1. Introduction
This manual describes the assembly, installation, operation, and troubleshooting of the PowMr 10.6KW Hybrid Inverter and 16kWh 48V LiFePO4 Battery system. Please read this manual carefully before installation and operation. Keep this manual for future reference.
This hybrid PV inverter and battery system is designed to provide continuous power to connected loads by utilizing PV power, utility power, and battery power. It is suitable for residential and commercial energy storage systems.
Key features of this combo include:
- Perfect Communication Match: RS485 and CAN ports are pre-configured for direct BMS communication between the inverter and battery, eliminating the need for extra configuration.
- Outdoor-Grade Protection: The inverter boasts an IP66 rating, and the battery an IP65 rating, ensuring protection against rain, snow, dust, and high humidity for reliable outdoor operation.
- Scalable Capacity: The system allows for expansion, starting with one battery and adding more later. Up to 9 inverters and 16 batteries can be paralleled for larger homes or light commercial use.
- Smart Energy Management: Real-time monitoring of solar generation, battery status, grid usage, and load consumption is available via the inverter's LCD and the i.Solar app.
- Ultra-Fast UPS Switch: A transfer time of less than 10ms for critical loads ensures uninterrupted power for essential appliances during outages.
A detailed user manual in PDF format is available for download: PowMr Solar Inverter User Manual (PDF)
2. Safety Instructions
⚠ WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION – To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION – Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
- Fuses are provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
- NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
3. Product Overview
The PowMr Hybrid Inverter and LiFePO4 Battery system is designed for efficient and reliable energy management. Below are the key components and their identification.
3.1. System Diagram



3.2. Inverter Components

The inverter features the following:
- PV connectors
- AC Grid connectors
- Battery connectors
- AC output connectors
- AC Generator connectors
- Sharing current ports & external sensor ports
- Parallel communication ports
- Dry contact/USB/RS-232/BMS communication ports
- LCD display
- Cold start button
For parallel model installation and operation, please check the separate parallel installation guide in Appendix I.
3.3. Battery Components

The battery is a POW-LIO48300-IP65 model, featuring a vertical design with wheels for easy movement and an IP65 rating for outdoor suitability.
3.4. Product Video Overview
4. Installation
4.1. Unpacking and Inspection
Before installation, carefully inspect the unit. Ensure that nothing inside the package is damaged. The package should contain the Inverter unit, Software CD, Manual, RS-232 cable, Parallel communication cable, Current sharing cable, Mounting screws, Mounting plate, WiFi antenna, and DC terminals (for 8.6KW, 10.6KW models).
4.2. Preparation and Mounting
Before connecting any wiring, remove the bottom cover by unscrewing the four screws. This hybrid inverter is designed for indoor or outdoor use (IP66), but ensure the installation site meets the following conditions:
- Not in direct sunlight.
- Not in areas where highly flammable materials are stored.
- Not in potential explosive areas.
- Not in direct cool air.
- Not near television antenna or antenna cable.
- Not higher than an altitude of about 2000 meters above sea level.
⚠ WARNING!! FIRE HAZARD. SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Mounting Steps:
- Fix two brackets on the two sides of the inverter with 8 screws.
- Install the inverter by screwing two screws on the top of two brackets.
- Fix the remaining two mounting holes with screws.
- The inverter should be installed in a shaded, rain-proof, or protected location.

4.3. Battery Connection
⚠ CAUTION: For safety and regulation compliance, install a separate DC over-current protector or disconnect device between the battery and inverter.
⚠ WARNING! All wiring must be performed by qualified personnel. Use appropriate cable for battery connection to reduce risk of injury.
Recommended Battery Cable and Terminal Size:
| MODEL | Typical Amperage | Wire Size | Torque Value |
|---|---|---|---|
| 6.6KW | 125A | 1*2AWG | 1.98 Nm |
| 8.6KW | 190A | 1*1/0 AWG | 5 Nm |
| 10.6KW | 210A | 1*1/0 AWG | 5 Nm |
Connection Steps:
- Remove insulation sleeve 18-19mm for two conductors.
