1. Introduction
This manual provides detailed information for the assembly, installation, operation, and maintenance of the LVYUAN Hybrid Solar Inverter. Please read this manual carefully before installation and operation to ensure proper functionality and safety.
1.1 Product Overview
The LVYUAN Hybrid Solar Inverter is a multifunctional device integrating an MPPT solar charge controller, a high-frequency pure sine wave inverter, and a UPS function module. It is designed for both off-grid backup power and self-consumption applications and can operate with or without batteries.
The complete system requires additional components such as PV modules, a generator, or a utility grid. Consult your system integrator for specific architectural needs. The inverter includes a built-in or plug-and-play WiFi module for remote monitoring via mobile phone or website.

1.2 Key Features
- Rated power: 6.6KW/6.6KVA, power factor 1
- MPPT range: 60V~450V, 500Voc
- High frequency design with small size and light weight
- Pure sine wave AC output
- Simultaneous solar and grid power to loads
- CAN/RS485 for BMS communication
- Ability to work without battery
- WIFI remote monitoring (optional)
2. Safety Instructions
WARNING! This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
To ensure personal safety and proper product function, observe the following:
- Battery System Compatibility: Ensure you select the correct battery system (lithium or lead-acid). Incorrect selection will prevent the energy storage system from functioning normally.
- Read Instructions: Before using, read all instructions and cautionary markings on the unit, batteries, and all relevant sections of this manual. The manufacturer is not responsible for damage caused by non-compliance with installation instructions.
- Qualified Personnel: All operations and connections must be performed by a professional electrical or mechanical engineer.
- Electrical Standards: All electrical installations must comply with local electrical safety standards.
- PV Module Installation: When installing PV modules during the daytime, cover them with opaque materials to prevent danger from high terminal voltage.
- Battery Type: Only charge deep-cycle lead-acid and lithium rechargeable batteries. Other battery types may burst, causing injury or damage.
- Do Not Disassemble: Do not disassemble the unit. Refer servicing to a qualified service center. Incorrect re-assembly poses risks of electric shock or fire.
- Disconnect Power: To reduce electric shock risk, disconnect all wiring before maintenance or cleaning. Turning off the unit alone does not eliminate this risk.
- Frozen Battery: NEVER charge a frozen battery.
- Cable Sizing: Use appropriate cable sizes as specified for optimum inverter operation.
- Metal Tools: Exercise extreme caution when working with metal tools near batteries to avoid sparks, short circuits, or explosions.
- AC/DC Disconnection: Strictly follow installation procedures when disconnecting AC or DC terminals.
- Grounding: The inverter must be connected to a permanent grounded wiring system, complying with local regulations.
- Avoid Short Circuits: NEVER short-circuit AC output and DC input. Do NOT connect to the mains when DC input short circuits.
- Full Assembly: Ensure the inverter is completely assembled before operation.
2.1 Label Description
Symbols used in this manual and on the inverter:
- WARNING!: Indicates a high level of potential danger that could result in death or serious injury.
- CAUTION!: Indicates a moderate or low level of potential danger that could result in moderate or minor injuries.
- Do not disconnect under load!
- Danger: High Voltage! Danger: Electrical Hazard!
- 5min: Start maintenance at least 5 minutes after the INVERTER is disconnected from all external power supplies.
- Read instructions carefully before performing any operation.
- Grounding: The system must be firmly grounded for operator safety.
3. Product Components and Interface
3.1 Front Panel Overview

3.2 Rear and Bottom Panel Overview

4. Installation
4.1 Unpacking and Inspection
Products are strictly tested before leaving the factory. Inspect the product upon receipt for any damage to the outer packaging or internal equipment. If damage is found, contact your local distributor.
