1. Introduction
The GEYA GPS8 Series Automatic Transfer Switch (ATS) is a high-performance dual or triple power controller designed to guarantee power continuity for critical loads. Combining rapid switching capabilities with advanced digital protection, this device monitors voltage and current in real-time, automatically transferring the load to a backup power source (such as a generator, inverter, or secondary grid) when the main power fails or becomes unstable. Ideal for residential, commercial, and industrial applications, the GPS8 ensures your equipment remains safe and operational.
The GPS8-17 is a dual power supply automatic transfer switch, 63A AC220V (L1-N1, L2-N2). The GPS8-18 is a three-way power supply automatic transfer switch, 63A AC220V (L1, L2, L3-N).

2. Safety Information
- Qualified Electrician Required: The products must be installed by qualified electricians. All electrical connections shall comply with appropriate safety standards.
- No Isolation Function: This product does not have an isolation function. Always disconnect the superior MCB (Miniature Circuit Breaker) during maintenance to prevent electric shock.
- Neutral Connection: For both GPS8-17 and GPS8-18 models, the neutral (N) poles are straight through to the load end N poles and are not cut off or converted with the switch. This is a critical design aspect for installation.
3. Product Features
- Integrated Protection: Combines 2/3-way automatic power transfer with over/under voltage and overcurrent protection, enhancing load safety and reducing installation costs.
- Real-time Monitoring: Digital display shows voltage and current values for easy observation and maintenance.
- Flexible Settings: Configurable power-on delay, protection delay, transfer delay, and adjustable power priority (no rewiring needed).
- Convenient Control: Panel button with 0.5s long-press anti-misoperation function to turn on/off load power (L line only).
- Flame Retardant Shell: Constructed with flame retardant PA66 material to prevent spontaneous ignition.
- DIN Rail Mounting: Designed for easy installation on a 35MM DIN rail (EN/IEC 60715) with securing clips and tunnel-type wiring ports for secure connections.


4. Specifications
| Parameter | Specification |
|---|---|
| Function | Automatic Transfer Switch with Protection |
| Rated Supply Voltage | AC220V (L1,L2,L3-N) |
| Rated Frequency | 45Hz ~ 65Hz |
| Operation Voltage Range | 80V ~ 400V (L-N) |
| Rated Operational Current | 63A, 80A (AC1) |
| Burden | AC max. 3VA |
| Over Voltage Setting | OFF, 230V ~ 300V (Adjustable) |
| Under Voltage Setting | OFF, 140V ~ 210V (Adjustable) |
| Over/Under Voltage Action Delay | 0.1s ~ 10s |
| Over Current Setting | 1A ~ 63A (or 80A) |
| Over Current Action Delay | 2s ~ 600s |
| Power-up Delay | 2s ~ 600s |
| Reset Time | 2s ~ 900s |
| Switching Time | 0s ~ 900s (Adjustable) |
| Measurement Error | ≤ 1% |
| Electrical Life (AC1) | 1 × 104 |
| Mechanical Life | 1 × 106 |
| Operating Temperature | -20°C ~ +60°C |
| Storage Temperature | -35°C ~ +75°C |
| Mounting | DIN Rail EN/IEC 60715 |
| Protection Degree | IP40 (front panel), IP20 (terminals) |
| Overvoltage Category | III |
| Pollution Degree | 2 |
| Dimensions | 82mm x 72mm x 68mm |
| Weight | 320g |
| Certification | CE |


5. Setup and Installation
Installation must be performed by a qualified electrician in compliance with all local and national electrical codes and safety standards.
5.1 Mounting
The GPS8 series ATS is designed for 35MM DIN rail mounting. Use the securing clips for easy installation.
- Ensure the back panel display is accessible.
- Press the latches on the device.
- Insert the device onto the DIN rail.
- Release the latches to secure the device.


5.2 Wiring
The GPS8-18 model can accept three input power sources. The upper end terminal is connected to the neutral wire of the three-phase power supply. L1, L2, and L3 are connected to the live wires of three separate power supplies. Connect the lower end to the output load.
Important Note on Neutral: For both GPS8-17 and GPS8-18, all neutral (N) poles are straight through to the load end N poles and are not cut off or converted with the switch. This means the neutral line is always connected, and only the live lines are switched.
5.3 Wiring Diagrams
Below are example wiring diagrams for the GPS8-17 (Dual Power) and GPS8-18 (Triple Power) models. These diagrams illustrate power conversion scenarios.


