STEPPERONLINE A6 Series 400W PROFINET AC Servo Motor Driver Kit

Contents

STEPPERONLINE A6 Series 400W PROFINET AC Servo Motor Driver Kit User Manual

Model: A6 Series 400W PROFINET AC Servo Motor Driver Kit

1. Introduction

The A6-PN series is a fast, reliable, and accurate platform servo drive from STEPPERONLINE, covering the most common power range of 0.40 kW to 1.0 kW for general automation. It supports both single-phase and three-phase power supply systems. It features a space-saving design and excellent servo control performance.

Working together with the A6 servo motor, the A6-PN series servo drive can optimize performance and ease of use. Compatible with Siemens 200/300/1200/1500 series PLCs, the A6-PN series servo drive provides efficient and convenient motion control solutions for various industries.

2. Safety Information

  • The product described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation.
  • All operations on the product must follow respective descriptions provided in the documentation, in particular, its warning notices and safety instructions.
  • Damage caused by improper use is not covered by warranty.
  • The company will disclaim any legal liability for any personal injury or property damage caused by improper usage.

2.2. General Safety Precautions

CAUTION

  • Do not connect the input power cables to the output terminals U, V and W. Failure to comply may cause damage to the servo drive.
  • Do not touch power terminals within 10 minutes after power-off because high voltage exists inside the drive after power off.
  • Do not bundle power cables and signal cables together or route them through the same duct. Power cables and signal cables must be separated by a distance of at least 30 cm to prevent interference.
  • Do not turn on and off the power supply frequently (once a minute). Failure to comply may cause drive faults.
  • Do not power on the servo drive when any screw of the terminal block or any cable becomes loose. Failure to comply may cause a fire.
  • When cables are bundled in a metal duct, take the current reduction ratio into consideration because of the inadequate cooling condition of the duct.
  • Select cables based on the ambient temperature of the controller: When the ambient temperature is high, use heat-resistant cables. Teflon cables are recommended.
  • Take heat preservation measures in low-temperature environments because the surface of regular cables may be easily hardened and cracked under low temperature.
  • Use cables whose bending radius is over 10 times its outer diameter, to prevent the internal conductor from breaking due to long-term bending.
  • Use cables that can resist a voltage of 600 V AC or above and have a rated temperature of 75°C or above for the main circuit.
  • Use a grounding cable with the same cross-sectional area as the main circuit cable. If the cross-sectional area of the main circuit cable is less than 1.6 mm², use a grounding cable with a cross-sectional area of 2.0 mm².
  • Ground the drive reliably. Failure to comply may result in malfunction or even damage of the drive.
  • Use shielded cables to comply with the EMC requirements.

3. Product Overview

3.1. Key Features

  • Excellent performance: High response (2 kHz speed loop bandwidth), high accuracy (17-bit absolute encoder), high dynamics (DSC mode), high adaptability (standard PROFIDRIVE protocol, mainstream PROFINET communication PLCs).
  • Sophisticated and novel design: Integrated communication ports, compact design for narrow spaces, easy connection with serial or USB commissioning cable, support for PROFINET bus servo parameter copy.
  • Safe and reliable: Built-in dynamic brake function, optional high-protection model for harsh application environments.

3.2. Components

The kit includes the servo motor driver, servo motor, and necessary cables.

STEPPERONLINE A6 Series 400W PROFINET AC Servo Motor Driver Kit
Main components of the STEPPERONLINE A6 Series 400W PROFINET AC Servo Motor Driver Kit.
Product Details: Servo Driver, Motor, and Cables
Detailed view of the servo driver, motor, and connecting cables.

3.3. Servo Drive Component Layout (SIZE A)

Servo Driver Component Layout with numbered parts
Components of the A6-PN servo drive (SIZE A).

The following table describes the numbered components:

No.NameNo.Name
①Commissioning and communication port (CN6)⑦STO terminal port (CN5)
②Display and operation area⑧QR code on machine
③Control signal port (CN1)⑨EtherCAT communication network port (CN3 and CN4)
④Power input⑩Encoder signal port (CN2)
⑤Braking resistor port⑪Motor power output
⑥Charging indicator⑫System ground

NOTICE

The above figure describes the component layout of the SIZE A drive. Component layout of other models may be different. For positions of ports of other models, see section 3.3 Ports.

4. Specifications

4.1. Rated Data

Single-phase 220 V Servo Drive

ItemSIZE-ASIZE-B
Power0.4 kW0.75 kW
Drive model A6-PNA6-400PNA6-750PN
Continuous output current (Arms)2.85.5
Maximum output current (Arms)10.116.9
Main circuit power supplySingle-phase 200–240 V AC, −10% to +10%, 50/60 Hz
Control circuit power supplyPowered up by the bus, sharing one power supply and rectification part with the main circuit
Braking capabilityExternal braking resistorBuilt-in braking resistor

Single-phase/Three-phase 220 V Servo Drive

ItemSIZE-C
Power1.0 kW
Drive model A6-PNA6-1000PN
Continuous output current (Arms)7.6
Maximum output current (Arms)23
Main circuit power supplySingle-phase/three-phase 200–240 V AC, -10% to +10%, 50/60 Hz
Control circuit power supplySingle-phase 200–240 V AC, -10% to +10%, 50/60 Hz
Braking capabilityBuilt-in braking resistor

NOTICE

The main circuits of A6-1000PN driver can be connected to a single-phase or a three-phase power supply, depending on which one is available on site.

