1. Introduction
1.1 Purpose
This manual describes the assembly, installation, operation, and troubleshooting of the DATOUBOSS DT4811B-48V-A-EU Hybrid Solar Inverter. Please read this manual carefully before installation and operation. Keep this manual for future reference.
1.2 Scope
This manual provides safety and installation guidelines, as well as information on tools and wiring for the inverter.
1.3 Features
- Pure sine wave inverter output.
- Configurable input voltage range for home appliances and personal computers via LCD setting.
- Configurable battery charging current based on applications via LCD setting.
- Configurable AC/Solar Charger priority via LCD setting.
- Compatible with mains voltage or generator power.
- Auto restart while AC is recovering.
- Overload/Over temperature/short circuit protection.
- Smart battery charger design for optimized battery performance.
- Cold start function.
- Dual MPPT solar charger with a wide voltage range (90-500VDC).
- Max PV input power of 11000W (2 x 5500W).
- Max charging current of 150A.
- Supports battery-less operation.
- Multi-level protection features.
1.4 Basic System Architecture
The inverter/charger combines functions of an inverter, solar charger, and battery charger to offer uninterruptible power support. It can power various appliances, including motor-type appliances like tube lights, fans, refrigerators, and air conditioners. The system typically includes the inverter, a generator or utility connection, PV modules, and external battery packs.
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION: Only qualified personnel can install this device with a battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow the required specifications to select the appropriate cable size. It is very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Refer to the INSTALLATION section of this manual for details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to the local dealer or service center for maintenance.
3. Product Overview
3.1 Dimensions and Accessories
The inverter unit measures approximately 47 cm (18.5 in) in width, 55 cm (21.7 in) in depth, and 14.5 cm (5.7 in) in height. The package includes the inverter unit, a user manual, various cables, connectors, and mounting hardware.

Figure 3.1: Inverter Dimensions and Accessories (Width: 47cm/18.5in, Depth: 55cm/21.7in, Height: 14.5cm/5.7in)
3.2 External View and Components
Familiarize yourself with the front panel display and rear panel connections of the inverter.

Figure 3.2: External View and Component Description
Front Panel Components:
- LCD Display
- Charging Indicator
- Status Indicator
- ESC Button
- UP Button
- Fault Indicator
- ENTER Button
- DOWN Button
- Power ON/OFF Switch
Rear Panel Connections:
- Dry Contact
- Second Output
- BMS/RS485 Communication Port
- Main Output
- AC Input
- Fan
- Solar Panel Input (PV1, PV2)
- RS232 Communication Port
- Parallel Connection Port
- Battery Input (DC Input)
3.3 LCD Screen Overview
The LCD screen provides real-time information about the inverter's status, input/output parameters, and operational modes. It includes various icons and numerical displays for easy monitoring.
LCD Display Icons:
- Input Source Information: Icons for AC input, PV input, and numerical displays for input voltage, frequency, PV voltage, charger current, charger power, and battery voltage.
- Configuration Program and Fault Information: Displays setting programs, warning codes, and fault codes.
- Output Information: Displays output voltage, frequency, load percentage, load in VA, load in Watt, and discharging current.
- Battery Information: Indicates battery level (0-24%, 25-49%, 50-74%, 75-100%) and charging status.
4. Setup and Installation
4.1 Unpacking and Inspection
Before installation, please inspect the unit. Ensure that nothing inside the package is damaged. You should have received the inverter unit (x1) and user manual (x1).
4.2 Preparation
Before connecting any wires, remove the bottom cover by unscrewing the two screws as shown in the manual.
4.3 Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level to allow the LCD display to be read easily.
- For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the sides and 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 50°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Be sure to keep other objects and surfaces clear to guarantee sufficient heat dissipation and space for removing wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two screws. Use M6*80mm expansion bolts.
4.4 Battery Connection
CAUTION:
- For safety and regulation compliance, it is requested to install a separate DC over-current protector or disconnect device between the battery and inverter.
- All wiring must be performed by qualified personnel.
- It is very important for system safety and efficient operation to use appropriate cables for battery connection.
Refer to the specifications table for recommended battery cable and terminal sizes based on amperage and battery capacity. Assemble battery ring terminals and connect battery wires flatly into battery connectors, ensuring correct polarity and tightening bolts with a torque of 2 Nm.
4.5 AC Input/Output Connection
CAUTION:
- Before connecting to an AC input power source, install a separate AC breaker between the inverter and AC input source. Recommended breaker specs: 32A for 3KW and 50A for 5KW.
