DAXTROMN GGH-10.2KW-PARALLEL

Contents

DAXTROMN 10.2KW Parallel Hybrid Solar Inverter User Manual

Model: GGH-10.2KW-PARALLEL

1. Introduction

This manual provides comprehensive instructions for the assembly, installation, operation, and troubleshooting of the DAXTROMN 10.2KW Parallel Hybrid Solar Inverter. Please read this manual carefully before installation and operation, and keep it for future reference.

1.1 Safety Instructions

▲ WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION – To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce risk of electric shock, disconnect all wire before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION – Only qualified personnel can install this device with battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for the details.
  10. Fuses are provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
  14. WARNING: Because this inverter is non-isolated, only three types of PV modules are acceptable: single crystalline, poly crystalline with class A-rated and CIGS modules. To avoid any malfunction, do not connect any PV modules with possible current leakage to the inverter. For example, grounded PV modules will cause current leakage to the inverter. When using CIGS modules, please be sure NO grounding.
  15. CAUTION: It's required to use PV junction box with surge protection. Otherwise, it will cause damage on inverter when lightning occurs on PV modules.

1.2 Features

  • Off-grid inverter
  • Pure sine wave inverter
  • External WIFI devices (APP is required)
  • Communication ports with BMS (RS485, CAN)
  • Supports selection of wide and narrow range of AC input
  • Configurable AC/Solar charger priority via LCD control panel
  • Configurable battery charging current based on applications via LCD control panel
  • Compatible with utility mains or generator power
  • Auto restart while AC is recovering
  • Overload / Over temperature / short circuit protection
  • Cold start function
  • Supports high-power applications and grid-connected storage
  • Full lithium battery charging and discharging management
  • Advanced support for Three-phase Mode and parallel connections (up to 6 units)
  • Built-in multiple communication ports: USB, RS232, RS485, CAN
  • Optional WiFi module for remote App monitoring
  • High-efficiency pure sine wave emergency output
  • Wide MPPT input range (120-450VDC) for maximum solar harvest

2. Product Overview

2.1 Basic System Architecture

The inverter is a multi-function unit combining inverter, solar charger, and battery charger functions to provide uninterruptible power. It can power various appliances in home or office environments, including motor-type appliances.

Basic Hybrid PV System Overview Diagram
Figure 1: Basic Hybrid PV System Overview. Shows connections between Solar Power, Generator, Utility, Inverter, External Battery Packs, and Home Appliances.

2.2 Component Identification

The front panel features an LCD display, status indicators, and function buttons. The rear panel includes various communication and power ports.

Product Overview with Labeled Components
Figure 2: Product Overview with Labeled Components

Key Components:

  1. LCD Display
  2. Status Indicator
  3. Charging Indicator
  4. Fault Indicator
  5. Function Buttons
  6. Power ON/OFF Switch
  7. RS232/RS485 Communication Port
  8. USB Communication Port
  9. Dry Contact (Optional)
  10. AC Input
  11. AC Output
  12. PV2 Input/Output (Dry contact Optional)
  13. PV1 Input/Output
  14. Parallel Communication Port (only parallel)
  15. BMS Communication Port (only parallel)
  16. Battery Input/Output

Note: RS232, RS485, and CAN communication share the same port, so they cannot be used simultaneously.

2.3 Communication Port Definition

The communication cable port for battery communication is defined as follows:

Pin NumberPort Function
PIN1, PIN8RS485-B
PIN2, PIN7RS485-A
PIN3GND
PIN4CAN-H
PIN5CAN-L
PIN6GND

Supports the Pylon CAN protocol.

Battery Communication Cable Port Definition
Figure 3: Battery Communication Cable Port Definition (RJ45)

3. Setup (Installation)

3.1 Unpacking and Inspection

Before installation, inspect the unit for any damage. The package should contain:

  • The inverter x1
  • User manual x 1
  • RS232 Communication cable x 1
  • USB Communication cable x 1
  • Parallel communication cable x 1 (only for parallel models)
  • Current sharing cable x 1 (only for parallel models)
  • PV connectors x 2 sets

3.2 Preparation

Before connecting any wires, remove the bottom cover by unscrewing two screws.

