contact your authorized DATOUBOSS dealer or the service center where you purchased the product. Ensure you have your product model and serial number available when contacting support.

A user manual in PDF format is available for download: View User Manual (PDF)