1. Introduction
This manual describes the assembly, installation, operation, and troubleshooting of the DAXTROMN 4.2KW 24V Hybrid Solar Inverter. Please read this manual carefully before installation and operation. Keep this manual for future reference.
This multi-function inverter/charger combines the functions of an inverter, solar charger, and battery charger to provide uninterruptible power support. Its comprehensive LCD display offers user-configurable and easy-accessible button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
1.1. Key Features
- Pure sine wave output.
- Output power factor 1.0.
- Built-in MPPT 120A solar charger.
- Photovoltaic input voltage range: 60-500VDC.
- Capable of working without a battery.
- Optional WiFi remote monitoring.
- Supports multiple output priorities: Utility first (USB), Solar first (SUB), SBU priority.
- Removable dust cover, suitable for harsh environments.
- One-key factory reset function.
- Supports PACE PYLON communication protocol BMS.
- Can connect to lithium iron phosphate batteries via RS485 interface.
- Lithium battery activation function, activatable by mains or photovoltaic system.
- Features two load outputs.
- Can be connected to the grid.
- Built-in RS232 (WIFI) / RS485 (BMS) port for configuring BMS battery charging protocol to extend battery life.
- Configurable input voltage range for home appliances and personal computers via LCD setting.
- Configurable battery charging current based on applications via LCD setting.
- Configurable AC/Solar Charger priority via LCD setting.
- Compatible with mains voltage or generator power.
- Auto restart while AC is recovering.
- Overload, over temperature, and short circuit protection.
- Smart battery charger design for optimized battery performance.
- Cold start function.
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION: Only qualified personnel can install this device with a battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow the required specifications to select appropriate cable sizes. It is very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Refer to the INSTALLATION section of this manual for details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
- Warning! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to a local dealer or service center for maintenance.
3. Product Overview
The DAXTROMN 4.2KW Hybrid Solar Inverter is designed for efficient power management in solar energy systems. Below is an overview of its components and display.

3.1. Component Identification
- LCD display
- Status indicator
- Charging indicator
- Fault indicator
- Function buttons
- Power on/off switch
- AC input
- Main output
- Second output
- Battery input
- PV input
- Anti-dust kit
- WIFI communication/RS-232 port
- Battery communication/RS-485 port

4. Setup and Installation
4.1. Unpacking and Inspection
Before installation, carefully inspect the unit for any damage. The package should contain:
- The Inverter Unit x 1
- User Manual x 1
4.2. Preparation
Before connecting any cables, remove the screws under the machine and detach the bottom cover plate.
4.3. Mounting the Unit
Consider the following points when selecting a mounting location:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install the inverter at eye level for easy LCD display readability.
- For proper air circulation and heat dissipation, allow approximately 20 cm clearance to the sides and 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C for optimal operation.
- The recommended installation position is vertically on a wall.
- Ensure sufficient space around the machine for adequate heat dissipation and wire management.
WARNING: Suitable for mounting on concrete or other non-combustible surfaces only.
Install the unit by screwing two M6 screws into the mounting surface.
4.4. Battery Connection
CAUTION: For safety and compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. This is crucial for over-current protection.
WARNING: All wiring must be performed by qualified personnel. Use appropriate cable sizes to reduce the risk of injury.
Recommended Battery Cable Size:
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 3.6KW/4.2KW/6.2KW | 1 x 2AWG | 25 | 2 Nm |
Follow these steps for battery connection:
- Remove 18 mm of insulation sleeve from positive and negative conductors.
- Attach bootlace ferrules to the ends of positive and negative wires using a proper crimping tool.
- Connect all battery packs as shown in the diagram below.

- Insert battery wires flatly into the inverter's battery connectors and tighten bolts to 2 Nm in a clockwise direction. Ensure correct polarity at both the battery and inverter/charger. Recommended tool: #2 Pozi Screwdriver.
WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.
CAUTION: Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).
