1. Overview
This intelligent electronic instrument is an auxiliary tool designed for the installation, testing, and maintenance of refrigeration equipment, including air conditioners and cold storage units. It features two-way pressure testing, dual-temperature testing with two optional temperature probes, digital readout, multi-unit switching, multi-mode functions, and a built-in database of 112 refrigerants.
The instrument is constructed with high-strength engineering plastics and non-slip rubber for durability and comfortable handling. A built-in 32-bit digital processing unit and high-precision data acquisition unit ensure enhanced calculation ability and stability. Its large LCD with backlight ensures clear test results, even in dark environments. The long-life valve switch and 1/4 inch standard inlet contribute to its durability and versatility.
The SW-620/SW-620Plus can simultaneously measure double pressure (gauge pressure) and dual temperatures. It offers automatic multi-unit pressure conversion and Celsius/Fahrenheit temperature conversion to suit various needs. It can also perform subcooling and superheat tests (with optional temperature probes), percentage of vacuum measurement, pressure leak measurement, and leak time recording. This multi-functional, accurate, and easy-to-operate digital manifold is an essential tool for refrigeration professionals.


2. Safety Rules and Precautions
This manual contains essential instructions and warnings for the safe operation and maintenance of the instrument. Failure to use the meter in accordance with this manual may damage the instrument or cause harm. This instrument strictly follows IEC/EN61010-1 safety standards for design and production.
General Safety Guidelines
- The pressure measured is gauge pressure.
- Pressure testing ranges from -101 KPa to 6 Mpa (-1.01 bar to 60 bar).
- The limit pressure is 10 Mpa (100 bar).
- The maximum operating pressure of standard hose is 600 PSI (approximately 4.13 Mpa, 41.3 bar). The limit pressure is 3000 PSI (approximately 20.68 Mpa, 206.8 bar).
- Always confirm the rated pressure value of the equipment before testing. Do not use the instrument if it exceeds its specified range.
- Do not use or store the instrument in high temperature, high humidity, flammable, explosive, or strong electromagnetic fields.
- Do not attempt to change the instrument's internal circuit to avoid damage or danger.
- Always wear qualified protective equipment to protect yourself during testing.
- Use the instrument in a well-ventilated environment to prevent inhalation of toxic gases.
- The port is equipped with a copper plug screw. It must be tightened every time before or after operation.
- Regularly check the refrigeration system's pipes and connectors for integrity.
International Electrical Symbols
| Symbol | Description |
|---|---|
| ~ | AC (Alternating Current) |
| DC (Direct Current) | |
| DC/AC (Direct Current / Alternating Current) | |
| ! | Warning |
| Dangerous Voltage (Electric Shock) | |
| Earth | |
| Π | Double Insulation |
| Fuse | |
| Battery |
3. Product Components and Controls
Familiarize yourself with the various parts and controls of your SWEVY Digital Manifold Gauge for effective operation.

- Clamp-on temperature probe socket
- Clamp-on temperature probe socket
- LCD display
- Run/Stop button: In Leak Test Mode, Test Control Button
- Function button: test function mode switch button
- R+/R- Refrigerant Type Selection Buttons: Switch to select different types of working refrigerants
- Unit button: pressure unit switch button
- °C/°F button: temperature unit switch button
- Zero button: pressure display zero button
- Backlit button
- Power button
- Refrigerant observation window
- Low pressure valve
- High pressure valve
- 1/4 inch low pressure inlet
- 1/4 inch high pressure inlet
- Pressure release valve
- Refrigerant inlet/vacuum pump inlet

4. Product Specifications
The following table details the technical specifications for the SWEVY Digital Manifold Gauge SW-620 and SW-620Plus models.

