1. Introduction
This manual describes the assembly, installation, operation, and troubleshooting of the Ecgsolax 1.2Kw Hybrid Solar Inverter. Please read this manual carefully before installation and operation to ensure safe and efficient use.
The Ecgsolax Hybrid Solar Inverter is a multifunctional device integrating an MPPT solar charge controller, a high-frequency pure sine wave inverter, and a UPS function module. It is designed for off-grid backup power and self-consumption applications.
The system requires additional components such as PV modules, a generator, or a utility grid to function completely. A WiFi module (plug-and-play or built-in) allows users to monitor the PV system status remotely via mobile phone or website.

Figure 1: System Architecture Overview. Shows solar panels, grid/generator, battery, inverter, and household loads, with cloud/app monitoring.
Key Features:
- Rated Output Power: 1200W
- Max Solar Charge Current: 50A
- Max PV Input Power: 800W
- MPPT Voltage Range: 17-115Vdc
- Pure Sine Wave Output: Provides high-quality AC power with high efficiency and stable output.
- Comprehensive Protection: Includes short circuit, over voltage, over current, under voltage, overload, backfill, over charge, and over-temperature protection.
- Battery Compatibility: Compatible with 12V Lead-Acid (FLD, SLD, AGM, GEL) and Lithium battery types, with user-defined settings.

Figure 2: Hybrid Inverter Features. Highlights 1200W output, 50A solar charge, 800W PV input, and 17-115Vdc MPPT range.
2. Safety Instructions
WARNING! This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Ensure you select the correct battery system (lithium or lead-acid) for normal operation.
- Read all instructions and cautionary markings on the unit, batteries, and this manual before use.
- All operations and connections must be performed by professional electrical or mechanical engineers.
- All electrical installations must comply with local electrical safety standards.
- When installing PV modules during the daytime, cover them with opaque materials to avoid high terminal voltage.
- CAUTION: To reduce risk of injury, charge only deep-cycle lead-acid or lithium rechargeable batteries. Other battery types may burst.
- Do not disassemble the unit. Refer to a qualified service center for repairs.
- Disconnect all wirings before maintenance or cleaning to reduce electric shock risk. Turning off the unit does not eliminate this risk.
- NEVER charge a frozen battery.
- Select appropriate cable sizes as per specifications for optimum operation.
- Be cautious when working with metal tools near batteries to prevent short circuits and explosions.
- Strictly follow installation procedures for disconnecting AC or DC terminals.
- This inverter must be connected to a permanent grounded wiring system. Comply with local requirements.
- NEVER short circuit AC output and DC input. Do NOT connect to mains when DC input is short-circuited.
- Ensure the inverter is completely assembled before operation.
Labels on Inverter and in Documentation:
- CAUTION: Do not disconnect under load!
- Danger: High Voltage! Electrical Hazard!
- Wait 5 minutes after disconnecting all external power supplies before maintenance.
- Read instructions carefully before any operation.
- Grounding: System must be firmly grounded for operator safety.
- WARNING! High potential danger, could result in death or serious injury.
- CAUTION! Moderate/low potential danger, could result in moderate/minor injuries.
3. Setup (Installation)
3.1 Unpacking and Inspection
Upon receipt, inspect the product for any damage. If damaged, contact your local distributor. Check outer packaging for integrity and internal equipment for damage.
3.2 Installation Tools
The following tools are recommended for installation:
- Multi-meter
- Protective gloves
- Insulated anti-smashing shoes
- Safety glasses
- ESD wrist strap
- Hammer drill
- Electric screwdriver
- Cross screwdriver
- Rubber mallet
- Spirit level
- Wire cutter / stripper
- Terminal crimping tool
3.3 Mounting Unit
Consider the following points for installation location:
- Do not mount on flammable construction materials.
- Mount on a solid surface.
- Install at eye level for LCD readability.
- Ambient temperature: -10°C to 60°C for optimal operation.
- Recommended installation: vertically on a wall.
- Maintain at least 30cm clearance on all sides (top, bottom, left, right) for heat dissipation and wiring access.
WARNING! Inverter is suitable for mounting on concrete or other non-combustible surfaces only.
WARNING! Stay away from strong magnetic fields and avoid electromagnetic interference. If wireless devices below 30MHz are nearby, maintain a distance of over 30m.
Mounting Steps:
- Drill two Ø8 holes 120mm apart on the mounting surface. Insert M6 expansion screws.
- Align the inverter with the installed screws and hang it securely.
- Before wiring, remove the bottom cover by unscrewing two screws.
3.4 External Protective Grounding Connection
DANGER! Ensure a reliable grounding wire connection to prevent electrical shock.