- Insert battery wires according to polarities indicated on the terminal block and tighten the terminal screws. Ensure correct polarity at both the battery and the inverter/charger.
- For 8.6KW and 10.6KW models, assemble battery ring terminals and fix two cable glands into positive and negative terminals. Insert the ring terminal flatly into the battery connector and tighten screws with a torque of 5Nm.
⚠ CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring terminal. Otherwise, overheating may occur.
⚠ CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected tightly.
⚠ CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) is connected to negative (-).
4.4. AC Input/Output Connection
⚠ CAUTION!! Install a separate AC breaker (recommended 50A) between the inverter and AC input power source. Do NOT mis-connect input and output connectors.
Recommended Cable Requirement for AC Wires:
| MODEL | Gauge | Torque Value |
|---|---|---|
| 6.6KW | 10 AWG | 1.2~1.6 Nm |
| 8.6KW/10.6KW | 8 AWG | 1.2~1.6 Nm |
Connection Steps:
- Before making AC input/output connection, open the DC protector or disconnector first.
- Remove insulation sleeve 10-11mm.
- Insert AC input wires according to polarities (Ground, LINE, Neutral) indicated on the terminal block and tighten the terminal screws.
- The inverter is equipped with dual-output (AC output 1 and AC output 2). Insert AC output wires according to polarities and tighten terminal screws.
- Ensure all wires are securely connected.
⚠ CAUTION: Important! Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.
⚠ CAUTION: Appliances like air conditioners require 2-3 minutes to restart. Check if your appliance has a time-delay function before installation to prevent damage from power shortages.
4.5. PV Connection
⚠ CAUTION: Install a separate DC circuit breaker between the inverter and PV modules. Switch off the inverter before connecting PV modules to prevent damage.
PV Module Selection Parameters:
- Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter (500 Vdc).
- Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
Solar Charging Mode Specifications:
| Parameter | Value |
|---|---|
| Max. PV Array Open Circuit Voltage | 500 Vdc |
| PV Array MPPT Voltage Range | 120~450Vdc |
| MPP Number | 2 |
Connection Steps:
- Remove insulation sleeve 10-11 mm for positive and negative conductors.
- Check correct polarity of connection cable from PV modules and PV input connectors.
- Connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.

4.6. Communication Connection
Use the supplied communication cable to connect the inverter and PC. Insert the bundled CD into a computer and follow the on-screen instructions to install the monitoring software.
Serial Connection (RS232): Use a RJ45 cable. PIN assignment: PIN1: TXD, PIN2:RXD, PIN4:12V, PIN8:GND.
BMS Communication: Use a RJ45 cable. It is recommended to purchase a special communication cable if connecting to a Lithium-ion battery.
BMS PIN Assignment:
| PIN | Assignment |
|---|---|
| PIN 3 | RS485-B |
| PIN 5 | RS485-A |
| PIN 8 | GND |
For detailed BMS communication installation for specific battery types (LIO-4805/LIO-4810-150A, PYLONTECH, WECO, SOLTARO), refer to Appendix II of the full PDF manual.
4.7. Dry Contact Signal
A dry contact (3A/250VAC) is available on the rear panel to start or stop the generator, configurable via the HMI LCD (Setting -> Generator Settings). Ensure Dry Contact Setting is enabled in LCD settings.
Dry Contact Signal Conditions:
| Unit Status | Condition | Dry contact port: NC & C | Dry contact port: NO & C |
|---|---|---|---|
| Power Off | Unit is off and no output is powered. | Close | Open |
| Power On | Output is powered from Utility (Utility available) | Close | Open |
| Power On | Generator Settings -> When Battery voltage /SOC < Generator ON voltage/SOC | Open | Close |
| Power On | Generator Settings -> When Battery voltage /SOC > Generator OFF voltage/SOC | Close | Open |
5. Operation
5.1. LCD Display Icons
The inverter features a touchscreen LCD for monitoring and configuration. The main interface displays real-time system status.

Main Interface Elements:
- Top Bar: Displays time, Wi-Fi status, BMS status, and alarm sound.
- System Settings Icon: Press to enter system settings (general, output, battery, advanced, grid, generator settings).
