Contents

STEPPERONLINE DSY Series 400W RS485 DC Servo Motor Kit User Manual

Model: DSY-RS400L2A2-M17S (Motor) & DSY-400RS (Driver)

This manual provides detailed instructions for the installation, operation, maintenance, and troubleshooting of your STEPPERONLINE DSY Series 400W RS485 DC Servo Motor Kit.

1. Introduction

The STEPPERONLINE DSY Series DC servo system is a state-of-the-art solution consisting of a 48VDC 400W servo motor and a 24-70VDC 400W servo driver. This kit is engineered for precision and performance, featuring a servo motor with a rated torque of 1.27Nm, a peak torque of 3.81Nm, and a rated speed of 3000rpm.

It comes standard with a 17-bit single-turn magnetic incremental encoder and adopts a high power density design, allowing it to deliver strong power in a compact size, achieving 3 times the instantaneous overload. The new magnetic circuit design reduces torque ripple, minimizing vibration during operation and providing smoother torque output.

This kit is versatile and can be widely used in various applications such as mobile robots (AMR, AGV), service robots, special robots, logistics warehousing and sorting, medical equipment, instruments, and light textile industries, especially where voltage and size constraints are important.

1.1 Kit Contents

The DSY Series 400W RS485 DC Servo Motor Kit typically includes the following components:

  • 1 x DSY-400RS: 400W Pulse/RS485 DC Servo Motor Driver
  • 1 x DSY60-400L2A2M17S: 400W 48V DC Servo Motor 3000rpm 1.27Nm 17-Bit Encoder IP65
  • 1 x P1-DS-03P15M: 3.0m Motor Cable
  • 1 x E2-DS-03AM: 3.0m Encoder Cable
  • 1 x RS232-5: 1.0m Debugging Cable

Video: Overview of the STEPPERONLINE DSY Series 400W RS485 DC Servo Motor Kit components.

2. Specifications

2.1 DSY-400RS Servo Driver Specifications

ParameterValue
Part NumberDSY-400RS
Continuous Output Current15.0A
Maximum Output Current48.0A
Power Supply Input24-70VDC
Rated Power400W
Dimension (L*W*H)141mm * 75.5mm * 25.4mm
Control MethodMOSFET SVPWM Space vector pulse width modulation algorithm
Encoder Interface17-bit magnetic encoder; 23-bit optical encoder
Network CommunicationRS485 (Modbus Communication), RS-232 (PC Debugging)
IP Grade / ContaminationIP20 / Contamination Rating 2
Operation Temperature0℃~55℃
Storage Temperature-40℃~80℃
Humidity0~90% RH (No dew environment)
Elevation≤1000m
Vibration/Strike5.88m/s² / 19.6m/s²

2.2 DSY60-400L2A2M17S Servo Motor Specifications

ParameterValue
Part NumberDSY60-400L2A2M17S
Rated Power400W (0.4KW)
Rated Voltage48VDC
Rated Torque1.27Nm
Peak Torque3.81Nm
Rated Current10.2A
Rated Speed3000rpm
Inertia0.49kg*m²*10⁻⁴
Encoder17-bit single-turn magnetic incremental encoder
Poles10
IP RatingIP65
Cable Length3m (optional lengths are 1.5m and 5m)

3. Setup and Installation

3.1 Servo Drive Dimensions (DSY-400RS)

The dimensions for the DSY-400RS servo drive are shown below. Ensure adequate space for installation and ventilation.

DSY-400RS Servo Drive Dimensions

Figure 3.1: DSY-400RS Servo Drive Dimensions. The drive measures 141mm in length, 75.5mm in width, and 25.4mm in height. Mounting holes are indicated.

3.2 Servo Drive Installation

For optimal performance and heat dissipation, install the servo drive vertically as shown in the diagram. Maintain minimum clearances for proper airflow.