3.3 Mounting the Unit

Consider the following points when selecting an installation location:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level for easy LCD display reading.
  • Ambient temperature should be between -10°C and 55°C for optimal operation.
  • The recommended installation position is vertically on the wall.
  • Ensure sufficient heat dissipation and space for wiring by maintaining clearances as shown in the diagram.
Mounting the Unit Diagram with Dimensions
Figure 4: Recommended Mounting Clearances (20cm top/bottom, 50cm sides)

WARNING: Suitable for mounting on concrete or other non-combustible surface only.

3.4 Battery Connection

CAUTION: For safety and regulation compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. All wiring must be performed by qualified personnel.

Use appropriate cable and terminal sizes as recommended:

ModelTypical AmperageBattery CapacityWire SizeCable mm²Ring Terminal D (mm)Ring Terminal L (mm)Torque ValueLength
10.2KW190.5A100AH1AWG508.4515 Nm1M
200AH1/0AWG70

Battery Connection Steps:

  1. Assemble battery ring terminal based on recommended cable and terminal size.
  2. Fix two cable glands into positive and negative terminals.
  3. Insert the ring terminal of the battery cable flatly into the battery connector of the inverter and ensure the nuts are tightened with a torque of 5 Nm. Verify polarity at both the battery and the inverter/charger.
48VDC Battery Connection Diagram
Figure 5: 48VDC Battery Connection Diagram

WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.

CAUTION: Do not place anything between the flat part of the inverter terminal and the ring terminal. Otherwise, overheating may occur.

CAUTION: Do not apply anti-oxidant substance on the terminals before they are connected tightly.

CAUTION: Before making the final DC connection, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).

3.5 AC Input/Output Connection

CAUTION: Before connecting to AC input power source, install a separate AC breaker between the inverter and AC input power source. All wiring must be performed by qualified personnel.

Recommended cable requirement for AC wires:

ModelGaugeTorque Value
10.2KW8 AWG1.4 ~ 1.6Nm

AC Input/Output Connection Steps:

  1. Before making AC input/output connection, ensure the protector is disconnected.
  2. Remove 10mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3mm.
  3. Fix two cable glands into the input and output sides.
  4. Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Connect PE protective conductor () first.
  • → Ground (yellow-green)
  • L → LINE (brown or black)
  • N → Neutral (blue)
AC Input/Output Connection Diagram
Figure 6: AC Input/Output Connection Diagram

WARNING: Be sure that AC power source is disconnected before connecting wire to the unit.

3.6 PV Connection

CAUTION: Before connecting to PV modules, install separate DC circuit breakers between the inverter and PV modules. It is forbidden for the inverter to share the same solar panel group.

Recommended cable size for PV module connection:

ModelCable (mm²)AWGTorque Value (max)
10.2KW4121.2-1.6 Nm

PV Module Connection Steps:

  1. Check the input voltage of the PV array modules. This system supports two strings of PV array. Ensure the maximum current load of each PV input connector is 18A.
  2. Disconnect the circuit breaker and switch off the DC switch.
  3. Assemble provided PV connectors with PV modules.
PV Connector Assembly Steps
Figure 7: PV Connector Assembly Steps

CAUTION: Exceeding the maximum input voltage can destroy the unit! Check the system before wire connection.

CAUTION: Never directly touch the terminals of the inverter. It might cause lethal electric shock.

3.7 Final Assembly

After connecting all wirings, re-connect the three cables and then replace the bottom cover by screwing two screws.

3.8 RS232/USB Communication Connection

Download "SolarPower" software from the official website. When the inverter is connected to the computer, the software interface will display monitoring data.

3.9 Wi-Fi Connection (Optional)

The device has a standard Wi-Fi port. To monitor the status and information via Wi-Fi, connect a Wi-Fi collector. Users can download "SmartEss" Wi-Fi monitoring software from their phone's app store. Inverters with factory-integrated Wi-Fi can easily integrate into a home network (Wi-Fi Dongle is Optional) for local or online monitoring.