| Feature | SW620 Refrigerant Fluorination Single Table | SW620PLUS Refrigerant Fluorination Gauge (with Temperature Clamp) |
|---|---|---|
| Model | SW-620/SW-620Plus | |
| Pressure Test | Gauge pressure | |
| Pressure Test Unit | KPa; Mpa; bar; inHg; PSI | |
| Pressure Test Range | 0 KPa - 6000 KPa | |
| Pressure Test Resolution | 1 KPa | |
| Pressure Test Accuracy | +/- 0.5 %(FS) + 5dgt | |
| Pressure Overload Limit | 10000 KPa (10 Mpa; 100 bar) | |
| Vacuum Test | Relative vacuum | |
| Vacuum Test Unit | KPa; Mpa; bar; inHg; PSI | |
| Vacuum Test Range | -101 KPa - 0 KPa | |
| Vacuum Test Resolution | 1 KPa | |
| Temperature Test Unit | °C (Celsius), °F (Fahrenheit) | |
| Temperature Test Range | -40°C - 150°C (-40°F - 302°F) | |
| Temperature Test Resolution | 0.1°C (-40°C - 99.9°C), 1°C (100°C - 150°C) 0.1°F (-40°F - 99.9°F), 1°F (100°F - 302°F) | |
| Temperature Test Accuracy | +/- 0.5 °C + 2dgt / +/- 0.9 °F + 2dgt | |
| Power Supply | 4 x 1.5V (SIZE.AA/LR6) (Battery not included) | |
| Dimensions | 190*120*50mm / 7.48*4.72*1.97inch | |
| Weight | 1000g | |
5. Setup
Battery Installation
The SWEVY Digital Manifold Gauge requires 4 x 1.5V (SIZE.AA/LR6) batteries for operation. Due to air freight restrictions, batteries are not included with the product. Please purchase these separately and install them before first use.
Initial Power On and Display Check
- Ensure the blue and red valves are turned off.
- Press the Power button (11) to turn on the instrument.
- Verify that the LCD display (3) shows the pressure test status. If not, press the Function button (5) to switch to the correct mode.
- If the high and low pressure display areas show 10 digits upon power-on, press and hold the Zero button (9) until the display returns to zero.
For detailed setup instructions and specific connection diagrams, refer to the User Manual PDF: SWEVY Digital Manifold Gauge User Manual (PDF).
6. Operation
6.1 Refrigerant Filling and Pressure Inspection
This procedure outlines how to fill refrigerant and inspect pressure in a refrigeration system.
- Ensure the blue and red valves on the manifold gauge are turned off.
- Power on the instrument. Confirm the LCD displays pressure test status. If not, press the Function button to switch modes.
- If optional temperature probe accessories are connected, the real-time temperature will be displayed.
- Use the R+/R- buttons (6), Unit button (7), and °C/°F button (8) to select the tested refrigerant and desired reading display units.
- If the instrument shows 10 digits in the high and low pressure display area, press and hold the Zero button (9) until it returns to zero.
- Connect the instrument to the refrigeration system as shown in the diagram below. Pay close attention to the direction of refrigerant flow. (Connected clamp-on temperature probes will not affect operation.)

- Turn on the refrigerant valve and gently press the pressure release valve (17) to vent air from the connecting hose.
- When the refrigeration system stops, turn on the high pressure valve (red valve) and fill with a certain amount of refrigerant, then quickly shut the valve.
- Run the refrigeration system, turn on the low pressure valve (blue valve), and fill the refrigerant into the refrigeration system. Vacuum operation is required if the system is initially filled or fully with refrigerant. Refer to the vacuum operation section for details.
- After filling is complete, shut the low pressure valve (blue valve) and refrigerant valve. Allow the refrigeration system to run.
- Shut down the refrigeration system, ensure all valves are turned off, then disconnect the instrument from the refrigeration system and source. Do not remove the high pressure valve connection until the pressure drops to a safe point. Then turn off the instrument.
Note: The refrigerant filling operation may vary depending on the equipment and refrigerant type. Always refer to specific operation requirements to prevent damage.
The instrument can display the corresponding Evaporation Temperature (EV) and Condensation Temperature (CO) during the refrigerant pressure test:
R 1348
Ev 18.0 °C Co 18.0 °C
2500 kPa 2500 kPa
If optional clamp-on temperature probes are connected, the LCD will display real-time temperature in T1 Sensor and T2 Sensor. Ensure probes are properly connected and in full contact with refrigeration pipes.
The instrument can calculate Superheat (SH) and Subcooling (SC) if the tested refrigerant is preset and optional clamp-on temperature probes are connected:
R 1348
SH 19.0 °C SC 19.0 °C
2500 kPa 2500 kPa
6.2 Vacuum Operation
This section details the steps for performing a vacuum operation with the manifold gauge.
- Turn off the blue valve (13) and red valve (14).
- Power on the instrument. Verify the LCD displays vacuum test status. If not, press the Function button (5) to switch to it.
- Press the Unit button (7) to adjust the reading unit as needed.
- Connect the instrument to the refrigeration system and vacuum pump as shown in the diagram below.

- Turn on the blue valve (13) and red valve (14), and start the vacuum pump.
- After the vacuum operation is completed, turn off the blue valve and red valve, then shut off the vacuum pump.
At this point, the pressure leak test mode can be used to check for leaks in the system. Refer to the 'Pressure Leak Test' section for specific operations.
6.3 Pressure Leak Test
To perform a pressure leak test:
- Ensure the instrument is powered on and the blue and red valves are turned off.
- Press the Function button (5) to enter the pressure leak test mode. The current pressure value will be displayed in the lower right corner of the LCD.

