DAXTROMN AGH-10.2KW-PLUS / AGH-8.2KW

Contents

DAXTROMN Hybrid Solar Inverter User Manual

Models: AGH-10.2KW-PLUS, AGH-8.2KW

Version: 1.0

1. About This Manual

1.1 Purpose

This manual describes the assembly, installation, operation, and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference.

1.2 Scope

This manual provides safety and installation guidelines as well as information on tools and wiring.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION --To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION - Only qualified personnel can install this device with battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for the details.
  10. One piece of 150A fuse is provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
  12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

3. Product Overview

This is a multi-function inverter/charger, combining functions of inverter, solar charger, and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.

3.1 Features

  • Pure sine wave inverter
  • Configurable input voltage range for home appliances and personal computers via LCD setting
  • Configurable battery charging current based on applications via LCD setting
  • Configurable AC/Solar Charger priority via LCD setting
  • Compatible to mains voltage or generator power
  • Auto restart while AC is recovering
  • Overload/ Over temperature/ short circuit protection
  • Smart battery charger design for optimized battery performance
  • Cold start function

3.2 Basic System Architecture

The following illustration shows basic application for this inverter/charger. It also includes following devices to have a complete running system: Generator or Utility, PV modules. Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power all kinds of appliances in home or office environment, including motor-type appliances such as tube light, fan, refrigerator and air conditioner.

Connection Diagram
Figure 1: Hybrid Power System Connection Diagram showing Solar Power, Generator/Utility, External Battery Packs connecting to the Inverter, which then powers Home Appliances.

3.3 Product Overview (Components)

Product Overview Diagram
Product Overview Diagram with numbered components.
No. Component
1LCD display
2Status indicator
3Charging indicator
4Fault indicator
5Touch Function buttons
6Power on/off switch
7AC input
8Main output
9Second output
10PV1 and PV2 input
11WIFI communication/RS-232 port
12Battery communication/RS-485 port
13Battery input
14Anti dust kit

4. Setup (Installation)

4.1 Unpacking and Inspection

Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package:

  • The unit x 1
  • User manual x 1
  • Ring terminal x 1
  • Mc4 terminal head x 2

4.2 Preparation

Before connecting all lines, remove the screws under the machine and remove the bottom cover plate.

4.3 Mounting the Unit

Consider the following points before selecting where to install:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level in order to allow the LCD display to be read at all times.
  • For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
  • The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.
  • Make sure that other objects and surfaces are left with enough space from the machine to ensure adequate heat dissipation and that there is enough room to remove the wires.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing two screws. It's recommended to use M4 or M5 screws.

4.4 Battery Connection

CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable as below.

Model Wire Size Cable (mm²) Torque value (max)
8.2KW/10.2KW1 x 2AWG252 Nm

Please follow below steps to implement battery connection:

  1. Remove insulation sleeve 18 mm for positive and negative conductors.
  2. Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Connect all battery packs as below chart.
Battery Connection Diagram
Battery Connection Diagram showing four 12V batteries connected in series to the inverter.
  1. Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.

WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.

CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).

4.5 AC Input/Output Connection

CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 63A for 8.2KW/10.2KW.

CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.

Model Gauge Cable (mm²) Torque Value
8.2KW/10.2KW10 AWG61.2 Nm

Please follow below steps to implement AC input/output connection:

  1. Before making AC input/output connection, be sure to open DC protector or disconnector first.
  2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
  3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (yellow-green) first.
AC Input/Output Connection Diagram
AC Input/Output Connection Diagram showing terminal block wiring.

WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.

  1. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.
  2. Make sure the wires are securely connected.

4.6 PV Connection

CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it's equipped with time-delay function before installation. Otherwise, this inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.

CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.

Model Wire Size Cable (mm²) Torque value (max)
8.2KW/10.2KW1 x 10AWG61.2 Nm

PV Module Selection:

When selecting proper PV modules, please be sure to consider below parameters:

  1. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
  2. Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
INVERTER MODEL 8.2KW/10.2KW
Max. PV Array Open Circuit Voltage500Vdc
PV Array MPPT Voltage Range90Vdc~450Vdc

Take 250Wp PV module as an example. After considering above two parameters, the recommended module configurations are listed as below table.

