Anern AN-FGI-S12000

Contents

Anern 12KW Hybrid Solar Inverter User Manual

Model: AN-FGI-S12000

MPPT Solar Inverter with Dual PV Input, Dual AC Output, and WIFI

1. Introduction

This manual provides essential information for the assembly, installation, operation, and maintenance of the Anern 12KW Hybrid Solar Inverter (Model AN-FGI-S12000). This multifunctional solar inverter integrates an MPPT solar charge controller, a high-frequency pure sine wave inverter, and a UPS function module into a single unit. It is designed for off-grid backup power and self-consumption applications and can operate with or without batteries.

The inverter supports coordinated control of multiple energy sources, including photovoltaic panels, energy storage batteries, and diesel generators. Its energy flow adheres to a clear priority principle to maximize clean energy utilization while ensuring power supply reliability. The built-in or plug-and-play WiFi module allows users to monitor the PV system's status from a mobile phone or website anytime, anywhere.

Diagram showing three solar energy usage modes: Solar First, Solar and Utility, and Only Solar Charging.
Figure 1: Solar Energy Usage Modes (Solar First, Solar and Utility, Only Solar Charging)

2. Safety Instructions

Please read and keep this manual for future reference. Adhere strictly to all safety precautions to prevent injury or damage to the equipment.

2.1. Important Safety Information

  • WARNING! High voltage: Above 50Vac or 75Vdc. Electrical Hazard!
  • WARNING! Do not disconnect under load!
  • WARNING! Start maintaining the INVERTER at least 5 minutes after the INVERTER is disconnected from all external power supplies.
  • WARNING! All wiring must be performed by qualified personnel.
  • WARNING! Do not disassemble the unit. Refer to a qualified service center for repairs. Incorrect re-assembly can lead to electric shock or fire.
  • WARNING! To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit alone does not eliminate this risk.
  • WARNING! Do not ground the positive or negative terminals of the PV modules, as this can severely damage the inverter.
  • WARNING! Exposure to sunlight can generate lethal high voltages in photovoltaic strings. Strictly adhere to safety precautions listed in photovoltaic string and related documents.
  • WARNING! Make sure to connect the PV terminals to the corresponding ports on the inverter, as reversing the polarity can damage the inverter.
  • WARNING! Do not connect any DC switches or AC/DC circuit breakers before completing the electrical connections.
  • WARNING! Shock Hazard! Installation must be performed with care due to high battery voltage in series.
  • WARNING! Do not place anything between the flat part of the inverter terminal and the DT terminal. Overheating may occur.
  • WARNING! Do not apply anti-oxidant substance on the terminals before terminals are connected tightly.
  • WARNING! Before making the final DC connection or closing DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).
  • CAUTION! Only charge deep-cycle lead-acid type rechargeable batteries and lithium batteries. Other battery types may burst.
  • CAUTION! Be very cautious when working with metal tools on or around batteries to avoid short circuits or explosions.
  • CAUTION! Install circuit breakers for all lines. Do not connect or disconnect lines at will after power is applied.

2.2. General Guidelines

  • Read all instructions and cautionary markings on the unit, batteries, and all appropriate sections of this manual before use.
  • All electrical installations must comply with local electrical safety standards.
  • When installing PV modules during the daytime, cover them with opaque materials to avoid danger from high terminal voltage.
  • NEVER charge a frozen battery.
  • For optimal operation, select appropriate cable sizes as specified in this manual.

3. Installation

3.1. Unpacking and Inspection

Upon receiving the product, inspect the packaging for any damage. If damaged, contact your distributor immediately. Open the box to check if the inverter or internal equipment is damaged.3.2. Installation Tools

The following tools are recommended for installation:

ToolDescription
Multi-meterFor electrical measurements
Protective glovesFor safety during handling
Insulated anti-smashing shoesFor foot protection
Safety glassesFor eye protection
ESD wrist strapTo prevent electrostatic discharge
Hammer drillFor drilling mounting holes
Electric screwdriverFor tightening screws
Cross screwdriverFor various screw types
Rubber malletFor gentle tapping
Spirit levelFor ensuring level installation
Wire cutter / stripperFor preparing cables
Terminal crimping toolFor securing cable terminals

3.3. Mounting Unit

Consider the following for installation location:

  • Do not mount on flammable materials.
  • Mount on a solid surface at eye level for LCD visibility.
  • Ambient temperature should be between -10°C and 60°C.
  • Install vertically on the wall.
  • Ensure sufficient space (30cm clearance on all sides) for heat dissipation and wiring.
  1. Use an Ø8 drilling bit to drill holes for mounting. The distance between holes is 110mm. Insert M6 expansion screw tubes.
  2. Align the inverter's top screw holes with the installed expansion tubes and fix the inverter with screws.
  3. Before connecting wires, remove the bottom cover by unscrewing four screws.
Diagram showing mounting dimensions and bottom cover removal for the inverter.
Figure 2: Inverter Mounting Dimensions and Bottom Cover Access

3.4. AC Input / Output Connection

Install a separate AC breaker (recommended 80A) between the inverter and the AC input power source. There are three terminal blocks: 'AC IN', 'AC OUT1', 'AC OUT2'. Do NOT mis-connect input and output connectors. Ensure correct polarity (L and N wires).

