DAXTROMN EGH-11KW

Contents

DAXTROMN 11KW Hybrid Solar Inverter User Manual

Model: EGH-11KW | Brand: DAXTROMN

DAXTROMN 11KW Hybrid Solar Inverter front view

Front view of the DAXTROMN 11KW Hybrid Solar Inverter.

1. Introduction

1.1 Purpose

This manual describes the assembly, installation, operation, and troubleshooting of the DAXTROMN EGH-11KW Hybrid Solar Inverter. Please read this manual carefully before installation and operation. Keep this manual for future reference.

1.2 Scope

This manual provides safety and installation guidelines, as well as information on tools and wiring required for the inverter.

1.3 Features

  • Pure sine wave output.
  • Capable of running without a battery.
  • Built-in dual MPPT solar controller with 160A maximum charging current.
  • Configurable input voltage range for home appliances and personal computers via LCD settings.
  • Configurable battery charging current based on applications via LCD settings.
  • Configurable AC/Solar Charger priority via LCD settings.
  • Compatible with mains voltage or generator power.
  • Auto restart while AC is recovering.
  • Overload, over temperature, and short circuit protection.
  • Smart battery charger design for optimized battery performance.
  • Cold start function.
  • Lithium battery activation function by PV or Utility.
  • Compatible with LiFePO4 battery via RS485 communication.
  • Maximum PV Input Voltage: 500Vdc.
  • Detachable dust cover for harsh environments.
  • Optional Wi-Fi remote monitoring (available on specific models).
  • Supports multiple output priorities: SUB (Solar-Utility-Battery), SBU (Solar-Battery-Utility), SUF (Solar-Utility-Feedback).
  • EQ (Equalization) function to optimize battery performance.

1.4 Basic System Architecture

The following illustration shows a basic application for this inverter/charger. A complete running system typically includes the inverter, a power source (Generator or Utility), PV modules (optional), and external battery packs.

Hybrid Power System Diagram showing connections between solar panels, inverter, battery, utility/generator, and home appliances.

Diagram illustrating the components of a hybrid power system with the inverter at its core.

This inverter can power various appliances in home or office environments, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION – To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION – Only qualified personnel can install this device with a battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow the required specifications to select appropriate cable sizes. It is very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts, which could cause an explosion.
  9. Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Refer to the INSTALLATION section of this manual for details.
  10. A fuse is provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  12. NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to a local dealer or service center for maintenance.

3. Installation

3.1 Unpacking and Inspection

Before installation, please inspect the unit. Ensure that nothing inside the package is damaged. You should have received the following items:

  • Inverter Unit x 1
  • User Manual x 1
  • PV Connector x 4
  • Battery Fuse x 1

3.2 Preparation

Before connecting all wirings, remove the bottom cover by unscrewing the four screws.

3.3 Mounting the Unit

Consider the following points when selecting the installation location:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install the inverter at eye level to allow the LCD display to be read easily.
  • The ambient temperature should be between 0°C and 55°C for optimal operation.
  • The recommended installation position is vertically on the wall.
  • Ensure sufficient heat dissipation and space for wiring by maintaining clearances as shown in the diagram.
Inverter mounting dimensions and recommended clearances for heat dissipation.

Diagram showing recommended mounting dimensions and clearances (20cm side, 50cm top/bottom).

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

3.4 Battery Connection

CAUTION: For safety and regulation compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. Over-current protection is always required.

WARNING! All wiring must be performed by qualified personnel.

WARNING! It is very important for system safety and efficient operation to use appropriate cables for battery connection. To reduce the risk of injury, use the proper recommended cable.

ModelMaximum AmperageBattery CapacityWire SizeCable mm²Terminal Size (mm) L x W x DTorque Value
8.5KW180A400AH4AWG*22537 x 22 x 8.410~12 Nm
11.0KW220A600AH2AWG*23837 x 22 x 8.410~12 Nm

Battery Connection Steps:

  1. Make positive and negative cables based on the recommended terminal size.
  2. Connect all battery packs as units require. It is suggested to use the recommended battery capacity.
  3. Insert the battery cable flatly into the battery connector of the inverter and ensure the bolts are tightened with a torque of 10-12Nm. Ensure polarity at both the battery and the inverter/charger is correctly connected, and battery cables are tightly screwed to the battery connector.

WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.