4.1.1 Installation Tools
The following tools are recommended for installation:
- Multi-meter
- Protective gloves
- Insulated anti-smashing shoes
- Safety glasses
- ESD wrist strap
- Hammer drill
- Electric screwdriver
- Cross screwdriver
- Rubber mallet
- Spirit level
- Wire cutter / stripper
- Terminal crimping tool
4.1.2 Packing List
| No. | Item | Quantity | Description | Remarks |
|---|---|---|---|---|
| 1 | Inverter | 1 | ||
| 2 | User manual | 1 | English | |
| 3 | Tubular terminal | 10 | E6010 | For AC input, AC output, PV input. |
| 4 | OT terminal | 1 | For PE |
4.2 Mounting Unit
Consider the following points when selecting an installation location:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install the inverter at eye level for easy LCD display readability.
- Maintain an ambient temperature between -10°C and 60°C for optimal operation.
- The recommended installation position is vertically on the wall.
- Ensure sufficient clearance (at least 30cm on top, bottom, and sides) for heat dissipation and wiring access.
WARNING! Inverter is suitable for mounting on concrete or other non-combustible surfaces only.
4.2.1 Mounting Steps
- Use an Ø8 drilling bit to drill holes on the mounting surface, 200mm apart. Insert expansion screw tubes (M6 expansion screws are suggested).
- Vertically align the inverter's top screw holes with the installed expansion screw tubes and fix the inverter with screws.
- Before connecting wiring, remove the bottom cover by unscrewing the four screws.
4.3 AC Input / Output Connection
CAUTION! Install a separate AC breaker (recommended 40A) between the inverter and AC input power source for maintenance and overcurrent protection. Do NOT mis-connect 'AC IN', 'AC OUT1', 'AC OUT2' terminals. Ensure correct polarity (L and N wires) to avoid utility short-circuiting in parallel operation.
WARNING! All wiring must be performed by qualified personnel. Use appropriate cable sizes for AC input/output connections to reduce injury risk.
| Connection | Gauge | Cable (mm²) |
|---|---|---|
| AC Input | 10 AWG | 5.26 |
| AC Output | 12 AWG | 4 |
WARNING! Disconnect AC power before connecting to the unit. All electrical connection operations must comply with local laws and regulations.
4.3.1 AC Input (AC IN) Connection Steps
- Open the AC circuit breaker.
- Remove 12mm insulation from cable ends, shorten conductor to 10mm. Insert into tubular terminal and crimp tightly.
- Insert AC input cables into terminal blocks according to polarities (PE: yellow-green, L: brown/black, N: blue) and tighten screws. Connect PE protective cable first.
- Ensure cables are securely connected.
4.3.2 AC Output (OUT1/OUT2) Connection Steps
Follow the same steps as AC input connection for L (LINE) and N (Neutral) cables.
CAUTION! Appliances like air conditioners require 2-3 minutes to restart. If a power shortage occurs and recovers quickly, it can damage connected appliances. Check if your appliance has a time-delay function. Otherwise, the inverter may trigger an overload fault to protect the appliance, but internal damage might still occur.
4.4 PV Connection
CAUTION! Install a separate DC circuit breaker between the inverter and PV modules. Do not ground positive or negative PV module terminals, as this can severely damage the inverter.
WARNING! Exposure to sunlight generates lethal high voltages in photovoltaic strings. Adhere to safety precautions in PV string documents. Connect PV terminals to corresponding inverter ports; reversing polarity can cause damage. All wiring must be performed by qualified personnel. Use appropriate cable sizes for PV module connection.
| Connection | Gauge | Cable (mm²) |
|---|---|---|
| PV Module | 10 AWG | 5.26 |
4.4.1 PV Module Selection Parameters
- Open circuit Voltage (Voc) of PV modules must not exceed the inverter's max. PV array open circuit voltage (500Vdc).
- Open circuit Voltage (Voc) of PV modules should be higher than the inverter's start-up voltage (80Vdc).
- PV Array MPPT Voltage Range: 60Vdc~450Vdc.
4.4.2 PV Connection Steps
WARNING! Do not connect any DC switches or AC/DC circuit breakers before completing electrical connections.
- Open the DC circuit breaker.
- Remove 12mm insulation from cable ends, shorten conductor to 10mm. Insert into tubular terminal and crimp tightly.