3.10 Dry Contact Signal

A dry contact (3A250VAC) is available on the rear panel to deliver a signal to an external device when the battery reaches a warning level.

Unit StatusConditionNC & CC & NO
Power OffUnit is off and no output is poweredOpenClose
Power OnBattery voltage <Setting the voltage in program 12CloseOpen
Battery voltage >Setting the voltage in program 13OpenClose

4. Operating Instructions

4.1 Power ON/OFF

Once the unit is properly installed and batteries are connected, simply press the On/Off switch (located on the button of the case) to turn on the unit.

4.2 Operation and Display Panel

The operation and display panel on the front of the inverter includes three indicators, four function keys, and an LCD display, showing operating status and input/output power information.

LCD Display and Control Panel
Figure 8: LCD Display and Control Panel

LED Indicator Messages:

LED IndicatorColorMessages
AC / INVGreenSolid On: Output is powered by utility in Line mode
Flashing: Output is powered by battery mode
CHGGreenSolid On: Battery is fully charged
Flashing: Battery is charging
▲FAULTRedSolid On: Fault occurs in the inverter
Flashing: Warning condition occurs in the inverter

Function Keys:

Function KeysDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

4.3 LCD Display Icons

The LCD displays various icons to indicate input source, digital information, battery mode, load information, and mode operation.

Input Source Information:

  • AC: Indicates the AC input.
  • PV1: Indicates the 1st PV panel input.
  • PV2: Indicates the 2nd PV panel input.

Left Digital Display Information:

  • INPUT BATT M: Indicates input voltage, input frequency, battery voltage, PV1 voltage, PV2 voltage, charger current, PV input current.

Middle Digital Display Information:

  • 88: Indicates the setting programs.
  • 88▲: Indicates warning and fault codes (flashing for warning, solid for fault).

Right Digital Display Information:

  • OUTPUTBATTLOAD: Indicates the output voltage, output frequency, load percent, load VA, load W, DC discharging current.

Battery Mode Information:

  • CHARGING: Indicates battery level by 0-24%, 25-49%, 50-74%, 75-100% and charging status.

Load Information:

  • OVER LOAD: Indicates over load.
  • Load level icons indicate 0-24%, 25-49%, 50-74%, 75-100%.

Mode Operation Information:

  • Indicates unit connects to the mains.
  • Indicates unit connects to the PV1 panel.
  • Indicates unit connects to the PV2 panel.
  • Indicates the solar charger is working.
  • Indicates the DC/AC inverter circuit is working.
  • Indicates unit alarm is disabled. Press and hold the "ESC" key for 3 seconds.
  • M02: Master unit, two parallel machines in single phase.
  • H02: Slave unit, two parallel machines in single phase.
  • A06: A-phase, six parallel machines in three phase.
  • B06: B-phase, six parallel machines in three phase.
  • C06: C-phase, six parallel machines in three phase.

4.4 LCD Setting

After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use "UP" or "DOWN" to select programs, then "ENTER" to confirm or "ESC" to exit. All settings must be modified in battery mode and rebooted to be valid.

Setting Programs (Examples):

ProgramDescriptionSelectable OptionFunction
00Exit setting modeESCExits the setting mode.
01Output source priorityUTL (Utility first)
SOL (Solar first)
SBU (Battery first)
PAL (Utility and Solar)
Configures the priority of power sources for loads.
02Maximum charging current10A to 120A (10A increment)Configures total charging current for solar and utility chargers.
03AC input voltage rangeAPL (Wide range: 90-280VAC)
UPS (Narrow range: 170-280VAC)
Sets the acceptable AC input voltage range.
05Battery typeAGM (Lead acid)
FLD (Flooded)
Nbt (No battery)
USE (User-Defined)
Selects the battery type or enables operation without battery.
06Auto restart when overload occursLtd (Disable)
LtE (Enable)
Enables or disables automatic restart after an overload.
07Auto restart when over temperature occursLtd (Disable)
LtE (Enable)
Enables or disables automatic restart after over temperature.
09Output frequency50Hz
60Hz
Sets the output frequency.
10Output voltage220V, 230V, 240VSets the output voltage. (Device must be restarted after modification)
18Alarm controlbON (Alarm on)
bOF (Alarm off)
Enables or disables audible alarms.
28Single and Parallel settingSle (Single enable)
PAL (Single-phase parallel enable)
3P1 (A-phase parallel enable)
3P2 (B-phase parallel enable)
3P3 (C-phase parallel enable)
Configures single or parallel operation mode.