CAUTION!! Do not place anything between the flat part of the inverter terminal. Otherwise, overheating may occur.

CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected tightly.

CAUTION!! Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) is connected to negative (-).

3.5 AC Input/Output Connection

CAUTION!! Before connecting to an AC input power source, install a separate AC breaker between the inverter and the AC input power source. This ensures the inverter can be securely disconnected during maintenance and fully protected from overcurrent of AC input. The recommended specification for the AC breaker is 63A.

CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by qualified personnel.

WARNING! It is very important for system safety and efficient operation to use appropriate cables for AC input connection. To reduce the risk of injury, use the proper recommended cable size.

Suggested Cable Requirement for AC Wires:

ModelGaugeTorque Value
All Models6 AWG1.2~1.4Nm

AC Input/Output Connection Steps:

  1. Before making AC input/output connections, ensure the DC protector or disconnector is open.
  2. Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3mm.
  3. Insert AC input wires according to the polarities indicated on the terminal block and tighten the terminal screws. Ensure the PE protective conductor (Ground, yellow-green) is connected first.
    • Ground (yellow-green)
    • L (brown or black)
    • N (blue)
  4. Then, insert AC output wires according to the polarities indicated on the terminal block and tighten the terminal screws. Ensure the PE protective conductor is connected first.
    • Ground (yellow-green)
    • L (brown or black)
    • N (blue)
  5. Make sure the wires are securely connected.

WARNING: Ensure the AC power source is disconnected before attempting to hardwire it to the unit.

CAUTION: Important! Ensure AC wires are connected with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuiting when these inverters are operated in parallel.

CAUTION: Appliances such as air conditioners require 2-3 minutes to restart to balance refrigerant gas. If a power shortage occurs and recovers quickly, it can damage connected appliances. Check if your appliance has a time-delay function. Otherwise, the inverter/charger may trigger an overload fault to protect the appliance, but internal damage can still occur.

3.6 PV Connection

CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.

WARNING! All wiring must be performed by qualified personnel.

WARNING! It is very important for system safety and efficient operation to use appropriate cables for PV module connection. To reduce the risk of injury, use the proper recommended cable size.

Suggested Cable Requirement for PV Wires:

ModelTypical AmperageCable SizeTorque
All Models18A*210 AWG1.4~1.6 Nm

PV Module Selection:

When selecting PV modules, consider the following parameters:

  • Open Circuit Voltage (Voc) of PV modules must not exceed the maximum PV array open circuit voltage of the inverter (500Vdc).
  • Open Circuit Voltage (Voc) of PV modules should be higher than the minimum battery voltage.
PV Connection diagram showing solar panels connected to the inverter.

Diagram illustrating the connection of solar panels to the inverter.

Table of PV module connection specifications including amperage, cable size, and torque.

Table detailing PV module connection specifications and recommended cable sizes.

PV Module Wire Connection Steps:

  1. Remove insulation sleeve 10mm for positive and negative conductors.
  2. Check the correct polarity of the connection cable from PV modules and PV input connectors. Connect the positive pole (+) of the connection cable to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection cable to the negative pole (-) of the PV input connector.
  3. Make sure the wires are securely connected.

3.7 Final Assembly

After connecting all wirings, replace the bottom cover by screwing in the two screws.

3.8 Dry Contact Signal

There is one dry contact (3A/250VAC) available on the rear panel. This can be used to deliver a signal to an external device when the battery voltage reaches a warning level (Program 16 of F0 set as "Model1"). When Program 16 of F0 is set as "Model2" and the unit is working in battery mode, it can trigger the grounding box to connect neutral and grounding of AC output.

Dry Contact Port (NC C NO) - Model1:

Unit StatusConditionNC & CNO & C
Power OffUnit is off and no output is powered.CloseOpen
Power OnOutput is powered from Utility.OpenClose
Power OnOutput is powered from Battery or Solar. (Battery voltage or Soc < Low DC warning voltage or Soc)OpenClose
Power OnOutput is powered from Battery or Solar. (Battery voltage or Soc > setting value program 5 of F2 or battery charging reaches floating stage)CloseOpen
Power OnOutput is powered from Battery or Solar. (Battery voltage < Setting value program 5 of F2)OpenClose
Power OnOutput is powered from Battery or Solar. (Battery voltage > setting value program 6 of F2 or battery charging reaches floating stage)CloseOpen

Dry Contact Port (NC C NO) - Model2:

Unit StatusConditionNC & CNO & C
Power OffUnit is off and no output is powered.CloseOpen
Power OnUnit works in standby mode, line mode or fault modeOpenOpen
Power OnUnit works in battery mode or power saving modeCloseOpen

4. Operation

4.1 Power ON/OFF

Once the unit is properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

4.2 Operation and Display Panel

The operation and display panel, located on the front panel of the inverter, includes three indicators, four function keys, and an LCD display, providing operating status and input/output power information.