4.2. Technical Specifications

Basic Specifications

ItemSpecifications
Control modeIGBT PWM control, sine wave current drive mode, 220 V, 380 V: Single-phase or three-phase full-bridge rectification
Encoder feedback17-bit multi-turn absolute encoder, which can be used as a single-turn absolute encoder in absence of the battery
Operating temperature0°C to +55°C (over 45°C: derate 10% for every additional 5°C)
Storage temperature-40°C to +70°C
AltitudeUp to 2000 m. For altitude above 1000 m, derate 1% for every additional 100 m
IP ratingIP20 (except for the power terminal IP00)

Speed/Torque Control Mode

ItemSpecifications
Speed control range1:6000 (The lower limit is the threshold within which the servo drive keeps running with the rated torque load.)
Speed loop bandwidth3 kHz
Torque control accuracy±1%
Ramp time0 s to 600 s (This parameter can be set for acceleration and deceleration separately.)
Speed reference inputSource of network-type references: PROFINET communication
Torque reference inputPROFINET communication

Position Control Mode

ItemSpecifications
Positioning time1 ms to 10 ms
Position referenceSource of network-type references: PROFINET communication
Digital input (DI) signalP-OT (positive limit switch), N-OT (negative limit switch), HomeSwitch (home switch), TouchProbe1 (probe 1), TouchProbe2 (probe 2)
Digital output (DO) signal3 DOs, Load capacity: 50 mA, Voltage range: 5 V to 30 V, S-RDY (servo ready), ALM (fault output), BK (brake output)

Built-in Functions

ItemSpecifications
Overtravel (OT) preventionThe servo drive stops immediately when P-OT or N-OT becomes active
Protection functionProtections against overcurrent, overvoltage, undervoltage, overload, main circuit detection error, heatsink overheat, overspeed, encoder error, CPU error, and parameter error
LED displayMain power supply CHARGE indicator, 5-digit LED display
Vibration suppressionFive notches (including two adaptive notches), 50 Hz to 8000 Hz
Connection protocolRS232, PROFINET, USB
Multi-station communication65535 (PROFINET, dependent on the PLC)
Axis address setting0 to 247 set through the software (RS232), Allocated automatically by the host controller (PROFINET)
FunctionStatus display, user parameter setting, monitored value display, alarm tracing display, jogging, and speed/torque reference signal observation
OtherGain tuning, alarm record, and I/O setting

Communication Specifications

ItemSpecifications
Communication protocolPROFINET protocol, RT and IRT modes
Process dataCommonly-used telegrams
Non-cyclic dataAccess to industry standard parameters and function code parameters
Bus cycleRT mode: minimum 1 ms, IRT mode: minimum 500 µs
Synchronization jitter<1 µs
Physical layer100 BASE-TX
Baud Rate100 M Bit/S (100Base-TX)
Duplex modeFull duplex
TopologyRing, linear, star, tree
Transmission mediumShielded Ethernet cable of Cat5e or above
Number of slavesUp to 65535 supported by protocol (Dependent on PLC performance.), Up to 100 tested
Communication bit error ratio10-10 Ethernet standard
I&M dataI&M0 to I&M4
Configuration versionTIA Portal V17 SP1 or later versions, STEP7 V5.5 SP4 or later versions
PROFINET versionV2.4
PROFINET interfaceNumber of ports: 2
Alarm/Diagnosis informationSupported
DCP CALLSupported
MRPSupported
MRPDSupported
PROFINET system redundancySupported
Boot prioritySupported
Port disablingSupported
Configuration free upon device changeSupported

4.3. Servo Motor Specification

Servo Motor Specification table
Servo Motor Specification for A6M60-400H2A1-M17 and A6M60-400H2B1-M17.

4.4. Product Dimensions

400W AC Servo Motor Driver

400W AC Servo Motor Driver dimensions (front, side, rear, top views)
Dimensions of the 400W AC Servo Motor Driver.

400W AC Servo Motor

400W Servo Motor with and without brake dimensions
Dimensions of the 400W AC Servo Motor (no brake and with brake).

4.5. Motor Torque-Speed Characteristics

The following graphs illustrate the continuous and short-time work areas for different motor models at 3000 rpm.

Motor torque-speed characteristics graphs
Motor torque-speed characteristics for 3000 rpm models. A: Continuous work area, B: Short-time work area.

5. Installation Guide

The A6-PN series servo drive must be installed on a base through a backplate. For the mounting holes, refer to the dimensions diagrams of each model.

5.1. Installation Dimensions

SIZE A (rated power: 0.4 kW)

Installation dimensions for SIZE A (unit: mm)
Installation dimensions for SIZE A (unit: mm).

SIZE B (rated power: 0.75 kW)

Installation dimensions for SIZE B (unit: mm)
Installation dimensions for SIZE B (unit: mm).

SIZE C (rated power: 1.0 kW)

Installation dimensions for SIZE C (unit: mm)
Installation dimensions for SIZE C (unit: mm).

5.2. Dimensions of the Outer Packing Box

SIZEDrive ModelOuter LengthOuter HeightOuter WidthWeight
AA6-400PN215 mm85 mm195 mm0.78 kg
BA6-750PN220 mm95 mm215 mm1.04 kg
CA6-1000PN220 mm95 mm215 mm1.20 kg

5.3. Fixing with Screws

NOTICE

  • SIZE-A/B/C: M4 screws, 1 each on top and bottom. Torque: 1.3 N·m to 1.6 N·m.

6. Wiring and Connections

6.1. System Topology (SIZE A)

System Topology diagram
System Topology for SIZE A, showing connections for power, control, and communication.

6.2. System Wiring

System Wiring diagram
Detailed system wiring diagram including host controller, next slave, power supply, and state output.

6.3. Ports Overview

SIZE A Ports

The following table details the ports for SIZE A drives.

PortFunction
CN6Commissioning and communication port
CN3Communication network port IN
CN1User control port
L1/L2Main power input
P+/CExternal braking resistor
N-Bus negative electrode
U/V/WMotor power output
PEMotor grounding terminal
CN5STO functional port
CN4Communication network port OUT
CN2Encoder port

SIZE B Ports

The following table details the ports for SIZE B drives.

