1. Introduction
This manual describes the assembly, installation, operation, and troubleshooting of the POWMr 6.6KW Hybrid Inverter and 48V 5.12kWh LiFePO4 Battery Solar Storage System Kit. Please read this manual carefully before installations and operations. Keep this manual for future reference.
This hybrid PV inverter system is designed to provide continuous power to connected loads by utilizing PV power, utility power, and battery power. It is ideal for residential and commercial energy storage systems, addressing power outage concerns and high electricity bills. The system features a high-efficiency POW-ELITE inverter and high-capacity lithium iron phosphate batteries, allowing storage of solar energy for night-time use or during outages.
The system is suitable for detached homes, remote farms, seafood farming facilities, small factories, and field construction offices.



2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION – To reduce risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION – Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short-circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for the details.
- Fuses are provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short-circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
3. Product Overview
The POW-ELITE 6.6KW Hybrid Inverter is an all-in-one solar inverter designed for residential and commercial energy storage systems. It delivers 10600 watts of pure sine wave output at 220 volts with adjustable output voltage. Up to nine units can operate in single-phase or three-phase parallel, reaching a total output of 95.4 kilowatts. It features dual MPPTs with 1.7 times PV oversizing, supporting up to 18 kilowatts of solar input and a 500-volt maximum open-circuit voltage. The inverter is compatible with 48-volt lithium or lead-acid batteries and supports up to 210 amps of charging current. It includes BMS communication for system safety, an IP66 rating, and built-in Wi-Fi for reliable outdoor operation and easy remote monitoring from your smartphone.
The POW-LIO48100-IP65 battery is a 48V 5.12kWh LiFePO4 battery with a 100Ah capacity, 100A max discharge current, and over 6000 cycles. It supports up to 16 parallel connections and features built-in Wi-Fi.



Product Components (Refer to Figure 7)

- PV connectors
- AC Grid connectors
- Battery connectors
- AC output connectors
- AC Generator connectors
- Sharing current ports & external sensor ports
- Parallel communication ports
- Dry contact/USB/RS-232/BMS communication ports
- LCD display
- Cold start button
4. Installation
4.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items:
- Inverter unit
- Software CD
- Manual
- RS-232 cable
- Parallel communication cable
- Current sharing cable
- Mounting screws
- Mounting plate
- WiFi antenna
- DC terminals (Only for 8.6KW, 10.6KW models)
4.2 Preparation
Before connecting all wirings, please take off the bottom cover by removing four screws.
4.3 Installing the Unit
This hybrid inverter is designed for indoor or outdoor use (IP66), please make sure the installation site meets below conditions:
- Not in direct sunlight
- Not in areas where highly flammable materials are stored.
- Not in potential explosive areas.
- Not in the cool air directly.
- Not near the television Antenna or antenna cable.
- Not higher than altitude of about 2000 meters above sea level.
- Please AVOID direct sunlight, rain exposure, snow laying up during installation and operation.
Select the Mounting Place
- Please select a vertical wall with load-bearing capacity for installation, appropriate for installation on concrete or other non-flammable surfaces.
- The ambient temperature should be between -25~60°C to ensure optimal operation.
- Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and have enough space for removing wires.
- For proper air ventilation to dissipate heat, allow a clearance of approx. 50cm to the side and approx. 50cm above and below the unit. And 100cm toward the front of the unit.
- The inverter should be installed in a shaded, rain proof or protected location.
Mounting the Unit
WARNING!!
Remember that this inverter is heavy! Please be careful when lifting out from the package.
Installation to the wall should be implemented with the proper screws. After that, the device should be bolted on securely.
The inverter only can be used in a CLOSED ELECTRICAL OPERATING AREA. Only service person can enter this area.
WARNING!! FIRE HAZARD. SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
- Step 1: Fix two brackets on the two sides of the inverter with 8 screws.
- Step 2: Install the inverter by screwing two screws on the top of two brackets.
- Step 3: Then, fix the remaining two mounting holes with screws.
- Step 4: The inverter should be installed in a shaded, rain proof or protected location.
4.4 Battery Connection
CAUTION:
For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable and terminal size as below.
Recommended battery cable and terminal size:
| MODEL | Typical Amperage | Wire Size | Torque Value |
|---|---|---|---|
| 6.6KW | 125A | 1*2AWG | 1.98 Nm |
| 8.6KW/10.6KW | 190A / 210A | 1*1/0 AWG | 5 Nm |
For 6.6KW model:
Please follow the below steps to implement battery connection:
- Remove insulation sleeve 18~19mm for two conductors.
- Insert battery wires according to polarities indicated on the terminal block and tighten the terminal screws. Make sure polarity at both the battery and the inverter/charger is correctly connected.
For 8.6KW and 10.6KW models:
Please follow the below steps to implement battery connection:
- Assemble battery ring terminal based on recommended battery cable.
- Fix two cable glands into positive and negative terminals.
- Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the screws are tightened with torque of 5Nm. Make sure polarity at both the battery and the inverter/charger is correctly connected and ring terminals are tightly screwed to the battery terminals.
WARNING: Shock Hazard
Installation must be performed with care due to high battery voltage in series.
CAUTION!!
Do not place anything between the flat part of the inverter terminal and the ring terminal. Otherwise, overheating may occur.