- There are two terminal blocks with "IN" and "OUT" markings. Do NOT mis-connect input and output connectors.
Refer to the specifications table for suggested cable requirements for AC wires. Follow these steps:
- Before making AC input/output connections, ensure the DC protector or disconnector is open.
- Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3mm.
- Insert AC input wires according to polarities indicated on the terminal block (Ground: yellow-green, Line: brown or black, Neutral: blue) and tighten the terminal screws. Connect the PE protective conductor first.
- Make sure the wires are securely connected.
CAUTION:
Appliances like air conditioners require 2-3 minutes to restart. If power shortages occur and recover quickly, it can damage connected appliances. Check if your air conditioner has a time-delay function. Otherwise, the inverter may trigger an overload fault.
4.6 PV Connection (For models with solar charger)
CAUTION:
- Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.
- All wiring must be performed by qualified personnel.
- It is very important for system safety and efficient operation to use appropriate cables for PV module connection.
Refer to the specifications table for suggested cable requirements for PV wires (e.g., 10A, 12AWG, 1.4-1.6Nm). When choosing PV modules, ensure the open circuit voltage (Voc) does not exceed the maximum PV array open circuit voltage of the inverter (500VDC). The supply voltage should be close to the optimal PV access voltage range (300-400VDC) for best performance. Connect multiple PV modules in series if one cannot meet the requirements.
PV Module Wire Connection Steps:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Suggest putting bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Fix the wire cover to the inverter with supplied screws.
- Check the correct polarity of wires from PV modules and PV input connectors. Connect positive to positive and negative to negative. Screw two wires tightly in a clockwise direction. Recommended tool: 4mm blade screwdriver.
4.7 Final Assembly
After connecting all wirings, put the bottom cover back by screwing the two screws.
4.8 Communication Connection
- PC Connection: Use the supplied communication cable to connect to the inverter and PC. Insert the bundled CD into a computer and follow on-screen instructions to install the monitoring software.
- Wi-Fi Cloud Communication (Option): Use the supplied communication cable to connect to the inverter and Wi-Fi module. Download and install the APP from the APP store. Refer to the "Wi-Fi Plug Quick Installation Guideline" to set up the network and register. The inverter status will be shown via the mobile phone APP or computer webpage.
- GPRS Cloud Communication (Option): Use the supplied communication cable to connect to the inverter and GPRS module. Download and install the APP. Refer to the "GPRS RTU Quick Installation Guideline" to set up the network and register. The inverter status will be shown via the mobile phone APP or computer webpage.
4.9 Wiring Diagram Overview
The inverter supports various configurations including solar panels, generator, utility grid, battery bank, and household loads. Ensure all connections follow local electrical codes and safety guidelines.

Figure 4.1: Wiring and Technical Specifications Diagram
Key Wiring Details:
- AC Input (Utility/Generator): 220V/230V/240V, Max Charging Current 160A. Recommended cable: 10 AWG/6 mm², Breaker: 63A.
- AC Output: 11000W, 220V/230V/240V. Recommended cable: 10 AWG/6 mm², Breaker: 63A.
- PV System: Max PV Power 11000W, Max Open Circuit Voltage 500VDC, MPPT Range 90-500VDC, Max Charging Current 150A. Recommended cable: 10 AWG/6 mm². Connect solar modules in series.
- Battery Bank: 48V system (lead-acid or lithium). Recommended wire size: 2 AWG (25 mm²), Fuse: 150A.
5. Operating Instructions
5.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.
Steps to Start Up:
Connect the battery (voltage needs to be beyond 23V) or AC (AC needs to confirm the suitable input range depending on the output mode), then you can start up the inverter.
- Mains Power On: Connect to normal AC power, press the switch. The system will automatically turn on. If AC output power priority is set, the panel will display AC mode after a period, indicating successful startup.
- Battery Boot: Connect to the battery, press the power-on button. The system will automatically turn on. After a period, the panel will display battery mode, indicating successful startup.
Shutdown Steps:
When the system is in battery mode or AC mode output, press the switch again to turn off the system.
5.2 Operation and Display Panel
The operation and display panel on the front of the inverter includes three indicators, four function keys, and an LCD display, indicating operating status and input/output power information.
LED Indicators:
| LED Indicator | Color | Status | Messages |
|---|---|---|---|
| AC/INV | Green | Solid On | Output is powered by utility in Line mode. |
| Flashing | Output is powered by battery or PV in battery mode. | ||
| CHG | Green | Solid On | Battery is fully charged. |
| Flashing | Battery is charging. | ||
| FAULT | Red | Solid On | Fault occurs in the inverter. |
| Flashing | Warning condition occurs in the inverter. |
Function Keys:
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
5.3 Operating Modes
The inverter operates in several modes, each with specific power flow characteristics.
