1. Introduction
This manual provides comprehensive instructions for the assembly, installation, operation, and troubleshooting of the DAXTROMN 10.2KW Parallel Hybrid Solar Inverter. Please read this manual carefully before installation and operation, and keep it for future reference.
1.1 Safety Instructions
▲ WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION – To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wire before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION – Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for the details.
- Fuses are provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
- WARNING: Because this inverter is non-isolated, only three types of PV modules are acceptable: single crystalline, poly crystalline with class A-rated and CIGS modules. To avoid any malfunction, do not connect any PV modules with possible current leakage to the inverter. For example, grounded PV modules will cause current leakage to the inverter. When using CIGS modules, please be sure NO grounding.
- CAUTION: It's required to use PV junction box with surge protection. Otherwise, it will cause damage on inverter when lightning occurs on PV modules.
1.2 Features
- Off-grid inverter
- Pure sine wave inverter
- External WIFI devices (APP is required)
- Communication ports with BMS (RS485, CAN)
- Supports selection of wide and narrow range of AC input
- Configurable AC/Solar charger priority via LCD control panel
- Configurable battery charging current based on applications via LCD control panel
- Compatible with utility mains or generator power
- Auto restart while AC is recovering
- Overload / Over temperature / short circuit protection
- Cold start function
- Supports high-power applications and grid-connected storage
- Full lithium battery charging and discharging management
- Advanced support for Three-phase Mode and parallel connections (up to 6 units)
- Built-in multiple communication ports: USB, RS232, RS485, CAN
- Optional WiFi module for remote App monitoring
- High-efficiency pure sine wave emergency output
- Wide MPPT input range (120-450VDC) for maximum solar harvest
2. Product Overview
2.1 Basic System Architecture
The inverter is a multi-function unit combining inverter, solar charger, and battery charger functions to provide uninterruptible power. It can power various appliances in home or office environments, including motor-type appliances.

2.2 Component Identification
The front panel features an LCD display, status indicators, and function buttons. The rear panel includes various communication and power ports.

Key Components:
- LCD Display
- Status Indicator
- Charging Indicator
- Fault Indicator
- Function Buttons
- Power ON/OFF Switch
- RS232/RS485 Communication Port
- USB Communication Port
- Dry Contact (Optional)
- AC Input
- AC Output
- PV2 Input/Output (Dry contact Optional)
- PV1 Input/Output
- Parallel Communication Port (only parallel)
- BMS Communication Port (only parallel)
- Battery Input/Output
Note: RS232, RS485, and CAN communication share the same port, so they cannot be used simultaneously.
2.3 Communication Port Definition
The communication cable port for battery communication is defined as follows:
| Pin Number | Port Function |
|---|---|
| PIN1, PIN8 | RS485-B |
| PIN2, PIN7 | RS485-A |
| PIN3 | GND |
| PIN4 | CAN-H |
| PIN5 | CAN-L |
| PIN6 | GND |
Supports the Pylon CAN protocol.

3. Setup (Installation)
3.1 Unpacking and Inspection
Before installation, inspect the unit for any damage. The package should contain:
- The inverter x1
- User manual x 1
- RS232 Communication cable x 1
- USB Communication cable x 1
- Parallel communication cable x 1 (only for parallel models)
- Current sharing cable x 1 (only for parallel models)
- PV connectors x 2 sets
3.2 Preparation
Before connecting any wires, remove the bottom cover by unscrewing two screws.
3.3 Mounting the Unit
Consider the following points when selecting an installation location:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level for easy LCD display reading.
- Ambient temperature should be between -10°C and 55°C for optimal operation.
- The recommended installation position is vertically on the wall.
- Ensure sufficient heat dissipation and space for wiring by maintaining clearances as shown in the diagram.

WARNING: Suitable for mounting on concrete or other non-combustible surface only.
3.4 Battery Connection
CAUTION: For safety and regulation compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. All wiring must be performed by qualified personnel.
Use appropriate cable and terminal sizes as recommended:
| Model | Typical Amperage | Battery Capacity | Wire Size | Cable mm² | Ring Terminal D (mm) | Ring Terminal L (mm) | Torque Value | Length |
|---|---|---|---|---|---|---|---|---|
| 10.2KW | 190.5A | 100AH | 1AWG | 50 | 8.4 | 51 | 5 Nm | 1M |
| 200AH | 1/0AWG | 70 |
Battery Connection Steps:
- Assemble battery ring terminal based on recommended cable and terminal size.