Do not apply anti-oxidant substance on the terminals before terminals are connected tightly.
Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
4.5 AC Input/Output Connection
CAUTION!!
Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. The recommended spec of AC breaker is 50A. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input.
CAUTION!!
There are two terminal blocks with “IN” and “OUT" markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires:
| MODEL | Gauge | Torque Value |
|---|---|---|
| 6.6KW | 10 AWG | 1.2~ 1.6 Nm |
| 8.6KW/10.6KW | 8 AWG | 1.2~ 1.6 Nm |
Please follow below steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open DC protector or disconnector first.
- Remove insulation sleeve 10-11mm.
- Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (➔) first.
- ➔Ground (yellow-green)
- L➔LINE (brown or black)
- N➔Neutral (blue)
WARNING:
Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
This inverter is equipped with dual-output. There are two outputs: AC output 1 and AC output 2. It's set up through LCD program or monitoring software to turn on and off the second output. Refer to "LCD setting" section for the details.
Insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. Be sure to connect PE protective conductor (➔) first.
- ➔Ground (yellow-green)
- L➔LINE (brown or black)
- N➔Neutral (blue)
Make sure the wires are securely connected.
CAUTION: Important
Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.
CAUTION:
Appliances such as air conditioner are required at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it's equipped with time-delay function before installation. Otherwise, this inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.
The working logic of the generator
The generator is mainly used to substitute the Utility power to ensure the normal operation of the inverter. There are two operation situations:
- Connect to the generator and Utility when the Utility is normal:
The inverter will close the Grid relay, and at this time, the utility will provide power to load, charge battery or feed the grid. In this case, the generator relay will be open.
- Connect to the generator when the Utility is abnormal or lost:
The inverter will close the generator relay, and at this time, the generator will provide power to load. The generator does not charge the battery by default, and if it needs to be charged, it needs to enable the Generator Charging Setting. In this case, the grid relay will be open.
NOTE 1: After the generator is connected, the inverter will automatically turn off the grid-connected function to protect the generator.
NOTE 2: Only when the inverter is set to single-machine mode, the generator will be connected.
4.6 PV Connection
CAUTION:
Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.
WARNING! All wiring must be performed by a qualified personnel.
WARNING: Please switch off the inverter before you connect PV modules. Otherwise, it will damage the inverter.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for PV wires:
| MODEL | Typical Amperage | Cable Size | Torque |
|---|---|---|---|
| 6.6KW | 21A | 14AWG | 2.0~2.4Nm |
| 8.6KW/10.6KW | 27A | 12AWG | 2.0~2.4Nm |
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
- Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
Solar Charging Mode:
| Max. PV Array Open Circuit Voltage | 500 Vdc |
| PV Array MPPT Voltage Range | 120~450Vdc |
| MPP Number | 2 |
Please follow below steps to implement PV module connection:
- Remove insulation sleeve 10-11 mm for positive and negative conductors.
- Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
Solar Panel Configuration (For 6.6KW)
| Solar Panel Spec | Solar 1 | Solar 2 |
|---|---|---|
| Nominal Max. power (Pmax)(W) | 450 / 615 | 454 / 620 |
| Opt. Operating Voltage (Vmp) (V) | 41.4 / 44.6 | 41.6 / 44.8 |
| Opt. Operating Current (Imp) (A) | 10.87 / 13.79 | 10.91 / 13.84 |
| Open Circuit Voltage (Voc) (V) | 48.9 / 52.4 | 49 / 52.6 |
| Short Circuit Current (Isc) (A) | 11.68 / 14.72 | 11.73 / 14.78 |
| Solar Panel Configuration (For 6.6KW) | ||
| Numbers in series of MPPT1 | 7 / 9 | 7 / 9 |
| Numbers of strings in MPPT1 | 2 / 1 | 2 / 1 |
| Maximum input voltage of MPPT1 (V) | 342.3 / 471.6 | 343 / 473.4 |
| Input power of MPPT1 (W) | 6300 / 5535 | 6356 / 5580 |
| Numbers in series of MPPT2 | 7 / 9 | 6 / 9 |
| Numbers of strings in MPPT2 | 2 / 1 | 2 / 1 |
| Maximum input voltage of MPPT1 (V) | 342.3 / 471.6 | 294 / 473.4 |
| Input power of MPPT2 (W) | 6300 / 5535 | 5448 / 5580 |
| Total input power (W) | 12600 / 11070 | 11804 / 11160 |
Solar Panel Configuration (For 8.6KW)
| Numbers in series of MPPT1 | 9 | 9 | 7 | 7 |
| Numbers of strings in MPPT1 | 2 | 2 | 2 | 2 |
| Maximum input voltage of MPPT1 (V) | 440.1 | 441 | 366.8 | 368.2 |
| Input power of MPPT1 (W) | 8100 | 8172 | 8610 | 8680 |
| Numbers in series of MPPT2 | 9 | 8 | 6 | 6 |
| Numbers of strings in MPPT2 | 2 | 2 | 2 | 2 |
| Maximum input voltage of MPPT1 (V) | 440.1 | 392 | 314.4 | 315.6 |
| Input power of MPPT2 (W) | 8100 | 7264 | 7380 | 7440 |
| Total input power (W) | 16200 | 15436 | 15990 | 16120 |
Solar Panel Configuration (For 10.6KW)
| Numbers in series of MPPT1 | 9 | 9 | 7 | 7 |
| Numbers of strings in MPPT1 | 2 | 2 | 2 | 2 |
| Maximum input voltage of MPPT1 (V) | 440.1 | 441 | 366.8 | 368.2 |
| Input power of MPPT1 (W) | 8100 | 8172 | 8610 | 8680 |
| Numbers in series of MPPT2 | 9 | 9 | 7 | 7 |
| Numbers of strings in MPPT2 | 2 | 2 | 2 | 2 |
| Maximum input voltage of MPPT1 (V) | 440.1 | 441 | 366.8 | 368.2 |
| Input power of MPPT2 (W) | 8100 | 8172 | 8610 | 8680 |
| Total input power (W) | 16200 | 16344 | 17220 | 17360 |
4.7 Communication Connection
Please use the supplied communication cable to connect to the inverter and PC. Follow the below procedure to connect communication wiring. Insert bundled CD into a computer and follow the on-screen instructions to install the monitoring software. For the detailed software operation, please check the user manual of the software inside of a CD.