- Use a multi-meter to check polarities.
- Insert PV cables into terminal block according to polarities (+ → PV+ (red), - → PV- (black)) and tighten screws.
- Ensure cables are securely connected.


4.5 Battery Connection
CAUTION! Install a separate DC over-current protector or disconnect device (recommended 150A) between the battery and inverter. All wiring must be performed by qualified personnel. Use appropriate cable sizes for battery connection.
| Connection | Gauge | Cable (mm²) |
|---|---|---|
| Battery | 2 AWG | 25 |
WARNING! Disconnect AC power before connecting to the unit. All electrical connection operations must comply with local laws and regulations.
4.5.1 Lead-acid Battery Connection
User can choose proper capacity lead-acid battery with a nominal voltage at 48V. Select battery type as 'AGM or FLD (flooded)'. Recommended charge current is 0.3C (C ≤ battery capacity).
- Unscrew pre-fixed screws on battery poles. Prepare 2 DT terminals for AWG2 cables.
- Remove 12mm insulation from cable ends, shorten conductor to 10mm. Insert into DT terminal and crimp tightly.
- Pass battery cable through battery installation hole on bottom shell and tighten terminal screws. Ensure correct polarity at both battery and inverter/charger, and that DT terminals are tightly screwed to battery terminals.
- Connect all battery packs as units require. It's suggested to connect at least 200Ah capacity battery.
WARNING! Shock Hazard: Installation must be performed with care due to high battery voltage in series.
4.5.2 Lithium Battery Connection
If using a lithium battery, check protocol compatibility first. Lithium batteries have two connectors: an RJ45 port for BMS and power cables.
- Follow section 4.5.1 to implement power cable connection.
- Connect the RJ45 terminal of the battery communication cable to the BMS communication port of the inverter. The communication protocol should be RS485 or CAN.
- Insert the other end of the RJ45 (battery communication cable) to the lithium battery's communication port.
Note: If choosing a lithium battery, ensure the BMS communication cable is connected between the battery and the inverter.
4.5.3 Lithium Battery Communication and Setting
To communicate with the battery BMS, set the battery type to 'LIb' or 'FEL' in Section 7.1, Program 17. Ensure the lithium battery BMS port connects to the inverter with a Pin-to-Pin configuration. The inverter BMS port pin assignment is as follows:
| Pin number | BMS port |
|---|---|
| 1 | RS485B |
| 2 | RS485A |
| 3 | - |
| 4 | CANH |
| 5 | CANL |
| 6 | - |
| 7 | - |
| 8 | - |
For parallel systems, connect the BMS communication cable between the battery and one inverter.
4.6 Final Assembly
After connecting all wiring, replace the bottom cover by screwing in the four screws removed earlier.
4.7 Smart Communication Stick Connection (Optional)
The smart communication stick (WiFi) connects to the cloud platform. Insert the stick directly into the COM port. Some models have built-in WiFi monitoring; refer to the solar APP quick configuration guide for details.
5. Operation
5.1 Power ON/OFF
Once the unit is properly installed and batteries are connected, press the ON/OFF switch (located on the bottom of the case) to turn on the unit.
5.1.1 Power-On Steps
The system can be powered on when connected to a qualified battery (voltage above 11.5V per cell) or mains power (input range meets output mode requirements).
- Mains Power-On: Connect to normal mains power, press the switch to ON. If set to prioritize mains output, wait until the panel displays 'Mains Mode' indicating startup is complete.
- Battery Power-On: Connect to a normal battery, press the switch. The inverter will establish working power and start up automatically. After a period, the panel will display 'Battery Mode' indicating startup is complete.
5.1.2 Power-Off Steps
When the system is operating in battery or mains mode, press the switch to OFF to shut down.
5.1.3 Mute Operation
You can set MUTE ON or OFF to enable or disable mute functionality in any mode.
5.2 Operation and Display Panel
The operation and display panel on the front of the inverter includes four indicators, four function keys, and an LCD display, showing operating status and input/output power information.