4.5. AC Input/Output Connection
CAUTION: Install a separate AC breaker between the inverter and the AC input power source. Recommended breaker spec: 32A for 3.6KW/4.2KW and 50A for 6.2KW.
CAUTION: Do NOT mis-connect input and output connectors. Terminal blocks are marked "IN" and "OUT".
WARNING: All wiring must be performed by qualified personnel. Use appropriate cable sizes for AC input connection.
Suggested Cable Requirement for AC Wires:
| Model | Gauge | Cable (mm²) | Torque Value |
|---|---|---|---|
| 3.6KW/4.2KW | 12 AWG | 4 | 1.2 Nm |
| 6.2KW | 10 AWG | 6 | 1.2 Nm |
Follow these steps for AC input/output connection:
- Before making AC input/output connection, open the DC protector or disconnector.
- Remove 10mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3mm.
- Insert AC input wires according to polarities (L→LINE (brown or black), N→Neutral (blue)) and tighten terminal screws.
WARNING: Ensure AC power source is disconnected before attempting to hardwire it to the unit.
- Insert AC output wires according to polarities (L→LINE (brown or black), N→Neutral (blue)) and tighten terminal screws.
- Ensure all wires are securely connected.

CAUTION: Appliances like air conditioners require 2-3 minutes to restart. If a power shortage occurs and recovers quickly, it can damage connected appliances. Check if your appliance has a time-delay function. The inverter will trigger an overload fault and cut off output, but internal damage may still occur.
4.6. PV Connection
CAUTION: Install a separate DC circuit breaker between the inverter and PV modules.
WARNING: Use appropriate cable sizes for PV module connection to reduce risk of injury.
Recommended PV Module Cable Size:
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 3.6KW/4.2KW/6.2KW | 1 x 12AWG | 4 | 1.2 Nm |
PV Module Selection:
When selecting PV modules, consider these parameters:
- Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than the minimum battery voltage.
| INVERTER MODEL | 3.6KW/4.2KW | 6.2KW |
|---|---|---|
| Max. PV Array Open Circuit Voltage | 500Vdc | |
| PV Array MPPT Voltage Range | 60Vdc~450Vdc | |

4.7. Final Assembly
After connecting all wirings, replace the bottom cover by screwing the two screws back in place.
4.8. Communication Connection
The inverter supports various communication methods:
- Wi-Fi Cloud Communication (Optional): Use the supplied communication cable to connect to the inverter and Wi-Fi module. Download the APP from the APP store and refer to the "Wi-Fi Plug Quick Installation Guideline" for setup. The inverter status can be monitored via mobile phone APP or computer webpage.
- GPRS Cloud Communication (Optional): Use the supplied communication cable to connect to the inverter and GPRS module, then apply external power to the GPRS module. Download the APP from the APP store and refer to the "GPRS RTU Quick Installation Guideline" for setup. The inverter status can be monitored via mobile phone APP or computer webpage.
- Battery Communication: Communication between the battery and the inverter is realized through the battery communication interface (Baud rate: 9600).
- Lithium Battery and Inverter Connection: Use power cables and communication cables for lithium batteries and inverters. Ensure correct polarity. The RJ45 connector of the communication cable connects to the BMS port of the inverter, and the other RJ45 connector connects to the RS485 port of the lithium battery. Turn off the lithium battery and inverter before connecting. It is recommended to install a circuit breaker for the power cables of the lithium battery and the inverter battery interface to prevent sparks.

5. Operation
5.1. Power ON/OFF
Once the unit is properly installed and batteries are connected, simply press the On/Off switch (located on the button of the case) to turn on the unit.
5.2. Operation and Display Panel
The operation and display panel on the front of the inverter includes three indicators, four function keys, and an LCD display, showing operating status and input/output power information.