Serial Connection
For RS232 port, you should use a RJ45 cable as follows: PIN1: TXD, PIN2:RXD, PIN4:12V, PIN8:GND. The RJ45 line sequence is as follows: 8-1.
For USB port, you should use a USB cable.
BMS Communication
For BMS port, you should use a RJ45 cable as follows:
| PIN Assignment | Definition |
|---|---|
| PIN 1 | RS232TX |
| PIN 2 | RS232RX |
| PIN 3 | RS485B |
| PIN 4 | NC |
| PIN 5 | RS485A |
| PIN 6 | CANH |
| PIN 7 | CANL |
| PIN 8 | GND |
It is recommended to purchase a special communication cable if you are connecting to Lithium-ion battery. Please use a RJ45 cable to connect BMS communication port and PIN assignment is listed as above table.
For more information, please refer to Appendix II: BMS Communication Installation.
4.8 Dry Contact Signal
There is one dry contact (3A/250VAC) available on the rear panel. This dry contact is used to start or stop the generator, which can be set in the Setting ->Generator Settings on the HMI LCD.
NOTE: Be sure to enable Dry Contact Setting in LCD setting. Otherwise, the dry contact state is consistent with the power off state.
| Unit Status | Condition | Dry contact port: NC C NO | |
|---|---|---|---|
| NC & C | NO & C | ||
| Power Off | Unit is off and no output is powered. | Close | Open |
| Power On | Output is powered from Utility.(Utility available) | Close | Open |
| Generator Settings➔When Battery voltage /SOC < Generator ON voltage/SOC | Open | Close | |
| Generator Settings➔When Battery voltage /SOC > Generator OFF voltage/SOC | Close | Open | |
4.9 Parallel Function
This inverter can be used in parallel with two different operation modes:
- Parallel operation in single phase with up to 9 units.
- Maximum nine units work together to support three-phase equipment. Seven units support one phase maximum.
Mounting the Unit for Parallel Operation
When installing multiple units, please follow below chart.
NOTE: For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit. Be sure to install each unit at the same level.
Wiring Connection for Parallel Operation
NOTICE: It's requested to connect to battery for parallel operation.
The cable size of each inverter is shown as below:
| MODEL | AWG no. | Torque |
|---|---|---|
| 6.6KW | 1*2AWG | 2~3 Nm |
| 8.6KW/10.6KW | 1*1/0 AWG | 2~3 Nm |
WARNING: Be sure the length of all battery cables is the same. Otherwise, there will be voltage difference between inverter and battery to cause parallel inverters not working.
Recommended AC input and output cable size for each inverter (Parallel):
| MODEL | AWG no. | Torque |
|---|---|---|
| 6.6KW | 10 AWG | 1.2~1.6Nm |
| 8.6KW/10.6KW | 8 AWG | 1.2~1.6Nm |
You need to connect the cables of each inverter together. Take the battery cables for example: You need to use a connector or bus-bar as a joint to connect the battery cables together, and then connect to the battery terminal. The cable size used from joint to battery should be X times cable size in the tables above. “X" indicates the number of inverters connected in parallel. Regarding AC input and output, please also follow the same principle.
WARNING!! Make sure all output N wires of each inverter must be connected all the time. Otherwise, it will cause inverter fault in error code #72.
Recommended breaker specification of battery for each inverter (Parallel):
| Model | 1 unit* |
|---|---|
| 6.6KW | 140A/70VDC |
| 8.6KW/10.6KW | 220A/70VDC |
*If you want to use only one breaker at the battery side for the whole system, the rating of the breaker should be X times current of 1 unit. "X" indicates the number of inverters connected in parallel.
Recommended breaker specification of AC input with single phase (Parallel):
| Model | 2 units | 3 units | 4 units | 5 units | 6 units | 7 units | 8 units | 9 units |
|---|---|---|---|---|---|---|---|---|
| 6.6KW | 80A/230VAC | 120A/230VAC | 160A/230VAC | 200A/230VAC | 240A/230VAC | 280A/230VAC | 320A/230VAC | 360A/230VAC |
| 8.6KW/10.6KW | 120A/230VAC | 180A/230VAC | 240A/230VAC | 300A/230VAC | 360A/230VAC | 420A/230VAC | 480A/230VAC | 540A/230VAC |
Note1: Also, you can use one unit of 50A and install one breaker at its AC input in each inverter.