5.2.1 LED Indicators
| LED Indicator | State | Messages |
|---|---|---|
| a. Status indicator (Green) | Solid On | Mains power is normal and enters mains power operation. |
| Flashing | Mains power is normal, but it has not entered mains power operation. | |
| Off | Mains power is abnormal. | |
| b. Invert indicator (Yellow) | Solid On | Output is powered by battery or PV in battery mode. |
| Off | Other states. | |
| c. Charging indicator (Yellow) | Solid On | The battery is in float charging. |
| Flashing | The battery is in constant voltage charging. | |
| Off | Other states. | |
| d. Fault indicator (Red) | Solid On | Fault occurs in the inverter. |
| Flashing | Warning condition occurs in the inverter. | |
| Off | The inverter is working properly. |
5.2.2 Function Buttons
| Button | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
5.2.3 LCD Display Icons
The LCD displays various icons:
- Load and Battery Icons: Represent load and battery capacity (each grid square is 25%). Load icon flashes when overloaded. Battery icon flashes when capacity is too low or disconnected.
- Buzzer Icon: Indicates if the buzzer is muted. Appears if background software sets MUTE ON.
- Settings Icon: Lights up when entering the setup menu; otherwise, hidden.
- Fault Icon: Only displayed in fault mode.
- Battery Capacity Display Logic: Displays SOC from BMS if connected. If BMS is not connected, capacity is 100% when battery current is 0 and voltage ≥ CV voltage point; 0% when current is 0 and voltage ≤ under voltage point. Adjusts based on battery current if BMS is not connected.
5.2.4 Numerical Display and Function Setting Area
In non-function setting mode, this area displays inverter-related information. Normal mode shows output information. Use UP/DOWN keys to switch between:
- Input voltage & output voltage
- Input frequency & output frequency
- Battery voltage & current
- PV voltage & PV current
- PV voltage & power
- Output power & output voltage
- Output apparent power & output voltage
- Load percentage & output voltage
- Software version, etc.
Fault mode displays the fault code.
In function setting interface, users can configure parameters (e.g., output voltage (OPU), battery low-voltage shutdown point (EOd)) using function setting and UP/DOWN keys.
5.2.5 Working Mode Display Area
After 4 seconds of power-on, this area shows the inverter's working mode (e.g., Standby, Mains, Battery, Fault mode). It also displays inverter status corresponding to alarm devices.
| Buzzer Alarm | Meaning |
|---|---|
| Long beep (10 seconds) | Fault Mode |
| Long beep (3 seconds) | PV Voltage / Input Voltage Loss or Recovery |
| One chime per second (1 minute) | All other alarms (low battery alarm only beeps in battery mode) |
5.3 Parameter Query Operations
There are seventeen display pages. Press the Query button (Button 2 or 3) for 0.1 to 1 second to cycle through pages showing input/output voltage, frequency, battery status, PV voltage/current, load status, software version, etc. Alarm or fault information will appear on dedicated pages.
5.4 Functional Settings Operation
To enter/exit functional settings and perform specific settings:
- Entering: Press and hold Function Setting Key (Key 4) for >2 seconds. Navigate with Query Key (Key 2 or 3) for 0.1-2 seconds until desired function setting flashes.
- Setting Parameters: Press Confirm Key (Key 4) for 0.1-2 seconds. Selected function text remains lit, value flashes. Adjust with Query Key (Key 2 or 3) for 0.1-2 seconds. Press Confirm Key (Key 4) for 0.1-2 seconds to apply.
- Exiting: Press Key 1 for 0.1-2 seconds or longer. System returns to main display page automatically after 30 seconds of inactivity.
Key functional settings include:
- Output Voltage (OPU): Set inverter output voltage (e.g., 230V, 208V, 220V, 240V). Takes effect immediately in standby or grid-tied mode.
- Output Frequency (OPF): Set inverter output frequency (e.g., 50Hz, 60Hz). Takes effect immediately in standby or grid-tied mode.