5. Parallel Installation Guide

The GGH-10.2KW model supports parallel operation for increased capacity, up to 6 units. The GGH-6.5KVA model cannot be connected in parallel.

5.1 Parallel Operation Cable

Ensure all battery cables are of the same length to prevent voltage differences that could hinder parallel operation.

Recommended Breaker Specification for Battery (per inverter):

ModelBreaker Rating
10.2KW1 unit * 250A/70Vdc

If using one breaker for the whole system, its rating should be X times the current of 1 unit, where X is the number of inverters in parallel.

Recommended AC Input and Output Cable Size (per inverter):

ModelGaugeTorque Value
10.2KW10AWG1.4 ~ 1.6Nm

Recommended AC Input and Output Cable Size for Parallel Units:

Model2 units3 units4 units5 units6 units
10.2KW120A/230VAC180A/230VAC240A/230VAC300A/230VAC360A/230VAC

5.2 Single-phase Parallel Operation

Up to 6 units can operate in single-phase parallel mode.

WARNING: Batteries are required for parallel operation. Do not operate in parallel without batteries.

WARNING: It is forbidden for inverters to share the same solar panel group.

WARNING: Ensure all cables are of the same length to prevent voltage differences.

Set the parameters of each inverter separately (working mode, single-phase parallel function). All inverters must have the same working mode and output frequency when operating in parallel.

WARNING: All inverters must share the battery pack when running in parallel.

5.3 Three-phase Parallel Operation

Up to 6 units can operate in three-phase parallel mode.

WARNING: Batteries are required for parallel operation. Do not operate in parallel without batteries.

WARNING: It is forbidden for inverters to share the same solar panel group.

WARNING: Ensure all cables are of the same length to prevent voltage differences.

Set the parameters of each inverter independently (working mode, three-phase parallel function, and A/B/C phase sequence). All inverters must have the same working mode and output frequency when operating in parallel.

WARNING: All inverters must share the battery pack when running in parallel.

WARNING: Do not connect the current sharing cable between inverters that are in different phases. This may damage the inverters.

6. Maintenance

Regular maintenance ensures the longevity and optimal performance of your inverter. Always disconnect all power sources before performing any maintenance.

  • Cleaning: Keep the inverter clean and free from dust. Use a dry cloth to wipe down the exterior. Ensure ventilation openings are clear of obstructions.
  • Connections: Periodically check all electrical connections (battery, AC input/output, PV) for tightness and signs of corrosion. Tighten any loose connections.
  • Environment: Ensure the installation environment remains within the specified temperature and humidity ranges. Proper ventilation is crucial for heat dissipation.
  • Battery Health: Monitor battery voltage and performance. Refer to battery manufacturer guidelines for specific maintenance.
  • Firmware: Keep the inverter firmware updated to the latest version for optimal performance and bug fixes.

7. Troubleshooting

7.1 Fault Codes

Fault CodeFault Event
01Fan is locked
02Over temperature
03Battery voltage is too high
04Battery voltage is too low
05Output short circuited
06Output voltage is too high
07Overload time out
08Bus voltage is too high
09Bus soft start failed
24PV over temperature
52Bus voltage is too low
53Inverter soft start failed
55Over DC voltage in AC output
57Current sensor failed
58Output voltage is too low

7.2 Warning Codes

Warning CodeWarning Event
01Fan is locked
02Over temperature
03Battery is over-charged
04Low battery
07Overload
10Output power derating
08Over current
15PV energy is low
16High AC input (>280VAC) during BUS soft start
21PV low voltage
22PV over voltage