PortFunction
CN6Commissioning and communication port
CN3Communication network port IN
CN1User control port
L1/L2Main power input
P+/D/CExternal braking resistor
N-Bus negative electrode
U/V/WMotor power output
PEMotor grounding terminal
CN5STO functional port
CN4Communication network port OUT
CN2Encoder port

SIZE C Ports

The following table details the ports for SIZE C drives.

PortFunction
CN3Communication network port IN
L1C/L2CControl power input
R/S/TMain power input
P+/D/CExternal braking resistor
N-Bus negative electrode
U/V/WMotor power output
PEMotor grounding terminal
CN4Communication network port OUT
CN6Commissioning and communication port
CN5STO functional port
CN1User control port
CN2Encoder port

6.4. Drive Terminals

TerminalPinDescription
Main circuit terminals of SIZE AL1 and L2: Power input terminalsConnected to the input power supply as per the rated voltage class on the nameplate.
P+ and N-: Servo bus terminalsUsed when multiple servo drives share one DC bus.
P+ and C: External braking resistor connection terminalsIf an external braking resistor is needed, connect it between terminals P+ and C.
U, V, and W: Servo motor connection terminalsConnected to U, V, and W phases of the servo motor.
PE: Motor grounding terminalConnected to the grounding terminal of the motor for grounding purpose.
L1C and L2C: Control circuit power input terminalsConnected to the control circuit power supply as per the rated voltage class on the nameplate.
Main circuit terminals of SIZE BL1 and L2: Power input terminalsConnected to the input power supply as per the rated voltage class on the nameplate.
P+ and N-: Servo bus terminalsUsed when multiple servo drives share one DC bus.
P+, D, and C: External braking resistor connection terminalsIf an external braking resistor is needed, connect it between terminals P+ and C. Note: Remove the jumper between terminals P+ and D before installing an external braking resistor. Otherwise, the braking transistor will be damaged due to overcurrent.
U, V, and W: Servo motor connection terminalsConnected to U, V, and W phases of the servo motor.
PE: Motor grounding terminalConnected to the grounding terminal of the motor for grounding purpose.
L1C and L2C: Control circuit power input terminalsConnected to the control circuit power supply as per the rated voltage class on the nameplate.
Main circuit terminals of SIZE CR, S, and T: Main circuit power input terminalsConnected to the main circuit power supply as per the rated voltage class on the nameplate.
P+ and N-: Servo bus terminalsUsed when multiple servo drives share one DC bus.
P+, D, and C: External braking resistor connection terminalsIf an external braking resistor is needed, connect it between terminals P+ and C. Note: Remove the jumper between terminals P+ and D before installing an external braking resistor. Otherwise, the braking transistor will be damaged due to overcurrent.
U, V, and W: Servo motor connection terminalsConnected to U, V, and W phases of the servo motor.
PE: Motor grounding terminalConnected to the grounding terminal of the motor for grounding purpose.

6.5. CN1 User Control Terminal

TerminalPinDescription
CN1 user control terminal10 (DI1)Positive limit switch
9 (DI2)Negative limit switch
8 (DI3)Home switch
7 (DI4)Probe 2
11 (DI5)Probe 1
15 (+24V)Internal 24 V power supply (Voltage range: 20 V to 28 V, Max. output current: 200 mA)
14 (COM-)Common terminal (Note: The drive shares a resettable fuse of a 200 mA total current limit with the CN5 Safe Torque Off (STO) function terminal.)
Digital Output1 (DO1+) / 6 (DO1-)Servo ready
3 (DO2+) / 2 (DO2-)Fault
5 (DO3+) / 4 (DO3-)Brake
1 (+5V) / 2 (0V)5 V power supply

6.6. CN2 Encoder Terminal

TerminalPinDescription
CN2 encoder terminal5 (PS+) / 6 (PS-)Encoder signal
Enclosure (PE)Shield

6.7. PROFINET Communication Terminals (CN3 and CN4)

TerminalPinDescription
PROFINET communication terminals1 (TD+) / 2 (TD-)Data transmit+ / Data transmit-
3 (RD+) / 6 (RD-)Data receive+ / Data receive-
9 (TD+) / 10 (TD-)Data transmit+ / Data transmit-
11 (RD+) / 14 (RD-)Data receive+ / Data receive-

6.8. CN6 Commissioning and Communication Terminal

TerminalTypeDescription
CN6 commissioning and communication terminalType-C1: Type-C to serial, serial to USB
2: Type-C to USB

6.9. Power Supply Connection

Refer to the safety precautions in Section 2.2 for important guidelines on power supply connections.

6.10. Communication Signal Connection (CN3 and CN4)

Communication signals are connected by PROFINET network cables. Connect CN3 (P1) to the communication port of the master and CN4 (P2) to a slave.

Communication Signal Connection diagram
Communication networking topology for PROFINET.

CAUTION

  • To enhance the system's anti-interference capability, the EtherCAT communication cable must be an Ethernet Category 5 (100BASE-TX) network cable or high-strength shielded network cable of no more than 100 m.
  • PROFINET servo drives support multiple connection methods, and the networking topology provided here is for reference only.

6.11. PROFINET Communication Connection

PROFINET communication supports multiple networking topologies and connection methods:

PROFINET Communication Connection (Linear and Redundant Ring)
PROFINET communication connection types: Linear and Redundant Ring.

7. Operation and Commissioning

7.1. Basic Functions of the Servo Drive

The servo system consists of three critical parts: the servo drive, servo motor, and encoder. The servo drive processes input signals and feedback signals to precisely control the position, speed, and torque of the servo motor.

Structure of a Servo System

Structure of a servo system diagram
Diagram illustrating the structure of a servo system.