Note2: Regarding three-phase system, you can use 4-pole breaker directly and the rating of the breaker should be compatible with the phase current limitation from the phase with maximum units.
Recommended battery capacity (Parallel):
| Inverter parallel numbers | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
|---|---|---|---|---|---|---|---|---|
| Battery Capacity | 400AH | 600AH | 800AH | 1000AH | 1200AH | 1400AH | 1600AH | 1800AH |
WARNING! Be sure that all inverters will share the same battery bank. Otherwise, the inverters will transfer to fault mode.
WARNING: When the number of parallel machines exceeds 6 PCS, add a magnetic ring to the output L cable. The magnetic ring is placed in the accessory bag of the inverter.
WARNING: Do not connect the current sharing cable between the inverters which are in different phases. Otherwise, it may damage the inverters.
PV Connection for Parallel Operation
Please refer to user manual of single unit for PV Connection.
CAUTION: Each inverter should connect to PV modules separately.
5. Operation
5.1 LCD Display Icons
The LCD is touchscreen. The main interface display screen is as follows:

- This top displays the time, WIFI status, BMS, and alarm sound.
- System settings icon, press this setting button to enter the system settings screen including general setting, output setting, battery setting, advanced setting, grid setting, and generator setting.
- The main screen show information including inverter solar, grid/ Generator, battery, load. It also displays the direction of energy flow through arrows, clearly showing the working status of the inverter.
- Touch "Press to ON" to enter the system turn on/off screen. This page can also display information such as inverter serial number, version number, event records, etc.
- Press the Home key to Back to home screen.
Icon Function Description:
| Icon | Function description |
|---|---|
| System on/off, Fault information and Configuration procedures | The top of the screen indicates the time of the local month, day and year. |
| Touch the "ON" icon to enter another interface to control the switch of the inverter and query the software version and machine status (including the serial number, parallel status, operating mode, DSP version, MCU version, remote version, and LCD version, TP Version of the inverter). Touch "➔" or "➔" check the machine S/N number, parallel status, system working status, software version number. Touch "System On/Off" to control the inverter switch. | |
| Touch "Event" to view the alarms and error records. |
Grid & Generator Information:
| Icon | Function description |
|---|---|
| Grid/Generator icon: | Cycle display of AC input voltage (grid and generator), current, and power. |
| When you touch this icon, it display detailed grid and generator information. It includes grid frequency, voltage, current, power flow state, power, Generator frequency and generator voltage. |
PV Information:
| Icon | Function description |
|---|---|
| Cycle display of the “PV1&PV2" voltage, current and power. When you touch this icon, it display detailed PV information. It includes total PV power, PV1/PV2 voltage and current power, daily power generation, monthly power generation, annual power generation, total power generation will be displayed. | |
| When you touch the "Energy Chart" you will enter the "Solar Power Flow page". Solar power curve for daily, monthly, yearly and total can be checked on the LCD, we can also view more detailed power generation through the monitoring system. Press "ESC" icon to back to previous page. |
Battery Information:
| Icon | Function description |
|---|---|
| Cycle display the "Battery" voltage (SOC), current and power. | |
| Battery detail page | 1. This page indicates the battery Type, statue, SOC, voltage, current and power. 2. If you use lithium battery, you can press "BMS Information" to check lithium battery information. |
| BMS Information | When you touch "BMS Information" it will display the communication status, maximum charge voltage, maximum charge current, cut-off voltage point, maximum discharge current point. |
Load Information:
| Icon | Function description |
|---|---|
| Cycle display the output 1 & 2 voltage, power and output current. | |
| Load | When you touch this icon, it will display the “OP1/OP2" frequency, battery current, power, and output percentage. |
5.2 LCD Setting
The marked section is for entering the settings interface, which includes general setting, output setting, battery setting, advanced setting, grid setting, generator setting.
System settings icon, press this setting button to enter the system settings screen including general setting, output setting, battery setting, system operation Mode setting, Grid setting. See "LCD Setting" section for the details.
Operation Status Information:
The red marked sections can respectively display the BMS, buzzer, and WIFI status.
The red marked display sections indicate the measurement mode: "V" for voltage value, “I” for current value, and “P” for power value.