- Fix two cable glands into positive and negative terminals.
- Insert the ring terminal of the battery cable flatly into the battery connector of the inverter and ensure the nuts are tightened with a torque of 5 Nm. Verify polarity at both the battery and the inverter/charger.

WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.
CAUTION: Do not place anything between the flat part of the inverter terminal and the ring terminal. Otherwise, overheating may occur.
CAUTION: Do not apply anti-oxidant substance on the terminals before they are connected tightly.
CAUTION: Before making the final DC connection, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).
3.5 AC Input/Output Connection
CAUTION: Before connecting to AC input power source, install a separate AC breaker between the inverter and AC input power source. All wiring must be performed by qualified personnel.
Recommended cable requirement for AC wires:
| Model | Gauge | Torque Value |
|---|---|---|
| 10.2KW | 8 AWG | 1.4 ~ 1.6Nm |
AC Input/Output Connection Steps:
- Before making AC input/output connection, ensure the protector is disconnected.
- Remove 10mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3mm.
- Fix two cable glands into the input and output sides.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Connect PE protective conductor () first.
- → Ground (yellow-green)
- L → LINE (brown or black)
- N → Neutral (blue)

WARNING: Be sure that AC power source is disconnected before connecting wire to the unit.
3.6 PV Connection
CAUTION: Before connecting to PV modules, install separate DC circuit breakers between the inverter and PV modules. It is forbidden for the inverter to share the same solar panel group.
Recommended cable size for PV module connection:
| Model | Cable (mm²) | AWG | Torque Value (max) |
|---|---|---|---|
| 10.2KW | 4 | 12 | 1.2-1.6 Nm |
PV Module Connection Steps:
- Check the input voltage of the PV array modules. This system supports two strings of PV array. Ensure the maximum current load of each PV input connector is 18A.
- Disconnect the circuit breaker and switch off the DC switch.
- Assemble provided PV connectors with PV modules.

CAUTION: Exceeding the maximum input voltage can destroy the unit! Check the system before wire connection.
CAUTION: Never directly touch the terminals of the inverter. It might cause lethal electric shock.
3.7 Final Assembly
After connecting all wirings, re-connect the three cables and then replace the bottom cover by screwing two screws.
3.8 RS232/USB Communication Connection
Download "SolarPower" software from the official website. When the inverter is connected to the computer, the software interface will display monitoring data.
3.9 Wi-Fi Connection (Optional)
The device has a standard Wi-Fi port. To monitor the status and information via Wi-Fi, connect a Wi-Fi collector. Users can download "SmartEss" Wi-Fi monitoring software from their phone's app store. Inverters with factory-integrated Wi-Fi can easily integrate into a home network (Wi-Fi Dongle is Optional) for local or online monitoring.
3.10 Dry Contact Signal
A dry contact (3A250VAC) is available on the rear panel to deliver a signal to an external device when the battery reaches a warning level.
| Unit Status | Condition | NC & C | C & NO |
|---|---|---|---|
| Power Off | Unit is off and no output is powered | Open | Close |
| Power On | Battery voltage <Setting the voltage in program 12 | Close | Open |
| Battery voltage >Setting the voltage in program 13 | Open | Close |
4. Operating Instructions
4.1 Power ON/OFF
Once the unit is properly installed and batteries are connected, simply press the On/Off switch (located on the button of the case) to turn on the unit.
4.2 Operation and Display Panel
The operation and display panel on the front of the inverter includes three indicators, four function keys, and an LCD display, showing operating status and input/output power information.

LED Indicator Messages:
| LED Indicator | Color | Messages |
|---|---|---|
| AC / INV | Green | Solid On: Output is powered by utility in Line mode Flashing: Output is powered by battery mode |
| CHG | Green | Solid On: Battery is fully charged Flashing: Battery is charging |
| ▲FAULT | Red | Solid On: Fault occurs in the inverter Flashing: Warning condition occurs in the inverter |
Function Keys:
| Function Keys | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
4.3 LCD Display Icons
The LCD displays various icons to indicate input source, digital information, battery mode, load information, and mode operation.