Servo Drive Vertical Installation

Figure 3.2: Recommended vertical installation for the servo drive. Ensure a minimum clearance of ≥50mm above and below, and ≥10mm between drives for proper air circulation.

3.3 System Structure Diagram

The following diagram illustrates the overall system connections for the servo drive and motor.

Servo System Structure Diagram

Figure 3.3: System structure diagram showing connections for DC power, encoder, motor power, pulse signal output device, serial port line, and RS485 communication devices.

3.4 Main Circuit Terminal Name and Function

Refer to the table below for the names, functions, and specifications of the main circuit terminals.

No.NameDescription
1DC+, DC-Input control circuit power according to specifications
2RB+, RB- (Regenerative Resistor Terminal)External Brake Resistor Connection Port
3Motor power cableConnect servo motor three-phase and ground wire
5Communication portConnected to PC via RS232 to monitor the drive, test and change parameters, etc.
6Communication controlConnected to RS485 communication device
7Control portConnect to host controller for IO signal control
8Encoder feedback portConnected to the motor encoder cable

3.5 Power Cable Connector

The motor power line pins are defined as follows. The structure diagram shows the connection types.

Conn.1 PinPin DefinitionConn.2 PinPin Color
1UURed
2VVYellow
3WWBlue
4PEPEYellow/Green
Power Cable Structure Diagram

Figure 3.4: Power cable structure diagram showing AnPu Connector Cable (P1) and Circular Connector Cable (P2) with pinouts.

3.6 Encoder Cable Connector

The motor encoder line pins are defined as follows. The structure diagram shows the connection types.

Conn.1 PinPin DefinitionConn.2 PinPin Color
75V1Blue
80V2Orange
3SD+5Brown
4SD-6Green
ShellPEShell/
Battery/3BAT+
4BAT-
Encoder Cable Structure Diagram

Figure 3.5: Encoder cable structure diagram (L=1.5m, 3m, 5m).

3.7 DIDO Port Wiring

The DIDO (Digital Input/Digital Output) port provides various control signals. Ensure correct wiring based on your host computer's output type.

PINDefinitionFunction
1BRK+Brake output
2BRK-Brake output
3DI1Digital input 1
4DI2Digital input 2
5DI3Digital input 3
6ICOMDI power supply input port, 24V
7DO+Digital output 1
8DO-Digital output 1
9PULSE+Pulse signal input (5V~24V, compatible)
10PULSE-Pulse signal input (5V~24V, compatible)
11SIGH+Direction signal input (5V~24V, compatible)
12SIGH-Direction signal input (5V~24V, compatible)

3.7.1 Digital Input Circuit (DI1-DI3)

The digital input circuit can be configured for different host computer output types:

  • When the host computer is relay output:
    Digital Input Relay Output Wiring

    Figure 3.6: Digital input wiring for relay output.

  • When the host computer is open collector output (NPN input):
    Digital Input NPN Output Wiring

    Figure 3.7: Digital input wiring for NPN open collector output.

  • When the host computer is open collector output (PNP input):
    Digital Input PNP Output Wiring

    Figure 3.8: Digital input wiring for PNP open collector output.

Note: The mixing of NPN and PNP inputs is not supported.

3.7.2 Digital Output Circuit (DO1)

The digital output circuit can be configured for different host computer input types:

  • When the host computer is a relay input:
    Digital Output Relay Input Wiring

    Figure 3.9: Digital output wiring for relay input. Ensure to connect a freewheeling diode in the correct direction to prevent damage.

  • When the host computer is optocoupler input:
    Digital Output Optocoupler Input Wiring

    Figure 3.10: Digital output wiring for optocoupler input. A current limiting resistor is required. Max voltage: DC30V, Max current: DC50mA.

3.8 Communication Signal Port (RS485 & RS232)

The DSY-400RS driver supports RS485 (Modbus Communication) via CN1/CN2 and RS232 for PC debugging via CN3.