General Setting:
| Program Description | Function description |
|---|---|
| This is General Setting detail page | |
| Time Setting: | Set system time. |
| LCD Sleep Time: | LCD sleep time can be set always/30 seconds/ 1 minute /never. |
| Alarm control: | Can set enable or disable alarms. |
| Overload Bypass: | Can set enable or disable bypass overload |
Output Setting:
| This is Output Setting detail page | |
| Output voltage: | The output Voltage can be set 220/230/240 V |
| Output frequency: | The frequency can be set 50/60 Hz |
| AC Output mode: | You can modify this parameter to set it to single mode or parallel mode. For more details please see "AC Output mode" setting section. |
| Output source priority: | You can modify "SUB" or "SBU". |
| Time Duration for Total AC Output On/off: | You can control the output1/2 Working time. |
| Time Duration for O/P-2 On/Off: | You can control the start and end time of Output 2 |
| Discharging Period for O/P-2: | You can control the output2 Working time. |
| Low DC Cut Off Voltage on O/P-2: | Turn off the OP output when the battery voltage is below the set point. |
| Battery Re-discharging Voltage O/P-2: | Turn off the OP output when the battery voltage is higher than the set point. |
Battery Setting:
| This is Battery Setting detail page | |
| Battery type: | "Use" means lead-acid battery, while others are lithium battery protocols. |
| Charging Source Priority: | It includes both regular settings and scheduled settings. Regular: Solar first, solar and Utility, Only solar. Schedule: You can customize the charging time period. |
| Max (Grid+ Solar) Charging Current: | setting range is from 10A to the maximum charging current. Increment of each click is 10A. |
| Max. Utility Charging Current: | setting range is from 2A to the maximum charging current. Increment of each click is 10A. |
| Max. Discharging Current: | You can set the maximum discharge current of the battery. |
| CV Voltage: | Setting range is from 48.0V to 60.0V. If the battery type is lithium battery, this parameter follows its BMS voltage parameter. |
| Floating Voltage: | Setting range is from 48.0V to 60.0V. If the battery type is lithium battery, this parameter follows its BMS voltage parameter. |
| Activate Lithium BAT when Power on: | Enabling this option will activate the lithium battery. |
| Battery low cut off and Re-discharging setting: | You can customize battery low cut off voltage/SOC and Re-discharging voltage/SOC. |
| Max Discharging Current in hybrid Mode: | When enabling the battery feed to grid function, this setting can set the maximum battery discharge current. |
| Time Of Use Setting: | It's to set up battery charging and discharging time periods. |
Advanced Setting:
| Advanced Setting | It is required a password to enter. The default password is 0000, but you can also change it in “Change Admin Password". |
| Reset to Default: | If this option is enabled, the machine will go back to factory Settings. |
| Erase All Data log: | Clear all energy generation data. |
| Solar Priority: | Set the priority of PV energy. |
| External CT: | If Zero Export To CT function is required, you need to enable this setting item, which default setting is "disable". |
| Touch Screen Calibration: | You can calibrate the touch screen sensitivity. |
| Lock All Changes: | If enabled is selected, key settings are locked and cannot be modified. |
| Change Admin Password: | You can change the password to access Advanced Setting page. |
Grid Setting:
| This is Grid Setting detail page | |
| Wide AC Input: | If APL selected, acceptable AC input voltage range will be within 90-280VAC. If UPS selected, acceptable AC input voltage range will be within 170-280VAC. |
| Reverse LED Calibration: | This will adjust the Grid power. |
| Certification: | It only shows IEC62116. It's not allowed to change. |
| Feed to Grid: | If enable is selected, solar energy is allowed to feed to the grid. |
| Battery Feed to Grid: | If enable is selected, battery energy is allowed to feed to the grid. |
| Feed to Grid Power Limitation: | Set limitation to feed to the grid. The available options are 6600W, 8600W and 10600W. |
Generator Setting:
| This is Generator Setting detail | |
| Generator On Voltage: | When the battery voltage/SOC is lower than this voltage, the dry contact will activate and start the generator. |
| Generator Off Voltage: | When the battery voltage/SOC is higher than this voltage, the dry contact will activate and stop the generator. |
| Generator Charging Setting: | Enable this setup item generator to charge the battery. |
| Dry Contact Setting: |
|
Please refer to "Dry Contact Signal" section for the details. Touch "ESC" to return to the previous screen, and touch "Home" to return to the home screen.
5.3 Operating Mode Description
We can check the system status according to "System Work Mode", as shown below:
| System work mode | Behaviors | State description |
|---|---|---|
| Standby mode Note: *Standby mode: The inverter is not turned on yet but at this time, the inverter can charge battery without AC output. | No output power, solar or utility charger available | Battery is charged by PV energy. No charging. |
| Line mode | Output power from utility. Charger is available | Utility charges battery and provides power to load. PV energy, battery power and utility provide power to load. PV energy and utility charge battery, and utility provides power to load. PV energy charges battery, utility and PV energy provide power to the load. |
| Battery mode | Output power from battery or PV | PV energy charges battery, PV energy provides power to the load and feeds remaining energy to the grid. PV energy and battery energy supply power to the load. PV energy charges battery and PV energy provide power to the load. Battery provides power to the load. |
| Only PV mode | Output power from PV | PV provides power to the load. |
| Fault mode Note: *Fault mode: Errors are caused by inside circuit error or external reasons such as over temperature, output short circuited and so on. | No output, no charging. | No charging. |
5.4 Wi-Fi Operation Guide
The Wi-Fi module enables wireless communication between solar inverters and the monitoring platform. Users can remotely monitor and control their inverters easily by i.Solar APP. The App uses the Wi-Fi chip to provide remote monitoring data services, which is beneficial for the daily data monitoring of the inverter, querying the real-time data in the device, sending commands from the device, and operating the device remotely. The app is available for both iOS and Android.
Download and install APP:
Operating system requirement for your smart phone:
- iOS system supports iOS 12.0 and above
- Android system supports Android 10.0 and above
You may find "i.Solar" app from the Apple® Store and Google® Play Store.
WiFi Model Setting:
- Turn on your mobile device. This example uses the Android system.