LED Indicator and Function Keys:
| LED Indicator | Messages | |
|---|---|---|
| INV/AC | Green | Solid On: Output is powered by utility in Line mode. Flashing: Output is powered by battery or PV in battery mode. |
| CHG | Green | Solid On: Battery is fully charged. Flashing: Battery is charging. |
| FAULT | Red | Solid On: Fault occurs in the inverter. Flashing: Warning condition occurs in the inverter. |
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
5.3. LCD Display Icons
The LCD display uses various icons to convey information about the inverter's status and operation.
| Icon | Function description |
|---|---|
| Input Source Information | |
| AC Input Icon | Indicates the AC input. |
| PV Input Icon | Indicates the PV input. |
| Configuration Program and Fault Information | |
| 8.8.8 | Indicates the setting programs. |
| 8.8.8 | Indicates the warning and fault codes. |
| Output Information | |
| 8.8.8 KW | Indicates output voltage, output frequency, load percent, load in VA, load in Watt, and discharging current. |
| Battery Information | |
| Battery Icon | Battery status. |
| Load Information | |
| OVER LOAD | Indicates overload. |
| Mode Operation Information | |
| Mains Connection Icon | Indicates unit connects to the mains. |
| PV Panel Connection Icon | Indicates unit connects to the PV panel. |
| AC BYPASS | Indicates load is supplied by utility power. |
| Utility Charger Circuit Icon | Indicates the utility charger circuit is working. |
| DC/AC Inverter Circuit Icon | Indicates the DC/AC inverter circuit is working. |
| Mute Operation | |
| Mute Icon | Indicates unit alarm is disabled. |
5.4. LCD Settings
To enter setting mode, press and hold the ENTER button for 3 seconds. Use the UP or DOWN buttons to select programs, then press ENTER to confirm or ESC to exit.
Key Settings:
- Program 00: Exit Setting Mode - Options: GOE (one-button restore setting options), GOK.
- Program 01: Output Source Priority - Configures load power source priority.
- Utility First (01 U5b): Utility provides power first. Solar and battery power only when utility is unavailable.
- Solar First (01 SUb - default): Solar energy provides power first. If insufficient, utility supplies power simultaneously. Battery provides power only if solar and utility are unavailable or insufficient.
- SBU Priority (01 SBU): Solar energy provides power first. If insufficient, battery supplies power simultaneously. Utility provides power only when battery voltage drops below a low-level warning or setting point (program 12).
- Program 02: Maximum Charging Current - Configures total charging current for solar and utility chargers (Max. charging current = utility charging current + solar charging current). Options: 10A, 20A, 30A, 40A, 50A, 60A (default), 70A, 80A, 90A, 100A, 110A, 120A.
- Program 03: AC Input Voltage Range - Options: APL (Appliances - default, 90-280VAC), UPS (170-280VAC).
- Program 05: Battery Type - Options: AGM (default), User-Defined, Flooded, LIB (Lithium battery communication for PACE 232 BMS), LIL (Lithium battery communication for PYLON 485 BMS).
- Program 06: Auto Restart When Overload Occurs - Options: Restart disable (default), Restart enable (LHE).
- Program 07: Auto Restart When Over Temperature Occurs - Options: Restart disable (default), Restart enable (EYE).
- Program 09: Output Frequency - Options: 50Hz (default), 60Hz.
- Program 10: Output Voltage - Options: 220V, 230V (default), 240V.
- Program 11: Maximum Utility Charging Current - Options: 2A, 10A, 20A, 30A (default).
- Program 12: Setting Voltage Point Back to Utility Source - Configures the voltage point for switching back to utility when "SBU priority" or "Solar first" is selected in program 01. Options vary by model (3.6KW/4.2KW: 21.0V-25.5V; 6.2KW: 42V-51V).
- Program 13: Setting Voltage Point Back to Battery Mode - Configures the voltage point for switching back to battery mode when "SBU priority" or "Solar first" is selected in program 01. Options vary by model (3.6KW/4.2KW: 24V-29V; 6.2KW: 48V-54V).
- Program 16: Charger Source Priority - Configures charger source priority when working in Line, Standby, or Fault mode.
- Solar First (16 OSO): Solar energy charges battery first.