WARNING! Use appropriate grounding conductors. Consult a professional if unsure.
Use a yellow-green grounding cable and an OT terminal (for M4 screws).
- Remove insulation from the cable head.
- Crimp the OT terminal tightly onto the cable.
- Connect the ground cable to the M4 screw on the inverter's grounding point.
3.5 AC Input / Output Connection
CAUTION! Install a separate 16A AC breaker between the inverter and AC input source.
CAUTION! Do NOT mis-connect AC IN and AC OUT terminals.
CAUTION! Connect AC cables with correct polarity (L and N). Do not connect input and output N lines together.
WARNING! All wiring must be performed by qualified personnel.
WARNING! Use appropriate cable size for AC input/output. Recommended: 16 AWG (1.31 mm²).
WARNING! Ensure AC power is disconnected before connecting.
Connection Steps:
- Open AC circuit breaker.
- Remove 9mm insulation, shorten conductor to 7mm. Insert into tubular terminal and crimp.
- Insert AC input/output cables into terminal block according to polarities (L: brown/black, N: blue) and tighten screws.
- Ensure cables are securely connected.
CAUTION! Appliances like air conditioners require 2-3 minutes to restart. Ensure they have a time-delay function to prevent damage during power fluctuations.
3.6 PV Connection
CAUTION! Install a separate 16A DC circuit breaker between inverter and PV modules. Max operating voltage > 115VDC.
WARNING! Do not ground positive or negative PV terminals.
WARNING! PV strings generate lethal voltages. Adhere to safety precautions.
WARNING! Connect PV terminals to corresponding ports; reversing polarity damages the inverter.
WARNING! All wiring by qualified personnel. Use appropriate cable size: 14 AWG (2.075 mm²).
PV Module Selection:
- Open circuit Voltage (Voc) of PV modules must not exceed max. PV array open circuit voltage (115Vdc).
- Open circuit Voltage (Voc) of PV modules must be higher than start-up voltage (20Vdc).
- PV Array MPPT Voltage Range: 17-115Vdc.
WARNING! Do not connect DC switches or AC/DC circuit breakers before completing electrical connections.
Connection Steps:
- Open DC circuit breaker.
- Remove 9mm insulation, shorten conductor to 7mm. Insert into tubular terminal and crimp.
- Use multi-meter to check polarities.
- Insert PV cables into terminal block according to polarities (+ to PV+ (red), - to PV- (black)) and tighten screws.
- Ensure cables are securely connected.
3.7 Battery Connection
User can choose a proper capacity 12V lead-acid battery (AGM or FLD) or lithium battery.
CAUTION! Install a separate DC over-current protector or disconnect device (recommended 150A) between battery and inverter.
WARNING! All wiring by qualified person. Use appropriate cable size: 2 AWG (35 mm²).
WARNING! Ensure AC power is disconnected before connecting.
Lead-acid Battery Connection Steps:
- Remove 18mm insulation from positive and negative conductors. Insert into tubular terminal and crimp.
- Pass battery cable through installation hole, tighten terminal screws. Ensure correct polarity.
- Connect all battery packs. Suggested minimum 200Ah capacity.
WARNING! Shock Hazard: Perform installation with care due to high battery voltage.
CAUTION! Do not apply anti-oxidant substance on terminals before connecting.
CAUTION! Ensure positive (+) connects to positive (+) and negative (-) to negative (-).
Lithium Battery Connection (Optional):
- Follow power cable connection steps as for lead-acid batteries.
- If inverter supports BMS communication, connect RJ45 terminal of battery communication cable to BMS port of inverter (RS485/CAN protocol). Insert other end to lithium battery's communication port.
Note: Some inverters may not support BMS. Check compatibility of protocol first.
BMS Communication and Setting: Set battery type to 'Llb' or 'FEL' in Program 17 (Section 4.2.2). Ensure Pin-to-Pin connection. Inverter BMS port pin assignment:
| Pin Number | BMS Port |
|---|---|
| 1 | RS485B |
| 2 | RS485A |
| 3 | - |
| 4 | CANH |
| 5 | CANL |
| 6 | - |
| 7 | - |
| 8 | - |
3.8 Final Assembly
After connecting all wiring, replace the bottom cover and secure it with the two screws.
3.9 Smart Communication Stick Connection (Optional)
If your inverter supports WiFi monitoring, insert the smart communication stick (WiFi) into the COM port. Refer to the solar APP quick configuration guide for setup.
4. Operating
4.1 Power ON/OFF
Once the unit is properly installed and batteries are connected, press the ON/OFF switch (located on the bottom of the case) to turn on the unit.