3.8.1 CN1/CN2 Bus Port (RS485)

CN1 and CN2 are the 485 communication connectors. The pin definitions are:

PinSignal NameDirectionTerminal
1RS485+Output
2RS485-Output
3GNDOutput
4-8-unused

3.8.2 CN3 Post Computer Communication Port (RS232)

CN3 is used for RS232 communication to debug the servo drive with a PC. The pin definitions are:

PinDefinitionFunctionTerminal
1-2-
3RS232-TXDRS232 communication port
4-5GND
6RS232-RXDRS232 communication port
7-8-
ShellPEShielding

3.9 RS485 Wiring Instructions and EMC Precautions

For multi-computer communication, the RS485 bus should use a hand-in-hand structure. The branch length between the bus and the node should not exceed 3m.

RS485 Network Cable Wiring

Figure 3.11: Network plug 568B serial connection method for RS485. White and Green (Pin 3) for RS485_GND, White and Orange (Pin 1) for RS485+, Orange (Pin 2) for RS485-.

RS485 Multi-computer Communication Scheme

Figure 3.12: Recommended hand-in-hand structure for RS485 multi-computer communication.

3.9.1 Ground PE Connection Requirements

  • The ground cable must be thicker than AWG12.
  • The PE connects to the ground terminal of a node or the ground bar of the cabinet where the node is located.
  • The distance between the PE and the bus should be greater than 5cm.
Ground PE Connection Diagram

Figure 3.13: Ground PE connection diagram, showing PE connections for external RS485 nodes and the drive.

3.9.2 Cable Layout Requirements

  • Keep the RS485 bus at least 1cm away from the metal backplane of the control cabinet.
  • Keep the RS485 bus at least 5cm away from the ground cable.
  • Maintain a distance of at least 20cm between the RS485 bus and strong current cables.
  • The distance between the RS485 bus and the motor power lines (U, V, W) should be at least 50cm.

3.9.3 Driver Interference Processing

To suppress interference from the driver, consider the following:

  • Add a filter magnetic ring at the power code position (position 1). Pass three UVW wires (excluding ground wire PE) through the magnetic ring three times.
  • Wrap a magnetic ring at position 2, and pass the power cable (excluding ground PE) through it three times.
Driver Interference Suppression Diagram

Figure 3.14: Diagram showing recommended magnetic loop placement for interference suppression on power and motor cables.

4. Operation

4.1 Basic Control Flow

Follow these steps for basic control and initial setup:

  1. Check before running: Verify wiring, condition, and machine.
  2. Power on: Turn on control circuit and main circuit power supply. Ensure servo enable is invalid.
  3. JOG operation: Perform PC JOG to confirm normal motor rotation without abnormal vibration or sound.
  4. Parameter set: Set common parameters and relevant parameters for the chosen control mode.
  5. Servo run: First run at low speed, set relevant parameters for the desired goal, and debug the driver.
  6. Servo stop: Disable servo, trigger servo failure shutdown, overtravel stop, or emergency stop.

4.1.1 Check Before Running

Before operating the servo driver and motor, perform the following checks:

  • Control circuit power input terminals (DC+, DC-) must be connected correctly.
  • Output terminals (U, V, W) of the main circuit and motor cables must have the same phase and be correctly connected.
  • All control signal cables must be correctly wired, including external signals like brake and overtravel protection.
  • Servo drives and motors must be reliably grounded.
  • All cables must be within their specified stress range.
  • Wiring terminals must be insulated.
  • Ensure no foreign objects inside or outside the servo drive that may cause short circuits.
  • Servo drives and external braking resistors must not be placed on combustible objects.
  • Servo motor installation, shaft connection, and machine must be reliable.
  • Servo motor and connected machinery must be in operable condition.

4.1.2 Power On

Turn on the control loop (DC+, DC-). After connecting the control circuit and main circuit power supply, the bus voltage indicator should show no abnormality. Wait for the host computer to give the servo enable signal. If the driver's red alarm light is on, check wiring and resolve the fault.