- Solar and Utility (16 SNU - default): Both solar and utility charge battery.
- Only Solar (16 OSO): Only solar energy charges battery.
- Program 18: Alarm Control - Options: Alarm on (default), Alarm off.
- Program 19: Auto Return to Default Display Screen - Options: ESP (default, returns to default display after 1 min inactivity), HEP (stays on last screen).
- Program 20: Backlight Control - Options: LON (Backlight on - default), LOF (Backlight off).
- Program 22: Beeps While Primary Source is Interrupted - Options: A00 (Alarm on - default), AOF (Alarm off).
- Program 23: Overload Bypass - Options: BYD (Bypass disable - default), BYE (Bypass enable).
- Program 25: Record Fault Code - Options: FEN (Record enable - default), FdS (Record disable).
- Program 26: Bulk Charging Voltage (C.V voltage) - Default: 28.2V (3.6KW/4.2KW), 56.4V (6.2KW). Range: 25.0V-30.0V (3.6KW/4.2KW), 48.0V-60.0V (6.2KW). Increment: 0.1V.
- Program 27: Floating Charging Voltage - Default: 27.0V (3.6KW/4.2KW), 54.0V (6.2KW). Range: 25.0V-30.0V (3.6KW/4.2KW), 48.0V-60.0V (6.2KW). Increment: 0.1V.
- Program 29: Low DC Cut-off Voltage - Default: 20.0V (3.6KW/4.2KW), 40.0V (6.2KW). Range: 20.0V-25.0V (3.6KW/4.2KW), 40.0V-50.0V (6.2KW). Increment: 0.1V.
- Program 30: Battery Equalization - Options: EEN (Battery equalization disable - default), EdS (Battery equalization enable).
- Program 31: Battery Equalization Voltage - Default: 29.2V (3.6KW/4.2KW), 58.4V (6.2KW). Range: 25.0V-31.5V (3.6KW/4.2KW), 48.0V-61.0V (6.2KW). Increment: 0.1V.
- Program 33: Battery Equalized Time - Default: 60min. Range: 5min-900min. Increment: 5min.
- Program 34: Battery Equalized Timeout - Default: 120min. Range: 5min-900min. Increment: 5min.
- Program 35: Equalization Interval - Default: 30 days. Range: 0-90 days. Increment: 1 day.
- Program 36: Equalization Activated Immediately - Options: AEN (Enable), A85 (Disable - default).
- Program 37: GRID-tie Operation - Options: OFF (Off grid - default), HYD (Hybrid).
- Program 38: GRID-tie Current - Default: 10A. Increment: 2A.
- Program 39: LED Pattern Light - Options: LOF (Led pattern off), LON (Led pattern on - default).
- Program 41: Dual Output - Options: L2F (disable - default), L20 (use).
- Program 42: Enter the Dual Output Functional Voltage Point - Default: 22.0V (3.6KW/4.2KW), 44.0V (6.2KW). Range: 20.0V-26.0V (24VDC), 40.0V-52.0V (48VDC). Increment: 0.1V.
- Program 43: BMS Communication Address 48-70 Setting - If in LIL mode, allows changing the mailing address.
- Program 44: Delayed Grid Access - Options: DIS (disable), ENA (enable - default).
- Program 45: Maximum Second Load - Range: 20%-70% of rated power.
5.5. Operating Mode Description
The LCD display information switches by pressing the "UP" or "DOWN" key. Information includes input voltage, frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, DC discharging current, and main CPU Version.
Example Display Screens:
- Charged State (Power less than 1KW): Displays input voltage, PV voltage, battery voltage, output voltage, load in Watt, and charging/inverter status.
- Charged State (Power greater than 1KW): Similar to above, but for higher power output.
- Discharged State (Power less than 1KW): Displays input voltage, PV voltage, battery voltage, output voltage, load in Watt, and charging/inverter status during discharge.
- Discharged State (Power greater than 1KW): Similar to above, but for higher power output during discharge.