Input Source Information:
- AC: Indicates the AC input.
- PV1: Indicates the 1st PV panel input.
- PV2: Indicates the 2nd PV panel input.
Left Digital Display Information:
- INPUT BATT M: Indicates input voltage, input frequency, battery voltage, PV1 voltage, PV2 voltage, charger current, PV input current.
Middle Digital Display Information:
- 88: Indicates the setting programs.
- 88▲: Indicates warning and fault codes (flashing for warning, solid for fault).
Right Digital Display Information:
- OUTPUTBATTLOAD: Indicates the output voltage, output frequency, load percent, load VA, load W, DC discharging current.
Battery Mode Information:
- CHARGING: Indicates battery level by 0-24%, 25-49%, 50-74%, 75-100% and charging status.
Load Information:
- OVER LOAD: Indicates over load.
- Load level icons indicate 0-24%, 25-49%, 50-74%, 75-100%.
Mode Operation Information:
- Indicates unit connects to the mains.
- Indicates unit connects to the PV1 panel.
- Indicates unit connects to the PV2 panel.
- Indicates the solar charger is working.
- Indicates the DC/AC inverter circuit is working.
- Indicates unit alarm is disabled. Press and hold the "ESC" key for 3 seconds.
- M02: Master unit, two parallel machines in single phase.
- H02: Slave unit, two parallel machines in single phase.
- A06: A-phase, six parallel machines in three phase.
- B06: B-phase, six parallel machines in three phase.
- C06: C-phase, six parallel machines in three phase.
4.4 LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use "UP" or "DOWN" to select programs, then "ENTER" to confirm or "ESC" to exit. All settings must be modified in battery mode and rebooted to be valid.
Setting Programs (Examples):
| Program | Description | Selectable Option | Function |
|---|---|---|---|
| 00 | Exit setting mode | ESC | Exits the setting mode. |
| 01 | Output source priority | UTL (Utility first) SOL (Solar first) SBU (Battery first) PAL (Utility and Solar) | Configures the priority of power sources for loads. |
| 02 | Maximum charging current | 10A to 120A (10A increment) | Configures total charging current for solar and utility chargers. |
| 03 | AC input voltage range | APL (Wide range: 90-280VAC) UPS (Narrow range: 170-280VAC) | Sets the acceptable AC input voltage range. |
| 05 | Battery type | AGM (Lead acid) FLD (Flooded) Nbt (No battery) USE (User-Defined) | Selects the battery type or enables operation without battery. |
| 06 | Auto restart when overload occurs | Ltd (Disable) LtE (Enable) | Enables or disables automatic restart after an overload. |
| 07 | Auto restart when over temperature occurs | Ltd (Disable) LtE (Enable) | Enables or disables automatic restart after over temperature. |
| 09 | Output frequency | 50Hz 60Hz | Sets the output frequency. |
| 10 | Output voltage | 220V, 230V, 240V | Sets the output voltage. (Device must be restarted after modification) |
| 18 | Alarm control | bON (Alarm on) bOF (Alarm off) | Enables or disables audible alarms. |
| 28 | Single and Parallel setting | Sle (Single enable) PAL (Single-phase parallel enable) 3P1 (A-phase parallel enable) 3P2 (B-phase parallel enable) 3P3 (C-phase parallel enable) | Configures single or parallel operation mode. |
5. Parallel Installation Guide
The GGH-10.2KW model supports parallel operation for increased capacity, up to 6 units. The GGH-6.5KVA model cannot be connected in parallel.
5.1 Parallel Operation Cable
Ensure all battery cables are of the same length to prevent voltage differences that could hinder parallel operation.
Recommended Breaker Specification for Battery (per inverter):
| Model | Breaker Rating |
|---|---|
| 10.2KW | 1 unit * 250A/70Vdc |
If using one breaker for the whole system, its rating should be X times the current of 1 unit, where X is the number of inverters in parallel.
Recommended AC Input and Output Cable Size (per inverter):
| Model | Gauge | Torque Value |
|---|---|---|
| 10.2KW | 10AWG | 1.4 ~ 1.6Nm |
Recommended AC Input and Output Cable Size for Parallel Units:
| Model | 2 units | 3 units | 4 units | 5 units | 6 units |
|---|---|---|---|---|---|
| 10.2KW | 120A/230VAC | 180A/230VAC | 240A/230VAC | 300A/230VAC | 360A/230VAC |
5.2 Single-phase Parallel Operation
Up to 6 units can operate in single-phase parallel mode.
