1. Introduction
The MGC320 SmartGen Controller is designed for single-unit automation control, enabling automatic starting and Automatic Mains Failure (AMF) functionality for small power generators. This controller integrates digital and intelligent technologies, featuring an intuitive LCD graphic display for straightforward operation and reliable performance.
Utilizing 32-bit micro-processor technology, the MGC320 ensures precise measurement of various parameters, along with adjustable set-values, timing functions, and limit value settings. Most parameters can be adjusted directly from the front panel, while all parameters can be configured via RS485 using a PC. Its compact structure, simple wiring, and high reliability make it suitable for a wide range of genset automation systems.
The MGC300 Series, including the MGC320, supports both true low power consumption (power off) and feigned low power consumption modes (awakening with screen light off, stop indicator flashing, but no active operations).
2. Performance and Characteristics
- Graphic LCD display with backlight, LED indicators, and push-button operation.
- Acrylic material for hard screen protection.
- Wide power supply range: DC (8~35)V, accommodating various starting battery voltages.
- Collects and displays mains/generator 3-phase voltage, 3-phase current, frequency, and power parameters:
- Mains: Line voltage (L12, L23, L31), Phase voltage (L1, L2, L3), Frequency (Hz)
- Generator: Line voltage (L12, L23, L31), Phase voltage (L1, L2, L3), Frequency (Hz)
- Load: Current (Ia, Ib, Ic) in Amperes (A), Total active power P in Kilowatts (kW)
- Mains protection functions: over voltage, under voltage, over frequency, under frequency, and loss of phase.
- Generator protection functions: over voltage, under voltage, over frequency, under frequency, over current, over power, and loss of phase.
- Precisely collects engine parameter values:
- Temperature (°C)
- Fuel level (%)
- Battery voltage (V)
- Accumulated running time (H, max. 9999 hours)
- Speed (RPM)
- Accumulated start times (max. 90,000,000 times, displayable only on PC software)
- Genset fault protection and display function.
- The MGC320 controller features 4 working modes: Manual, Auto, Stop, and Test.
- Parameter setting function: allows users to change and set parameters, which are retained even after system power-off. Most parameters are adjustable from the front panel, and all can be configured via RS485 on a PC.
- 1 digital input port, 2 fixed input ports.
- 2 fixed relay output ports (fuel output, starting output).
- 2 digital relay output ports.
- All parameters are digitally adjusted for improved reliability and stability.
- Sealing gasket between the enclosure and control panel provides IP65 dustproof and waterproof performance.
- Metal fixing clips ensure stable controller mounting.
- Modular structure design, pluggable wiring terminals, and built-in installation for compact structure and easy installation.
3. Setup and Installation
3.1 Overall and Cutout Dimensions

The diagram illustrates the physical dimensions of the MGC320 controller and the required panel cutout size for installation. Overall dimensions are 126mm (width) x 106mm (height) x 46.5mm (depth). The panel cutout should be 111mm (width) x 91mm (height).
3.2 Controller Back Panel

This image displays the rear view of the MGC320 controller, highlighting the various terminal blocks for electrical connections.
3.3 Terminal Connection Description