- Standby Mode: Displays zero output and load when in standby.
- Line Mode: Displays input/output voltages and load when operating from AC line.
- Grid-Tie Operation: Displays relevant parameters when feeding power to the grid.
- Lithium Battery Communication (PACE 232 BMS): Displays total battery voltage, residual capacity, charging/discharge current, nominal voltage, total capacity, remaining capacity, and charge/discharge cycles.
- Lithium Battery Communication (PYLON 485 BMS): Displays total battery voltage, residual capacity, charging/discharge current, nominal voltage, total capacity, remaining capacity, and charge/discharge cycles.
5.6. Battery Equalization Description
The equalization function helps reverse the buildup of negative chemical effects (stratification) and removes sulfate crystals from battery plates, which can reduce battery capacity. Periodic equalization is recommended.
How to Apply Equalization Function:
First, enable battery equalization in LCD setting program 30. Then, activate it by:
- Setting the equalization interval in program 35.
- Activating equalization immediately in program 36.
When to Equalize:
In the float stage, when the set equalization interval is reached or equalization is activated immediately, the controller will enter the Equalize stage.
Equalize Charging Time and Timeout:
During equalization, the controller charges the battery until it reaches the equalization voltage. Constant-voltage regulation maintains this voltage. The battery remains in this stage until the set equalized time is reached. If the battery voltage doesn't reach the equalization voltage within the set time, the charge controller extends the time until it does. If the battery voltage is still lower than the equalization voltage after the timeout, the controller stops equalization and returns to the float stage.
5.7. Mains and Lithium Battery Activation Function
- After 90 seconds of mains power connection, the inverter connects to the mains and starts operation.
- If the inverter is in lithium battery mode (item 05 is LIP or LIL) and the mains are connected but the battery is not, the mains activation function is automatically enabled.
6. Maintenance
6.1. Anti-Dust Kit Clearance and Maintenance
Every inverter comes with an anti-dust kit installed from the factory. This kit helps prevent dust ingress and increases product reliability, especially in harsh environments. The inverter automatically detects the kit and adjusts its internal thermal sensor to manage temperature.
Maintenance Steps:
- Loosen the screw on the top of the inverter in a counterclockwise direction.
- Remove the dustproof case and take out the air filter foam.
- Clean the air filter foam and dustproof case. After cleaning, re-assemble the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.
7. Troubleshooting
This section provides guidance for common issues. If problems persist after following these steps, contact a qualified service person.
7.1. Fault Reference Code Table
| Fault Code | Fault Event | Icon on |
|---|---|---|
| 01 | Fan is locked when inverter is off. | 01 ERROR |
| 02 | Over temperature | 02 ERROR |
| 03 | Battery voltage is too high | 03 ERROR |
| 04 | Battery voltage is too low | 04 ERROR |
| 05 | Output short circuited or over temperature is detected by internal converter components. | 05 ERROR |
| 06 | Output voltage is too high. | 06 ERROR |
| 07 | Overload time out | 07 ERROR |
| 08 | Bus voltage is too high | 08 ERROR |
| 09 | Bus soft start failed | 09 ERROR |
| 51 | Over current or surge | 51 ERROR |
| 52 | Bus voltage is too low | 52 ERROR |
| 53 | Inverter soft start failed | 53 ERROR |
| 55 | Over DC voltage in AC output | 55 ERROR |