Product Overview diagram showing LCD display, status indicators, and function buttons.

Diagram of the inverter's front panel, highlighting the LCD display, LED indicators, and function buttons.

LED Indicator Messages:

LED IndicatorColorStatusMessages
AC / INVGreenSolid OnOutput is powered by utility in Line mode.
AC / INVGreenFlashingOutput is powered by battery or PV in battery mode.
CHGGreenSolid OnBattery is fully charged.
CHGGreenFlashingBattery is charging.
FAULTRedSolid OnFault occurs in the inverter.
FAULTRedFlashingWarning condition occurs in the inverter.

Function Keys:

Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

4.3 LCD Display

The LCD display information can be switched by pressing the “UP” or “DOWN” key. All information can be shown in areas 1, 2, or 3 of the LCD.

LCD display showing various parameters like input/output voltage, frequency, power, and battery status.

Example of the LCD display showing operational parameters.

4.4 LCD Setting

  1. Press and hold the ENTER button for 3 seconds to enter setting groups mode.
  2. Press "UP" or "DOWN" to select setting groups (F0/F1/F2/F3/F4). Press “ENTER” to confirm or ESC to exit.
  3. Press "ENTER" to confirm the selection groups or ESC to return to selection groups or exit.

F0: Setting General Parameters

ProgramDescriptionSelectable OptionDetails
01AC input voltage rangeAPL (Appliances)
UPS
GNE (Generator)
APL: 90-280VAC
UPS: 170-280VAC
GNE: 170-280VAC (compatible with generators, but output may be unstable)
02Power saving mode enable/disableSdS (Disable)
SEn (Enable)
Disable: Inverter output unaffected by low/high load.
Enable: Inverter output turns off if connected load is very low or not detected.
03Overload bypassbPd (Disable)
bPE (Enable)
Disable: Inverter transfers to line mode if overload occurs in battery mode.
Enable: Inverter transfers to line mode if overload occurs in battery mode.
04Auto restart when overload occursLFd (Disable)
LFE (Enable)
Enable: Inverter will automatically restart after an overload event.
05Auto restart when over temperature occursEFd (Disable)
EFE (Enable)
Enable: Inverter will automatically restart after an over temperature event.
06Auto bypassnOL (Manual)
Ato (Auto)
Manual: Inverter bypasses manually.
Auto: Inverter automatically bypasses if mains power is normal, even if the switch is off.
07Auto return to default display screenESP (Return to default)
HEP (Stay at latest)
Return to default: Returns to default display (Input/Output voltage) after 1 minute of no button press.
Stay at latest: Display stays on the last screen.
08Backlight controlLon (On)
LoF (Off)
On: Backlight is always on.
Off: Backlight is off.
09Buzzer modend1 (Mute)
nd2 (Input source change/warning/fault)
nd3 (Warning/fault)
nd4 (Fault)
Mute: Buzzer is silent.
Input source change/warning/fault: Buzzer sounds for these events.
Warning/fault: Buzzer sounds for these events.
Fault: Buzzer sounds only for faults.
10Modbus ID Setting001~247Modbus ID setting range.
16Dry contact modeModel1
Model2
Model1: Delivers signal when battery voltage reaches warning level.
Model2: Connects neutral and grounding of AC output when inverter is in battery mode (with external grounding box).