List of Servo Functions

FunctionDescription
Measurement probeLatches the position value when a DI external signal or Z signal of the motor changes.
High-resolution encoderUtilizes a high-performance encoder with a resolution of 1,310,72 P/r.
Mechanical characteristics analysisAnalyzes the resonance frequency and other characteristics of the mechanical system when using a PC that has a drive commissioning platform installed on it.
Automatic gain adjustmentYou only need to set one parameter, and the servo automatically provides a set of matching gain parameters suitable for the current working condition.
Gain switchoverUses different gains in different servo motor status (running or stopping), and switches gains through external terminals during running.
Torque disturbance observationAutomatically estimates the disturbance torque on the system and compensates for it to reduce vibration.
Resonance suppressionAutomatically sets filter characteristics after the servo drive detects mechanical resonant points to suppress system vibration.
Torque command filterSuppresses mechanical resonance that may occur when the servo drive responds too quickly.
Position first-order low-pass filterEnables smooth acceleration and deceleration.
Torque limitLimits the output torque of the servo motor.
Velocity limitLimits the velocity of the servo motor.
External braking resistorUsed when the braking capability of the built-in brake resistor of the servo drive is insufficient.
Input signal selectionAssigns functions such as emergency stop to corresponding pins.
Alarm historyRecords the latest 20 alarms and can clear the alarm history.
Status displayDisplays the status of the servo drive on a 5-digit 8-segment LED.
External I/O displayDisplays the ON/OFF status of external I/O signals.
Forced signal outputEnables the independent output of signals regardless of the servo drive status, useful for checking the wiring of output signals.
Trial running modeAllows running the servo motor directly from the servo drive panel without requiring a start signal.
Drive commissioning platformEnables parameter setting, trial running, status display using a personal computer.
Alarm code outputOutputs a 4-digit alarm code when an alarm occurs.

7.2. Commissioning Tool

The A6-PN series servo drive can be commissioned by the operating panel which consists of an LED display area and five buttons.

Display and Operation Area

Servo drive display and operation area
The display and buttons on the servo drive.

Buttons

ButtonDescription
M (MODE)Press: Switch/return to menus of different levels.
Press and hold: Switch the group number quickly in level-2 menus.
▲ (UP)Press: Switch the state display quickly in level-1 menus, Increase the value.
▼ (DOWN)Press: Switch the state display quickly in level-1 menus, Decrease the value.
◀ (SHIFT)Press: Move the cursor to the left.
Press and hold: Enter the JOG mode quickly in level-1 menus, Page up or down when the content is displayed on multiple pages.
S (SET)Press: Switch to the lower-level menu.
Execute commands such as storing parameter setpoints.

Display Menus

When the servo drive is running, the servo drive status, parameters, faults, and monitored values are displayed in the LED display area.

  • Status display: Display current servo drive status, such as servo ready or servo running.
  • Parameter display: Display parameters and their setpoints.
  • Fault display: Display faults and alarms that occurred on the servo drive.
  • Monitored value display: Display values of running parameters of the servo drive.

NOTICE

  • After power-on, "Init" is displayed in the LED display area and then the system enters the level-1 menu status display mode.
  • In the status display mode, select the parameter to be monitored. When the motor rotates, the display area automatically switches to monitored value display. After the motor stops, the display area automatically returns to status display.
  • In the parameter display mode, after you select the parameter to be monitored, the system switches to monitored value display.
  • Once a fault occurs, the LED display area switches to fault display automatically, with all the LEDs blinking. Press S to stop the LEDs from blinking, and then press M to switch to parameter display.
Level-1 Menu: Status Display

Press ▲ and ▼ to switch among different display modes. Press M to enter a level-2 menu.

Level-2 Menu: Parameter Group Number

Displays the parameter group number in hexadecimal. Press and hold M to switch the group number. Press S to enter a level-3 menu. Press M to return to the level-1 menu.

Level-3 Menu: Offset within Parameter Group

Offset within the parameter group in hexadecimal. Press S to enter a level-4 menu. Press M to return to a level-2 menu.

Level-4 Menu: Parameter Setpoints

Parameter setpoints in decimal. Press ▲ to increase or decrease the value. Press S to confirm the setting. Then, the system displays the new value. Press M to return to a level-3 menu.

7.3. Jogging

Use the jogging function for trial run of the servo motor and servo drive to check whether the servo motor rotates properly without abnormal vibration or noise generated during rotation.

NOTICE

  • To use the jogging function, deactivate the S-ON signal. Otherwise, this function cannot be used.
  • During the jog, use F30.03 to set the acceleration/deceleration time constant for the velocity/position reference.

Procedure for Setting the Jogging Function

  1. Start: Power on the servo drive. Press and hold ◀ in the level-1 menu.
  2. Set parameter F30-00 on the panel: Press S to confirm the setting.
  3. Set the jog speed: Press ▲ to increase or decrease the value.
  4. Confirm the motor speed: Press S to confirm the setting.
  5. JOG-S is displayed. Press ▲/▼.
  6. Enable forward/reverse motor rotation: Press M.
  7. Finish.

NOTICE

  • Press ▲/▼ to increase or decrease the motor speed for the jog running. If the system exits jog running, the motor speed restores to the initial value.
  • Press ▲/▼ to make the servo motor rotate in the forward or reverse direction. After the button is released, the servo motor stops running immediately.

7.4. Inertia Auto-tuning

The load inertia ratio is the ratio of the total moment of inertia of motor load to the moment of inertia of the motor. A correct load inertia ratio facilitates commissioning.

You can set the C00.06 (load inertia ratio) manually, but it is tedious. It can also be automatically auto-tuned by F30.10 (inertia auto-tuning function) of the servo drive.

During auto-tuning, the drive will drive the servo motor to run in the forward or reverse direction multiple times to obtain the load inertia ratio.