4.1.3 JOG Operation

Use JOG mode in the host computer software to verify normal motor rotation without abnormal vibration or sound.

4.2 Brake Setting

The brake prevents the servo motor shaft from moving when the servo driver is not running, keeping the motor locked in position. This prevents moving parts from shifting due to gravity or external forces.

4.2.1 Brake Wiring

The brake input signal connection has no polarity. A 24V power supply is required. The standard wiring example is:

Brake Wiring Diagram

Figure 4.1: Standard brake wiring diagram. Connect DO2+(BK+) and DO2-(BK-) to the brake control relay.

  • Ensure the motor brake cable length considers voltage drop; input voltage must be at least 21.6V.
  • Avoid sharing the power supply with other electrical appliances to prevent malfunction.
  • When connecting a relay, use a freewheeling diode (e.g., UF1010G) in the correct direction.
  • Recommended cable size: above 0.5mm².
  • The 24V power supply inside the servo driver can directly drive the motor lock and drive current 1A.

4.2.2 Brake Resistor Wiring

When the motor decelerates, energy is fed back to the driver, increasing bus voltage. A braking resistor consumes this energy to prevent damage to the servo drive. DS3 series drivers require an external braking resistor.

Braking Resistor Wiring Diagram

Figure 4.2: Wiring diagram for external braking resistor. Connect between RB+ and RB- terminals.

The recommended parameters for the brake resistor are:

ModeBrake Resistance Value (Ω)Brake Resistance Power (W)
DSY-200RS10100
DSY-400RS10100
DSY-750RS5100
DSY-1200RS3.5200

4.3 Control Modes

The DSY Series servo drive supports Position, Speed, and Torque control modes, as well as mixed mode switching.

4.3.1 Position Control Mode

This is a common working mode. Key steps include connecting power/cables, performing JOG tests, configuring pulse/direction inputs and DI/DO signals, setting position mode parameters, and adjusting gain.

4.3.2 Speed Control Mode

Similar to position control, this mode requires correct wiring, JOG testing, connecting necessary DI/DO and analog inputs, setting speed mode parameters, and adjusting gain.

4.3.3 Torque Control Mode

This mode involves connecting power/cables, JOG testing, connecting DI/DO and torque command sources, setting torque mode parameters, and enabling servo with appropriate speed limits and torque commands.

4.3.4 Homing Function

The homing function allows the servo drive to find a defined home position. Various homing modes are available, utilizing reverse limit switches, positive limit switches, home switches, and motor Z signals. The specific homing mode (0x6098 parameter) determines the sequence of movements and signal detection.

For detailed information on specific homing modes (e.g., Homing Mode 1-34), refer to the full PDF user manual, Chapter 4, Section 4.2.2.6.

5. Maintenance

To ensure the longevity and optimal performance of your DSY Series Servo Motor Kit, follow these general maintenance guidelines:

  • Keep Clean: Regularly clean the servo motor and driver to prevent dust and debris accumulation, which can affect heat dissipation and component lifespan. Use a soft, dry cloth.
  • Check Connections: Periodically inspect all cable connections (power, encoder, DIDO, communication) for tightness and signs of wear or damage. Loose connections can lead to intermittent operation or faults.
  • Environmental Conditions: Ensure the operating environment adheres to the specified temperature (0℃~55℃) and humidity (0~90% RH, non-condensing) ranges. Avoid exposure to excessive vibration, moisture, or corrosive substances.
  • Ventilation: Verify that the servo drive's ventilation openings are clear and unobstructed to allow for proper airflow and cooling.
  • Cable Integrity: Inspect cables for any kinks, cuts, or abrasions. Replace damaged cables immediately to prevent electrical hazards or signal loss.

6. Troubleshooting

This section provides guidance on diagnosing and resolving common issues. The servo drive categorizes alarms into two levels: Fault and Warning.