F1: Setting AC Output Parameters

ProgramDescriptionSelectable OptionDetails
01Output source prioritySUb (Solar->Utility->Battery)
Sbu (Solar->Battery->Utility)
SUF (Solar->Utility->Battery with grid feedback)
SUb: Solar charges first, then powers loads. Utility supplies power if solar is insufficient.
Sbu: Solar provides power first. Battery supplies power if solar is insufficient. Utility supplies power only when battery voltage drops.
SUF: Solar powers loads and charges battery. Excess solar can feedback to grid. Utility supplies power if solar is insufficient.
03Output voltage220V
230V (default)
240V
Sets the AC output voltage.
04Output frequency050 (50Hz default)
060 (60Hz)
Sets the AC output frequency.
06Slave output source priorityOFF (Turn off)
SUb
Sbu
Sets a secondary output source priority for a specific period. Functions similar to program 01.
07Start timer setting for slave output source priority (Hours)00-23Sets the hour for the slave priority to start.
08Start timer setting for slave output source priority (Minutes)00-59Sets the minute for the slave priority to start.
09End timer setting for slave output source priority (Hours)00-23Sets the hour for the slave priority to end.
10End timer setting for slave output source priority (Minutes)00-59Sets the minute for the slave priority to end.

F2: Setting Battery Parameters

ProgramDescriptionSelectable OptionDetails
01Battery typeAGM (default)
FLd (Flooded)
USE (User-Defined)
L.2 (PYLON US2000)
L.4 (Standard Protocol 2)
L.b (Lithium Battery)
Sets the battery type. User-Defined allows custom charge/cut-off voltages. L.2 for PYLON US2000. L.b for generic lithium batteries without communication.
02Charger source prioritySof (Solar first)
SOU (Solar and Utility default)
OSo (Only Solar)
Sot (Solar residual)
Sof: Solar charges first, Utility only if solar is unavailable.
SOU: Solar and Utility charge simultaneously.
OSo: Only solar charges, regardless of Utility availability.
Sot: Solar powers loads first, residual charges battery.
03Bulk charging voltage (C.V voltage)56.4V (default)If User-Defined or LIB is selected in program 01, range is from program 04 of F2 to 62.0V.
04Floating charging voltage54.0V (default)If User-Defined or LIB is selected in program 01, range is from 48.0V to program 03 of F2.
05Setting voltage or Soc point back to utility source (SBU priority)Lithium battery without communication: 46V
Lithium battery with communication: 50%
Battery fully charged: FUL (default)
Range 44.0V-57.2V (voltage) or 5%-50% (Soc). Must be less than program 06 and more than program 08.
06Setting voltage point back to battery mode (SBU priority)FUL (Battery fully charged default)
95% (Default)
Range 48V to program 03 of F2 (voltage) or 60%-100% (Soc). Must be more than program 05.
08Low DC cut-off voltage or Soc42.0V (default for User-Defined/LIB)
20% (default for LIx with communication)
Range 40.0V-54.0V (voltage) or 3%-30% (Soc). Must be less than program 05.
09Maximum charging current (AC+PV)80A (default)8.5KW Model: 10-140A. 11.0KW Model: 10-160A. Must be ≥ AC charging current (program 10).
10Maximum utility charging current60A (default)Range 5-120A. Must be less than program 09.
11Slave charger source priorityOFF (Turn off)
Sof
SNU
OSo
Sot
Functions similar to program 02 of F2 group.
12Start timer setting for slave charger source priority (Hours)00-23Sets the hour for the slave priority to start.
13Start timer setting for slave charger source priority (Minutes)00-59Sets the minute for the slave priority to start.
14End timer setting for slave charger source priority (Hours)00-23Sets the hour for the slave priority to end.
15End timer setting for slave charger source priority (Minutes)00-59Sets the minute for the slave priority to end.
16Bulk charging time (C.V stage)AUE (Automatically)
005-900 min
Sets the bulk charging time. Increment of 5 min.
17Battery equalizationEEN (Enable)
EdS (Disable)
Enable/Disable battery equalization (if User-Defined or Flooded battery type selected).
18Battery equalization voltage58.4V (default)Range 48V-62V. Increment of 0.1V. Must be greater than floating recharge value.
19Battery equalized time60 min (default)Range 0-900 min. Increment of 5 min.
20Battery equalized timeout120 min (default)Range 0-900 min. Increment of 5 min.
21Equalization interval30 days (default)Range 1-90 days. Increment of 1 day.
22Equalization activated immediatelyAEn (Enable)
AdS (Disable)
Enable: Activates battery equalization immediately. Disable: Cancels equalization until next scheduled time.
23Manual activate lithium battery settingACE (Active)
nL (Disable)
If LIx battery type is selected and not detected, this activates the lithium battery.
24Automatic activation for lithium batteryAto (Auto)
OFF (Disable)
If LIx battery type is selected and not detected, this automatically activates the lithium battery (requires unit restart).
25Max battery discharge current setting50-500AIf battery discharge current exceeds this value, the unit stops discharging and goes to bypass/standby mode.