This table provides detailed information for each terminal on the MGC320 controller, including its function, recommended cable size, and specific notes for connection.
| No. | Function | Cable Size | Note |
|---|---|---|---|
| 1 | B- | 1.5mm² | Connected with negative of starting battery |
| 2 | B+ | 1.5mm² | Connected with positive of starting battery |
| 3 | Fuel Relay Output | 1.0mm² | B+ power is supplied by terminal 2, rated 7A |
| 4 | Crank Relay Output | 1.0mm² | B+ power is supplied by terminal 2, rated 7A |
| 5 | Digital Input | 1.0mm² | Digital input, grounded active (B-); Fuel level sensor; connected with level low digital signal or level resistance sensor. |
| 6 | Remote Start Input Port/Power Port | 1.0mm² | Grounded active (B-) 1. For MGC320, when mains failure and mains detection is active, this port is active; MGC310 is always active; 2. This port is power port, when it is disconnected, controller will power off. |
| 7 | Oil Pressure Input | 1.0mm² | Connected with digital signals of oil pressure low |
| 8 | Fuel Level Sensor Input | 1.0mm² | Fuel level sensor input |
| 9 | Temp. Sensor Input | 1.0mm² | Connected with water/cylinder digital signals or temp. resistance sensor |
| 10 | RS485- | 1.0mm² | |
| 11 | RS485+ | 1.0mm² | |
| 12 | Digital Output 1 | 1.0mm² | Relay N/O connector, volt free output, rated 7A |
| 13 | |||
| 14 | Digital Output 2 | 1.0mm² | N/C output, rated 7A |
| 15 | Relay COM | ||
| 16 | N/O output, rated 7A |
3.4 Mains and Genset Voltage Wiring
| No. | Function | Cable Size | Note |
|---|---|---|---|
| 17 | Mains R Voltage | 1.0mm² | Connected to Mains R Phase |
| 18 | Mains S Voltage | 1.0mm² | Connected to Mains S Phase |
| 19 | Mains T Voltage | 1.0mm² | Connected to Mains T Phase |
| 20 | Mains N1 Input | 1.0mm² | Connected to Mains N1 wire |
| 21 | Gens U Voltage | 1.0mm² | Connected to genset output U Phase |
| 22 | Gens V Voltage | 1.0mm² | Connected to genset output V Phase |
| 23 | Gens W Voltage | 1.0mm² | Connected to genset output W Phase |
| 24 | Gens N2 Input | 1.0mm² | Connected to genset output N2 wire |
| 25 | CT COM | 1.0mm² | Outside connected with CT secondary coil (rated 62.5mA) |
| 26 | CT IC | 1.0mm² | Outside connected with CT secondary coil (rated 62.5mA) |
| 27 | AT IB | 1.0mm² | Outside connected with CT secondary coil (rated 62.5mA) |
| 28 | CT IA | 1.0mm² | Outside connected with CT secondary coil (rated 62.5mA) |
3.5 Typical Application Diagram

This diagram illustrates the typical wiring for the MGC320 controller in a genset application, including connections for mains voltage, generator voltage, current transformers, and various control inputs/outputs.
CAUTION! Crank and fuel output ports shall expand big capacity relays.
CAUTION! When sensor port is configured to "Digital High Input Active", hanging up means high electrical level, and power positive connected is prohibited.
4. Operating Instructions
4.1 Panel Indication

This diagram labels the various indicators and keys on the front panel of the MGC320 controller, including Alarm Indicator, Gen Status Indicator, Mains Status Indicator, Stop Indicator, Stop/On Key, Auto Key, Auto Indicator, Test/Confirm Key, Manual Indicator, Up/Increase Key, Set (Up/Down Group), Down/Decrease Key, Mains Close Indicator, Gen Close Indicator, and Start Key.
4.2 Key Functions

This table outlines the function and description for each key on the MGC320 controller's front panel.
| Icons | Function | Description |
|---|---|---|
| Stop/On | Stop the running genset both in manual mode and in auto mode; In alarm status, press this button to reset any shutdown alarms; In stop mode, press this button and Down to test if LCD icons and LED indicators are OK; In stop mode, press this button and Down to set backlight always on; In stop process, re-press this button to stop generator immediately; In parameter setting process, press this button to exit the setting quickly; In stop status, press this button to start; In start status, press longer for 3s and release to stop; | |
| Auto | Press this key and controller enters to Auto mode; under this mode, genset can be controlled by remote start input signals; | |
| Start | Press this key and genset will start; | |
| Down/Decrease | LCD page scroll; In parameter settings, decrease the value where the cursor is; | |
| Up/Increase | LCD page scroll; In parameter settings, increase the value where the cursor is; Press the two keys simultaneously to enter parameter settings page; | |
| Manual/Confirm | Confirm key for parameter settings page; Manual key for other pages and press it to make controller in Manual mode; This key is especially for MGC310; | |
| Test/Confirm | Test key for other pages and press it to make controller commissioning; This key is especially for MGC320. |
4.3 Working Modes
The MGC320 controller offers four distinct working modes:
- Manual Mode: Allows direct control over the genset operations via the front panel buttons.
- Auto Mode: The genset can be controlled by remote start input signals, enabling automated operation based on external triggers (e.g., AMF).
- Stop Mode: Halts genset operation and allows for resetting alarms or performing tests.
- Test Mode: Used for commissioning and testing the controller's functions.
4.4 Parameter Setting
Parameters can be adjusted to customize the controller's behavior. These settings are stored and will not be lost upon power cycling. Most common parameters can be modified directly from the front panel. For comprehensive configuration and advanced settings, all parameters can be accessed and adjusted via RS485 communication using PC software.
4.5 LCD Icons Description