- Open the mobile's Wi-Fi settings.
- Connect your device to the Wi-Fi with the name that begins with "FC41D_". The default password for this Wi-Fi is 12345678.
- After the Wi-Fi connection is successful, click the i.Solar App installed on the phone to enter the login page. Then, click the "Network Config" button to enter the Wi-Fi configuration page.
- After click the "Network Config" button to enter the Wi-Fi configuration page.
- Enter your router name (STA SSID) and router password (STA Password), then click the "Save" button to complete the setting. If you check the "Open" box marked in red, you only need to enter the router name (STA SSID), you don't need to enter the router password. Click the "Save" button to complete the setting.
- Enter the Wi-Fi name (AP SSID) and Wi-Fi password (AP Password) of the Wi-Fi card, confirm the password again and click the "Save" button to complete the setting of the Wi-Fi module. If you check "Open" marked in red, you only need to enter the Wi-Fi name (AP SSID), you don't need to enter the Wi-Fi password and Confirmation. Click the "Save" button to complete the setting.
- After entering the value of the baud rate, click the "Save" button to complete the setting of Uart Baud Rate.
Login:
After opening the app, enter the login page. After filling in all required information (user name and password), click the "Register" button to complete the user registration. Once registration is complete, click "Click to log in" or return to the previous page. Swipe left or click the left arrow to return to the login page. Enter the user name and password to log in.
Home Page:
Log in to enter the App. The default Home page will appear where you can view the charts. Click the button 'Day', 'Month', and 'Year' to query the power generation data. Click 'Total' to query the annual power generation data.
Tap the icon (located on the top right corner) to enter the page to add, delete or rename the device. Enter the device serial number to add the device.
Rename (left screenshot) and delete (right) the devices by pressing the buttons highlighted by the red box.
Real-time Data:
'Energy' displays battery power, grid power, solar power, and load consumption. Rename the device by pressing the 'Rename' button.
'Real-time' displays solar, grid, load, and battery information. Press 'Day', 'Month', or 'Year' to query the hourly, daily, or monthly power generation data. Press 'Total' to query the annual power generation data.
Parameter:
'Parameter' displays the setting items. Note that the setting items on the parameter page will be different for different models. Tap on the dropdown icon to select the setting and click the "Apply" button to change the setting.
Control:
'Control' is reserved. 'Product' displays the product and rating information.
Log:
'Log' displays the data log and event. The following are instructions on how to navigate through each of the options.
Data log:
Tap the time, select the date and click the "Browse" button to update log.
Power Generation Log:
Tap the time, select the day, month or year, and click the "Done" button to update log.
Event Log:
Tap the time, select the month and click the "Browse" button to update log.
Click the "Custom" and it will show time duration list. Select the date and click the “Browse" button to update log.
Configuration:
Click the "Config" tab to enter setting screen. 'Change Password' by entering the old password, entering the new password, confirming the new password, and clicking the Apply button to complete the password modification function. 'Delete Account' by pressing delete account.
About:
Click the 'About' tab to enter the about page, where you can view the information about the App.
OTA Operation:
NOTE: The inverter output should be turned off during updating.
Preparations:
- The inverter is online;
- Contact the supplier to obtain the password;
- Contact the supplier to upload the firmware;
- Be sure to maintain good network conditions during updating.
- Click the ">" icon circled in red to enter the corresponding inverter screen.
- Click the "Product" button marked in red square to enter the Product Screen.
- Click the "v" icon marked in red on the right side of the "Update" to open the collapsible panel.
- Click the "Apply" button marked in red on the right side of the "Firmware Update" to call an update pop-up dialog.
- Enter the password provided by the supplier in the input field and then click "OK". The dialog "Send update command success" will pop up. The firmware will start updating. Please wait until it is successfully updated. (Be sure to maintain good network conditions and ensure that the inverter is powered on during updating.)
- Click the "Apply" button circled in red on the right side of the "Query Update Status" to enter the Query Screen and search for the latest update result.
Troubleshooting OTA Update:
Fault 1: After you click the "Apply" button for "Firmware Update", the warning dialog "The machine is being prepared. Please try again later." pops up.
Causes: (1) The inverter has been powered off before updating. (2) The inverter fails to upload the firmware. (3) The inverter becomes off-line before updating.
Solutions: (1) Check whether the inverter is powered on. Power it on again and then repeats Steps 4 to 7. (2) Contact the supplier to upload the firmware. (3) Check the network status of the inverter. Reconnect the inverter to the network and then repeat Steps 4 to 7.
Fault 2: After you click the "Apply" button for "Firmware Update" or "Query Update Status", there is no any response on the screen.
Causes: (1) The mobile phone becomes off-line.
Solutions: (1) Check the network status of the mobile phone and then reconnect it to the network.
Fault 3: On the Query Screen of update results, "Update failed" is displayed in the "Updating" column.
Causes: (1) The inverter has been powered off during updating. (2) The inverter becomes off-line during updating.
Solutions: (1) Check whether the inverter is powered on. Power it on again and then repeats Steps 4 to 7. Alternatively, contact the supplier for a solution. (2) Check the network status of the inverter. Reconnect the inverter to the network and then repeat Steps 4 to 7. Alternatively, contact the supplier for a solution.