WARNING: Batteries are required for parallel operation. Do not operate in parallel without batteries.
WARNING: It is forbidden for inverters to share the same solar panel group.
WARNING: Ensure all cables are of the same length to prevent voltage differences.
Set the parameters of each inverter separately (working mode, single-phase parallel function). All inverters must have the same working mode and output frequency when operating in parallel.
WARNING: All inverters must share the battery pack when running in parallel.
5.3 Three-phase Parallel Operation
Up to 6 units can operate in three-phase parallel mode.
WARNING: Batteries are required for parallel operation. Do not operate in parallel without batteries.
WARNING: It is forbidden for inverters to share the same solar panel group.
WARNING: Ensure all cables are of the same length to prevent voltage differences.
Set the parameters of each inverter independently (working mode, three-phase parallel function, and A/B/C phase sequence). All inverters must have the same working mode and output frequency when operating in parallel.
WARNING: All inverters must share the battery pack when running in parallel.
WARNING: Do not connect the current sharing cable between inverters that are in different phases. This may damage the inverters.
6. Maintenance
Regular maintenance ensures the longevity and optimal performance of your inverter. Always disconnect all power sources before performing any maintenance.
- Cleaning: Keep the inverter clean and free from dust. Use a dry cloth to wipe down the exterior. Ensure ventilation openings are clear of obstructions.
- Connections: Periodically check all electrical connections (battery, AC input/output, PV) for tightness and signs of corrosion. Tighten any loose connections.
- Environment: Ensure the installation environment remains within the specified temperature and humidity ranges. Proper ventilation is crucial for heat dissipation.
- Battery Health: Monitor battery voltage and performance. Refer to battery manufacturer guidelines for specific maintenance.
- Firmware: Keep the inverter firmware updated to the latest version for optimal performance and bug fixes.
7. Troubleshooting
7.1 Fault Codes
| Fault Code | Fault Event |
|---|---|
| 01 | Fan is locked |
| 02 | Over temperature |
| 03 | Battery voltage is too high |
| 04 | Battery voltage is too low |
| 05 | Output short circuited |
| 06 | Output voltage is too high |
| 07 | Overload time out |
| 08 | Bus voltage is too high |
| 09 | Bus soft start failed |
| 24 | PV over temperature |
| 52 | Bus voltage is too low |
| 53 | Inverter soft start failed |
| 55 | Over DC voltage in AC output |
| 57 | Current sensor failed |
| 58 | Output voltage is too low |
7.2 Warning Codes
| Warning Code | Warning Event |
|---|---|
| 01 | Fan is locked |
| 02 | Over temperature |
| 03 | Battery is over-charged |
| 04 | Low battery |
| 07 | Overload |
| 10 | Output power derating |
| 08 | Over current |
| 15 | PV energy is low |
| 16 | High AC input (>280VAC) during BUS soft start |
| 21 | PV low voltage |
| 22 | PV over voltage |
7.3 Parallel Fault Codes
| Fault Code | Fault Event |
|---|---|
| 60 | Power feedback protection |
| 71 | Firmware version inconsistent |
| 72 | Current sharing fault |
| 73 | Output voltage different |
| 80 | CAN fault |
| 81 | Host loss |
| 82 | Synchronization loss |
| 83 | Battery voltage detected different |
| 84 | AC input voltage and frequency detected different |
| 85 | AC output current unbalance |
| 86 | AC output mode setting is different |
7.4 Troubleshooting Guide
| Problem | LCD/LED/Buzzer | Possible Cause | What to Do |
|---|---|---|---|
| Unit shuts down automatically during start-up | LCD/LED and buzzer active then complete off | The battery voltage is too low | 1. Re-charge battery. 2. Replace battery. |
| No response after power on | No indication | 1. The battery voltage is too low. 2. Internal fuse tripped. | 1. Contact repair center for fuse replacement. 2. Re-charge battery. 3. Replace battery. |
| Mains exist but unit works in battery mode | Input voltage displayed as '0' on LCD, green LED flashing LED flashing | Input protector is triggered Insufficient quality of AC power (grid or generator) | Check if AC breaker is turned on and AC wiring is connected well. 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. |