Solar Panel Spec. (reference) SOLAR INPUT (Min in serial: 6 pcs, max. in serial: 13 pcs) Q'ty of panels Total input power
250Wp
Vmp: 30.1Vdc
Imp: 8.3A
Voc: 37.7Vdc
- Isc: 8.4A
Cells: 60
6 pcs in serial6 pcs1500W
8 pcs in serial8 pcs2000W
12 pcs in serial12 pcs3000W
13 pcs in serial13 pcs3250W
12 pieces in serial and 3 sets in parallel36 pcs8200W
10 pieces in serial and 4 sets in parallel40 pcs10200W

PV Module Wire Connection

Step 1: Check the input voltage of PV array modules. The acceptable input voltage of the inverter is 120VDC - 500VDC. Please make sure that the maximum current load of each PV input connector is 10A.

CAUTION: Exceeding the maximum input voltage can destroy the unit!! Check the system before wire connection.

Step 2: Disconnect the DC circuit breaker.

Step 3: Assemble provided PV connectors with PV modules by the following below steps.

Step 4: Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV Input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.

PV Connection Diagram
PV Connection Diagram showing solar panels, inverter, battery, and home appliances.

4.7 Final Assembly

After connecting all wirings, please put bottom cover back by screwing two screws as shown below.

4.8 Communication Connection

1. Wi-Fi cloud communication (option):

Please use supplied communication cable to connect to inverter and Wi-Fi module. Download APP and installed from APP store, and Refer to "Wi-Fi Plug Quick Installation Guideline" to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.

2. GPRS cloud communication (option):

Please use supplied communication cable to connect to inverter and GPRS module, and then applied external power to GPRS module. Download APP and installed from APP store, and Refer to "GPRS RTU Quick Installation Guideline" to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.

3. Battery communication

The communication between the battery and the inverter can be realized through the battery communication interface, so that the inverter and the lithium battery can exchange information (Baud rate:9600).

4. Lithium battery and inverter connection:

Use power cables, communication cables for lithium batteries, and inverters to connect. Note: Lithium battery and inverter positive and negative positions, check the correct installation; The RJ45 connector of the communication cable connects to the BMS port of the inverter, and the other RJ45 connector connects to the RS485 port of the lithium battery; Before connecting, make sure that the lithium battery and inverter are turned off. (It is recommended to install a circuit breaker for the power cables of the lithium battery and the inverter battery interface. Otherwise, a spark may occur.)

In order to communicate with the lithium battery BMS, you should press the "ENTER" button for a long time, and set the battery type as "LIB-485" in program 05. Then select the matching battery protocol in Program 43.

5. Operating (Operation)

5.1 Power ON/OFF

Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the button of the case) to turn on the unit.

5.2 Operation and Display Panel

The operation and display panel is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.

LED Indicator and Function Keys Table
LED Indicator and Function Keys Table.

5.3 LCD Display Icons

The LCD display shows various icons to indicate input source information, configuration program and fault information, output information, and battery information.

Refer to the user manual PDF for a detailed table of LCD display icons and their descriptions.

5.4 LCD Setting

After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press "UP" or "DOWN" button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to exit.

Key settings include:

  • Program 00: Exit setting mode (Escape, One-button restore setting options)
  • Program 01: Output source priority (Utility first, Solar first, SBU priority, MKS priority)
  • Program 02: Maximum charging current (10A to 160A options)
  • Program 03: AC input voltage range (Appliances, UPS)
  • Program 05: Battery type (AGM, Flooded, User-Defined, LIB-485)
  • Program 06: Auto restart when overload occurs (Disable, Enable)
  • Program 07: Auto restart when over temperature occurs (Disable, Enable)
  • Program 09: Output frequency (50Hz, 60Hz)
  • Program 10: Output voltage (220V, 230V, 240V)
  • Program 11: Maximum utility charging current
  • Program 12: Setting voltage point back to utility source (42V to 51V options)
  • Program 13: Setting voltage point back to battery mode (Battery fully charged, 48V to 58V options)
  • Program 16: Charger source priority (Solar first, Solar and Utility, Only Solar)
  • Program 18: Alarm control (Alarm on/off)
  • Program 19: Auto return to default display screen (Default, Stay at latest screen)
  • Program 20: Backlight control (On, Off)
  • Program 22: Beeps while primary source is interrupted (On, Off)
  • Program 23: Overload bypass (Disable, Enable)
  • Program 25: Record Fault code (Enable, Disable)
  • Program 26: Bulk charging voltage (C.V voltage) (48.0V to 61.0V)
  • Program 27: Floating charging voltage (48.0V to 61.0V)
  • Program 29: Low DC cut-off voltage (40.0V to 48.0V)
  • Program 30: Battery equalization (Enable, Disable)
  • Program 31: Battery equalization voltage (48.0V to 61.0V)
  • Program 33: Battery equalized time (5min to 900min)
  • Program 34: Battery equalized timeout (5min to 900min)
  • Program 35: Equalization interval (0 to 90 days)
  • Program 36: Equalization activated immediately (Enable, Disable)
  • Program 37: GRID-tie operation (Off grid, Hybrid)
  • Program 38: GRID-tie current (10A, increment of 2A)
  • Program 39: Led pattern light (Off, On)
  • Program 41: Dual output (Disable, Use)
  • Program 42: Enter the dual output functional voltage point / power point
  • Program 43: Lithium battery protocol (PYLON, PACE)
  • Program 44: Delayed grid access (Disable, Enable)
  • Program 45: Maximum Second Load (20%~70%)
Output Source Priority Settings
Output Source Priority Settings (Program 01).
Off Grid or Hybrid Mode Setting
Setting Off Grid or Hybrid Mode (Program 37).