6.1 Fault Diagnosis and Treatment

Faults are serious alarms requiring immediate attention and often a power cycle. They can be non-resettable (requiring re-power) or resettable (cleared via P11-01=1 or DI function 2).

6.1.1 Non-Resettable NO.1 Faults

These faults indicate critical issues that prevent normal operation and require the drive to be re-powered after the cause is eliminated.

Fault Number (Er_)Fault NameCause of Fault
1System parameter exceptionAbnormal data of servo internal parameters
2Product model selection failureInvalid drive model
3Motor model selection failureP01.00 Function code Set an invalid motor code
4Fault in parameter storageParameter storage device failure; Parameters read/write too frequently; Control power supply instability; Drive failure
5FPGA faultFPGA initialization exception; FPGA logic version is abnormal; FPGA detected an exception
6Encoder matching faultIn absolute value system mode (P00.06 ≠0), an incremental or single-turn absolute value encoder motor is used
7Control power supply undervoltageControl circuit power supply undervoltage
9Overcurrent ADrive or motor parameters are incorrect; UVW phase-to-phase short circuit; Motor burned out; Motor is shorted to ground; Drive failure
10Overcurrent BServo motor wiring is not normal; Software detects the overcurrent of power transistor
11Encoder disconnectionIncremental encoder A/B/Z three-phase line break
13Encoder check exceptionThe bus encoder data check is abnormal; The incremental encoder zero check is abnormal
14Motor initial angle detection abnormalThe encoder signal interferes when the incremental encoder is powered on
15Motor out of controlMotor UVW phase sequence setting error; UVW wiring error; Initial position or encoder parameter setting error
16Current sampling faultThe current A/D sampling circuit is faulty
18Motor data verification failureNo motor parameters are written into the encoder EEPROM; Motor parameter verification error

6.1.2 Resettable NO.1 Faults

These faults can be reset after the cause is addressed.

Fault Number (Er_)Fault NameCause of Fault
20OvervoltageThe main circuit DC voltage abnormally high.
21UndervoltageThe main circuit DC voltage low.
22OverspeedSpeed command exceeds maximum speed; UVW phase sequence error; Speed response too high; Drive failure.
25Abnormal motor rotation during bootstrap chargingAbnormal motor rotation during bootstrap charging.
27DI terminal parameter setting faultDifferent DI are assigned with same function repeatedly.
28DO terminal parameter setting faultDifferent DO are assigned with same output.
30Reference position failureWhen using the PTP function, P04.00=5 is not set.

6.1.3 Resettable NO.2 Faults

These faults can be reset after the cause is addressed.

Fault Number (Er_)Fault NameCause of Fault
43Position deviation is too largeIn the servo ON state, the position deviation exceeds the position deviation value (P09.09).
46Drive overloadLoad operation exceeds the inverse time curve of the drive; UVW output may be lack of phase or phase sequence connected incorrectly.
47Motor overloadLoad operation exceeds the inverse time curve of the motor; UVW output may be lack of phase or phase sequence connected incorrectly.
48Motor stallThe mechanical position is stuck, causing the motor current to continuously increase abnormally.
49Electronic gear setting errorInconsistent response of dual-drive motors with gantry structure; Electronic gear ratio exceeds specification range [0.001, 4000].
50Heat sink (fan) overheatingServo unit heat sink (fan) exceeds the set fault value.
51Encoder battery failureNo battery or battery voltage below 2.6V.
52Encoder multi-turn count errorAbsolute encoder multi-turn count error.
53Encoder multi-turn count overflowAbsolute encoder multi-turn count overflow.
54Soft limit setting errorPosition between positive/negative limit is too short; Motor runs counterclockwise (positive direction) and positive limit value is smaller than negative limit value; Motor runs clockwise (negative direction) and negative limit value is smaller than positive limit value.

6.2 Reasons for Warning and Treatment

Warnings indicate potential issues that should be addressed to prevent faults.