F3: Setting Time Parameters

ProgramDescriptionSelectable OptionDetails
01Time setting - Year00-99Sets the year (e.g., 24 for 2024).
02Time setting - Month01-12Sets the month.
03Time setting - Day01-31Sets the day.
04Time setting - Hour00-23Sets the hour (24-hour format).
05Time setting - Minute00-59Sets the minute.
06Time setting - Second00-59Sets the second.

F4: Setting Systems Parameters

ProgramDescriptionSelectable OptionDetails
01Reset all stored data of PV generated power and output load energyno (Reserve data)
YES (Reset data)
Resets the accumulated PV generated power and output load energy data.

4.5 Fault Reference Code

Fault codes consist of a group code and a number (e.g., A0). Group codes indicate the fault category:

  • A: Inverter group fault code
  • B: Battery group fault code
  • C: PV group fault code
  • D: Output group fault code
  • E: Parallel group fault code
  • F: Other group fault code
  • G: Grid group fault code
Fault CodeFault Event
A0Output short circuited.
A1Output voltage is too high.
A2Over current or surge.
A3Over DC voltage in AC output.
A4Inverter current offset is too high.
A5Output voltage is too low.
A6Inverter negative power.
B0Battery voltage is too high.
B1DCDC over current.
B2DC/DC current offset is too high.
C0PV over current.
C1PV over voltage.
C2PV1 current offset is too high.
C3PV2 current offset is too high.
D0Overload time out.
D1Op current offset is too high.
F0Over temperature of inverter module.
F1Over temperature of PV module.
F2Over temperature of DCDC module.

4.6 Warning Indicator

Warning codes consist of a group code and a number (e.g., 0B). Group codes indicate the warning category:

  • A: Inverter group fault code
  • B: Battery group fault code
  • C: PV group fault code
  • D: Output group fault code
  • E: Parallel group fault code
  • F: Other group fault code
  • G: Grid group fault code
Warning CodeWarning EventAudible Alarm
0BBattery lowBeep once every second
1BBattery is not connectedNone
2BBattery equalizationNone
3BBattery low and it isn't up to the setting value of program 06 of F2 groupBeep twice every 3 seconds
4BLithium battery communication is abnormalBeep once every 0.5 second
5BBattery discharge overcurrentNone
1CPV energy is too weakBeep twice every 3 seconds
0DOverloadBeep once every 0.5 second
1DOutput power deratingBeep twice every 3 seconds
0FTemperature is too HighBeep three times every second

5. Battery Equalization

The equalization function in the charge controller reverses the buildup of negative chemical effects like stratification (uneven acid concentration) and helps remove sulfate crystals from battery plates. This process is crucial for maintaining battery capacity and is recommended periodically.

5.1 How to Apply Equalization Function

To use this function, you must first enable battery equalization in LCD setting program 17 (F2). Then, you can apply it using one of the following methods:

  1. Set the equalization interval in program 21 (F2).
  2. Activate equalization immediately in program 22 (F2).

5.2 When to Equalize

The controller enters the Equalize stage when the set equalization interval is reached during the float stage, or when equalization is actively initiated.

Battery equalization voltage and float voltage diagram.

Diagram showing the battery equalization process over time, including bulk, absorption, float, and equalize stages.

5.3 Equalize Charging Time and Timeout

During the Equalize stage, the controller supplies power to charge the battery until its voltage reaches the battery equalization voltage. It then applies constant-voltage regulation to maintain this voltage. The battery remains in the Equalize stage until the set battery equalized time is reached.

If the battery equalized time expires and the battery voltage has not reached the equalization voltage point, the charge controller will extend the equalized time until the battery voltage achieves the equalization voltage. If the battery voltage is still lower than the equalization voltage when the battery equalized timeout setting is over, the charge controller will stop equalization and return to the float stage.

6. Setting for Lithium Battery

6.1 Lithium Battery Connection

If using a lithium battery with the inverter, ensure it is a compatible model. There are two connectors on the lithium battery: an RS485 port for the BMS and a power cable.

Lithium Battery Connection Steps:

  1. Assemble the battery terminal based on recommended battery cable and terminal size (similar to Lead-acid battery connection).
  2. Connect the RS485 port of the battery to the BMS (RS485) communication port of the inverter.