Recommended AC Input Wire Size:

GaugeCable (mm²)
6 AWG13.3

Recommended AC Output Wire Sizes:

TerminalGaugeCable (mm²)
AC OUT1 (Max current is 70A)6 AWG13.3
AC OUT2 (Max current is 40A)10 AWG5.26

WARNING! AC OUT2 terminal cannot be connected with a load current > 40A, or an error will be raised.

AC Input Connection Steps:

  1. Open the AC circuit breaker.
  2. Remove 12mm insulation from cable ends, shorten conductor to 10mm, insert into tubular terminal, and crimp tightly.
  3. Insert AC input cables according to polarities (PE: yellow-green, L: brown/black, N: blue) and tighten screws. Connect PE cable first.
  4. Ensure all cables are securely connected.
Diagram showing AC input and output terminal connections on the inverter.
Figure 3: AC Input/Output Terminal Connections

3.5. PV Connection

Install a separate DC circuit breaker between the inverter and PV modules. Ensure correct polarity for PV connections.

Recommended PV Module Cable Size:

GaugeCable (mm²)
10AWG5.26

PV Module Selection Parameters:

  • Open circuit Voltage (Voc) of PV modules must not exceed max. PV array open circuit voltage of inverter (500Vdc).
  • Open circuit Voltage (Voc) of PV modules should be higher than start-up voltage (80Vdc).
  • PV Array MPPT Voltage Range: 60Vdc~450Vdc.

PV Module Connection Steps:

  1. Open the DC circuit breaker.
  2. Remove 12mm insulation from cable ends, shorten conductor to 10mm, insert into tubular terminal, and crimp tightly.
  3. Use a multi-meter to check polarities.
  4. Insert PV cables according to polarities (PV+: red, PV-: black) and tighten screws.
  5. Ensure cables are securely connected.
  6. PV1 and PV2 can be connected to different panel strings. If connected to the same string, change setting 62 to enable PV parallel mode.
Wiring diagram for a solar panel array connected to the inverter and grid.
Figure 4: General Wiring Diagram for Solar System

3.6. Battery Connection

Install a separate DC over-current protector or disconnect device (recommended 250A) between the battery and inverter. Choose a 48V nominal voltage battery (AGM, FLD, or Lithium).

Recommended Battery Cable and Terminal Size:

GaugeCable (mm²)
000 AWG85

Battery Connection Steps:

  1. Unscrew pre-fixed screws on battery poles. Prepare 2 DT terminals.
  2. Remove 10mm insulation from cable ends, insert into DT terminal, and crimp tightly.
  3. Pass battery cables through the bottom shell's installation hole and tighten terminal screws. Ensure correct polarity (BAT+ and BAT-).
  4. Connect all battery packs as required. A minimum 200Ah capacity battery is suggested.

Lithium Battery Connection:

If using a lithium battery, check protocol compatibility. Connect the RJ45 terminal of the battery communication cable to the BMS communication port of the inverter. The protocol should be RS485 or CAN. Ensure the BMS communication cable is connected between the battery and the inverter.

Diagram showing dual input dual output mode with inverter, battery, and connected devices.
Figure 5: Dual Input Dual Output Mode Example
Image showing inverter compatibility with lead-acid and lithium batteries.
Figure 6: Inverter Compatibility with Lead Acid and Lithium Batteries

3.7. Smart Communication Stick Connection (Optional)

The smart communication stick (WIFI) connects to the cloud platform. Insert the stick into the COM port directly. Some models have built-in WIFI monitoring.

3.8. Final Assembly

After all wiring is connected, reinstall the bottom cover by screwing in the four screws.

Video 1: Inverter and Lithium Battery Connection and Commissioning Guide. This video demonstrates the step-by-step process of connecting the inverter to a lithium battery, including opening the cover plate, connecting battery and solar panel wires, mains AC input, AC output, reinstalling the cover, starting the battery and inverter, connecting communication cables, and configuring BMS settings.

4. Operation

4.1. Power ON/OFF

Once the unit is properly installed and batteries are connected, press the ON/OFF switch (located on the bottom of the case) to turn on the unit.

4.2. Operation and Display Panel

The front panel features four indicators, four function keys, and an LCD display to show operating status and input/output power information.