Fault 4: The inverter has been updated (the dialog "Send update command success" pops up). When you view the "Update Time" on the Query Screen of update results after 30 min, no log for the present update is displayed. Example: For the first update, the pop-up dialog is shown below (Figure 1). If not the first update, the latest update log will be displayed, as shown in Figure 2.
Causes: (1) The inverter has been powered off before or during updating. (2) The inverter becomes off-line during updating.
Solutions: (1) Check whether the inverter is powered on. Power it on again and then repeats Steps 4 to 7. (2) Check the network status of the inverter. Reconnect the inverter to the network. Wait for 30 min until the inverter is successfully updated. Check whether the inverter is online. If yes, it indicates that the inverter has been successfully updated. If the inverter is off-line, please check whether the inverter has been reconnected to the network. Alternatively, contact the supplier for a solution.
Fault 5: The inverter has been updated (the dialog "Send update command success" pops up). After 30 min, the inverter is always off-line.
Causes: (1) The inverter has been powered off during updating. (2) The inverter becomes off-line during updating.
Solutions: (1) Check whether the inverter is powered on. Power it on again. If it is online, repeat Steps 4 to 7. If it is still off-line, please contact the supplier for a solution. (2) Check the network status of the inverter. Reconnect the inverter to the network. Wait for 30 min until the inverter is successfully updated. Check whether the inverter is online. If yes, it indicates that the inverter has been successfully updated. If the inverter is off-line, please check whether the inverter has been reconnected to the network. Alternatively, contact the supplier for a solution.
Fault 6: When you view the "Update Time" shown below on the Query Screen of update results, the "Updating" is always displayed.
Causes: (1) The inverter has been powered off during updating. (2) The inverter becomes off-line during updating.
Solutions: (1) Check whether the inverter is powered on. Power it on again and then repeats Steps 4 to 7. Alternatively, contact the supplier for a solution. (3) Check the network status of the inverter. Reconnect the inverter to the network. Repeat Steps 4 to 7. Alternatively, contact the supplier for a solution.
6. Specifications
| MODEL | 6.6KW | 8.6KW | 10.6KW |
|---|---|---|---|
| RATED OUTPUT POWER | 6600W | 8600W | 10600W |
| PV INPUT (DC) | |||
| Max. PV Power | 12000W | 16000W | 18000W |
| Max. PV Array Open Circuit Voltage | 500 VDC | 500 VDC | 500 VDC |
| MPPT Range @ Operating Voltage | 120 VDC~450 VDC | 120 VDC~450 VDC | 120 VDC~450 VDC |
| Max. PV Array Maximum Imp/per MPPT | 2*21A | 2*27A | 2*27A |
| Max. PV Array Maximum Isc/per MPPT | 26.25 | 2*34A | 2*34A |
| Number of MPPT Tracker | 2 | 2 | 2 |
| GRID-TIE OPERATION | |||
| GRID OUTPUT (AC) | |||
| Nominal Output Voltage | 220/230/240 VAC | ||
| Feed-in Grid Voltage Range | 195.5~253 VAC @India regulation 184 ~ 264.5 VAC @Germany regulation 184 ~ 264.5 VAC @South America regulation 195.5~253 VAC @ South Africa 182~260 VAC @ Pakistan | ||
| Feed-in Grid Frequency Range | 49~51Hz @India regulation 47.5~51.5Hz @Germany regulation 57~62Hz @South America 47~52Hz @ South Africa 45.1~54.9Hz @ Pakistan | ||
| Nominal Output Current | 28.7A | 37.4A | 46.1A |
| Power Factor Range | >0.99 | ||
| Maximum Conversion Efficiency (DC/AC) | 97% | ||
| OFF-GRID, HYBRID OPERATION | |||
| GRID INPUT | |||
| Acceptable Input Voltage Range | 90-300 VAC or 170-300 VAC | ||
| Frequency Range | 50 Hz/60 Hz (Auto sensing) | ||
| Transfer Time | < 10ms (for UPS) < 20ms (for home appliances) < 50ms (for parallel system operation) | ||
| Rating of AC Transfer Relay | 40A | 60A | 60A |
| GENERATOR INPUT | |||
| Acceptable Input Voltage Range | 90-300 VAC | 90-300 VAC | 90-300 VAC |
| Frequency Range | 50 Hz/60 Hz (Auto sensing) | 50 Hz/60 Hz (Auto sensing) | 50 Hz/60 Hz (Auto sensing) |
| Rating of AC Transfer Relay | 40A | 60A | 60A |
| BATTERY MODE OUTPUT (AC) | |||
| Nominal Output Voltage | 220/230/240 VAC | ||
| Output Waveform | Pure Sine Wave | ||
| Efficiency (DC to AC) | 93% | ||
| BATTERY & CHARGER | |||
| Nominal DC Voltage | 48 VDC | ||
| Maximum Charging Current (from Grid) | 135A | 190A | 210A |
| Maximum Charging Current (from PV) | 135A | 190A | 210A |
| Maximum discharging Current | 135A | 190A | 210A |
| GENERAL | |||
| Dimension, D X W X H (mm) | 633 x 418 x 192 | ||
| Net Weight (kgs) | 23.5 | 28 | 29 |
| INTERFACE | |||
| Parallel-able | Yes | ||
| External Safety Box (Optional) | Yes | ||
| Communication | USB or RS232 / RS 485/WIFI | ||
| ENVIRONMENT | |||
| Humidity | 0 ~ 95% RH (No condensing) | ||
| Operating Temperature | -25°C to 50°C | ||
7. Troubleshooting
| Problem | HMI/Buzzer | Explanation / Possible cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | HMI and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. The battery voltage is far too low. (<1.4V/Cell) 2. Battery polarity is connected reversed. | 1. Check if batteries and the wiring are connected well. 2. Re-charge battery. 3. Replace battery. |
| Mains exist but the unit works in battery mode. | HMI shows grid voltage is 0V | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. |
| When the unit is turned on, internal relay is switched on and off repeatedly. | HMI shows battery voltage is 0V | Battery is disconnected. | Check if battery wires are connected well. |