| Internal relay switches on and off repeatedly | LCD display and LED flashing | Set "Solar First" as the priority of output source. | Change output source priority to utility first. |
| Buzzer beeps continuously and red LED is on | Fault code 01 | Fan fault | Replace the fan. |
| Fault code 02 | Internal temperature of inverter component is over 85°C | Check whether the environment around the equipment is well ventilated. | |
| Fault code 03 | The battery voltage is too high Battery is over charged | Check if specifications and quantity of batteries meet requirements. Return to repair center. | |
| Fault code 04 | The battery voltage is too low | 1. The battery is dead, charge immediately. 2. Check the battery for damage. | |
| Fault code 05 | Output short circuited | 1. Check that the output cable is connected. 2. Return to the maintenance center. | |
| Fault code 06/58 | Output abnormal (Inverter voltage range 180-260VAC) | Return to the maintenance center. | |
| Fault code 07 | Overload error, inverter is overload 110% and overload time reaches upper limit | Reduce load. | |
| Fault code 08/09/12/53/57 | Internal fault of inverter | Return to the maintenance center. | |
| Fault code 10 | Over current or surge | Remove abnormal load or check PV input. | |
| Fault code 11 | Solar panel configuration is higher than PV input voltage required | Remove excess solar panels. | |
| Fault code 13 | Battery discharge over current | Check if discharge current of Item 40 is lower than the discharge current of the inverter. | |
| Fault code 52/55 | Internal fault of inverter | Return to the maintenance center. | |
| Fault code 60 | Power feedback protection | 1. Restart the inverter. 2. Check if L/N cables are not connected reversely in all inverters. 3. For parallel system in single phase, ensure sharing cables are connected in all inverters. For three-phase system, ensure sharing cables are connected in inverters in the same phase and disconnected in inverters in different phase. | |
| Fault code 71 | Firmware version inconsistent | 1. Update all inverter firmware to the same version. 2. If problem remains, contact your installer. | |
| Fault code 72 | Output current of each inverter is different | 1. Check if sharing cables are connected well and restart the inverter. 2. If problem remains, contact your installer. | |
| Fault code 73 | AC output voltage setting is different | Check whether the output voltage of each inverter is set the same. | |
| Fault code 80 | CAN data loss | 1. Check if communication cables are connected well and restart the inverter. 2. If problem remains, contact your installer. | |
| Fault code 81 | Host data loss (only for three-phase parallel) | 1. Check if communication cables are connected well and restart the inverter. 2. If problem remains, contact your installer. | |
| Fault code 82 | Synchronization data loss | 1. Check if communication cables are connected well and restart the inverter. 2. If problem remains, contact your installer. | |
| Fault code 83 | Battery voltage of each inverter is not the same | 1. Make sure all inverters share same groups of batteries. 2. Remove all loads and disconnect AC input and PV input. Check battery voltage of all inverters. If values are close, check if all battery cables are same length and material type. 3. If problem remains, contact your installer. | |
| Fault code 84 | AC input voltage and frequency detected different | Check whether the input voltage and frequency of each inverter are set the same. | |
| Fault code 85 | AC output current unbalance | 1. Restart the inverter. 2. Remove some excessive loads and re-check load information from LCD of inverters. If values are different, check if AC input and output cables are same length and material type. | |
| Fault code 86 | AC output mode setting is different | Check whether it is set to parallel mode. 2. Return to the maintenance center. |
8. Specifications
8.1 Line Mode Specifications
| Parameter | Specification (GGH-10.2KW-PARALLEL) |
|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) |
| Nominal Input Voltage | 230Vac |