6.2 Lithium Battery Communication and Setting

If using a lithium battery, connect the BMS communication cable between the battery and the inverter. This cable facilitates information and signal exchange, including:

  • Re-configuring charging voltage, charging current, and battery discharge cut-off voltage according to the lithium battery parameters.
  • Inverter starting or stopping charging based on the lithium battery status.

Connecting RS485 of Battery to RS485 Communication Port of Inverter:

Ensure the lithium battery RS485 port connects to the inverter is Pin to Pin. The communication cable is included in the package. The inverter RS485 port pin assignment is as follows:

Pin NumberRS485 Port
PIN1RS485-B
PIN2RS485-A
PIN7RS485-A
PIN8RS485-B

6.3 Setting for PYLON US2000 Lithium Battery

PYLONTECH US2000 Lithium Battery Setting:

The Dip Switches (4 switches) set the baud rate and battery group address. "OFF" is 0, "ON" is 1.

  • Dip 1 "ON" for baud rate 9600.
  • Dip 2, 3, and 4 are reserved for battery group address.
  • Dip switch 2, 3, and 4 on the master battery (first battery) set or change the group address.

NOTE: "1" is the upper position and "0" is the bottom position.

Installation Process:

  1. Use the RS485 cable to connect the inverter and the Lithium battery.
  2. Switch on the Lithium battery.
  3. Press and hold for more than three seconds to start the Lithium battery; power output will be ready.
  4. Turn on the inverter.
  5. Ensure to select battery type as “L.2” in LCD program 01 (F2). If communication between the inverter and battery is successful, the battery icon "Li" on the LCD display will light up.

6.4 Setting for Lithium Battery Without Communication

This method is for lithium battery applications without BMS communication. Follow these steps:

  • Set battery type as "L.b" in program 01 (F2).
  1. Before setting, obtain the battery BMS specifications: Max charging voltage, Max charging current, Discharging protection voltage.
  2. Set battery type as "L.b" in program 01 (F2).
  3. Set C.V voltage as Max charging voltage of BMS - 0.5V in program 03 (F2).
  4. Set floating charging voltage as C.V voltage in program 04 (F2).
  5. Set Low DC cut-off voltage ≥ discharging protection voltage of BMS + 3V.
  6. Set Max charging current in program 09 (F2) which must be less than the Max charging current of BMS.
  7. Set voltage point back to utility source when selecting “SBU priority” in program 05 (F2). The setting value must be ≥ Low DC cut-off voltage + 2V, otherwise the inverter will show a warning for low battery voltage.

Remark:

  • It is recommended to finish setting without turning on the inverter (just let the LCD show, no output).
  • After finishing settings, restart the inverter.

7. Specifications

7.1 Table 1 Line Mode Specifications

INVERTER MODEL8.5KW11.0KW
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS); 90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS); 100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionBattery mode: Electronic Circuits
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)
Output PowerOutput Power

Output power derating: When AC input voltage drops to 95V or 170V, the output power will be derated.

Output power derating: When battery voltage drops to 50.5V (8.5K) / 55.0V (11K), the output power will be derated.

7.2 Table 2 Inverter Mode Specifications

INVERTER MODEL8.5KW11.0KW
Rated Output Power8.5KVA/8.5KW11.0KVA/11.0KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency60Hz or 50Hz
Peak Efficiency94%
Overload Protection5.5s@≥140% load; 10.5s@100%~140% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage48Vdc
Cold Start Voltage46.0Vdc
Low DC Warning Voltage (AGM and Flooded) @ load < 20%44.0Vdc
Low DC Warning Voltage (AGM and Flooded) @ 20% ≤ load < 50%42.8Vdc
Low DC Warning Voltage (AGM and Flooded) @ load ≥ 50%40.4Vdc
Low DC Warning Return Voltage (AGM and Flooded) @ load < 20%46.0Vdc
Low DC Warning Return Voltage (AGM and Flooded) @ 20% ≤ load < 50%44.8Vdc
Low DC Warning Return Voltage (AGM and Flooded) @ load ≥ 50%42.4Vdc
Low DC Cut-off Voltage (AGM and Flooded) @ load < 20%42.0Vdc
Low DC Cut-off Voltage (AGM and Flooded) @ 20% ≤ load < 50%40.8Vdc
Low DC Cut-off Voltage (AGM and Flooded) @ load ≥ 50%38.4Vdc