- Output Priority (OPP): Set output priority (GPB: Grid Power Priority, PGB: PV Power Priority, PBG: PV & Battery Priority, MKS: Generator Power Priority). Takes effect immediately.
- Input Mode (MOD): Set inverter input mode (APP: Appliance, UPS: for computers, GEN: for generator).
- Charging Priority (CHP): Set inverter charging priority (PNG: PV and Grid, OPV: Only PV, PVF: PV First).
- Maximum Charging Current (MCC): Set maximum charge current from PV and grid power (2A to 120A). Adjusts to BMS value if connected.
- Battery Type (BAT): Select battery type (AGM, FLD, LIT, FEL, CUS). Automatically switches to FEL if BMS is connected and current type is AGM or FLD.
- Equalization Voltage (EQV), Equalization Time (EQT), Equalization Timeout (EQO), Equalization Interval (EQI), Equalization Now (EQN): Settings for battery equalization (see Section 6).
- Grid Tie Invert (GTI), Grid Tie Power (GTP): Configure grid-tie functionality and maximum grid-tied power.
- Dual Output Battery Mode Cut-off Voltage (DBV), Cut-off Time (DBT), Cut-off SOC (DBS): Settings for secondary output in battery mode (requires dual-output auxiliary board).
- Battery Manage System (BMS), BMS Identity Document (BMI), Battery SOC Under Lock (BSU), Battery SOC Turn to Battery Mode (STB), Battery SOC Turn to Grid Mode (STG), Max Discharge Current (MDC): Advanced battery management settings, especially for lithium batteries with BMS.
6. Battery Equalization
The equalization function in the charge controller reverses negative chemical effects like stratification and removes sulfate crystals, which can reduce battery capacity. Periodic equalization is recommended for lead-acid batteries.
Note: Do NOT activate this mode when using lithium batteries.
6.1 How to Apply Equalization Function
Enable battery equalization in monitoring LCD setting Program 32 by setting time, or choose immediate equalization on Program 35. You can apply this function by:
- Set equalization voltage point on Program 31.
- Set equalization charging time on Program 32.
- Set equalization delay time on Program 33.
- Set equalization interval time on Program 34.
- Set immediate equalization mode activation on Program 35.
6.2 When to Equalize
In float stage, when the set equalization interval (battery equalization cycle) is reached, or equalization is active immediately, the controller will enter the Equalize stage.
6.3 Equalize Charging Time and Timeout
During the Equalize stage, the controller charges the battery until it reaches the equalization voltage. It then maintains this voltage. The battery remains in Equalize stage until the set equalization time is reached.
If the battery voltage doesn't reach the equalization voltage before the equalized time expires, the controller extends the time. If the voltage is still below the equalization voltage when the extended timeout ends, the charge controller stops equalization and returns to float stage.
7. Specifications
7.1 Line Specifications
| Model | Item | Value | Comments |
|---|---|---|---|
| Input Voltage | Main topology | L + N + PE | |
| Nominal voltage | 220VAC | Settable: 208/220/230/240 Vac | |
| Input Voltage Range | 90~280Vac | Settable | |
| Input Low Loss | 154Vac (default) Settable: 90–154 | APP/GEN mode | |
| 185Vac (default) Settable: 170-200 | UPS mode | ||
| Input Low Comeback | Low Loss voltage +9V | ||
| Input High Loss | 264Vac(default) Settable:264-280 | APP/GEN mode | |
| 264Vac | UPS mode | ||
| Input High Comeback | High Loss voltage -9V | ||
| Max Current (RMS) | 40A | Bypass current | |
| Input Frequency | Nominal Frequency | 50 / 60Hz | |
| Frequency Range | 40 / 70Hz | ||
| Freq. Low loss / Comeback | 40/43.5Hz@50Hz (UPS mode) 50/53.5Hz@60Hz (UPS mode) 40/43.5Hz@60Hz (APP/GEN mode) | ||
| 60/56.5Hz@50Hz (UPS mode) | |||
| Freq. High loss / Comeback | 70/66.5Hz@60Hz (UPS mode) 70/69.5Hz@60Hz (APP/GEN mode) | ||
Note: Max input current is 40A. If external circuit breaker is less than 40A, max input current depends on breaker spec.