4.2 Operation and Display Panel
The front panel of the inverter features four indicators, four function keys, and an LCD display to show operating status and power information.
LED Indicators:
| Indicator | State | Message |
|---|---|---|
| AC Status (Green) | Solid On | Mains power normal, in operation |
| Flashing | Mains power normal, not yet in operation | |
| Off | Mains power abnormal | |
| Invert (Yellow) | Solid On | Output powered by battery or PV |
| Off | Other states | |
| Charging (Yellow) | Solid On | Battery in float charging |
| Flashing | Battery in constant voltage charging | |
| Off | Other states | |
| Fault (Red) | Solid On | Fault occurs in inverter |
| Flashing | Warning condition occurs | |
| Off | Inverter working properly |
Function Buttons:
- ESC: Exit setting mode
- UP: Go to previous selection
- DOWN: Go to next selection
- ENTER: Confirm selection in setting mode or enter setting mode
4.2.1 LCD Display Icons
The LCD displays various icons representing AC input, PV input, output, load, battery information, and other status indicators like overload, alarm, fault, power saving mode.
4.2.2 LCD Setting
Press and hold ENTER for 2 seconds to enter setting mode. Use UP/DOWN to select programs, then ENTER to confirm or ESC to exit.
Detailed settings are available for Output Voltage, Output Frequency, Output Source Priority, Output Mode, Charger Source Priority, Grid Charging Current, Maximum Charging Current, Menu Default, Auto Restart (overload/over-temp), Main Input Cut Warning, Energy-saving Mode, Overload Transfer to Bypass, Silent Mode, Battery Return to Mains Voltage Point, Switching Back to Battery Mode Voltage Points, Battery Type, Battery Low Voltage Point, Battery Shutdown Voltage Point, Constant Voltage Mode Voltage Point, Floating Charge Mode Voltage Point, Grid Low/High Voltage Point, Automatic Screen Shutdown, Inverter Soft Start, Reset Factory Settings, Battery Disconnection Alarm, Equalization Voltage Point, Equalization Charging Time, Equalization Delay Time, Equalization Interval Time, Enable Equalization Immediately, BMS Communication Function, BMS ID Setting, Low SOC Shutdown, High SOC to Battery, Low SOC to Grid, Max Discharge Current.
Refer to the detailed tables in the original manual for specific values and options for each program.
4.3 Display Information
The LCD display information can be cycled through by pressing the UP or DOWN keys. Information includes voltage, frequency, current, power, and firmware version for AC input, PV input, battery, and output.
5. Maintenance
Regular maintenance ensures the longevity and optimal performance of your inverter. Always observe safety precautions before performing any maintenance.
- Cleaning: Periodically clean the inverter's exterior with a dry, soft cloth. Ensure ventilation openings are free from dust and debris to prevent overheating.
- Connections: Annually check all electrical connections (AC, DC, PV, Battery) for tightness and corrosion. Loose connections can lead to poor performance or safety hazards.
- Battery Inspection: For lead-acid batteries, check electrolyte levels (if applicable) and terminal corrosion. For all battery types, ensure cables are secure and free from damage.
- Environment: Ensure the installation environment remains within specified temperature and humidity ranges.
- Firmware: Check for any available firmware updates from the manufacturer, if applicable, to ensure optimal performance and security.
WARNING! Always disconnect all power sources (PV, AC input, Battery) and wait at least 5 minutes before performing any maintenance or inspection inside the inverter.
6. Troubleshooting
This section provides guidance for identifying and resolving common issues. For persistent problems, contact qualified service personnel.
6.1 Fault Reference Code
If a fault occurs, the fault indicator will be solid red, and the LCD will display a fault code. The system attempts to restart automatically up to 6 times within 15 minutes. If it fails, a fault lock is triggered. Power off the unit completely or wait 30 minutes to reset.
| Code | Meaning | Trigger Conditions | Resume Conditions |
|---|---|---|---|
| 1 | Bus soft boost start failed | Bus voltage not reach set value | Can restore |
| 2 | Bus voltage high | Bus voltage higher than protection point | Can restore |
| 3 | Bus voltage low | Bus voltage below under voltage protection point | Can restore |
| 4 | Battery over current | TZ interrupt triggered > 2 times within 2ms | Cannot restore |
| 5 | Over temperature | Temperature exceeds threshold or fan stuck | Can restore |
| 6 | Battery high voltage | Battery voltage higher than set value | Can restore |
| 8 | Bus short circuit | Inverter on or PFC on, bus voltage below threshold | Can restore |
| 14 | Over load | Overload exceeds limit | Can restore |
| 26 | BMS fault | Error code in BMS message | Turn off BMS communication or BMS fault recovery |
| 27 | MCU fault | MCU error | Cannot restore |
(This table is a partial list. Refer to the full manual for all fault codes.)