- Main Screen: Shows information for inverter, solar, grid/generator, battery, and load. Energy flow is indicated by arrows.
- "Press to ON" Button: Toggles system on/off and displays inverter serial number, version, and event records.
- "Event" Button: View alarms and error records.
- Back Key: Returns to the home screen.
5.2. LCD Settings
Access settings by pressing the system settings icon on the main display. This allows configuration of various parameters.
General Settings:
- Time Setting: Set system time.
- LCD Sleep Time: Configurable (always/30 seconds/1 minute/never).
- Alarm Control: Enable or disable alarms.
- Overload Bypass: Enable or disable bypass overload.
Output Settings:
- Output Voltage: 220/230/240 V.
- Output Frequency: 50/60 Hz.
- AC Output Mode: Single or parallel mode.
- Output Source Priority: "SUB" or "SBU".
- Time Duration for Total AC Output On/Off: Control output 1/2 working time.
- Time Duration for O/P-2 On/Off: Control output 2 start and end time.
- Discharging Period for O/P-2: Control output 2 working time.
- Low DC Cut Off Voltage on O/P-2: Turn off output when battery voltage is below set point.
- Battery Re-discharging Voltage O/P-2: Turn off output when battery voltage is above set point.
Battery Settings:
- Battery Type: "Use" for lead-acid, others for lithium battery protocols.
- Charging Source Priority: Regular (Solar first, solar and Utility, Only solar) or Scheduled.
- Max (Grid+Solar) Charging Current: 10A to max charging current (10A increments).
- Max. Utility Charging Current: 2A to max charging current (10A increments).
- Max. Discharging Current: Set maximum discharge current.
- CV Voltage: 48.0V to 60.0V (follows BMS for lithium batteries).
- Floating Voltage: 48.0V to 60.0V (follows BMS for lithium batteries).
- Activate Lithium BAT When Power On: Enables lithium battery activation.
- Battery Low Cut Off and Re-discharging Setting: Customize low cut off voltage/SOC and re-discharging voltage/SOC.
- Max Discharging Current in Hybrid Mode: Sets max battery discharge current when feeding to grid.
- Time Of Use Setting: Set battery charging and discharging time periods.
Advanced Settings:
- Password Protected: Default password is 0000.
- Reset to Default: Restores factory settings.
- Erase All Data Log: Clears energy generation data.
- Solar Priority: Sets priority of PV energy.
- External CT: Enable for Zero Export To CT function.
- Touch Screen Calibration: Calibrate touch screen sensitivity.
- Lock All Changes: Locks key settings.
- Change Admin Password: Change password for Advanced Setting page.
Grid Settings:
- Wide AC Input: 90-280VAC (APL) or 170-280VAC (UPS).
- Reverse LED Calibration: Adjusts Grid power.
- Certification: Shows IEC62116 (not changeable).
- Feed to Grid: Allows solar energy to feed to the grid.
- Battery Feed to Grid: Allows battery energy to feed to the grid.
- Feed to Grid Power Limitation: Set limits (6600W, 8600W, 10600W).
Generator Settings:
- Generator On Voltage/SOC: Activates generator when battery voltage/SOC is low.
- Generator Off Voltage/SOC: Stops generator when battery voltage/SOC is high.
- Generator Charging Setting: Enables generator to charge battery.
- Dry Contact Setting: Disable (consistent with Power Off state) or Enable (depends on generator ON voltage/SOC).
5.3. Operating Mode Description
The system operates in various modes depending on power availability and configuration. You can check the current operating mode via the LCD.
| System Work Mode | Behaviors | State Description |
|---|---|---|
| Standby mode | No output power, solar or utility charger available | Battery is charged by PV energy. No charging. |
| Line mode | Output power from utility. Charger is available. | Utility charges battery and provides power to load. PV energy, battery power and utility provide power to load. PV energy and utility charge battery, and utility provides power to load. PV energy charges battery, utility and PV energy provide power to the load. PV energy charges battery, PV energy provides power to the load and feeds remaining energy to the grid. |
| Battery mode | Output power from battery or PV | PV energy and battery energy supply power to the load. PV energy charges battery and provides power to the load. Battery provides power to the load. |
| Only PV mode | Output power from PV | PV provides power to the load. No charging. |
| Fault mode | No output, no charging. | Errors caused by internal circuit or external reasons (e.g., over temperature, output short circuit). |
6. Specifications
Detailed technical specifications for the PowMr 10.6KW Hybrid Inverter and 16kWh 48V LiFePO4 Battery system.
