DAXTROMN AGH-4.2KW-PRO-24V

Contents

DAXTROMN 4.2KW 24V Hybrid Solar Inverter User Manual

Model: AGH-4.2KW-PRO-24V

Brand: DAXTROMN

1. Introduction

This manual describes the assembly, installation, operation, and troubleshooting of the DAXTROMN 4.2KW 24V Hybrid Solar Inverter. Please read this manual carefully before installation and operation. Keep this manual for future reference.

This multi-function inverter/charger combines the functions of an inverter, solar charger, and battery charger to provide uninterruptible power support. Its comprehensive LCD display offers user-configurable and easy-accessible button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.

1.1. Key Features

  • Pure sine wave output.
  • Output power factor 1.0.
  • Built-in MPPT 120A solar charger.
  • Photovoltaic input voltage range: 60-500VDC.
  • Capable of working without a battery.
  • Optional WiFi remote monitoring.
  • Supports multiple output priorities: Utility first (USB), Solar first (SUB), SBU priority.
  • Removable dust cover, suitable for harsh environments.
  • One-key factory reset function.
  • Supports PACE PYLON communication protocol BMS.
  • Can connect to lithium iron phosphate batteries via RS485 interface.
  • Lithium battery activation function, activatable by mains or photovoltaic system.
  • Features two load outputs.
  • Can be connected to the grid.
  • Built-in RS232 (WIFI) / RS485 (BMS) port for configuring BMS battery charging protocol to extend battery life.
  • Configurable input voltage range for home appliances and personal computers via LCD setting.
  • Configurable battery charging current based on applications via LCD setting.
  • Configurable AC/Solar Charger priority via LCD setting.
  • Compatible with mains voltage or generator power.
  • Auto restart while AC is recovering.
  • Overload, over temperature, and short circuit protection.
  • Smart battery charger design for optimized battery performance.
  • Cold start function.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION: Only qualified personnel can install this device with a battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow the required specifications to select appropriate cable sizes. It is very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Refer to the INSTALLATION section of this manual for details.
  10. One piece of 150A fuse is provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  12. NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
  13. Warning! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to a local dealer or service center for maintenance.

3. Product Overview

The DAXTROMN 4.2KW Hybrid Solar Inverter is designed for efficient power management in solar energy systems. Below is an overview of its components and display.

Product Overview Diagram with numbered components
Figure 1: Product Overview Diagram. This diagram shows the inverter's front panel and side view with numbered components for easy identification.

3.1. Component Identification

  1. LCD display
  2. Status indicator
  3. Charging indicator
  4. Fault indicator
  5. Function buttons
  6. Power on/off switch
  7. AC input
  8. Main output
  9. Second output
  10. Battery input
  11. PV input
  12. Anti-dust kit
  13. WIFI communication/RS-232 port
  14. Battery communication/RS-485 port
Product Display showing various angles of the inverter
Figure 2: Product Display. Various views of the inverter, highlighting its physical design and connection points.

4. Setup and Installation

4.1. Unpacking and Inspection

Before installation, carefully inspect the unit for any damage. The package should contain:

  • The Inverter Unit x 1
  • User Manual x 1

4.2. Preparation

Before connecting any cables, remove the screws under the machine and detach the bottom cover plate.

4.3. Mounting the Unit

Consider the following points when selecting a mounting location:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install the inverter at eye level for easy LCD display readability.
  • For proper air circulation and heat dissipation, allow approximately 20 cm clearance to the sides and 50 cm above and below the unit.
  • The ambient temperature should be between 0°C and 55°C for optimal operation.
  • The recommended installation position is vertically on a wall.
  • Ensure sufficient space around the machine for adequate heat dissipation and wire management.

WARNING: Suitable for mounting on concrete or other non-combustible surfaces only.

Install the unit by screwing two M6 screws into the mounting surface.

4.4. Battery Connection

CAUTION: For safety and compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. This is crucial for over-current protection.

WARNING: All wiring must be performed by qualified personnel. Use appropriate cable sizes to reduce the risk of injury.