5.5 Display Setting

The LCD display information will be switched in turns by pressing "UP" or "DOWN" key. The selectable information is switched as below order: input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in Watt, DC discharging current, main CPU Version.

5.6 Operating Mode Description

The inverter supports various operating modes, including Standby mode, Line mode, and Grid-Tie Operation. Each mode has specific conditions and display indications.

Various Working Modes Diagrams
Various Working Modes Diagrams (without battery connected and with battery connected).

5.7 Battery Equalization Description

Equalization function is added into the charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize battery periodically.

How to Apply Equalization Function

You must enable battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in device by either one of following methods:

  1. Setting equalization interval in program 35.
  2. Active equalization immediately in program 36.

When to Equalize

In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter Equalize stage.

Equalize charging time and timeout

In Equalize stage, the controller will supply power to charge battery as much as possible until battery voltage raises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.

However, in Equalize stage, when battery equalized time is expired and battery voltage doesn't rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.

5.8 Mains and lithium battery activation function

  1. After 90s of mains power connection to the inverter, the machine is connected to the mains and starts to work.
  2. The inverter is in lithium battery mode (item 05 is LIP or LIL). After the mains is connected, the battery is not connected, and the mains activation function is automatically enabled.

6. Maintenance

6.1 Overview (Anti-Dust Kit)

Every inverter is already installed with an anti-dust kit from the factory. The inverter will automatically detect this kit and activate an internal thermal sensor to adjust the internal temperature. This kit also keeps dust from your inverter and increases product reliability in harsh environments.

6.2 Clearance and Maintenance

Step 1: Please loosen the screw in a counterclockwise direction on the top of the inverter.

Step 2: Then, the dustproof case can be removed, and the air filter foam can be taken out.

Step 3: Clean the air filter foam and dustproof case. After clearance, re-assemble the dust-kit back to the inverter.

NOTICE: The anti-dust kit should be cleaned from dust every one month.

8. Troubleshooting

Problem LCD/LED/Buzzer Explanation / Possible cause What to do
Unit shuts down automatically during startup process.LCD/LEDs and buzzer will be active for 3 seconds and then complete off.The battery voltage is too low (<1.91V/Cell)1. Re-charge battery.
2. Replace battery.
No response after power on.No indication.1. The battery voltage is far too low. (<1.4V/Cell)
2. Internal fuse tripped.
1. Contact repair center for replacing the fuse.
2. Re-charge battery.
3. Replace battery.
Input voltage is displayed as 0 on the LCD and green LED is flashing.Input protector is trippedCheck if AC breaker is tripped and AC wiring is connected well.
Mains exist but the unit works in battery mode.Green LED is flashing.Insufficient quality of AC power. (Shore or Generator)1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS/Appliance)
Green LED is flashing.Set "Solar First" as the priority of output source.Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly.LCD display and LEDs are flashingBattery is disconnected.Check if battery wires are connected well.
Fault code 07Overload error. The inverter is overload 110% and time is up.Reduce the connected load by switching off some equipment.
Fault code 05Output short circuited.Check if wiring is connected well and remove abnormal load.
Fault code 02Temperature of internal converter component is over 120°C. Internal temperature of inverter component is over 100°C.Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Buzzer beeps continuously and red LED is on.Fault code 03Battery is over-charged. The battery voltage is too high.Return to repair center. Check if spec and quantity of batteries are meet requirements.
Fault code 01Fan faultReplace the fan.
Fault code 06/58Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac)1. Reduce the connected load.
2. Return to repair center
Fault code 08/09/53/57Internal components failed.Return to repair center.
Fault code 51Over current or surge.Restart the unit, if the error happens again, please return to repair center.
Fault code 52Bus voltage is too low.
Fault code 55Output voltage is unbalanced.