7.2 Battery Specifications
| Item | Value | Comments |
|---|---|---|
| Battery Pieces | 4pcs | 12V/PCS |
| Auto Restart Function | Yes | |
| Battery test function | No | |
| Battery type | AGM/FLD/LIB/FEL/CUS | |
| Nominal Battery voltage | N*12V | @25°C |
| Battery management | Yes | |
| Battery over Voltage | 61V | |
| Battery under voltage | 10.5V*N | Settable: 10*N~11*N |
| Battery low voltage alarm | 10.8V*N | Settable: 10.3*N~11.3*N |
| Over current protection | Fuse | Fast acting |
7.3 Charger Specifications
| Item | Value | Comments |
|---|---|---|
| Charging voltage | FV MODE: 54V Settable: 53.2~55.6V | |
| CV MODE: 56.4V Settable: 56~58V | ||
| Temperature Compensation | No | |
| Charging Current | 2~120A | Settable |
| Default Charging Current | 60A | |
| Charging mode | Two/Auto Settable | Three states: CC/CV/Float Two states: CC/Float |
| Charge Voltage Accuracy | ±5% | Calibrated by RS232 |
| PV Charging method | MPPT | |
| PV Maximum Input Power | 27A/9000W | |
| Efficiency | 99.5% max | |
| MPPT | 60~450Vdc | |
| Minimum activation voltage | 80V | |
| Max PV voltage | 500Vdc | |
| Max PV charge current | 120A | |
| Max charging current | 120A (Maximum allowable) Default: 100A | Settable |
7.4 Output Specifications
| Item | Value | Comments |
|---|---|---|
| Output topology | L+N+PE | |
| Output power | 6.6KW (Battery and PV hybrid power supply) | When setting output voltage to 208V, power rating reduces to 90%. |
| Nominal Voltage | 208/220/230/240 VAC | Default 230V, manual set by RS232 or LCD |
| Waveform | Sinusoidal | |
| Voltage Regulation | ±5% | Empty load and linear load mode |
| DC offset | ±100mV (Bat mode) | |
| Nominal Frequency | 50 / 60Hz | 50/60Hz auto selection (default on) |
| Line Mode Frequency | 50Hz: (43.5 – 56.5)Hz (UPS mode) (40 – 70)Hz (APP/GEN mode) 60Hz: (53.5 - 66.5)Hz (UPS mode) (40 – 70)Hz (APP/GEN mode) | |
| Battery Mode Frequency | 50 / 60Hz | |
| Frequency regulation | 0.1% | |
| Overload capacity (battery mode) | Previous continuous load < 2.5kW: 15min@ 102%~108% load 1min@ 108%~120% load 10s@ >120% load Or: 1min@ 102%~120% load 10s@ >120% load | |
| Output short circuit protection | Battery mode: Current limitation Line mode: Breaker (40A) |
7.5 Switch Time Specifications
| Item | Value | Comments |
|---|---|---|
| Switch time | Line Mode To Battery Mode: 10ms (typical) | UPS mode |
| 10ms (typical) | Appliance mode | |
| 20ms (typical) | Generator mode |
7.6 Efficiency Specifications
| Item | Value | Comments |
|---|---|---|
| Line Mode Efficiency | >99.5%@6kVA | Full R load, without battery connect. |
| Battery Mode Efficiency | 94% (Max) | Full R load. |
| Standby power | <30W | Empty load / Battery mode |
8. Troubleshooting
This section provides information on fault and alarm codes, their meanings, trigger conditions, and recommended actions.