Inertia Auto-tuning Process

  1. Start: Power on the servo drive.
  2. Set the parameter F30-10 on the panel: Press S to confirm the setting.
  3. Set the number of auto-tuning turns: Press ▲ to increase or decrease the value.
  4. Confirm the number of auto-tuning turns: Press S to confirm the setting.
  5. Display the inertia value: Press ▲/▼.
  6. Perform auto-tuning on auto/manual gains: Press M.
  7. End.

8. PROFINET Communication Details

8.1. Overview of PROFINET

PROFINET IO is an Ethernet-based real-time protocol used as a high-level network in industrial automation applications. It provides two real-time communication types: PROFINET IO RT (real-time) and PROFINET IO IRT (isochronous real-time).

  • PROFINET IO RT: Used for the transmission of I/O data and alarms. Real-time data is transferred through prioritized Ethernet frames, no special hardware required.
  • PROFINET IO IRT: Used for more precise timing requirements, special hardware for IO devices and switches required.

All diagnostic and configuration data is transferred through the non-real time (NRT) channel and the TCP/IP protocol is used.

8.2. Supported Telegrams

The A6-PN series servo drive supports AC1, AC4, AC3, and DSC applications. It supports standard telegrams and Siemens telegrams for velocity control mode and basic positioner control mode.

From the perspective of the drive unit, the received process data represents the receive words and the process data to be sent represents the send words.

Description of Supported Telegrams

TelegramMax. Number of PZDs (One PZD = One word)
Receive WordSend Word
Standard telegram 122
Standard telegram 359
Standard telegram 599
Siemens telegram 102610
Siemens telegram 1051010
Standard telegram 722
Standard telegram 9105
Siemens telegram 1111212
Annex telegram 75031

8.3. Telegrams for Velocity Control Mode

Telegram1 (AC1)3 (AC4)5 (AC4)102 (AC4)105 (AC4)
PZD1STW1STW1STW1STW1STW1
PZD2NSOLL_ANIST_BNIST_BNIST_BNIST_B
PZD3ZSW1STW2STW2STW2STW2
PZD4ZSW2ZSW2ZSW2ZSW2
PZD5G1_STWG1_STWMOMREDMELDW
PZD6G1_ZSWG1_ZSWG1_STWG1_ZSW
PZD7G1_XIST1G1_XIST1G1_XIST1G1_XIST1
PZD8XERRXERRXERRXERR
PZD9G1_XIST2G1_XIST2G1_XIST2G1_XIST2
PZD10KPCKPCKPCKPC

8.4. Telegrams for Basic Positioner Control Mode

Telegram7 (AC3)9 (AC3)111 (AC3)
PZD1STW1STW1STW1
PZD2SATZANWSATZANWPOS_STW1
PZD3STW2STW2POS_STW2
PZD4MDI_TARPOSMDI_TARPOSOVERRIDE
PZD5MDI_VELOCITYMDI_VELOCITYMDI_TARPOS
PZD6MDI_ACCMDI_ACCMDI_ACC
PZD7MDI_DECMDI_DECMDI_DEC
PZD8MDI_MODMDI_MODMDI_MOD
PZD9ZSW1ZSW1ZSW1
PZD10ZSW2ZSW2ZSW2
PZD11USER_PZD
PZD12USER_PZD

8.5. Annex Telegram 750

NOTICE

When telegram 750 is used, the motor will accelerate uncontrollably if any of the following settings are made:

  • The torque upper limit is set by PZD M_LIMIT_POS to a negative value.
  • The torque lower limit is set by PZD M_LIMIT_NEG to a positive value.
Telegram750
Application Mode-
PZD1M_ADD1
PZD2M_LIMIT_POS
PZD3M_LIMIT_NEG

8.6. I/O Data Signals

Overview of I/O Data in Telegrams

SignalDescriptionReceive Word/Send WordData TypeValue and Meaning
STW1Control word 1Receive wordU16-
STW2Control wordReceive wordU16-
ZSW1Status word 1Send wordU16-
ZSW2Status word 2Send wordU16-
NSOLL_AVelocity setpoint AReceive wordU164000 hex ≒ 3000 rpm
NSOLL_BVelocity setpoint BReceive wordU3240000000 hex ≒ 3000 rpm
NIST_AVelocity actual value ASend wordU164000 hex ≒ 3000 rpm
NIST_BVelocity actual value BSend wordU3240000000 hex ≒ 3000 rpm
MOMREDTorque decrease valueReceive wordU164000 hex = Maximum torque
M_ADD1Supplementary torque valueSend wordU164000 hex = Maximum torque, C000 hex = Minimum torque
M_LIMIT_POSPositive torque limitSend wordU164000 hex = Maximum torque
M_LIMIT_NEGNegative torque limitSend wordU16C000 hex = Minimum torque
M_ACTThrust actual valueReceive wordU164000 hex = Maximum torque, C000 hex = Minimum torque
MELDWMessage wordSend wordU16-
G1_STWEncoder 1 control wordReceive wordU16-
G1_ZSWEncoder 1 status wordSend wordU16-
G1_XIST1Encoder 1 actual positionSend wordU32-
G1_XIST2Encoder 1 actual positionSend wordU32-
MELDWMessage wordSend wordU16-
MDI_TARPOSMDI positionReceive wordU321 hex ≒ 1 LU
MDI_VELOCITYMDI velocityReceive wordU321 hex ≒ 1000 LU/min
MDI_ACCMDI acceleration overrideReceive wordU164000 hex ≒ 100%
MDI_DECMDI deceleration overrideReceive wordU164000 hex ≒ 100%
XIST_APosition actual value ASend wordU321 hex ≒ 1 LU
OVERRIDEPosition velocity overrideReceive wordU164000 hex ≒ 100%
FAULT_CODEFault codeSend wordU16-
WARN_CODEAlarm codeSend wordU16-
userUser-defined receive word (0: No function, 1: Supplementary torque)Receive wordU164000 hex ≒ 100%
userUser-defined send word (0: No function, 1: Actual torque, 2: Actual current, 3: DI status)Send wordU164000 hex ≒ 100%
XERRDSC deviationReceive wordU32-
KPCDSC gainReceive wordU32-
SATZANWPosition program block selectionReceive wordU16-
AKTSATZEPOS selected program blockSend wordU16-
MDI_MODMDI modeReceive wordU16-