7. Specifications

Table 1 Line Mode Specifications

INVERTER MODEL 8.2KW 10.2KW
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS); 90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS); 100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)
10.2KW Inverter Charger Specifications
Detailed Inverter Charger specifications for the 10.2KW model.
8.2KW Inverter Charger Specifications
Detailed Inverter Charger specifications for the 8.2KW model.

Table 2 Inverter Mode Specifications

INVERTER MODEL 8.2KW 10.2KW
Rated Output Power8.2KW10.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency50Hz
Peak Efficiency93%
Overload Protection3s@≥150% load; 5s@101%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage48Vdc
Cold Start Voltage46.0Vdc
Low DC Warning Voltage@ load < 50%: 44.0Vdc
@ load ≥ 50%: 42.0Vdc
Low DC Warning Return Voltage@ load < 50%: 45.0Vdc
@ load ≥ 50%: 44.0Vdc
Low DC Cut-off Voltage@ load < 50%: 41.0Vdc
@ load ≥ 50%: 40.0Vdc
High DC Recovery Voltage62Vdc
High DC Cut-off Voltage63Vdc
No Load Power Consumption70W75W

Table 3 Two Load Output Power

INVERTER MODEL 8.2KW 10.2KW
Full Load8200W10200W
Maximum Main Load8200W10200W
Second Load Range1640W~5740W2040W~7140W
Main Load Cut Off Voltage52VDC
Main Load Return Voltage54VDC

Table 4 Charge Mode Specifications

Utility Charging Mode 8.2KW 10.2KW
Charging Algorithm3-Step
AC Charging Current (Max)140Amp
Bulk Charging VoltageFlooded Battery: 58.4
AGM / Gel Battery: 56.4
Floating Charging Voltage54Vdc

MPPT Solar Charging Mode

INVERTER MODEL 8.2KW 10.2KW
Max. PV Array PowerPV1 Channel: 5400WPV1 Channel: 5400W
PV2 Channel: 5400WPV2 Channel: 5400W
IMax.PVPV1 Channel: 18A
PV2 Channel: 18A
Nominal PV Voltage360Vdc
PV Array MPPT Voltage Range90Vdc~450Vdc
Max. PV Array Open Circuit Voltage500Vdc
Max Charging Current (AC charger plus solar charger)160Amp

Table 5 Grid-Tie Operation

INVERTER MODEL 8.2KW 10.2KW
Nominal Output Voltage220/230/240 VAC
Feed-in Grid Voltage Range195~253VAC
Feed-in Grid Frequency Range50±1Hz/60±1Hz
Nominal Output Current35.6A44.3A
Power Factor Range>0.99
Maximum Conversion Efficiency (DC/AC)98%

Table 6 General Specifications

INVERTER MODEL 8.2KW 10.2KW
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm500*390*136mm
Net Weight, kg14.514.7
Product Dimensions and Weight
Product Dimensions and Net Weight for the inverter.

9. Approximate Back-up Time Table

Model Load (W) Backup Time @ 48Vdc 100Ah (min) Backup Time @ 48Vdc 200Ah (min)
8.2KW / 10.2KW5006131288
1000268613
1500158402
2000111271
250090215
320076182
350065141
400050112
450044100
50004090
62003680
72003270
82002860
92002450
102002040

Note:

  1. Backup time depends on the quality of the battery, age of battery and type of battery. Specifications of batteries may vary depending on different manufacturers.
  2. The final interpretation right of this product belongs to the company.

User Tips

  • This is a wide voltage Hybrid Solar inverter. If the Solar Inverter is used without an external battery, the voltage which starts to connect to the solar panel must be above 120V for the inverter to work normally. If used with an external battery, 90V is sufficient for operation.
  • The DAXTROMN Hybrid Solar Inverter is a single-phase unit. It is not designed for 3-phase AC connections.

Warranty and Support

For warranty claims, technical support, or service inquiries, please contact your authorized DAXTROMN dealer or the manufacturer's customer service. Ensure you have your product model and serial number available when contacting support.