8.1 Fault Reference Code
When a fault occurs, the alarm code (e.g., '20') flashes, the fault indicator remains steadily lit, and the buzzer sounds continuously for 10 seconds before stopping. If restart fails six times, the machine enters a fault state requiring a complete power-off or 30-minute wait before restart. The fault and alarm are displayed on the LCD.
| Fault code | Meaning | Relevant action | Trigger conditions | Resume conditions |
|---|---|---|---|---|
| 1 | Bus boost fail | Turn fault mode | Grid soft start process starts but bus voltage does not reach set value | Restore after reaching the set voltage for 15 seconds |
| 2 | Bus over voltage | Turn fault mode | Bus voltage is higher than set value | Restore after reaching the set voltage for 15 seconds |
| 3 | Bus below voltage | Turn fault mode | Bus voltage is lower than set value | Cannot restore |
| 4 | Battery over current | Turn fault mode | Battery current is higher than set value | Cannot restore |
| 5 | System over temperature | Turn fault mode | PFC temperature is higher than set value or fan is not connected | Restore after temperature lower than set value and fan connected for 15 minutes |
| 6 | Battery over voltage | Turn fault mode | Battery voltage is higher than set value | Restore after reaching the set voltage for 15 seconds |
| 7 | Bus soft start failed | Turn fault mode | Battery soft start process starts but the bus voltage has not reached set value | Restore after reaching the set voltage for 15 seconds |
| 8 | Bus short circuit | Turn fault mode | Bus voltage is lower than set value | Cannot restore |
| 9 | Inverter soft start failed | Turn fault mode | Inverter soft start process starts but the inverter voltage has not reached set value | Restore after reaching the set voltage for 15 seconds |
| 11 | Inverter under voltage | Turn fault mode | The inverter voltage is lower than the set value in battery mode | Restore after reaching the set voltage for 15 seconds |
| 12 | Inverter short circuit | Turn fault mode | Inverter voltage is less than the set value and current is higher than the set value | Restore after reaching the set value for 15 seconds |
| 13 | Inverter negative power | Turn fault mode | The inverter power is negative and exceeds the set value for a period of time | Restore after reaching the set value for 15 seconds |
| 14 | Over load | Turn fault mode | The load current is higher than the set value | Restore after reaching the set value for 15 seconds |
| 17 | Program updating | Turn fault mode | Inverter updating or OTA | Restore after updating |
| 18 | PV reverse connection | Turn fault mode | PV reverse connection | Restore after connecting correctly for 15 seconds |
| 26 | BMS fault | Turn fault mode | Error code in BMS message. | Restore after BMS fault resolved |
| 29 | Inverter load abnormal | Turn fault mode | Abnormal inverter load leads to abnormal voltage | Restore after voltage returning normal for 15 seconds |
8.2 Alarm Reference Code
When an alarm occurs, the inverter does not enter fault mode, the red LED light flashes, and the LCD displays the Alarm code.
| Alarm code | Meaning | Relevant action | Trigger conditions | Resume conditions |
|---|---|---|---|---|
| 50 | Battery open | Alarm | Battery disconnected for no more than 10 minutes | Restore after battery connected and charging for 2 minutes |
| 51 | Battery under voltage | Alarm, battery low voltage shutdown or cannot power on | Battery voltage is lower than BAU set value | Restore after the battery voltage exceeding the BAU set value by 2V |
| 52 | Battery low voltage | Alarm | Battery voltage is lower than BAL set value | Restore after the battery voltage exceeding the BAL set value by 2V |
| 53 | Battery charge short circuit | Alarm, battery does not charge | Battery voltage is less than 24V and the charging current exists. | Restore after a maximum of 1 minute when the short circuit is eliminated. |
| 56 | BMS loss | Alarm | Communication failure after BMS communication function is enabled | Restore after communication function disabled or communication success |
| 58 | Fan error | Alarm, fan operation in full speed | No fan speed signal detected | Restore after fan speed signal detected |
| 59 | EEPROM error | Alarm | EEPROM read/write exception | Can not restore |
| 60 | Overload | Alarm | The mains current/battery discharge current/load power is higher than the rated value. | Restore after the mains current/battery discharge current/load power is less than the rated value. |