Diagram of the inverter's front panel with LCD display, indicators, and buttons labeled.
Figure 7: Product Overview and Control Panel

LED Indicators:

IndicatorStateMessage
AC (Green)Solid OnMains power is normal and in operation.
FlashingMains power is normal but not yet in operation.
OffMains power is abnormal.
Invert (Yellow)Solid OnOutput powered by battery or PV in battery mode.
OffOther states.
Charging (Yellow)Solid OnBattery is in float charging.
FlashingBattery is in constant voltage charging.
OffOther states.
Fault (Red)Solid OnFault occurs in the inverter.
FlashingWarning condition occurs in the inverter.
OffInverter is working properly.

Function Buttons:

ButtonDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

4.3. LCD Display Icons and Settings

The LCD displays various information, including battery status, AC input/output, PV input, and load capacity. You can navigate through information using the UP/DOWN keys. To enter settings mode, press and hold the ENTER button for 2 seconds. Use UP/DOWN to select programs and ENTER to confirm.

Key settings include Output Voltage (220V/230V/240V), Output Frequency (50Hz/60Hz), Output Source Priority (Grid First, Solar First, SBU Priority, SUB Priority), Input Mode (APP, UPS, GEN), Charger Source Priority (PV and Grid, Only PV, PV First), Grid Charging Current (up to 160A), Maximum Charging Current (up to 160A), Energy-saving Mode, and various battery-related settings (e.g., battery type, low voltage points, equalization).

Diagram showing the inverter's display with various parameters like battery voltage, AC output, and charging status.
Figure 8: Inverter Display Screen showing operational status

5. Maintenance

5.1. Battery Equalization

The equalization function helps reverse negative chemical effects in lead-acid batteries, such as stratification and sulfation, which can reduce battery capacity. This function is not recommended for lithium batteries.

How to Apply Equalization Function:

Enable battery equalization in LCD setting Program 32 or choose immediate equalization on Program 35. Then, set:

  1. Equalization voltage point (Program 31).
  2. Equalization charging time (Program 32).
  3. Equalization delay time (Program 33).
  4. Equalization interval time (Program 34).
  5. Immediate equalization mode activation (Program 35).

The controller will enter the Equalize stage when the set equalization interval is reached or immediate equalization is activated.

Graph illustrating battery charging stages: Bulk, Absorption, Float, and Equalize.
Figure 9: Battery Charging Stages with Equalization

6. Troubleshooting

This section provides guidance on identifying and resolving common issues indicated by fault and alarm codes.

6.1. Fault Reference Code

When a fault occurs, the fault indicator is always on, and the buzzer sounds for 10 seconds before stopping. The system will attempt to restart automatically. If it fails after six attempts, the machine and LCD will remain in fault status. You must power off the machine completely or wait 15 minutes to restart.

Fault CodeMeaningTrigger ConditionsResume Conditions
1Bus boost failGrid soft start process starts but bus voltage does not reach set valueRestore after reaching the set voltage for 15 seconds
2Bus over voltageBus voltage is higher than set valueRestore after reaching the set voltage for 15 seconds
3Bus below voltageBus voltage is lower than set valueRestore after 15 seconds
4Battery over currentBattery current is higher than set valueCannot restore
5System over temperatureTemperature is higher than set value or fan is not connectedRestore after temperature lower than set value and fan connected for 15 minutes
6Battery over voltageBattery voltage is higher than set valueRestore after reaching the set voltage for 15 seconds
7Bus soft start failedBattery soft start process starts but the bus voltage has not reached set valueRestore after reaching the set voltage for 15 seconds
8Bus short circuitBus voltage is lower than set valueCannot restore
9Inverter soft start failedInverter soft start process starts but the inverter voltage has not reached set valueRestore after reaching the set voltage for 15 seconds
11Inverter under voltageThe inverter voltage is lower than the set value in battery modeRestore after reaching the set voltage for 15 seconds
12Inverter short circuitInverter voltage is less than the set value and current is higher than the set valueRestore after reaching the set voltage for 15 seconds
13Inverter negative powerThe inverter power is negative and exceeds the set value for a period of timeRestore after reaching the set value for 15 seconds
14Over loadThe load current is higher than the set valueRestore after reaching the set value for 15 seconds
17Program updatingInverter updating or OTARestore after updating
18PV reverse connectionPV reverse connectionRestore after connecting correctly for 15 seconds
26BMS faultError code in BMS message.Restore after BMS fault resolved
29Inverter load abnormalAbnormal inverter load leads to abnormal voltageRestore after voltage returning normal for 15 seconds

6.2. Alarm Reference Code

When an alarm occurs, the inverter does not enter fault mode; the red LED light flashes, and the LCD displays the alarm code.