- Press the Run/Stop button (4) to start the leak test.
During the leak test, the lower left corner of the display records the initial pressure value, while the lower right corner shows the instantaneous pressure value. The 'ΔP' display area shows the difference between the initial and instantaneous pressure values. The time display area shows how long the leak test has lasted in the format of Hour:Minute (HH:MM). All pressure units on the screen are the same; you can switch different pressure units by pressing the Unit button (7).
6.4 Built-in Refrigerant NIST Database
The instrument features a built-in database of 112 refrigerants, compliant with American NIST standards. This allows you to select the appropriate refrigerant type based on your specific needs.

Remarks:
- R744 (CO2) has a maximum test range of 50 bar.
- R717 and other Ammonia refrigerants are not allowed to be tested with this instrument.
7. Maintenance
To ensure the longevity and accuracy of your SWEVY Digital Manifold Gauge, follow these maintenance guidelines:
- Cleaning: Wipe the instrument with a soft, damp cloth. Do not use abrasive cleaners or solvents. Ensure no liquid enters the device.
- Storage: Store the instrument in a dry, cool place, away from direct sunlight, extreme temperatures, and high humidity. Remove batteries if the device will not be used for an extended period to prevent leakage.
- Hose and Valve Inspection: Regularly inspect all hoses and valve stems for any signs of wear, cracks, or damage. Replace damaged components immediately to prevent leaks and ensure accurate readings.
- Battery Replacement: Replace batteries promptly when the low power indicator appears on the display to avoid interruptions during operation and potential damage from depleted batteries.
8. Troubleshooting
This section addresses common issues you might encounter with your digital manifold gauge.
8.1 Common Problems
- Low battery power supply: If the low power sign is displayed, the battery power is insufficient. Replace the 4 x 1.5V (SIZE.AA/LR6) batteries immediately to ensure normal operation.
- Damaged refrigerant hose or valve stem: Before each test, check all pipe fittings and hoses. If any damage is found, replace them immediately to prevent improper use or accidents.
- Failure of refrigerant filling: The refrigerant inlet of the refrigeration system has a valve core. When connecting the instrument, ensure that one terminal of the hose with a core is connected to the refrigeration system, and the other terminal without a core is connected to the instrument.
- Potential leak points: Each hose terminal is equipped with a nylon pad, which has a limited lifespan. Overuse or other situations can cause it to become defective, leading to leaks. Inspect and replace these pads as necessary. The instrument's refrigerant inlet (middle port) has a valve core used to vent air from the hoses after connecting to the refrigerant.
9. Glossary
- Saturation
- The state where a refrigerant coexists in both liquid and gas phases.
- Condensation Temperature
- In the condenser, the temperature at which high-temperature gaseous refrigerant condenses into liquid refrigerant. This is the saturation temperature under the condensing pressure.
- Evaporation Temperature
- In the evaporator, the temperature at which liquid refrigerant evaporates into gaseous refrigerant. This is the saturation temperature under the evaporation pressure.
- Subcooling
- The difference between the condensing temperature and the condensing outlet temperature.
- Superheat
- The difference between the evaporation outlet temperature and the evaporation temperature.
- Gauge Pressure
- Refers to the pipeline pressure measured by pressure gauges, vacuum gauges, U-shaped tubes, etc., also known as relative pressure. It starts with atmospheric pressure and is denoted as Pg.
- Absolute Pressure
- The pressure directly acting on the surface of a container or object. Its value is measured from absolute vacuum (0 KPa) and is denoted as PABS. Absolute pressure = atmospheric pressure + gauge pressure. At atmospheric pressure, gauge pressure is 0 and absolute pressure is 1.013 bar.
- Dry Bulb Temperature
- The temperature measured by ordinary thermometers.
- Wet Bulb Temperature
- The temperature indicated by a thermometer with a wet cloth wrapped around its bulb, reflecting the cooling effect of evaporation.
10. User Tips
- Zeroing Before Use: Always ensure the gauge is zeroed before starting any pressure or vacuum test for accurate readings.
- Refrigerant Selection: Double-check that you have selected the correct refrigerant type from the built-in NIST database before beginning any operation.
- Probe Contact: When using temperature clamp probes, ensure they are securely attached and in full contact with the refrigeration pipes for precise temperature measurements.
- Battery Life: Keep spare AA/LR6 batteries on hand, especially for prolonged use, as the device does not include them.
11. Warranty and Support
For information regarding warranty coverage, technical support, or service, please contact SWEVY customer service or refer to the official product documentation provided with your purchase. Keep your purchase receipt as proof of purchase.