ModelWire SizeCable (mm²)Torque value (max)
3.6KW/4.2KW/6.2KW1 x 2AWG252 Nm

Follow these steps for battery connection:

  1. Remove 18 mm of insulation sleeve from positive and negative conductors.
  2. Attach bootlace ferrules to the ends of positive and negative wires using a proper crimping tool.
  3. Connect all battery packs as shown in the diagram below.
Battery Connection Diagram for 3.6KW/4.2KW and 6.2KW inverters
Figure 3: Battery Connection Diagram. Shows how to connect 12V batteries in series for 3.6KW/4.2KW and 6.2KW inverters.
  1. Insert battery wires flatly into the inverter's battery connectors and tighten bolts to 2 Nm in a clockwise direction. Ensure correct polarity at both the battery and inverter/charger. Recommended tool: #2 Pozi Screwdriver.

WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.

CAUTION: Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).

4.5. AC Input/Output Connection

CAUTION: Install a separate AC breaker between the inverter and the AC input power source. Recommended breaker spec: 32A for 3.6KW/4.2KW and 50A for 6.2KW.

CAUTION: Do NOT mis-connect input and output connectors. Terminal blocks are marked "IN" and "OUT".

WARNING: All wiring must be performed by qualified personnel. Use appropriate cable sizes for AC input connection.

Suggested Cable Requirement for AC Wires:

ModelGaugeCable (mm²)Torque Value
3.6KW/4.2KW12 AWG41.2 Nm
6.2KW10 AWG61.2 Nm

Follow these steps for AC input/output connection:

  1. Before making AC input/output connection, open the DC protector or disconnector.
  2. Remove 10mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3mm.
  3. Insert AC input wires according to polarities (L→LINE (brown or black), N→Neutral (blue)) and tighten terminal screws.

WARNING: Ensure AC power source is disconnected before attempting to hardwire it to the unit.

  1. Insert AC output wires according to polarities (L→LINE (brown or black), N→Neutral (blue)) and tighten terminal screws.
  2. Ensure all wires are securely connected.
AC Input/Output Connection Diagram
Figure 4: AC Input/Output Connection. This diagram illustrates the proper wiring for AC input and output.

CAUTION: Appliances like air conditioners require 2-3 minutes to restart. If a power shortage occurs and recovers quickly, it can damage connected appliances. Check if your appliance has a time-delay function. The inverter will trigger an overload fault and cut off output, but internal damage may still occur.

4.6. PV Connection

CAUTION: Install a separate DC circuit breaker between the inverter and PV modules.

WARNING: Use appropriate cable sizes for PV module connection to reduce risk of injury.

ModelWire SizeCable (mm²)Torque value (max)
3.6KW/4.2KW/6.2KW1 x 12AWG41.2 Nm

PV Module Selection:

When selecting PV modules, consider these parameters:

  • Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
  • Open circuit Voltage (Voc) of PV modules should be higher than the minimum battery voltage.
INVERTER MODEL3.6KW/4.2KW6.2KW
Max. PV Array Open Circuit Voltage500Vdc
PV Array MPPT Voltage Range60Vdc~450Vdc
PV Connection Diagram with cable requirements
Figure 5: PV Connection. This diagram shows the solar panel connection to the inverter and associated cable requirements.

4.7. Final Assembly

After connecting all wirings, replace the bottom cover by screwing the two screws back in place.

4.8. Communication Connection

The inverter supports various communication methods:

  • Wi-Fi Cloud Communication (Optional): Use the supplied communication cable to connect to the inverter and Wi-Fi module. Download the APP from the APP store and refer to the "Wi-Fi Plug Quick Installation Guideline" for setup. The inverter status can be monitored via mobile phone APP or computer webpage.
  • GPRS Cloud Communication (Optional): Use the supplied communication cable to connect to the inverter and GPRS module, then apply external power to the GPRS module. Download the APP from the APP store and refer to the "GPRS RTU Quick Installation Guideline" for setup. The inverter status can be monitored via mobile phone APP or computer webpage.
  • Battery Communication: Communication between the battery and the inverter is realized through the battery communication interface (Baud rate: 9600).
  • Lithium Battery and Inverter Connection: Use power cables and communication cables for lithium batteries and inverters. Ensure correct polarity. The RJ45 connector of the communication cable connects to the BMS port of the inverter, and the other RJ45 connector connects to the RS485 port of the lithium battery. Turn off the lithium battery and inverter before connecting. It is recommended to install a circuit breaker for the power cables of the lithium battery and the inverter battery interface to prevent sparks.
RJ45 Communication Cable Diagram for Lithium Battery
Figure 6: Lithium Battery Communication Cable Interface. This diagram shows the RJ45 cable connection for BMS and RS485 ports.

5. Operation

5.1. Power ON/OFF

Once the unit is properly installed and batteries are connected, simply press the On/Off switch (located on the button of the case) to turn on the unit.