7.3 Table 3 Charge Mode Specifications

Utility Charging Mode8.5KW11.0KW
Charging Current (Max) (AC+PV)140Amp160Amp
AC Charging Current (Max)120Amp (@ VI/P=230Vac)
Bulk Charging Voltage (Flooded Battery)58.4Vdc
Bulk Charging Voltage (AGM / Gel Battery)56.4Vdc
Floating Charging Voltage54Vdc
Overcharge Protection63Vdc
Charging Algorithm3-Step

Charging Curve: Illustrates the 3-step charging process (Bulk, Absorption, Maintenance).

Solar Input Specifications:

INVERTER MODEL8.5KW11.0KW
Rated Power5000W*25500W*2
Max. PV Array Open Circuit Voltage500Vdc
PV Array MPPT Voltage Range60Vdc~500Vdc
Max. MPPT Charge Current140A160A
Max. Input Current18A*218A*2

7.4 Table 4 General Specifications

INVERTER MODEL8.5KW11.0KW
Safety CertificationCE
Operating Temperature Range-10°C to 55°C
Storage temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension(D*W*H), mm540x403x122
Net Weight, kg14.414.8

8. Troubleshooting

ProblemLCD/LED/BuzzerExplanation / Possible CauseWhat to do
Unit shuts down automatically during startup process.LCD/LEDs and buzzer active for 3 seconds, then off.The battery voltage is too low.1. Re-charge battery.
2. Replace battery.
No response after power on.No indication.1. The battery voltage is far too low.
2. Battery polarity is connected reversed.
1. Check if batteries and wiring are connected well.
2. Re-charge battery.
3. Replace battery.
Input voltage displayed as 0 on LCD, green LED flashing.Input protector is tripped.Check if AC breaker is tripped and AC wiring is connected well.
Mains exist but the unit works in battery mode.Green LED is flashing.Insufficient quality of AC power (Shore or Generator).1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct (UPS/Appliance).
Green LED is flashing.Set "SBU" or "SUB" as the priority of output source.Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly.LCD display and LEDs are flashing.Battery is disconnected.Check if battery wires are connected well.
Fault code D0Overload error. The inverter is overloaded 100% and time is up.Reduce the connected load by switching off some equipment.
Fault code A2Output short circuited.Check if wiring is connected well and remove abnormal load.
Fault code F2Internal temperature of inverter component is over 100°C.Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Buzzer beeps continuously and red LED is on.Fault code B0Battery is over-charged.Return to repair center.
Fault code B0The battery voltage is too high.Check if spec and quantity of batteries meet requirements.
Fault code A1/A5Output abnormal (Inverter voltage below 190Vac or higher than 260Vac).1. Reduce the connected load.
2. Return to repair center.
Fault code F3/F4Internal components failed.Return to repair center.
Fault code A2Over current or surge.Restart the unit; if the error happens again, return to repair center.
Fault code F5Bus voltage is too low.Restart the unit; if the error happens again, return to repair center.
Fault code A3Output voltage is unbalanced.Restart the unit; if the error happens again, return to repair center.
Another fault code.If the wires are connected well, return to repair center.

9. User Tips

  • Troubleshooting First Steps: The vast majority of "malfunctions" are caused by incorrect wiring or parameter settings. Before contacting support, always double-check all wiring connections and review your LCD parameter settings against the manual.
  • Professional Installation: In some European countries, the installation of photovoltaic equipment must be carried out by a licensed electrician. We strongly recommend contacting a local professional for assistance to ensure safe and compliant installation.
  • Malfunction Reporting: If you encounter any problems, please provide a video/photo of the malfunction to support for remote troubleshooting assistance.

10. Support

10.1 Warranty Information

This product comes with a one-year official warranty. For product quality issues (non-human-caused damage), the manufacturer supports free replacement parts or provides repair technical guidance.

10.2 Contact and Technical Assistance

If you encounter any problems or require technical assistance, please contact the seller or manufacturer directly. Providing a video or photo of the malfunction can significantly aid in remote troubleshooting by engineers.

Important Note: Due to the large size and weight of the inverter, international return shipping can be expensive and time-consuming. It is highly recommended to utilize remote troubleshooting and repair guidance whenever possible.

10.3 Additional Resources