Definitions of Control Words

STW1 Control Word (for Telegrams 1 and 3)
SignalDescription
STW1.01 = ON (Allow enabling pulses), 0 = OFF1 (Ramp to stop, disable pulses, and get ready for switching on)
STW1.11 = No OFF2 (Allow enabling), 0 = OFF2 (Coast to stop, disable pulses, and inhibit switching on)
STW1.21 = No OFF3 (Allow enabling), 0 = OFF3 (Quick stop, disable pulses, and inhibit switching on)
STW1.31 = Allow running, 0 = Inhibit running
STW1.41 = Running condition, 0 = Freeze command
STW1.51 = Running condition, 0 = Freeze command
STW1.61 = Enable setpoint, 0 = Disable setpoint
STW1.70-1 rising edge: Acknowledgment fault
STW1.8Reserved
STW1.9Reserved
STW1.101 = Control through PLC, 0 = Not control through PLC
STW1.111 = Start referencing, 0 = Stop referencing
STW1.12Reserved
STW1.13Reserved
STW1.14Reserved
STW1.15Reserved
STW1 Control Word (for Telegram 111)
SignalDescription
STW1.01 = ON (Allow enabling pulses), 0 = OFF1 (Ramp to stop, disable pulses, and get ready for switching on)
STW1.11 = No OFF2 (Allow enabling), 0 = OFF2 (Coast to stop, disable pulses, and inhibit switching on)
STW1.21 = No OFF3 (Allow enabling), 0 = OFF3 (Quick stop, disable pulses, and inhibit switching on)
STW1.31 = Allow running, 0 = Inhibit running
STW1.41 = Do not reject traversing task, 0 = Reject traversing task
STW1.51 = Do not pause traversing task, 0 = Pause traversing task
STW1.60-1 rising edge: Activate traversing task
STW1.70-1 rising edge: Acknowledgment fault
STW1.81 = Enable JOG1, 0 = Disable JOG1
STW1.91 = Enable JOG2, 0 = Disable JOG2
STW1.101 = Control through PLC, 0 = Not control through PLC
STW1.111 = Start referencing, 0 = Stop referencing
STW1.12Reserved
STW1.13Reserved
STW1.14Reserved
STW1.15Reserved
STW2 Control Word (for Telegrams 1, 3, and 111)
SignalDescription
STW2.0-STW2.11Reserved
STW2.12Master sign-of-life, bit 0
STW2.13Master sign-of-life, bit 1
STW2.14Master sign-of-life, bit 2
STW2.15Master sign-of-life, bit 3
POS_STW1 Positioning Control Word (for Telegram 111)
SignalDescription
POS_STW1.0Traversing blocks selection, bit
POS_STW1.1Traversing blocks selection, bit
POS_STW1.2Traversing blocks selection, bit
POS_STW1.3Traversing blocks selection, bit
POS_STW1.4Reserved
POS_STW1.5Reserved
POS_STW1.6Reserved
POS_STW1.7Reserved
POS_STW1.81 = Absolute positioning, 0 = Relative positioning
POS_STW1.9Absolute positioning, bit 0
POS_STW1.10Absolute positioning, bit 1
POS_STW1.11Reserved
POS_STW1.121 = Continuous transfer, 0 = Activate MDI block update with the rising edge of traversing blocks (STW1.6)
POS_STW1.13Reserved
POS_STW1.141 = Setting-up signal selected, 0 = Positioning signal selected
POS_STW1.151 = MDI selection
POS_STW2 Positioning Control Word (for Telegram 111)
SignalDescription
POS_STW2.0Reserved
POS_STW2.1Velocity limit activated
POS_STW2.2Reserved
POS_STW2.3Reserved
POS_STW2.41 = Axis moving forward, 0 = Axis not moving
POS_STW2.51 = Axis moving backward, 0 = Axis not moving
POS_STW2.61 = Negative soft limit switch reached
POS_STW2.71 = Positive soft limit switch reached
POS_STW2.8Reserved
POS_STW2.9Reserved
POS_STW2.10Reserved
POS_STW2.11Reserved
POS_STW2.12Reserved
POS_STW2.13Reserved
POS_STW2.141 = Activate the soft limit switch, 0 = Deactivate the soft limit switch
POS_STW2.151 = Activate the hard limit switch, 0 = Deactivate the hard limit switch