6.2 Alarm Reference Code
When an alarm occurs, the LED red light flashes, and the LCD displays an alarm code. The inverter does not enter fault mode.
| Code | Meaning | Trigger Conditions | Resume Conditions |
|---|---|---|---|
| 50 | Battery open | Battery voltage below 8V | Restore after battery voltage > 10V |
| 51 | Battery low voltage shutdown | Battery voltage below set point | Restore after battery voltage recover |
| 53 | Charger short circuit | Battery voltage < 5V and charging current > 4A | Cannot restore |
| 55 | Battery over charge | Battery voltage higher than set value | Restore after battery voltage < (set value - 0.5V) |
| 56 | BMS disconnect | No correct BMS communication response | Restore after communication recover |
| 58 | Fan error | Fan speed less than set value | Restore after fan recover |
| 60 | Overload | Not in mains mode or PV normal, output priority not mains, load exceeds 102% | Restore after load back to normal |
(This table is a partial list. Refer to the full manual for all alarm codes.)
6.3 General Troubleshooting
| Problem | Fault Event | What to do |
|---|---|---|
| Unable to start | Battery | 1. Check battery voltage sampling and calibration. 2. Measure battery voltage with multimeter (must be ≥11.5V/cell for startup). 3. Check BSU configuration. |
| Utility power | 1. Check for short circuits at mains terminal. 2. Check for wiring errors (e.g., mains input to output). | |
| PV | Check if PV input voltage is too close to critical threshold. | |
| PV not charging | PV | Connecting wrong battery voltage can damage auxiliary power supply on PV side. |
7. Specifications
Detailed specifications for the Ecgsolax MPPT Solar Inverter ECG-HVM1.2K-12V:

Figure 3: Detailed Specifications for ECG-HVM1.2K-12V.
| Category | Parameter | Value |
|---|---|---|
| General Info | Operating Temperature Range | -10°C ... 60°C |
| IP Grade | IP21 | |
| Safety Class | I | |
| AC Output | Rated Power | 1200VA/1200W |
| Voltage a.c. | 230V ± 5% | |
| No. of Output | 1 | |
| Rated Current a.c. | 5.2A | |
| Battery Input | Voltage Range d.c. | 10-15V |
| Rated Voltage d.c. | 12V | |
| Max. Charge Current d.c. | 50A | |
| AC Input | Voltage Range a.c. | 90-280V |
| Frequency | 50Hz/60Hz | |
| Max. AC Bypass Current a.c. | 10A | |
| PV Input | Max. Power | 800W |
| Max. PV Input Current d.c. | 18A | |
| Max. Open Voltage d.c. | 115V | |
| MPPT Input Voltage Range d.c. | 17-115V | |
| Max. Charge Current d.c. | 50A |
Physical Dimensions:
- Size: 518 x 342 x 170mm
- Weight: 4.5kg
8. Battery Equalization
The equalization function, integrated into the charge controller, helps reverse negative chemical effects like stratification and removes sulfate crystals from battery plates. This process is crucial for maintaining battery capacity and extending its lifespan.
Note: Do NOT activate this mode when using lithium batteries.
How to Apply Equalization Function:
First, enable the battery equalization function by setting the charging time from 'off' to another setting. Then, you can apply this function by:
- Setting equalization voltage point (Program 31).
- Setting equalization delay time (Program 33).
- Setting equalization interval time (Program 34).
- Setting immediate equalization mode activation (Program 35).
When to Equalize:
In the float stage, when the set equalization interval is reached, or if equalization is activated immediately, the controller will enter the Equalize stage.
Equalize Charging Time and Timeout:
During the Equalize stage, the controller charges the battery until its voltage reaches the equalization voltage. It then maintains this voltage using constant-voltage regulation until the set battery equalization time is reached.
If the battery voltage does not reach the equalization voltage point by the end of the set equalization time, the charge controller will extend the equalization time. If the battery voltage is still below the equalization voltage after the extended timeout, the charge controller will stop equalization and return to the float stage.
9. User Tips
- Quiet Operation: Users have noted that the device operates very quietly under low load conditions, making it suitable for environments where noise is a concern.
- Installation: The inverter is designed for straightforward installation, allowing for quick setup when following the provided instructions.
- Packaging: The product is typically delivered in neat and secure packaging, ensuring it arrives in good condition.
10. Warranty and Support
For warranty information, technical support, or service inquiries, please contact your original seller or the manufacturer directly. Keep your purchase receipt and product serial number handy for faster assistance.