5.2. Operation and Display Panel

The operation and display panel on the front of the inverter includes three indicators, four function keys, and an LCD display, showing operating status and input/output power information.

LED Indicator and Function Keys:

LED IndicatorMessages
INV/ACGreenSolid On: Output is powered by utility in Line mode.
Flashing: Output is powered by battery or PV in battery mode.
CHGGreenSolid On: Battery is fully charged.
Flashing: Battery is charging.
FAULTRedSolid On: Fault occurs in the inverter.
Flashing: Warning condition occurs in the inverter.
Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

5.3. LCD Display Icons

The LCD display uses various icons to convey information about the inverter's status and operation.

IconFunction description
Input Source Information
AC Input IconIndicates the AC input.
PV Input IconIndicates the PV input.
Configuration Program and Fault Information
8.8.8Indicates the setting programs.
8.8.8Indicates the warning and fault codes.
Output Information
8.8.8 KWIndicates output voltage, output frequency, load percent, load in VA, load in Watt, and discharging current.
Battery Information
Battery IconBattery status.
Load Information
OVER LOADIndicates overload.
Mode Operation Information
Mains Connection IconIndicates unit connects to the mains.
PV Panel Connection IconIndicates unit connects to the PV panel.
AC BYPASSIndicates load is supplied by utility power.
Utility Charger Circuit IconIndicates the utility charger circuit is working.
DC/AC Inverter Circuit IconIndicates the DC/AC inverter circuit is working.
Mute Operation
Mute IconIndicates unit alarm is disabled.

5.4. LCD Settings

To enter setting mode, press and hold the ENTER button for 3 seconds. Use the UP or DOWN buttons to select programs, then press ENTER to confirm or ESC to exit.

Key Settings:

  • Program 00: Exit Setting Mode - Options: GOE (one-button restore setting options), GOK.
  • Program 01: Output Source Priority - Configures load power source priority.
    • Utility First (01 U5b): Utility provides power first. Solar and battery power only when utility is unavailable.
    • Solar First (01 SUb - default): Solar energy provides power first. If insufficient, utility supplies power simultaneously. Battery provides power only if solar and utility are unavailable or insufficient.
    • SBU Priority (01 SBU): Solar energy provides power first. If insufficient, battery supplies power simultaneously. Utility provides power only when battery voltage drops below a low-level warning or setting point (program 12).
  • Program 02: Maximum Charging Current - Configures total charging current for solar and utility chargers (Max. charging current = utility charging current + solar charging current). Options: 10A, 20A, 30A, 40A, 50A, 60A (default), 70A, 80A, 90A, 100A, 110A, 120A.
  • Program 03: AC Input Voltage Range - Options: APL (Appliances - default, 90-280VAC), UPS (170-280VAC).
  • Program 05: Battery Type - Options: AGM (default), User-Defined, Flooded, LIB (Lithium battery communication for PACE 232 BMS), LIL (Lithium battery communication for PYLON 485 BMS).
  • Program 06: Auto Restart When Overload Occurs - Options: Restart disable (default), Restart enable (LHE).
  • Program 07: Auto Restart When Over Temperature Occurs - Options: Restart disable (default), Restart enable (EYE).
  • Program 09: Output Frequency - Options: 50Hz (default), 60Hz.
  • Program 10: Output Voltage - Options: 220V, 230V (default), 240V.
  • Program 11: Maximum Utility Charging Current - Options: 2A, 10A, 20A, 30A (default).
  • Program 12: Setting Voltage Point Back to Utility Source - Configures the voltage point for switching back to utility when "SBU priority" or "Solar first" is selected in program 01. Options vary by model (3.6KW/4.2KW: 21.0V-25.5V; 6.2KW: 42V-51V).
  • Program 13: Setting Voltage Point Back to Battery Mode - Configures the voltage point for switching back to battery mode when "SBU priority" or "Solar first" is selected in program 01. Options vary by model (3.6KW/4.2KW: 24V-29V; 6.2KW: 48V-54V).
  • Program 16: Charger Source Priority - Configures charger source priority when working in Line, Standby, or Fault mode.
    • Solar First (16 OSO): Solar energy charges battery first.
    • Solar and Utility (16 SNU - default): Both solar and utility charge battery.
    • Only Solar (16 OSO): Only solar energy charges battery.
  • Program 18: Alarm Control - Options: Alarm on (default), Alarm off.
  • Program 19: Auto Return to Default Display Screen - Options: ESP (default, returns to default display after 1 min inactivity), HEP (stays on last screen).
  • Program 20: Backlight Control - Options: LON (Backlight on - default), LOF (Backlight off).
  • Program 22: Beeps While Primary Source is Interrupted - Options: A00 (Alarm on - default), AOF (Alarm off).
  • Program 23: Overload Bypass - Options: BYD (Bypass disable - default), BYE (Bypass enable).
  • Program 25: Record Fault Code - Options: FEN (Record enable - default), FdS (Record disable).
  • Program 26: Bulk Charging Voltage (C.V voltage) - Default: 28.2V (3.6KW/4.2KW), 56.4V (6.2KW). Range: 25.0V-30.0V (3.6KW/4.2KW), 48.0V-60.0V (6.2KW). Increment: 0.1V.
  • Program 27: Floating Charging Voltage - Default: 27.0V (3.6KW/4.2KW), 54.0V (6.2KW). Range: 25.0V-30.0V (3.6KW/4.2KW), 48.0V-60.0V (6.2KW). Increment: 0.1V.
  • Program 29: Low DC Cut-off Voltage - Default: 20.0V (3.6KW/4.2KW), 40.0V (6.2KW). Range: 20.0V-25.0V (3.6KW/4.2KW), 40.0V-50.0V (6.2KW). Increment: 0.1V.
  • Program 30: Battery Equalization - Options: EEN (Battery equalization disable - default), EdS (Battery equalization enable).
  • Program 31: Battery Equalization Voltage - Default: 29.2V (3.6KW/4.2KW), 58.4V (6.2KW). Range: 25.0V-31.5V (3.6KW/4.2KW), 48.0V-61.0V (6.2KW). Increment: 0.1V.
  • Program 33: Battery Equalized Time - Default: 60min. Range: 5min-900min. Increment: 5min.
  • Program 34: Battery Equalized Timeout - Default: 120min. Range: 5min-900min. Increment: 5min.
  • Program 35: Equalization Interval - Default: 30 days. Range: 0-90 days. Increment: 1 day.
  • Program 36: Equalization Activated Immediately - Options: AEN (Enable), A85 (Disable - default).
  • Program 37: GRID-tie Operation - Options: OFF (Off grid - default), HYD (Hybrid).
  • Program 38: GRID-tie Current - Default: 10A. Increment: 2A.
  • Program 39: LED Pattern Light - Options: LOF (Led pattern off), LON (Led pattern on - default).
  • Program 41: Dual Output - Options: L2F (disable - default), L20 (use).
  • Program 42: Enter the Dual Output Functional Voltage Point - Default: 22.0V (3.6KW/4.2KW), 44.0V (6.2KW). Range: 20.0V-26.0V (24VDC), 40.0V-52.0V (48VDC). Increment: 0.1V.
  • Program 43: BMS Communication Address 48-70 Setting - If in LIL mode, allows changing the mailing address.
  • Program 44: Delayed Grid Access - Options: DIS (disable), ENA (enable - default).
  • Program 45: Maximum Second Load - Range: 20%-70% of rated power.

5.5. Operating Mode Description

The LCD display information switches by pressing the "UP" or "DOWN" key. Information includes input voltage, frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, DC discharging current, and main CPU Version.

Example Display Screens:

  • Charged State (Power less than 1KW): Displays input voltage, PV voltage, battery voltage, output voltage, load in Watt, and charging/inverter status.
  • Charged State (Power greater than 1KW): Similar to above, but for higher power output.
  • Discharged State (Power less than 1KW): Displays input voltage, PV voltage, battery voltage, output voltage, load in Watt, and charging/inverter status during discharge.
  • Discharged State (Power greater than 1KW): Similar to above, but for higher power output during discharge.
  • Standby Mode: Displays zero output and load when in standby.
  • Line Mode: Displays input/output voltages and load when operating from AC line.
  • Grid-Tie Operation: Displays relevant parameters when feeding power to the grid.
  • Lithium Battery Communication (PACE 232 BMS): Displays total battery voltage, residual capacity, charging/discharge current, nominal voltage, total capacity, remaining capacity, and charge/discharge cycles.
  • Lithium Battery Communication (PYLON 485 BMS): Displays total battery voltage, residual capacity, charging/discharge current, nominal voltage, total capacity, remaining capacity, and charge/discharge cycles.