| MODEL | 6.6KW | 10.6KW |
|---|---|---|
| RATED OUTPUT POWER | ||
| Rated Output Power | 6600W | 10600W |
| PV INPUT (DC) | ||
| Max. PV Power | 12000W | 18000W |
| Max. PV Array Open Circuit Voltage | 500 VDC | |
| MPPT Range @ Operating Voltage | 120 VDC~450 VDC | |
| Max. PV Array Maximum Imp/per MPPT | 2*21A | 2*27A |
| Number of MPPT Tracker | 2 | |
| GRID-TIE OPERATION | ||
| GRID OUTPUT (AC) | ||
| Nominal Output Voltage | 220/230/240 VAC | |
| Feed-in Grid Voltage Range | 195.5~253 VAC @India regulation 184 ~ 264.5 VAC @Germany regulation 184 ~ 264.5 VAC @South America regulation 195.5~253 VAC @ South Africa 182~260 VAC @ Pakistan | |
| Feed-in Grid Frequency Range | 49~51Hz @India regulation 47.5~51.5Hz @Germany regulation 57~62Hz @South America 47~52Hz @ South Africa 45.1~54.9Hz @ Pakistan | |
| Nominal Output Current | 28.7A | 46.1A |
| Maximum Conversion Efficiency (DC/AC) | 97% | |
| OFF-GRID, HYBRID OPERATION | ||
| GRID INPUT | ||
| Acceptable Input Voltage Range | 90 - 300 VAC or 170 - 300 VAC | |
| Frequency Range | 50 Hz/60 Hz (Auto sensing) | |
| Transfer Time | < 10ms (for UPS) < 20ms (for home appliances) < 50ms (for parallel system operation) | |
| Rating of AC Transfer Relay | 40A | 60A |
| GENERATOR INPUT | ||
| Acceptable Input Voltage Range | 90 - 300 VAC | |
| Frequency Range | 50 Hz/60 Hz (Auto sensing) | |
| Rating of AC Transfer Relay | 40A | 60A |
| BATTERY MODE OUTPUT (AC) | ||
| Nominal Output Voltage | 220/230/240 VAC | |
| Output Waveform | Pure Sine Wave | |
| Efficiency (DC to AC) | 93% | |
| BATTERY & CHARGER | ||
| Nominal DC Voltage | 48 VDC | |
| Maximum Charging Current (from Grid) | 135A | 210A |
| Maximum Charging Current (from PV) | 135A | 210A |
| Maximum discharging Current | 135A | 210A |
| GENERAL | ||
| Dimension, D X W X H (mm) | 633 x 418 x 192 | |
| Net Weight (kgs) | 23.5 | 29 |
| INTERFACE | ||
| Parallel-able | Yes | |
| External Safety Box (Optional) | Yes | |
| Communication | USB or RS232 / RS 485/WIFI | |
| ENVIRONMENT | ||
| Humidity | 0 ~ 95% RH (No condensing) | |
| Operating Temperature | -25°C to 50°C | |
Battery Specifications (POW-LIO48300-IP65):
- Nominal Energy: 16.18kWh (51.2V, 316Ah)
- Cells: Grade A LiFePO4
- Cycle Life: ≥6000 cycles (80% DOD)
- IP Rating: IP65 (rainproof and dust-tight)
- BMS: Built-in with 2A active balancing
- Parallel Connection: Up to 16 batteries (max 258kWh)
- Design: Floor-standing with heavy-duty casters
- Max Charge Current: 200A
- Continuous Discharge Current: 200A
- Communication Interfaces: RS232, RS485, CAN, dry contact
- Safety: Built-in DC Breaker, low-voltage switch design
7. Maintenance
Regular maintenance ensures the longevity and optimal performance of your PowMr Hybrid Inverter and Battery system.