This table provides a comprehensive list of icons displayed on the MGC320's LCD screen and their corresponding definitions, indicating various statuses and alarms.
| Icon | Definition | Icon | Definition |
|---|---|---|---|
| Gen power indication | FL | Fuel level sensor indication | |
| Mains power indication | L1 | AC phase voltage indication | |
| Start countdown (crank disconnect is satisfied) | L12 | AC line voltage indication | |
| Over frequency alarm | DC | Battery voltage indication | |
| Under frequency alarm | A | Load current unit | |
| Temp high alarm | H | Accumulated running time unit | |
| Fuel level low | Hz | Frequency unit | |
| Outside input alarm | °C | Temperature unit | |
| Engine oil pressure low alarm | rpm | Speed unit (r/min) | |
| Crank failure | kW | Active power unit | |
| Stop failure | V | Voltage unit | |
| Battery voltage abnormal | % | Percentage | |
| Gen voltage high | I# Mains Close | ||
| Gen voltage low | II# Gen Close | ||
| Load over current |
5. Maintenance
To ensure optimal performance and longevity of your MGC320 SmartGen Controller, consider the following general maintenance guidelines:
- Cleaning: Regularly wipe the controller's front panel with a soft, dry cloth to remove dust and debris. Avoid using abrasive cleaners or solvents that could damage the acrylic screen or buttons.
- Connections: Periodically inspect all wiring connections to ensure they are secure and free from corrosion. Loose connections can lead to erratic behavior or system failure.
- Environment: Ensure the controller is installed in an environment that adheres to the specified operating and storage conditions (see Specifications section). Protect it from excessive moisture, extreme temperatures, and direct sunlight.
- Firmware Updates: Check the manufacturer's website periodically for any available firmware updates that may improve performance or add new features.
6. Troubleshooting
While specific troubleshooting steps are not detailed in the provided information, here are general approaches to common issues:
- No Power/Display: Check the DC power supply range (8~35V) and ensure all power connections (B+, B-) are secure. Verify the battery voltage.
- Genset Fails to Start: Confirm the controller is in the correct operating mode (Manual or Auto). Check fuel levels, oil pressure, and engine temperature sensors. Review the digital input signals for any active shutdown conditions.
- Alarms Displayed: Refer to the 'LCD Icons Description' (Table 3) to identify the specific alarm. Address the underlying issue indicated by the alarm icon. For example, if an 'Over frequency alarm' is shown, investigate the generator's speed control.
- Incorrect Readings: Verify sensor connections and calibration settings. Ensure current transformers (CTs) are correctly installed and rated.
- Communication Issues (RS485): Check RS485 wiring for proper polarity and connection. Ensure the PC software settings match the controller's communication parameters.
If issues persist, consult a qualified technician or contact SHALUO AVR Official Store for support.
7. Specifications
7.1 Technical Parameters

This table lists the key technical specifications and performance characteristics of the MGC320 controller.
| Items | Contents |
|---|---|
| Working Voltage | DC (8.0~35.0)V continuous power supply |
| Overall Consumption | ≤1.4W (Standby mode: ≤0.35W, 0W=low power consumption) |
| AC Volt Input: | |
| 3 phase 4 wire | 30V AC ~ 360V AC (ph-N) |
| 3 phase 3 wire | 30V AC ~ 620V AC (ph-ph) |
| Single phase 2 wire | 15V AC ~ 360V AC (ph-N) |
| 2 phase 3 wire | 15V AC ~ 360V AC (ph-N) |
| Alternator Frequency | 50Hz/60Hz |
| Crank Relay Output | 7A 24V DC power supply |
| Fuel Relay Output | 7A 24V DC power supply |
| Digital Relay Output Port 1 | 7A 250V AC volt free output |
| Digital Relay Output Port 2 | 7A 250V AC volt free output |
| Overall Dimensions | 126mm x 106mm x 46.5mm |
| Panel Cutout | 111mm x 91mm |
| CT Secondary Current | Rated: 62.5mA |
| Working Condition | Temperature: (-25~+70)°C Humidity: (20~93)% RH |
| Storage Condition | Temperature: (-30~+80)°C |
| Protection Level | Front panel IP65 |
| Insulation Intensity | Apply AC2.2kV voltage between high voltage terminal and low voltage terminal and the leakage current is not more than 3mA within 1min. |
| Weight | 0.27kg |
8. User Tips
No specific user tips were available from provided reviews or Q&A content.
9. Warranty and Support
For warranty information, technical support, or service inquiries regarding your MGC320 SmartGen Controller, please contact the SHALUO AVR Official Store directly. Ensure you have your product model number (SMARTGEN MGC320) and any relevant purchase details ready when seeking assistance.
10. Product Video
This video provides a visual overview of the MGC320 SmartGen Controller, showcasing its design and key features.