Definitions of Status Words

ZSW1 Status Word (for Telegrams 1 and 3)
SignalDescription
ZSW1.01 = Ready for switching on, 0 = Not ready for switching on
ZSW1.11 = Ready for operation, 0 = Not ready for operation
ZSW1.21 = Operation enabled, 0 = Operation disabled
ZSW1.31 = Fault present, 0 = No fault
ZSW1.41 = Coast-to-stop inactive, 0 = Coast-to-stop active
ZSW1.51 = Quick stop inactive, 0 = Quick stop active
ZSW1.61 = Inhibit switching on active, 0 = Inhibit switching on inactive
ZSW1.71 = Alarm present, 0 = No alarm
ZSW1.81 = Velocity error within tolerance, 0 = Velocity error exceeding tolerance
ZSW1.91 = Have control request, 0 = No control request
ZSW1.101 = Reference velocity reached or exceeded, 0 = Reference velocity not reached or exceeded
ZSW1.11Reserved
ZSW1.12Reserved
ZSW1.13Reserved
ZSW1.14Reserved
ZSW1.15Reserved
ZSW1 Status Word (for Telegram 111)
SignalDescription
ZSW1.01 = Ready for switching on, 0 = Not ready for switching on
ZSW1.11 = Ready for operation, 0 = Not ready for operation
ZSW1.21 = Operation enable, 0 = Operation disable
ZSW1.31 = Fault present, 0 = No fault
ZSW1.41 = Coast-to-stop inactive, 0 = Coast-to-stop active
ZSW1.51 = Quick stop inactive, 0 = Quick stop active
ZSW1.61 = Inhibit switching on active, 0 = Inhibit switching on inactive
ZSW1.71 = Alarm present, 0 = No alarm
ZSW1.81: Position following error within tolerance, 0: Position following error exceeding tolerance
ZSW1.91 = Have control request, 0 = No control request
ZSW1.101 = Target position reached, 0 = Target position not reached
ZSW1.111 = Reference point set, 0 = Reference point not set
ZSW1.120-1 rising edge: Positioning activated, movement task confirmed
ZSW1.131 = Drive stopped, 0 = Drive running
ZSW1.141 = Drive accelerating, 0 = Drive not accelerating
ZSW1.151 = Drive decelerating, 0 = Drive not decelerating
ZSW2 Status Word (for Telegrams 1, 3, and 111)
SignalDescription
ZSW2.0~ZSW2.9Reserved
ZSW2.101 = Pulses enabled
ZSW2.11Reserved
ZSW2.12Slave sign-of-life, bit 0
ZSW2.13Slave sign-of-life, bit 1
ZSW2.14Slave sign-of-life, bit 2
ZSW2.15Slave sign-of-life, bit 3
POS_ZSW1 Status Word (for Telegram 111)
SignalDescription
POS_ZSW1.0Traversing blocks bit 0 activated
POS_ZSW1.1Traversing blocks bit 1 activated
POS_ZSW1.2Traversing blocks bit 2 activated
POS_ZSW1.3Traversing blocks bit 3 activated
POS_ZSW1.4Reserved
POS_ZSW1.5Reserved
POS_ZSW1.6Reserved
POS_ZSW1.7Reserved
POS_ZSW1.81 = Negative hard limit activated, 0 = Negative hard limit not activated
POS_ZSW1.91 = Positive hard limit activated, 0 = Positive hard limit not activated
POS_ZSW1.101 = JOG mode activated, 0 = JOG mode not activated
POS_ZSW1.111 = Reference point approach activated, 0 = Reference point approach not activated
POS_ZSW1.12Reserved
POS_ZSW1.131 = Traversing blocks activated
POS_ZSW1.14Reserved
POS_ZSW1.151 = MDI activated, 0 = MDI not activated
POS_ZSW2 Status Word (for Telegram 111)
SignalDescription
POS_ZSW2.0Reserved
POS_ZSW2.1Velocity limit activated
POS_ZSW2.2Reserved
POS_ZSW2.3Reserved
POS_ZSW2.41 = Axis moving forward, 0 = Axis not moving
POS_ZSW2.51 = Axis moving backward, 0 = Axis not moving
POS_ZSW2.61 = Negative soft limit switch reached
POS_ZSW2.71 = Positive soft limit switch reached
POS_ZSW2.8Reserved
POS_ZSW2.9Reserved
POS_ZSW2.10Reserved
POS_ZSW2.11Reserved
POS_ZSW2.12Reserved
POS_ZSW2.13Reserved
POS_ZSW2.14Reserved
POS_ZSW2.15Reserved

9. Troubleshooting

9.1. Troubleshooting Checklist

Troubleshooting checklist diagram
Troubleshooting checklist for common issues.

Reset Operation

  • Set F31.00 (Fault reset) to 1 to stop displaying the fault on the panel.
  • To reset resettable faults, switch off the S-ON signal first and then send the fault reset signal (set F31.00 to 1).
  • To reset resettable alarms, eliminate the alarm source and then the servo drive automatically resets the alarms.

CAUTION

  • Some faults/alarms can only be reset after the causes are rectified through setting modifications. However, a reset operation does not activate modifications.
  • If the modification can be effective only after power-on, power on the device again.
  • If the modification can be effective only after stop, turn off the S-ON signal. The servo drive can operate properly only after modifications are activated.

9.2. List of Faults and Alarms

List of Factory Fault Codes (Class 1)