Alarm CodeMeaningTrigger ConditionsResume Conditions
50Battery openBattery disconnected for no more than 10 minutesRestore after battery connected for 2 minutes
51Battery under voltageBattery voltage is lower than BAU set valueRestore after the battery voltage exceeding the BAU set value by 2V
52Battery low voltageBattery voltage is lower than BAL set valueRestore after the battery voltage exceeding the BAL set value by 2V
53Battery charge short circuitBattery voltage is less than 24V and the charging current exists.Restore after the short circuit is eliminated.
56BMS lossCommunication failure after BMS communication function is enabledRestore after communication function disabled or communication success
58Fan errorNo fan speed signal detectedRestore after fan speed signal detected
59EEPROM errorEEPROM read/write exceptionCannot restore
60OverloadThe mains current/battery discharge current/load power is higher than the rated value.Restore after the mains current/battery discharge current/load power is less than the rated value.
62PV energy weakWhen the battery is not connected, the bus voltage is lower than the set valueRestore after battery connected or grid connected, or 10 minutes later.
68Battery under SOC shutdownBMS reports SOC lower than BSU set valueRestore after meeting one of the following: 1. Disable low SOC shutdown function. 2. Disable BMS communication function. 3. SOC is higher than the set value by 5%.
69Battery below SOC warningLithium battery SOC is lower than set value+5% (grid mode or battery mode), lower than set value+10% (standby mode).Restore after meeting one of the following: 1. Disable low SOC shutdown function. 2. Disable BMS communication function. 3. SOC is higher than the set value by 10%.
72Battery can not startupDuring standby, battery voltage is lower than the allowed startup voltageRestore after the battery voltage is higher than the allowed startup voltage
77Grid power is unstableLost of grid power three times within 5 minutesRestore after 5 mins
78Meter LossWhen the grid power is connected and the grid connected inverter function is set to Meter, the meter communication is disconnectedRestore after grid is disconnected, or detection device is not set to Meter, or meter communication restore

7. Specifications

Detailed technical specifications for the Anern 12KW Hybrid Solar Inverter (AN-FGI-S12000).

AC Input
Rated Input Voltage (VAC)220/230/240; L+N+PE
Voltage Range (VAC)90~280 (APP mode); 170~280 (UPS mode)
Frequency (Hz)50/60 (Auto Adaptive)
AC Output
Rated Capacity (kW)12 (Max current of AC output 1 is 70A. Max current of AC output 2 is 40A)
Surge Power (kVA)24
Voltage (VAC)220/230/240
Power Factor (PF)1
Frequency (Hz)50/60±0.1%
Switch Time (ms)10 (APP/UPS mode) / 20 (GEN mode)
WaveFormPure Sine Wave
Overload Capacity (Battery Mode)1min@ 102%~125% load; 10s@ >125% load
Max. Efficiency (Battery Mode)94%@48V
Charger (PV/AC)
Solar Charger TypeMPPT
Max PV Input Current/PowerSingle PV Input: 27A/9000W; Dual PV Input: 22.5*2A/15000W
MPPT Range@Operating Voltage (VDC)60~450
PV Start-up Voltage80Vdc
Max PV Open Circuit Voltage (VDC)500
Max PV Charge Current (A)160
Max AC Charge Current (A)160
Max. Charge Current (PV+AC) (A)160
Battery
Normal Voltage (VDC)48
Battery TypeLithium and Lead-acid
General Data
HMILCD
InterfaceRS232/RS485/CAN
MonitoringWiFi (Optional)
Ingress ProtectionIP21
Operating Temperature-10°C~60°C
Relative Humidity5%~95% (Non-condensing)
Storage Temperature-15°C~60°C
Max. Operating Altitude4000m (Derating above 1000m)
Size53*43*14cm
Weight16kg

8. User Tips

  • Flexible Operation: This inverter can function both with and without a battery, and can draw power from the mains or solar panels. This offers versatility for various energy setups.
  • Inductive Load Sizing: For inductive loads (e.g., air conditioners, refrigerators), ensure their starting power is at least three times the inverter's rated power to prevent damage. Select a suitable model based on your appliance requirements.
  • Professional Installation: It is highly recommended to have a professional worker install the inverter to ensure correct wiring and prevent potential damage or hazards.
  • Correct Connection Sequence: Always follow the specified connection and disconnection sequences:
    • Starting: Battery switch ON → Inverter ON → PV, Mains, and Load switches ON.
    • Shutdown: Load, PV, and Mains switches OFF → Inverter OFF → Battery switch OFF.

9. Warranty and Support

For detailed warranty information, service, and support, please refer to the complete user manual PDF available for download. The manufacturer is not responsible for issues arising from non-compliance with the instructions in this manual.

You can access the full user manual PDF here: Anern 12KW Hybrid Solar Inverter User Manual (PDF)

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.