| 62 | PV energy weak | Alarm, Turn off the PV output to the load, but keep the PV charging the battery | When the battery is not connected, the bus voltage is lower than the set value | Restore after battery connected or grid connected, or 10 minutes later. |
| 68 | Battery under SOC shutdown | Alarm, turn to standby mode | BMS reports SOC lower than BAU set value | Restore after meeting one of the following three conditions: 1. Disable low SOC shutdown function 2. Disable BMS communication function 3. SOC is higher than the set value by 5% |
| 69 | Battery below SOC warning | Alarm, if it is in standby mode, it will remain in standby mode. | Lithium battery SOC is lower than set value+5% (grid mode or battery mode), lower than set value+10% (standby mode) | Restore after meeting one of the following three conditions: 1. Disable low SOC shutdown function 2. Disable BMS communication function 3. SOC is higher than the set value by 10% |
| 72 | Battery can not startup | Alarm | During standby, battery voltage is lower than the allowed startup voltage | Restore after the battery voltage is higher than the allowed startup voltage |
| 77 | Grid power is unstable | Alarm | Lost of grid power three times within 5 minutes | Restore after 5 mins |
8.3 General Troubleshooting
| Problem | Fault Event | Trigger conditions | What to do |
|---|---|---|---|
| LED screen display fault code 5 | Over temperature | 1. PFC temperature exceeds protection threshold for >20 seconds. | Check if fan is connected or if there are loose wiring issues. If fan is not connected for >5 minutes, machine reports fault code 5. |
| 2. Alarm 58 lasts for 5 seconds. | |||
| LED screen display fault code 12 | Inverter short circuit | In battery or standby mode, if inverter voltage is <80V and current is >30A, it should respond within 100-120ms. | 1. Check for short circuits at output terminals. 2. Verify inverter voltage and current meet triggering conditions. |
| LED screen display fault code 58 | Fan malfunction | Any of the fans rotating less than 8 times within 2 seconds. | 1. Check if fan is connected properly or if there are loose connections. 2. If fan is properly connected: a) Check for issues with fan detection circuit. b) Check if fan itself is damaged. |
| Unable to start | Battery | Requires voltage ≥11.5V/N to start in battery mode. Common reasons: improper calibration or insufficient battery voltage. | 1. Check battery voltage sampling and calibration. 2. Use multimeter to measure battery terminal voltage (using DC power supply or real battery) to ensure it reaches 11.5V per cell for startup. Note: Configure battery voltage according to machine model to avoid capacitor explosion. |
| Unable to start | Utility power | 1. Check for short circuits at mains terminal. 2. Check for wiring errors (e.g., mains input connected to output terminals). | |
| Unable to start | PV | 1. Check if PV input voltage is too close to critical threshold. 2. For low voltage versions, check if software versions of main control are compatible. Significant differences may prevent activation. | |
| PV not charging | Connecting wrong battery voltage can damage auxiliary power supply on PV side, causing power loss and inability to communicate with main control. |
9. User Tips
For optimal performance and longevity of your LVYUAN Hybrid Solar Inverter, consider the following user tips:
- Regularly check all connections for tightness and corrosion, especially after initial installation and during seasonal changes.
- Monitor the LCD display and the remote monitoring app frequently to understand system status, identify any warnings or faults early, and track energy production/consumption.
- Ensure adequate ventilation around the inverter to prevent overheating, which can impact efficiency and lifespan.
- Keep the inverter's firmware updated to benefit from the latest features and performance improvements.
- If using a lithium battery with BMS, always ensure the communication cable is securely connected and the correct battery type is selected in the inverter settings for accurate monitoring and control.
- In case of persistent issues, consult the troubleshooting section thoroughly before contacting support.
10. Warranty and Support
For warranty information, technical support, or service inquiries, please refer to the official user manual PDF available at LVYUAN Hybrid Solar Inverter User Manual (PDF) or contact your local distributor. Ensure you have your model number (TY-SIC-6.6KBE-W1) and purchase details ready when seeking support.