| Low Loss Voltage | 170Vac±7Vac (narrow range) 90Vac±7Vac (wide range) |
| Low Loss Return Voltage | 180Vac±7Vac (narrow range) 100Vac±7Vac (narrow range) |
| High Loss Voltage | 280Vac±7Vac |
| High Loss Return Voltage | 270Vac±7Vac |
| Max AC Input Voltage | 300Vac |
| Max AC Input Current | 60A |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) |
| Low Loss Frequency | 40±1Hz |
| Low Loss Return Frequency | 42±1Hz |
| High Loss Frequency | 65±1Hz |
| High Loss Return Frequency | 63±1Hz |
| Output Short Circuit Protection | Line mode: AC input fuse Battery mode: Electronic Circuits |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) |
| Transfer Time | 10ms typical (narrow range) 20ms typical (wide range) |
8.2 Inverter Mode Specifications
| Parameter | Specification (GGH-10.2KW-PARALLEL) |
|---|---|
| Rated Output Power | 10200W |
| Output Voltage Waveform | Pure Sine Wave |
| Output Voltage Regulation | 230Vac±5% |
| Output Frequency | 60Hz or 50Hz |
| Max. peak Efficiency | 93% |
| Overload Protection | 5s@≥150% load; 10s@110%~150% load |
| Surge Capacity | 2* rated power for 5 seconds |
| Low DC Cut-off Voltage | 42Vdc |
| Nominal DC Input Voltage | 48Vdc |
| Cold Start Voltage | 46.0Vdc |
| Low DC Warning Voltage @load < 20% | 44.0Vdc |
| @20% ≤ load < 50% | 42.8Vdc |
| @load ≥ 50% | 40.4Vdc |
| Low DC Warning Return Voltage @load < 20% | 48.0Vdc |
| @20% ≤ load < 50% | 44.8Vdc |
| @load ≥ 50% | 42.4Vdc |
| Low DC Cut-off Voltage @load < 20% | 44.0Vdc |
| @20% ≤ load < 50% | 40.8Vdc |
| @load ≥ 50% | 38.4Vdc |
| High DC Recovery Voltage | <60Vdc |
| High DC Cut-off Voltage | >60Vdc |
| Communication | RS232 or RS485 or CAN, WIFI(option) and Bluetooth(option) |
8.3 Charge Mode Specifications
| Parameter | Specification (GGH-10.2KW-PARALLEL) |
|---|---|
| Charging Current @Nominal Input Voltage | 120A |
| Bulk Charging Voltage (Flooded Battery) | 58.4Vdc |
| Bulk Charging Voltage (AGM / Gel Battery) | 56.4Vdc |
| Floating Charging Voltage | 54.0Vdc |
| Overcharge Protection | 60.0Vdc |
| Charging Algorithm | 3-Step |
| Max. PV Array Power | 5000W*2 |
| Max. PV Array Open Circuit Voltage | >450Vdc |
| Nominal PV Voltage | 360Vdc |
| PV Array MPPT Voltage Range | 90Vdc~450Vdc |
| Max. Input Current | 18A*2 |
8.4 General Specifications
| Parameter | Specification (GGH-10.2KW-PARALLEL) |
|---|---|
| Safety Certification | CE |
| Operating Temperature Range | -10°C to 50°C |
| Storage temperature | -15°C~60°C |
| Humidity | 5% to 95% Relative Humidity (Non-condensing) |
| Dimension (L*W*H), mm | 554*420*141.9 |
| Net Weight, kg | 19.5 |
8.5 Installation Dimension Drawing

9. User Tips
- Battery-Free Operation: This inverter can work efficiently with or without batteries, offering flexibility in system design and potentially saving costs.
- Pure Sine Wave Output: The inverter produces a pure sine wave output, ensuring that the electricity generated is as clean as mains power, safely supplying power to sensitive appliances without damage.
- Battery Compatibility: The inverter is compatible with a variety of battery types, including lead-acid, lithium, and lithium iron phosphate (LiFePO4) batteries.
- Professional Installation: In some regions, the installation of photovoltaic equipment must be carried out by a licensed electrician. It is recommended to contact a local professional for assistance to ensure compliance and safety.
- User Manual PDF: A detailed user manual in PDF format is available for download. Refer to the seller's product page or contact support for the link.
10. Warranty and Support
The product comes with a one-year warranty. If a part fails due to damage within the warranty period, you may be eligible for a free replacement. Please contact the seller or an authorized service center for warranty claims and support.
For installation and commissioning guidance, a detailed English installation manual is provided. In some European countries, installation of photovoltaic equipment must be carried out by a licensed electrician; it is recommended to contact a local professional for assistance.
For further assistance or if errors persist after following troubleshooting steps, please contact your local dealer or service center for maintenance.