| 57 | Current sensor failed | 57 ERROR |
| 58 | Output voltage is too low | 58 ERROR |
| 59 | PV voltage is over limitation | 59 ERROR |
7.2. Battery Fault Codes (Lithium Battery Mode)
| Fault code | Fault event | Fault condition |
|---|---|---|
| 02 | The battery temperature is too high | Lithium battery charging temperature ≥65°C; Discharge temperature of the lithium battery is higher than 70°C. |
| 03 | The battery voltage is too high | Lithium battery maximum single cell voltage >3.65V; Total voltage of lithium battery >54.6V (48V lithium battery); Total voltage of lithium battery >29.1V (24V lithium battery). |
| 04 | The battery voltage is too low | Minimum voltage of a lithium battery cell <2.71V; Lithium battery total voltage <40.4V (48V lithium battery); Lithium battery voltage <21.5V (24V lithium battery). |
7.3. Warning Indicators
| Warning Code | Warning Event | Audible Alarm | Icon flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second | 01 |
| 03 | Battery is over-charged | Beep once every second | 03 |
| 04 | Low battery | Beep once every second | 04 |
| 07 | Overload | Beep once every 0.5 second | 07 |
| 10 | Output power derating | Beep twice every 3 seconds | 10 |
| 15 | PV energy is low. | Beep twice every 3 seconds | 15 |
| E9 | Battery equalization | None | E9 |
| bP | Battery is not connected | None | bP |
Added Battery Warning Codes (Lithium Battery Mode):
| Warning code | Warning event | Warning condition |
|---|---|---|
| 04 | The battery voltage is too low | Minimum voltage of a lithium battery cell <2.85V; Lithium battery total voltage <42V (48V lithium battery); Lithium battery voltage <22.4V (24V lithium battery). |
| 05 | The battery voltage is too high | Lithium battery maximum single cell voltage >3.55V; Total voltage of lithium battery >54V (48V lithium battery); Total voltage of lithium battery >28.8V (24V lithium battery). |
| 06 | The battery is low warning | Remaining battery capacity ≤10% |
8. Specifications
Detailed technical specifications for the DAXTROMN 4.2KW Hybrid Solar Inverter are provided below.

8.1. Line Mode Specifications (Table 1)
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) | ||
| Nominal Input Voltage | 230Vac | ||
| Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) | ||
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) | ||
| High Loss Voltage | 280Vac±7V | ||
| High Loss Return Voltage | 270Vac±7V | ||
| Max AC Input Voltage | 300Vac | ||
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | ||
| Low Loss Frequency | 40±1Hz | ||
| Low Loss Return Frequency | 42±1Hz | ||
| High Loss Frequency | 65±1Hz | ||
| High Loss Return Frequency | 63±1Hz | ||
| Output Short Circuit Protection | Circuit Breaker | ||
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | ||
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | ||
8.2. Inverter Mode Specifications (Table 2)
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Rated Output Power | 3.6KW | 4.2KW | 6.2KW |
| Output Voltage Waveform | Pure Sine Wave | ||
| Output Voltage Regulation | 230Vac±5% | ||
| Output Frequency | 50Hz | ||
| Peak Efficiency | 93% | ||
| Overload Protection | 3s@≥150% load; 5s@101%~150% load | ||
| Surge Capacity | 2* rated power for 5 seconds | ||
| Nominal DC Input Voltage | 24Vdc | 48Vdc | |
| Cold Start Voltage | 23.0Vdc | 46.0Vdc | |
| Low DC Warning Voltage @ load < 50% | 22.0Vdc | 44.0Vdc | |
| Low DC Warning Voltage @ load ≥ 50% | 21.0Vdc | 42.0Vdc | |
| Low DC Warning Return Voltage @ load < 50% | 22.5Vdc | 45.0Vdc | |
| Low DC Warning Return Voltage @ load ≥ 50% | 22.0Vdc | 44.0Vdc | |
| Low DC Cut-off Voltage @ load < 50% | 20.5Vdc | 41.0Vdc | |