5.6. Battery Equalization Description

The equalization function helps reverse the buildup of negative chemical effects (stratification) and removes sulfate crystals from battery plates, which can reduce battery capacity. Periodic equalization is recommended.

How to Apply Equalization Function:

First, enable battery equalization in LCD setting program 30. Then, activate it by:

  • Setting the equalization interval in program 35.
  • Activating equalization immediately in program 36.

When to Equalize:

In the float stage, when the set equalization interval is reached or equalization is activated immediately, the controller will enter the Equalize stage.

Equalize Charging Time and Timeout:

During equalization, the controller charges the battery until it reaches the equalization voltage. Constant-voltage regulation maintains this voltage. The battery remains in this stage until the set equalized time is reached. If the battery voltage doesn't reach the equalization voltage within the set time, the charge controller extends the time until it does. If the battery voltage is still lower than the equalization voltage after the timeout, the controller stops equalization and returns to the float stage.

5.7. Mains and Lithium Battery Activation Function

  • After 90 seconds of mains power connection, the inverter connects to the mains and starts operation.
  • If the inverter is in lithium battery mode (item 05 is LIP or LIL) and the mains are connected but the battery is not, the mains activation function is automatically enabled.

6. Maintenance

6.1. Anti-Dust Kit Clearance and Maintenance

Every inverter comes with an anti-dust kit installed from the factory. This kit helps prevent dust ingress and increases product reliability, especially in harsh environments. The inverter automatically detects the kit and adjusts its internal thermal sensor to manage temperature.

Maintenance Steps:

  1. Loosen the screw on the top of the inverter in a counterclockwise direction.
  2. Remove the dustproof case and take out the air filter foam.
  3. Clean the air filter foam and dustproof case. After cleaning, re-assemble the dust-kit back to the inverter.

NOTICE: The anti-dust kit should be cleaned from dust every one month.

7. Troubleshooting

This section provides guidance for common issues. If problems persist after following these steps, contact a qualified service person.

7.1. Fault Reference Code Table

Fault CodeFault EventIcon on
01Fan is locked when inverter is off.01 ERROR
02Over temperature02 ERROR
03Battery voltage is too high03 ERROR
04Battery voltage is too low04 ERROR
05Output short circuited or over temperature is detected by internal converter components.05 ERROR
06Output voltage is too high.06 ERROR
07Overload time out07 ERROR
08Bus voltage is too high08 ERROR
09Bus soft start failed09 ERROR
51Over current or surge51 ERROR
52Bus voltage is too low52 ERROR
53Inverter soft start failed53 ERROR
55Over DC voltage in AC output55 ERROR
57Current sensor failed57 ERROR
58Output voltage is too low58 ERROR
59PV voltage is over limitation59 ERROR

7.2. Battery Fault Codes (Lithium Battery Mode)

Fault codeFault eventFault condition
02The battery temperature is too highLithium battery charging temperature ≥65°C; Discharge temperature of the lithium battery is higher than 70°C.
03The battery voltage is too highLithium battery maximum single cell voltage >3.65V; Total voltage of lithium battery >54.6V (48V lithium battery); Total voltage of lithium battery >29.1V (24V lithium battery).
04The battery voltage is too lowMinimum voltage of a lithium battery cell <2.71V; Lithium battery total voltage <40.4V (48V lithium battery); Lithium battery voltage <21.5V (24V lithium battery).

7.3. Warning Indicators

Warning CodeWarning EventAudible AlarmIcon flashing
01Fan is locked when inverter is on.Beep three times every second01
03Battery is over-chargedBeep once every second03
04Low batteryBeep once every second04
07OverloadBeep once every 0.5 second07
10Output power deratingBeep twice every 3 seconds10
15PV energy is low.Beep twice every 3 seconds15
E9Battery equalizationNoneE9
bPBattery is not connectedNonebP

Added Battery Warning Codes (Lithium Battery Mode):

Warning codeWarning eventWarning condition
04The battery voltage is too lowMinimum voltage of a lithium battery cell <2.85V; Lithium battery total voltage <42V (48V lithium battery); Lithium battery voltage <22.4V (24V lithium battery).
05The battery voltage is too highLithium battery maximum single cell voltage >3.55V; Total voltage of lithium battery >54V (48V lithium battery); Total voltage of lithium battery >28.8V (24V lithium battery).
06The battery is low warningRemaining battery capacity ≤10%

8. Specifications

Detailed technical specifications for the DAXTROMN 4.2KW Hybrid Solar Inverter are provided below.