7.3 Parallel Fault Codes

Fault CodeFault Event
60Power feedback protection
71Firmware version inconsistent
72Current sharing fault
73Output voltage different
80CAN fault
81Host loss
82Synchronization loss
83Battery voltage detected different
84AC input voltage and frequency detected different
85AC output current unbalance
86AC output mode setting is different

7.4 Troubleshooting Guide

ProblemLCD/LED/BuzzerPossible CauseWhat to Do
Unit shuts down automatically during start-upLCD/LED and buzzer active then complete offThe battery voltage is too low1. Re-charge battery.
2. Replace battery.
No response after power onNo indication1. The battery voltage is too low.
2. Internal fuse tripped.
1. Contact repair center for fuse replacement.
2. Re-charge battery.
3. Replace battery.
Mains exist but unit works in battery modeInput voltage displayed as '0' on LCD, green LED flashing
LED flashing
Input protector is triggered
Insufficient quality of AC power (grid or generator)
Check if AC breaker is turned on and AC wiring is connected well.
1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct.
Internal relay switches on and off repeatedlyLCD display and LED flashingSet "Solar First" as the priority of output source.Change output source priority to utility first.
Buzzer beeps continuously and red LED is onFault code 01Fan faultReplace the fan.
Fault code 02Internal temperature of inverter component is over 85°CCheck whether the environment around the equipment is well ventilated.
Fault code 03The battery voltage is too high
Battery is over charged
Check if specifications and quantity of batteries meet requirements.
Return to repair center.
Fault code 04The battery voltage is too low1. The battery is dead, charge immediately.
2. Check the battery for damage.
Fault code 05Output short circuited1. Check that the output cable is connected.
2. Return to the maintenance center.
Fault code 06/58Output abnormal (Inverter voltage range 180-260VAC)Return to the maintenance center.
Fault code 07Overload error, inverter is overload 110% and overload time reaches upper limitReduce load.
Fault code 08/09/12/53/57Internal fault of inverterReturn to the maintenance center.
Fault code 10Over current or surgeRemove abnormal load or check PV input.
Fault code 11Solar panel configuration is higher than PV input voltage requiredRemove excess solar panels.
Fault code 13Battery discharge over currentCheck if discharge current of Item 40 is lower than the discharge current of the inverter.
Fault code 52/55Internal fault of inverterReturn to the maintenance center.
Fault code 60Power feedback protection1. Restart the inverter.
2. Check if L/N cables are not connected reversely in all inverters.
3. For parallel system in single phase, ensure sharing cables are connected in all inverters. For three-phase system, ensure sharing cables are connected in inverters in the same phase and disconnected in inverters in different phase.
Fault code 71Firmware version inconsistent1. Update all inverter firmware to the same version.
2. If problem remains, contact your installer.
Fault code 72Output current of each inverter is different1. Check if sharing cables are connected well and restart the inverter.
2. If problem remains, contact your installer.
Fault code 73AC output voltage setting is differentCheck whether the output voltage of each inverter is set the same.
Fault code 80CAN data loss1. Check if communication cables are connected well and restart the inverter.
2. If problem remains, contact your installer.
Fault code 81Host data loss (only for three-phase parallel)1. Check if communication cables are connected well and restart the inverter.
2. If problem remains, contact your installer.
Fault code 82Synchronization data loss1. Check if communication cables are connected well and restart the inverter.
2. If problem remains, contact your installer.
Fault code 83Battery voltage of each inverter is not the same1. Make sure all inverters share same groups of batteries.
2. Remove all loads and disconnect AC input and PV input. Check battery voltage of all inverters. If values are close, check if all battery cables are same length and material type.
3. If problem remains, contact your installer.
Fault code 84AC input voltage and frequency detected differentCheck whether the input voltage and frequency of each inverter are set the same.
Fault code 85AC output current unbalance1. Restart the inverter.
2. Remove some excessive loads and re-check load information from LCD of inverters. If values are different, check if AC input and output cables are same length and material type.
Fault code 86AC output mode setting is differentCheck whether it is set to parallel mode.
2. Return to the maintenance center.