Line Mode:
- The unit provides output power from the mains and charges the battery.
- If "Solar First" is selected and solar energy is insufficient, solar and utility provide loads and charge the battery.
- If "Solar First" is selected as output source priority and battery is not connected, solar and utility provide loads.
- Power from utility only.
Battery Mode:
- Power from battery and PV energy.
- PV energy supplies power to loads and charges the battery.
- Power from battery only.
Battery Free Mode:
- The device provides output power from the PV power supply only.
Standby Mode:
No output is supplied, but the unit can still charge batteries.
Fault Mode:
Errors are caused by internal circuit errors or external reasons such as over-temperature or output short circuits.
5.4 LCD Setting Programs
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use UP/DOWN to select programs and ENTER to confirm or ESC to exit.
Key settings include:
- Output Source Priority: Utility first, Solar first, SBU priority (Solar-Battery-Utility).
- Maximum Charging Current: Configures total charging current for solar and utility chargers (10A to 100A).
- AC Input Voltage Range: Appliances (90-280VAC) or UPS (170-280VAC).
- Battery Type: AGM, Flooded, or User-Defined.
- Battery Equalization: Enable/disable, voltage, time, timeout, interval.
- Charger Source Priority: Utility first, Solar first, Solar and Utility, Only Solar.
- Output Frequency: 50Hz/60Hz.
- Output Voltage: 220V/230V/240V.
6. Maintenance
Regular maintenance ensures the longevity and optimal performance of your DATOUBOSS Hybrid Solar Inverter.
- Regular Inspection: Periodically inspect all wiring connections for tightness and signs of corrosion. Ensure the inverter's ventilation openings are clear of dust and debris to prevent overheating.
- Cleaning: Keep the inverter's exterior clean and free from dust. Use a dry, soft cloth for cleaning. Do not use liquid cleaners or solvents.
- Battery Maintenance: Follow the battery manufacturer's guidelines for maintenance. Check battery terminals for corrosion and ensure they are clean and tight. For flooded batteries, check electrolyte levels regularly.
- Environmental Conditions: Ensure the inverter is operating within its specified temperature and humidity ranges. Avoid exposing the unit to direct sunlight or excessive moisture.
- Firmware Updates: If available, check the manufacturer's website for any firmware updates that may improve performance or address known issues.
- Error Monitoring: Regularly check the LCD display for any warning or fault codes. Address any issues promptly by referring to the troubleshooting section.
WARNING: Always disconnect all power sources (AC, PV, and Battery) before performing any maintenance or cleaning to avoid electric shock.
7. Troubleshooting
This section provides solutions to common problems encountered with the inverter. Refer to the LCD display, LED indicators, and buzzer for diagnostic information.
7.1 Fault Codes and Descriptions
| Fault Code | Fault Event |
|---|---|
| 01 | Fan is locked when inverter is off. |
| 02 | Over temperature or NTC is not connected well. |
| 03 | Battery voltage is too high. |
| 04 | Battery voltage is too low. |
| 05 | Output short circuited or over temperature is detected by internal converter components. |
| 06 | Output voltage is too high. |
| 07 | Over load time out. |
| 08 | Bus voltage is too high. |
| 09 | Bus soft start failed. |
| 51 | Over currents or surge. |
| 52 | Bus voltage is too low. |
| 53 | Inverter soft start failed. |
| 55 | Over DC voltage in AC output. |
| 57 | Current sensor failed. |
| 58 | Output voltage is too low. |
| 59 | PV voltage is over limitation. |
7.2 Warning Codes and Descriptions
| Warning Code | Warning Event | Audible Alarm |
|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second |
| 02 | Over temperature | None |
| 03 | Battery is over-charged | Beep once every second |
| 04 | Low battery | Beep once every second |
| 07 | Overload | Beep once every 0.5 second |
| 10 | Output power derating | Beep twice every 3 seconds |
| 15 | PV energy is low. | Beep twice every 3 seconds |
| 16 | High AC input (>280VAC) during BUS soft start | None |
| 49 | Battery equalization | None |
| 6P | Battery is not connected | None |
7.3 General Troubleshooting Table