6. Operation
6.1 Panel Overview

- Power Button (
): Used to manually turn on or off the load. Press and hold for 0.5 seconds to activate. - Setting Button (
): Press and hold for 3 seconds to enter the setting mode. After modifying, press and hold for 3 seconds to save. - Up Arrow Button (
): Used to increase the value when setting parameters. - Down Arrow Button (
): Used to reduce the value when setting parameters.
6.2 Power-on and Reset Delay
During power-on or fault reset, the product will display a countdown. Once the countdown ends, the device will enter its normal running state.
6.3 LED Status Indicators
- LED: L1/L2/L3: Indicates if the corresponding phase is selected or not.
- LED: FLT: Indicates voltage fault recovery delay in progress, or if L1, L2, L3 voltages are all faulty, or a contact disconnection fault.
7. Parameter Setting
To enter parameter setting mode, press and hold the 'M' key for 3 seconds. Use the up and down arrow keys to adjust values. Press and hold 'M' for 3 seconds again to save changes and exit, returning to running mode. If no key is operated for 60 seconds, the device will automatically exit setting mode without saving changes.


7.1 Factory Settings
| Parameter | Range | Step value | Factory settings |
|---|---|---|---|
| Over voltage value | OFF, 230V~300V | 1V | 275V |
| Over voltage recovery value | 225V~295V | 1V | 265V |
| Under voltage value | 140V~210V, OFF | 1V | 175V |
| Under voltage recovery value | 145V-215V | 1V | 180V |
| Voltage fault action time | 0.1s~10s | 0.1s | 0.5s |
| Over current value | OFF, 1A~63A | 0.1A | 60A, 80A |
| Over current action delay | 2s~600s | 1s | 5s |
| Power on delay time | 2s~600s | 1s | 5s |
| Reset time | 2s~900s | 1s | 10s |
| Switching time | 0s~900s | — | 0s |
| Fault reset | ON-OFF | — | ON |
| Priority phase | L1-L2-L3-AUTO | — | L1 |
8. Applications
The GEYA GPS8 ATS is suitable for a wide range of applications requiring uninterrupted power supply and protection against voltage and current fluctuations.

9. Troubleshooting
If you encounter issues with your GEYA GPS8 ATS, refer to the following common problems and solutions:
- Slow Switching / Outputs Reboot: If the device exhibits slow switching between lines or causes outputs to reboot, check the configured 'Switching Time' and 'Power-on Delay' parameters. Adjust these settings as needed (refer to Section 7: Parameter Setting).
- Unexpected Neutral Behavior: Remember that the neutral (N) poles are always straight through and not switched. If your setup requires a switched neutral, this device may not be suitable. Ensure your wiring accounts for this design.
- Fault Indication: If the FLT LED is on, check the voltage levels of L1, L2, L3. It may indicate a voltage fault recovery delay, all voltages being faulty, or a contact disconnection fault.

10. User Tips
- Verify Neutral Connection: Always double-check that your neutral wiring is correctly configured, understanding that the N poles are straight through and not switched by the device.
- Parameter Customization: Take advantage of the flexible parameter settings to fine-tune the device's response to your specific power supply conditions and load requirements.
- Professional Installation: For optimal performance and safety, always have the device installed by a certified electrician.
11. Maintenance
Regular maintenance is crucial for the longevity and reliable operation of your ATS. Always ensure power is disconnected before performing any maintenance.
- Disconnect Power: Before any maintenance, always disconnect the superior MCB (Miniature Circuit Breaker) to ensure no power is supplied to the ATS.
- Visual Inspection: Periodically inspect the device for any signs of damage, loose connections, or overheating.
- Cleaning: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning.
12. Disposal
All electrical waste should be disposed of in compliance with current WEEE (Waste Electrical and Electronic Equipment) regulations. Do not dispose of electrical appliances with unsorted municipal waste; use separate collection facilities. Contact your local government for information regarding available collection systems.