- Periodic Inspection: Regularly check all wiring connections for tightness and signs of wear or corrosion.
- Cleaning: Keep the inverter and battery surfaces clean and free from dust and debris. Ensure ventilation openings are not blocked.
- Environmental Check: Verify that the installation environment remains within the specified temperature and humidity ranges.
- Software Updates: Periodically check for and apply any available firmware updates for the inverter via the i.Solar app to ensure optimal performance and security.
- Battery Health: Monitor battery performance through the LCD display and i.Solar app. Pay attention to any warnings or fault codes related to battery health.
8. Troubleshooting
This section provides common problems, their possible causes, and solutions. For persistent issues, contact customer support.
8.1. General Troubleshooting
| Problem | HMI/Buzzer | Explanation / Possible cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | HMI and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. The battery voltage is far too low. (<1.4V/Cell) 2. Battery polarity is connected reversed. | 1. Check if batteries and the wiring are connected well. 2. Re-charge battery. 3. Replace battery. |
| Mains exist but the unit works in battery mode. | HMI shows grid voltage is 0V | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. |
| When the unit is turned on, internal relay is switched on and off repeatedly. | HMI shows battery voltage is 0V | Battery is disconnected. | Check if battery wires are connected well. |
| Overload error | The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. | |
| Output short circuited. | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Over Temperature | Internal temperature of inverter component is over 100°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Battery high voltage | Buzzer beeps continuously and HMI show the Fault icon | Battery is over-charged. The battery voltage is too high. | Return to repair center. Check if spec and quantity of batteries are meet requirements. |
| FAN lock | Fan fault | Replace the fan. | |
| Output abnormal | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center | |
| DC-DC overcurrent | DC/DC over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
| Inverter overcurrent | Over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
| BUS low voltage | Bus voltage is too low. | Restart the unit, if the error happens again, please return to repair center. | |
| Abnormal output voltage | Output voltage is unbalanced. | Restart the unit, if the error happens again, please return to repair center. | |
| Solar high voltage | Solar input voltage is more than 550V. | Reduce the number of solar panels | |
| Battery Low | The battery voltage is less than 30V | Charge the battery voltage to above 30V | |
| Battery overcurrent | The battery is over-discharged | The discharge current of the battery needs to be reduced |
8.2. Parallel Operation Troubleshooting
| Fault Code | Fault Event Description | Solution |
|---|---|---|
| 60 | Current feedback into the inverter is detected. | 1. Restart the inverter. 2. Check if L/N cables are not connected reversely in all inverters. 3. For parallel system in single phase, make sure the sharing cables are connected in all inverters. 4. For supporting three-phase system, make sure the sharing cables are connected in the inverters in the same phase, and disconnected in the inverters in different phases. 5. If the problem remains, please contact your installer. |
| 71 | The firmware version of each inverter is not the same. | 1. Update all inverter firmware to the same version. 2. Check the version of each inverter via LCD setting and make sure the CPU versions are same. If not, please contact your installer to provide the firmware to update. 3. After updating, if the problem still remains, please contact your installer. |
| 72 | The output current of each inverter is different. | 1. Check if sharing cables are connected well and restart the inverter. 2. If the problem remains, please contact your installer. |
| 80 | CAN data loss | 1. Check if communication cables are connected well and restart the inverter. 2. If the problem remains, please contact your installer. |
| 81 | Host data loss | 1. Check if communication cables are connected well and restart the inverter. 2. If the problem remains, please contact your installer. |
| 82 | Synchronization data loss | 1. Check if communication cables are connected well and restart the inverter. 2. If the problem remains, please contact your installer. |
| 83 | The battery voltage of each inverter is not the same. | 1. Make sure all inverters share same groups of batteries together. 2. Remove all loads and disconnect AC input and PV input. Then, check battery voltage of all inverters. If the values from all inverters are close, please check if all battery cables are the same length and same material type. Otherwise, please contact your installer to provide SOP to calibrate battery voltage of each inverter. 3. If the problem still remains, please contact your installer. |
| 84 | AC input voltage and frequency are detected different. | 1. Check the utility wiring connection and restart the inverter. 2. Make sure utility starts up at same time. If there are breakers installed between utility and inverters, please be sure all breakers can be turned on AC input at same time. 3. If the problem remains, please contact your installer. |
| 85 | AC output current unbalance | 1. Restart the inverter. 2. Remove some excessive loads and re-check load information from LCD of inverters. If the values are different, please check if AC input and output cables are in the same length and material type. 3. If the problem remains, please contact your installer. |
| 86 | AC output mode setting is different. | 1. Switch off the inverter and check LCD setting of “AC OUTPUT MODE”. 2. For parallel system in one phase, make sure no 3P1, 3P2 or 3P3 is set. 3. For supporting three-phase system, make sure no “PAL” is set. |
| 87 | Single Machine exists in parallel system | 1. Check whether a single machine exists in parallel system. |
9. User Tips
Here are some helpful tips for optimizing your PowMr Hybrid Inverter and Battery system:
- Monitor Regularly: Use the i.Solar app to keep an eye on your system's performance, battery charge, and energy flow. This helps in identifying potential issues early.