Warning Number (Er_)Warning NameCause of Warning
81Drive overload warningWarning when 80% of the drive overload limit value is reached.
82Motor overload warningThe warning before the motor is about to fail, the warning value is determined by P09-05.
83Changed parameters need to be re-powered to take effectChanged parameters that need to be re-powered.
84Reset encoder warningIn enabled state, resets encoder when host computer sending commands.
86Forward overtravel warningPositive overtravel switch POT terminal is valid; The motor position exceeds the maximum soft limit.
87Negative overtravel warningNegative overtravel switch NOT terminal is valid; The motor position exceeds the soft limit minimum.
88Divided pulse output setting faultThe number of encoder divided pulses does not meet set condition or range.
89Al1\Al2 zero drift too largeAl1\Al2 zero drift too large.
90External regenerative resistor overloadExternal regenerative resistor power is too small.
91External regenerative resistor value is too smallThe external regenerative resistor is less than the minimum requirement by the drive; Or parameter setting error.
94DI emergency brakeExternal emergency brake E_STOP terminal trigger.
95Absolute encoder battery lowBattery voltage is lower than 3.2V.
96Homing timeoutHome switch failure; Time limit to find home is too short; High speed for searching home signal is too small.
97Mechanical home point offset errorIncorrect homing mode parameter settings for mechanical home offset.
99Multi-segment position reference position faultSystem not performing homing operation or not set to absolute value system in multi-segment absolute position mode; System not performing zero return operation in multi-segment incremental position mode with P13.07=1.
100The homing mode is incorrectly setHoming mode set to 0, or the mode is not supported.

6.3 Alarm Light Information Description

The servo drive's alarm light provides visual cues for different fault types:

FaultDescriptionFlicker FrequencyFlicker NumberFlicker TimesCyclic Flicker
Voltage faultOvervoltage, Undervoltage (The main circuit)1HZ13 secondsYES
Current faultOvercurrent (Overcurrent A, Overcurrent B)1HZ23 secondsYES
Overload/ Motor stallDrive overload, Motor overload, Motor stall1HZ33 secondsYES
Parameter setting errorDI/DO terminal parameter setting fault, Soft limit setting error1HZ43 secondsYES
Encoder errorEncoder matching fault, Encoder disconnection, Encoder check exception1HZ53 secondsYES
Motor verification errorMoto data verification failure1HZ63 secondsYES
Remaining faultsFaults other than the above faultsStay on
No faults-Stay off

7. User Tips

  • Initial Setup: Always perform a JOG test after initial wiring to confirm motor rotation and check for abnormal sounds or vibrations before proceeding with full operation.
  • Parameter Adjustment: When adjusting gain parameters, start with conservative values and gradually increase them while monitoring motor behavior to avoid instability or vibration. Refer to the full manual for detailed gain adjustment procedures.
  • RS485 Communication: For reliable RS485 communication, ensure proper grounding (PE connection) and maintain recommended cable separation from strong current lines. Use shielded twisted pair cables for long distances.
  • Brake Resistor: If your application involves frequent deceleration or high inertia loads, ensure the correct brake resistor is installed and wired to prevent overvoltage faults.
  • Consult PDF Manual: For in-depth parameter lists, advanced control modes (e.g., multi-segment positioning, homing modes), and detailed wiring diagrams, always refer to the comprehensive PDF user manual provided by STEPPERONLINE.

8. Support and Further Information

For detailed technical support, advanced parameter configurations, or specific application guidance, please refer to the official STEPPERONLINE resources:

  • Full User Manual (PDF): A comprehensive PDF user manual is available for download. This manual contains extensive details on all parameters, advanced control functions, and detailed wiring diagrams not fully covered in this summary. You can find the PDF manual at DSY-RS Series Low-voltage Servo Drive User Manual (V1.0).
  • Web: www.omc-stepperonline.com
  • Sales: sales@stepperonline.com
  • Support: technical@stepperonline.com