8. Specifications

8.1 Line Mode Specifications

ParameterSpecification (GGH-10.2KW-PARALLEL)
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7Vac (narrow range)
90Vac±7Vac (wide range)
Low Loss Return Voltage180Vac±7Vac (narrow range)
100Vac±7Vac (narrow range)
High Loss Voltage280Vac±7Vac
High Loss Return Voltage270Vac±7Vac
Max AC Input Voltage300Vac
Max AC Input Current60A
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionLine mode: AC input fuse
Battery mode: Electronic Circuits
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (narrow range)
20ms typical (wide range)

8.2 Inverter Mode Specifications

ParameterSpecification (GGH-10.2KW-PARALLEL)
Rated Output Power10200W
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency60Hz or 50Hz
Max. peak Efficiency93%
Overload Protection5s@≥150% load; 10s@110%~150% load
Surge Capacity2* rated power for 5 seconds
Low DC Cut-off Voltage42Vdc
Nominal DC Input Voltage48Vdc
Cold Start Voltage46.0Vdc
Low DC Warning Voltage @load < 20%44.0Vdc
@20% ≤ load < 50%42.8Vdc
@load ≥ 50%40.4Vdc
Low DC Warning Return Voltage @load < 20%48.0Vdc
@20% ≤ load < 50%44.8Vdc
@load ≥ 50%42.4Vdc
Low DC Cut-off Voltage @load < 20%44.0Vdc
@20% ≤ load < 50%40.8Vdc
@load ≥ 50%38.4Vdc
High DC Recovery Voltage<60Vdc
High DC Cut-off Voltage>60Vdc
CommunicationRS232 or RS485 or CAN, WIFI(option) and Bluetooth(option)

8.3 Charge Mode Specifications

ParameterSpecification (GGH-10.2KW-PARALLEL)
Charging Current @Nominal Input Voltage120A
Bulk Charging Voltage (Flooded Battery)58.4Vdc
Bulk Charging Voltage (AGM / Gel Battery)56.4Vdc
Floating Charging Voltage54.0Vdc
Overcharge Protection60.0Vdc
Charging Algorithm3-Step
Max. PV Array Power5000W*2
Max. PV Array Open Circuit Voltage>450Vdc
Nominal PV Voltage360Vdc
PV Array MPPT Voltage Range90Vdc~450Vdc
Max. Input Current18A*2

8.4 General Specifications

ParameterSpecification (GGH-10.2KW-PARALLEL)
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (L*W*H), mm554*420*141.9
Net Weight, kg19.5

8.5 Installation Dimension Drawing

Installation Dimension Drawing
Figure 9: Installation Dimension Drawing (unit: mm)

9. User Tips

  • Battery-Free Operation: This inverter can work efficiently with or without batteries, offering flexibility in system design and potentially saving costs.
  • Pure Sine Wave Output: The inverter produces a pure sine wave output, ensuring that the electricity generated is as clean as mains power, safely supplying power to sensitive appliances without damage.
  • Battery Compatibility: The inverter is compatible with a variety of battery types, including lead-acid, lithium, and lithium iron phosphate (LiFePO4) batteries.
  • Professional Installation: In some regions, the installation of photovoltaic equipment must be carried out by a licensed electrician. It is recommended to contact a local professional for assistance to ensure compliance and safety.
  • User Manual PDF: A detailed user manual in PDF format is available for download. Refer to the seller's product page or contact support for the link.

10. Warranty and Support

The product comes with a one-year warranty. If a part fails due to damage within the warranty period, you may be eligible for a free replacement. Please contact the seller or an authorized service center for warranty claims and support.

For installation and commissioning guidance, a detailed English installation manual is provided. In some European countries, installation of photovoltaic equipment must be carried out by a licensed electrician; it is recommended to contact a local professional for assistance.

For further assistance or if errors persist after following troubleshooting steps, please contact your local dealer or service center for maintenance.