| Low DC Cut-off Voltage @ load ≥ 50% | 20.0Vdc | 40.0Vdc | |
| High DC Recovery Voltage | 32Vdc | 62Vdc | |
| High DC Cut-off Voltage | 33Vdc | 63Vdc | |
| No Load Power Consumption | 30W | 35W | 50W |
8.3. Two Load Output Power (Table 3)
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Full Load | 3600W | 4200W | 6200W |
| Maximum Main Load | 3600W | 4200W | 6200W |
| Second Load Range | 720W~2520W | 840W~2940W | 1240W~4340W |
| Main Load Cut Off Voltage | 26VDC | ||
| Main Load Return Voltage | 27VDC | ||
8.4. Charge Mode Specifications (Table 4)
| Utility Charging Mode | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Charging Algorithm | 3-Step | ||
| AC Charging Current (Max) | 100Amp (@VI/P=230Vac) | ||
| Bulk Charging Voltage (Flooded Battery) | 29.2 | 58.4 | |
| Bulk Charging Voltage (AGM / Gel Battery) | 28.2 | 56.4 | |
| Floating Charging Voltage | 27Vdc | 54Vdc | |
MPPT Solar Charging Mode:
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Max. PV Array Power | 6200W | 6500W | |
| Nominal PV Voltage | 240Vdc | 360Vdc | |
| PV Array MPPT Voltage Range | 60Vdc~500Vdc | ||
| Max. PV Array Open Circuit Voltage | 500Vdc | ||
| Max Charging Current (AC charger plus solar charger) | 120Amp | 120Amp | 120Amp |
8.5. Grid-Tie Operation (Table 5)
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Nominal Output Voltage | 220/230/240 VAC | ||
| Feed-in Grid Voltage Range | 195~253VAC | ||
| Feed-in Grid Frequency Range | 50±1Hz/60±1Hz | ||
| Nominal Output Current | 15.7A | 18.2A | 26.9A |
| Power Factor Range | >0.99 | ||
| Maximum Conversion Efficiency (DC/AC) | 97% | ||
8.6. General Specifications (Table 6)
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Safety Certification | CE | ||
| Operating Temperature Range | -10°C to 50°C | ||
| Storage temperature | -15°C~60°C | ||
| Humidity | 5% to 95% Relative Humidity (Non-condensing) | ||
| Dimension (D*W*H), mm | 358×442×116 | ||
| Net Weight, kg | 8.0 | 8.0 | 8.9 |
8.7. Approximate Back-up Time Table (Table 9)
The backup time depends on battery quality, age, and type. Battery specifications may vary.
| Model | Load (W) | Backup Time @ 24Vdc 100Ah (min) | Backup Time @ 24Vdc 200Ah (min) |
|---|---|---|---|
| 3.6KW/4.2KW | 300 | 449 | 1100 |
| 600 | 222 | 525 | |
| 900 | 124 | 303 | |
| 1200 | 95 | 227 | |
| 1500 | 68 | 164 | |
| 1800 | 56 | 126 | |
| 2100 | 48 | 108 | |
| 2400 | 35 | 94 | |
| 2700 | 31 | 74 | |
| 3200 | 28 | 67 | |
| 3600 | 25 | 60 | |
| 4200 | 22 | 53 |
| Model | Load (W) | Backup Time @ 48Vdc 100Ah (min) | Backup Time @ 48Vdc 200Ah (min) |
|---|---|---|---|
| 6.2KW | 500 | 613 | 1288 |
| 1000 | 268 | 613 | |
| 1500 | 158 | 402 | |
| 2000 | 111 | 271 | |
| 2500 | 90 | 215 | |
| 3200 | 76 | 182 | |
| 3500 | 65 | 141 | |
| 4000 | 50 | 112 | |
| 4500 | 44 | 100 | |
| 5000 | 40 | 90 | |
| 6200 | 36 | 80 |
9. User Tips
- When operating without an external battery, ensure the solar panel input voltage is above 90V for normal inverter operation. If an external battery is connected, 60V input is sufficient.
- Regularly clean the anti-dust kit (monthly) to ensure optimal performance and longevity of the inverter, especially in dusty environments.
- For lithium battery systems, utilize the RS485 interface to configure the BMS battery charging protocol, which can help extend battery life.
10. Support and Further Information
For detailed information, including comprehensive diagrams and advanced settings, please refer to the full user manual PDF:
If you encounter persistent issues not covered in the troubleshooting section, please contact your local dealer or service center for assistance. Only qualified service personnel should attempt repairs.