| Overload error | The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. | |
| Output short circuited. | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Over Temperature | Internal temperature of inverter component is over 100°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Battery high voltage | Battery is over-charged. The battery voltage is too high. | Return to repair center. Check if spec and quantity of batteries are meet requirements. | |
| Buzzer beeps continuously and HMI show the Fault icon | FAN lock | Fan fault | Replace the fan. |
| Output abnormal | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center | |
| DC-DC overcurrent | DC/DC over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
| Inverter overcurrent | Over current or surge. | ||
| BUS low voltage | Bus voltage is too low. | ||
| Abnormal output voltage | Output voltage is unbalanced. | ||
| Solar high voltage | Solar input voltage is more than 550V. | Reduce the number of solar panels | |
| Battery Low | The battery voltage is less than 30V | Charge the battery voltage to above 30V | |
| Battery overcurrent | The battery is over-discharged | The discharge current of the battery needs to be reduced | |
| 60 | Current feedback into the inverter is detected. | 1. Check if L/N cables are not connected reversely in all inverters. 2. For parallel system in single phase, make sure the sharing are connected in all inverters. 3. For supporting three-phase system, make sure the sharing cables are connected in the inverters in the same phase, and disconnected in the inverters in different phases. 4. If the problem remains, please contact your installer. | 1. Restart the inverter. |
| 71 | The firmware version of each inverter is not the same. | 1. Update all inverter firmware to the same version. 2. Check the version of each inverter via LCD setting and make sure the CPU versions are same. If not, please contact your installer to provide the firmware to update. 3. After updating, if the problem still remains, please contact your installer. | |
| 72 | The output current of each inverter is different. | 1. Check if sharing cables are connected well and restart the inverter. 2. If the problem remains, please contact your installer. | |
| 80 | CAN data loss | 1. Check if communication cables are connected well and restart the inverter. 2. If the problem remains, please contact your installer. | |
| 81 | Host data loss | ||
| 82 | Synchronization data loss | ||
| 83 | The battery voltage of each inverter is not the same. | 1. Make sure all inverters share same groups of batteries together. 2. Remove all loads and disconnect AC input and PV input. Then, check battery voltage of all inverters. If the values from all inverters are close, please check if all battery cables are the same length and same material type. Otherwise, please contact your installer to provide SOP to calibrate battery voltage of each inverter. 3. If the problem still remains, please contact your installer. | |
| 84 | AC input voltage and frequency are detected different. | 1. Check the utility wiring connection and restart the inverter. 2. Make sure utility starts up at same time. If there are breakers installed between utility and inverters, please be sure all breakers can be turned on AC input at same time. 3. If the problem remains, please contact your installer. | |
| 85 | AC output current unbalance | 1. Restart the inverter. 2. Remove some excessive loads and re-check load information from LCD of inverters. If the values are different, please check if AC input and output cables are in the same length and material type. 3. If the problem remains, please contact your installer. | |
| 86 | AC output mode setting is different. | 1. Switch off the inverter and check LCD setting of “AC OUTPUT MODE". 2. For parallel system in one phase, make sure no 3P1, 3P2 or 3P3 is set. 3. For supporting three-phase system, make sure no “PAL” is set. If the problem remains, please contact your installer. | |
| 87 | Single Machine exists in parallel system | 1. Check whether a single machine exists in parallel system. |
8. User Tips
- For optimal battery life, utilize the built-in intelligent balancing feature and ensure proper BMS communication.
- When installing outdoors, take advantage of the IP66/IP65 ratings, but still consider shaded locations to prevent excessive heat exposure and prolong component life.
- Leverage the flexible Time-of-Use settings to optimize energy efficiency and reduce costs by scheduling battery charging during off-peak hours and discharging during peak hours.
- For parallel systems, always ensure all inverters share the same battery bank to avoid fault modes.
- Regularly check the i.Solar APP for real-time data and event logs to monitor system performance and address any warnings or faults promptly.
9. Warranty & Support
The POWMr 6.6KW Hybrid Inverter and 48V 5.12kWh LiFePO4 Battery Solar Storage System Kit comes with a 1-year warranty.
For technical support, service, or warranty claims, please contact:
- Brand: PowMr
- Email: support@powmr.com
- Website: www.powmr.com
- Tel/Fax: +86755-28219903
- Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China
If errors persist after following the troubleshooting guide, please send the inverter/charger back to your local dealer or service center for maintenance.
A PDF user manual is available for download at: POWMr Solar Inverter User Manual (PDF)