- Optimize Time-of-Use: Configure the "Time Of Use Setting" in the LCD to charge batteries during off-peak electricity hours and discharge during peak hours to save on energy costs.
- Proper Sizing for Parallel Systems: If expanding with multiple inverters or batteries, ensure all cables (battery, AC input/output, current sharing) are of the same length and material type to prevent voltage differences and ensure stable operation.
- Secure Connections: Always double-check all electrical connections for tightness and correct polarity to prevent faults and ensure safety.
- Environmental Awareness: While outdoor-rated, placing the units in a shaded, protected location can extend their lifespan and maintain optimal operating temperatures.
10. Warranty and Support
The PowMr 10.6KW Hybrid Inverter and 16kWh 48V LiFePO4 Battery system typically comes with a 1-year warranty. For any technical support, service, or warranty claims, please contact the manufacturer directly.
Contact Information:
- Brand: PowMr
- Email: support@powmr.com
- Web: www.powmr.com
- Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China
- Tel/Fax: +86755-28219903
11. Appendix
11.1. Parallel Function
This inverter supports parallel operation in two modes:
- Single phase parallel operation with up to 9 units.
- Three-phase equipment support with up to 9 units (max 7 units per phase).
When installing multiple units, ensure proper spacing for heat dissipation (approx. 20cm to the side, 50cm above and below, 100cm to the front). All battery cables must be of the same length and material. For detailed wiring diagrams and breaker specifications for parallel configurations, refer to Appendix I in the full PDF manual.
⚠ WARNING: When the number of parallel machines exceeds 6, add a magnetic ring to the output L cable. The magnetic ring is found in the inverter's accessory bag.
⚠ WARNING: Do not connect the current sharing cable between inverters in different phases, as this may damage the inverters.
11.2. BMS Communication Installation
For connecting to a lithium battery, a custom-made RJ45 communication cable is recommended. This cable facilitates information exchange between the lithium battery and the inverter, including re-configuring charging voltage/current and battery discharge cut-off voltage, and controlling inverter charging based on battery status.
For detailed pin assignments and specific battery communication configurations (e.g., LIO-4805/LIO-4810-150A, PYLONTECH, WECO, SOLTARO), refer to Appendix II in the full PDF manual.
11.3. Wi-Fi Operation Guide
The built-in Wi-Fi module enables wireless communication with the monitoring platform, allowing remote monitoring and control via the i.Solar APP (available for iOS 12.0+ and Android 10.0+).
Key Functions of i.Solar App:
- Daily data monitoring of the inverter.
- Querying real-time data.
- Sending commands to the device.
- Remote operation of the device.
Wi-Fi Model Setting:
- Turn on your mobile device and open Wi-Fi settings.
- Connect to the Wi-Fi network starting with "FC41D_" (default password: 12345678).
- Open the i.Solar App, log in, and navigate to "Network Config" to enter your home router's Wi-Fi name (STA SSID) and password (STA Password).
- Save the settings.
For detailed instructions on app usage, login, home page features, real-time data, parameter settings, and OTA firmware updates, refer to Appendix III in the full PDF manual.