| Problem | LCD/LED/Buzzer | Explanation/Possible Cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD/LEDs and buzzer active for 3s then off. | Battery voltage too low (<1.91V/Cell). | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. Battery voltage far too low (<1.4V/Cell). 2. Internal fuse tripped. | 1. Contact repair center. 2. Re-charge battery. 3. Replace battery. |
| Input voltage 0 on LCD, green LED flashing. | Input protector is tripped. | Check AC breaker, AC wiring. | |
| Mains exist but unit works in battery mode. | Green LED flashing. | Insufficient quality of AC power. | 1. Check AC wires. 2. Check generator/input voltage range. |
| Green LED flashing. | "Solar First" as priority of output source. | Change output source priority to Utility first. | |
| When unit turned on, internal relay switches on/off repeatedly. | LCD display and LEDs flashing. | Battery is disconnected. | Check battery wires. |
| Buzzer beeps continuously, red LED on. | Fault code 07 | Overload error or PV input voltage too high. | Reduce connected load or PV modules in series. |
| Fault code 05 | Output short circuited. | Check wiring, remove abnormal load. | |
| Fault code 02 | Internal temperature over 100°C/120°C. | Check air flow, ambient temperature. | |
| Fault code 03 | Battery is over-charged or voltage too high. | Return to repair center, check battery specs. | |
| Fault code 01 | Fan fault. | Replace the fan. | |
| Fault code 06/58 | Output abnormal (Inverter voltage out of range). | 1. Reduce connected load. 2. Return to repair center. | |
| Fault code 08/09/53/57 | Internal components failed. | Return to repair center. | |
| Fault code 51/52/55 | Over current/surge, Bus voltage too low, Output voltage unbalanced. | Restart unit, if error persists, return to repair center. | |
| Fault code 59 | PV input voltage beyond specification. | Reduce number of PV modules in series. |
8. Specifications
Detailed technical specifications for the DATOUBOSS DT4811B-48V-A-EU Hybrid Solar Inverter.
| Category | Parameter | Value |
|---|---|---|
| Input | Rated Input Voltage | 220/230/240VAC |
| Voltage Range | 90-280VAC±3V (APL Mode), 170-280VAC±3V (UPS Mode) | |
| Frequency | 50Hz/60Hz (Auto Adaptive) | |
| Output | Rated Power | 11000W / 11000VA |
| Output Voltage | 220/230/240VAC±5% | |
| Output Frequency | 50/60Hz±0.1% | |
| Waveform | Pure Sine Wave | |
| Peak Efficiency (Battery Mode) | >98% | |
| Battery | Battery Voltage | 48VDC |
| Constant Charging Voltage (Adjustable) | 56.4Vdc | |
| Float Charging Voltage (Adjustable) | 54Vdc | |
| Chargers | PV Charging Mode | MPPT Dual MPPT |
| Max. PV Input Power | 2*5500W | |
| MPPT Tracking Range | 90-500VDC | |
| Max. PV Input Voltage | 500VDC | |
| Max. PV Charging Current | 150A | |
| Max. AC Charging Current | 150A | |
| Max. Charging Current (Total) | 150A | |
| Display | LCD Display | Display Running Mode/Loads/Input/Output etc. |
| RS232 | Baud Rate 2400 | |
| Interface | Communication Port | Lithium Battery BMS Communication Card, WifiCard, Dry Contact |
| Parallel Connect Interface | With parallel function | |
| Environments | Operating Temperature | -10~50°C |
| Humidity | 20%~95% (Non-condensing) | |
| Storage Temperature | -15~60°C | |
| Noise | ≤50dB | |
| Physical | Size (L x W x H) | 70.80 x 57.00 x 24.10 cm |
| Weight | 21.94 kg | |
| Certification | CE |
9. User Tips
- Ease of Setup: Users have reported that the inverter is straightforward to connect and get working. Follow the detailed instructions in this manual for a smooth installation.
- Ventilation is Key: Always ensure the inverter has adequate clearance around it for proper airflow. Good ventilation prevents overheating and ensures optimal performance and longevity.
- Regular Checks: Periodically inspect all wiring connections for tightness and signs of wear or corrosion. Loose connections can lead to inefficiencies or safety hazards.
- Monitor the Display: Pay attention to the LCD display for any warning or fault codes. Addressing issues promptly can prevent more significant problems.
- Battery Compatibility: Ensure your battery bank (lithium or lead-acid) is compatible with the inverter's 48V system and that charging parameters are correctly set in the LCD menu.
10. Warranty and Support
For warranty information, technical support, or service inquiries, please contact your original seller or the DATOUBOSS customer service department. Keep your purchase receipt or proof of purchase handy as it may be required for warranty claims.