Fault GroupFault CodeFault NameBus Fault CodeResettable
Class 1Er01.0Mismatch of software versions0x6100Non-resettable
Er01.1Mismatch of motor parameters0x7122Non-resettable
Er02.0Product matching fault. No specified drive0x6100Non-resettable
Er02.1Product matching fault. No specified motor0x6100Non-resettable
Er02.2Product matching fault. No specified encoder0x6100Non-resettable
Er03.0System parameter error0x6320Non-resettable
Er03.1Parameter out-of-range0x6320Non-resettable
Er03.2Parameter writing error0x6320Non-resettable
Er03.3Parameter reading error0x6320Non-resettable
Er04.0FPGA power-on check error0x6100Non-resettable
Er04.1FPGA power-on not reset0x6100Non-resettable
Er04.2FPGA transmission interrupted0x6100Non-resettable
Er05.0Current loop timeout0x7500Non-resettable
Er05.1Speed loop timeout0x7500Non-resettable
Er05.2Position loop timeout0x7500Non-resettable
Er06.0Protection from out of control0x8400Non-resettable
Er10.0P-hardware overcurrent0x2312Non-resettable
Er10.1N-hardware overcurrent0x2312Non-resettable
Er10.2U phase software overcurrent0x2312Non-resettable
Er10.3V phase software overcurrent0x2312Non-resettable
Er10.4Output short circuited to ground0x2330Non-resettable
Er10.5Current sampling failure0x6100Non-resettable
Er10.6Incorrect current parameter setting0x6320Non-resettable
Er10.7UV current correction failure0x6100Non-resettable
Er10.8Excessive current zero drift0x6100Non-resettable
Er10.9Current exception during enabling0x2312Non-resettable
Er11.0Excessive motor speed upon servo drive power-on-Non-resettable
Er11.1Drive over-temperature0x2312Non-resettable
Er12.0PWM buffer detection failure-Non-resettable
Er20.1Encoder internal fault0x7305Non-resettable
Er20.2Encoder reading/writing error0x7305Non-resettable
Er20.3Encoder data frame loss0x7305Non-resettable
Er20.4Excessive encoder incremental position0x7305Non-resettable
Er20.5Abnormal encoder data0x7305Non-resettable
Er20.6Mismatch of encoder type0x7305Non-resettable
Er20.7Encoder model not supported0x7305Non-resettable
Er20.8Encoder battery failure0x7305Non-resettable
Er20.9Encoder multi-turn error0x7305Non-resettable
Er21.0Mismatch between encoder pulses per revolution and drive pulses per revolution0x7305Non-resettable
Er22.0Second encoder disconnection0x7305Non-resettable
Er32.8200P parallel port check failure-Non-resettable
Er32.9Mismatch between 200P version and MCU version-Non-resettable
Er40.0Drive overload0x3230Resettable
Er41.0Motor overload0x3230Resettable
Er41.1Motor over-temperature due to locked-rotor0x7121Resettable
Er41.2Motor over-temperature0x4210Resettable
Er42.0IGBT temperature too high0x4210Resettable
Er42.1Discharge tube temperature too high0x4210Resettable
Er42.2Heatsink temperature too high0x4210Resettable
Er43.0Overvoltage0x3210Resettable
Er43.1Undervoltage0x3220Resettable
Er45.0S-ON enabling failure0xFF00Resettable
Er46.0Motor overspeed0x8400Resettable
Er47.0Excessive position deviation0x8611Resettable
Er47.1Position deviation overflow0x8611Resettable
Er47.2Excessive fully closed-loop mixed deviation0x8611Resettable
Er48.0STO status exception0x0480Resettable
Er48.1STO buffer 5 V power fault0x0481Resettable
Er48.2Optocoupler fault in STO pulse detection0x0482Resettable
Er48.3STO buffer detection failure0x0483Resettable
Er50.1D/Q current overflow0x6100Resettable
Er51.0Offline inertia auto-tuning failure0x6310Resettable
Er51.1Offline inertia parameter error0x6310Resettable
Er52.0Angle auto-tuning failure0x7122Resettable
Er53.0Motor parameter auto-tuning timeout0x7122Resettable
Er53.1Resistance parameter auto-tuning failure0x7122Resettable
Er53.2Inductance parameter auto-tuning failure0x7122Resettable
Er53.3Back EMF parameter auto-tuning failure0x7122Resettable
Er54.0Current loop auto-tuning failure0x7122Resettable
Er55.0Excessive vibration0x7122Resettable
Er80.0Control power undervoltage0x3120Resettable
Er81.0Input phase loss 10x3130Resettable
Er81.1Input phase loss 20x3130Resettable
Er81.2Output phase loss-Resettable
Er82.0DI function allocation fault0x6320Resettable
Er82.1DO function allocation fault0x6320Resettable
Er82.2VDI function allocation fault0xFF00Resettable
Er82.3VDO function allocation fault0xFF00Resettable
Er84.0Electronic gear ratio setting error0x6320Resettable
Er84.1Software limit setting error0x6320Resettable
Er84.2Encoder resolution setting error0x7122Resettable
Er84.3Home position setting error0xFF00Resettable
Er87.3Overflow of 32-bit sign bit of the target position during limiting0xFF00Resettable
Er87.4Target position exceeding maximum value of mechanical single-turn position in rotating mode0xFF00Resettable
ErA0.1Multi-turn overflow fault0x7305Resettable
ErC2.1DSC cannot be used in non-IRT mode-Resettable
ErC1.4Unreliable network cable connection, disconnected in network operating mode-Resettable
ErC1.8Bus switched from operational to non-operational state-Resettable
ErC1.1IRT synchronization lost-Resettable
ErC1.2PN network switched to disconnected status when enabled-Resettable
ErC2.3Network parameters cannot be set with network cable connected-Resettable

List of Factory Alarm Codes (Class 3)

Fault GroupAlarm CodeAlarm NameBus Fault CodeResettable
Class 3ALF0.0Emergency stop alarm0xF00Resettable
ALF1.0Re-power-on required for parameter settings to take effect0x6320Resettable
ALF1.1Frequent parameter storage alarm0x5530Resettable
ALF1.2Torque reached parameter error0x6320Resettable
ALF1.3Excessive parameter write frequency from the host controller-Resettable
ALF2.0Forward overtravel alarm0x5443Resettable
ALF2.1Reverse overtravel alarm0x5444Resettable
ALF2.2Position limit warning in absolute linear mode-Resettable
ALF4.0Homing timeout0x6320Resettable
ALF4.1Homing DI conflict0x6320Resettable
ALF4.2Homing mode conflict0x6320Resettable
ALF5.0Braking resistor overload0x3210Resettable
ALF5.1Too small resistance of external regenerative resistor0x6320Resettable
ALF6.1Output phase loss0x3230Resettable
ALF7.1Program block limit exceeded (PN)-Resettable
ALF7.2MDI absolute position setpoint exceeding soft limit value (PN)-Resettable
ALF8.0Vibration occurred during auto-tuning0x7122Resettable
ALF9.0Encoder battery voltage low0x7305Resettable

10. User Tips

No specific user tips were available from provided reviews or Q&A content. Always refer to the detailed instructions for optimal performance and safety.

11. Warranty and Support

For warranty information, technical support, or service inquiries, please contact STEPPERONLINE customer service or visit their official website. Ensure to have your product model and serial number ready for faster assistance.

© 2023 STEPPERONLINE. All rights reserved.