Inverter Charger Specifications Label
Figure 8: Inverter Charger Specifications. A label showing key electrical specifications for PV input, Grid/AC output, and battery.

8.1. Line Mode Specifications (Table 1)

INVERTER MODEL3.6KW4.2KW6.2KW
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS); 90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS); 100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)

8.2. Inverter Mode Specifications (Table 2)

INVERTER MODEL3.6KW4.2KW6.2KW
Rated Output Power3.6KW4.2KW6.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency50Hz
Peak Efficiency93%
Overload Protection3s@≥150% load; 5s@101%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage24Vdc48Vdc
Cold Start Voltage23.0Vdc46.0Vdc
Low DC Warning Voltage @ load < 50%22.0Vdc44.0Vdc
Low DC Warning Voltage @ load ≥ 50%21.0Vdc42.0Vdc
Low DC Warning Return Voltage @ load < 50%22.5Vdc45.0Vdc
Low DC Warning Return Voltage @ load ≥ 50%22.0Vdc44.0Vdc
Low DC Cut-off Voltage @ load < 50%20.5Vdc41.0Vdc
Low DC Cut-off Voltage @ load ≥ 50%20.0Vdc40.0Vdc
High DC Recovery Voltage32Vdc62Vdc
High DC Cut-off Voltage33Vdc63Vdc
No Load Power Consumption30W35W50W

8.3. Two Load Output Power (Table 3)

INVERTER MODEL3.6KW4.2KW6.2KW
Full Load3600W4200W6200W
Maximum Main Load3600W4200W6200W
Second Load Range720W~2520W840W~2940W1240W~4340W
Main Load Cut Off Voltage26VDC
Main Load Return Voltage27VDC

8.4. Charge Mode Specifications (Table 4)

Utility Charging Mode3.6KW4.2KW6.2KW
Charging Algorithm3-Step
AC Charging Current (Max)100Amp (@VI/P=230Vac)
Bulk Charging Voltage (Flooded Battery)29.258.4
Bulk Charging Voltage (AGM / Gel Battery)28.256.4
Floating Charging Voltage27Vdc54Vdc

MPPT Solar Charging Mode:

INVERTER MODEL3.6KW4.2KW6.2KW
Max. PV Array Power6200W6500W
Nominal PV Voltage240Vdc360Vdc
PV Array MPPT Voltage Range60Vdc~500Vdc
Max. PV Array Open Circuit Voltage500Vdc
Max Charging Current (AC charger plus solar charger)120Amp120Amp120Amp

8.5. Grid-Tie Operation (Table 5)

INVERTER MODEL3.6KW4.2KW6.2KW
Nominal Output Voltage220/230/240 VAC
Feed-in Grid Voltage Range195~253VAC
Feed-in Grid Frequency Range50±1Hz/60±1Hz
Nominal Output Current15.7A18.2A26.9A
Power Factor Range>0.99
Maximum Conversion Efficiency (DC/AC)97%

8.6. General Specifications (Table 6)

INVERTER MODEL3.6KW4.2KW6.2KW
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm358×442×116
Net Weight, kg8.08.08.9

8.7. Approximate Back-up Time Table (Table 9)

The backup time depends on battery quality, age, and type. Battery specifications may vary.

ModelLoad (W)Backup Time @ 24Vdc 100Ah (min)Backup Time @ 24Vdc 200Ah (min)
3.6KW/4.2KW3004491100
600222525
900124303
120095227
150068164
180056126
210048108
24003594
27003174
32002867
36002560
42002253
ModelLoad (W)Backup Time @ 48Vdc 100Ah (min)Backup Time @ 48Vdc 200Ah (min)
6.2KW5006131288
1000268613
1500158402
2000111271
250090215
320076182
350065141
400050112
450044100
50004090
62003680

9. User Tips

  • When operating without an external battery, ensure the solar panel input voltage is above 90V for normal inverter operation. If an external battery is connected, 60V input is sufficient.
  • Regularly clean the anti-dust kit (monthly) to ensure optimal performance and longevity of the inverter, especially in dusty environments.
  • For lithium battery systems, utilize the RS485 interface to configure the BMS battery charging protocol, which can help extend battery life.

10. Support and Further Information

For detailed information, including comprehensive diagrams and advanced settings, please refer to the full user manual PDF:

Download User Manual (PDF)

If you encounter persistent issues not covered in the troubleshooting section, please contact your local dealer or service center for assistance. Only qualified service personnel should attempt repairs.