Contents

ZL-7815A Incubator Controller User Manual

Model: ZL-7815A | Brand: Lilytech

1. Introduction

The ZL-7815A is a versatile incubator controller designed for precise temperature management, egg turning, and air exhaustion control. It features two independent timers and a temperature control output, making it suitable for various incubation needs. This manual provides detailed instructions for installation, operation, and troubleshooting to ensure optimal performance of your incubator controller.

ZL-7815A Incubator Thermostat with two external timers, sensor, and a chick
Figure 1: ZL-7815A Incubator Thermostat with two external timers, sensor, and a chick.
ZL-7815A Incubator Thermostat controller with attached temperature sensor
Figure 2: ZL-7815A Incubator Thermostat controller with attached temperature sensor.

2. Specifications

Feature Specification
Power Supply 100~240Vac, 50/60Hz
Sensor NTC, R25=10K, B25/85=3435K
Setting Range 1.0 ~ 75.0°C
Display Range -9.9 ~ 99.9°C
Terminal 2*1.5mm², or 1*2.5mm²
Output R1 (Temperature Control) 16A/250Vac (Resistive)
Output R3/R4 (Egg Tray Timer) 3A/250Vac (Resistive)
Output R5 (Timer 2 / Over Temp. Protection) 5A/250Vac (Resistive)
Working Conditions -10~45°C, 5~85%RH (without dew)
Case Materials PC + ABS, fireproof
Protection Level IP65 (Front side only)
Dimensions (W x H x D) 78 x 34.5 x 71 mm
Installation Drilling (W x H) 71 x 29 mm
Material Plastic
Type Medium-sized Incubator Controller
Egg Turning Mode Automatic Egg Turning
Usage Chicken, Reptile, Bird, Emu, Ostrich, Turkey, Goose, Duck
Hatching Rate 90% (Controller capability, actual rate depends on setup)
Voltage 220V (Note: Power supply is 100-240Vac)
Key Selling Points Multifunctional
Side view of the ZL-7815A controller showing wiring terminals and specifications
Figure 3: Side view of the ZL-7815A controller showing wiring terminals and specifications.

3. Installation and Wiring

3.1 Physical Installation

  1. Insert into drilling hole: Prepare a rectangular opening of W71 x H29 mm in your incubator panel.
  2. Clamp: Insert the controller into the opening and secure it using the provided clamps from the rear.
Page 2 of the ZL-7815A manual, showing installation steps
Figure 4: Installation diagram for the ZL-7815A controller.

3.2 Wiring Diagram

Connect the power supply, sensor, and output loads according to the diagram below. Ensure all connections are secure and correct before applying power.

Wiring diagram for the ZL-7815A Incubator Thermostat
Figure 5: ZL-7815A Wiring Diagram. R1: Temp. Control (16A/250Vac), R3/R4: Timer 1 (3A/250Vac), R5: Timer 2 / Over Temp. protection (5A/250Vac), L/N: 100~240Vac Power, Sensor: Terminals 9 & 10.

Important: Do not install the sensor under power. Ensure the power supply matches the controller's specifications (100-240Vac).

4. Operating Instructions

4.1 Keypad and Display

Front panel of the ZL-7815A controller displaying '20.5' and control buttons (S, P, T1%, CNT)
Figure 6: ZL-7815A Controller Front Panel with buttons (S, P, T1%, CNT) and indicators (Set, T2, H/C).
  • S (Set): Used to enter/exit set-point adjustment and confirm parameter values.
  • P (Parameter): Used to enter/exit system parameter settings.
  • T1% (Up/Timer 1): Used to increase values or manually switch Timer 1 (R3/R4) status.
  • CNT (Down/Counter): Used to decrease values or display the R3/R4 switching counter.
  • Indicators: Set (Yellow), T2 (Green), H/C (Red).

4.2 Fast Check

  • Press T1% (Up arrow) for 5 seconds to manually switch the outputs R3 and R4 status.
  • Press CNT (Down arrow) to display the counter value for 2 seconds. The 'Set' lamp will blink at 2Hz.

4.3 Setting the Temperature Set-Point

The factory default set-point is 37.8°C.

  1. Press the S key for 3 seconds. The 'Set' lamp will blink, and the current set-point will be displayed.
  2. Use the T1% (Up arrow) or CNT (Down arrow) keys to adjust the value.
  3. Keep the S key pressed to exit the setting mode. The new set-point will be saved.

4.4 Setting System Parameters

  1. Press the P key for 3 seconds. The 'Set' lamp will blink, and the first system parameter code (e.g., U10) will be displayed.
  2. Use the T1% (Up arrow) or CNT (Down arrow) keys to select the desired parameter code.
  3. Press the S key to display the value of the selected parameter code.
  4. Use the T1% (Up arrow) or CNT (Down arrow) keys to adjust the value.
  5. Keep the S key pressed to exit the parameter value adjustment.
  6. Press the P key for 3 seconds to exit the system parameter setting mode. All changes will be saved.
Page 1 of the ZL-7815A manual, covering Operation, Keypad and Display functions, and System Parameter Table (U10-U19)
Figure 7: Manual Page 1 - Operation and System Parameters (U10-U19).
Page 3 of the ZL-7815A manual, presenting the System Parameter Table (U20-U40)
Figure 8: Manual Page 3 - System Parameters (U20-U40).

4.5 Temperature Control (R1 Output)

The controller supports both cooling and heating modes, determined by parameter U10.

  • Cooling Mode (U10 = CO):
    • R1 is energized when Room Temp. ≤ Set-point + Hysteresis (U11).
    • R1 is de-energized when Room Temp. ≥ Set-point + Hysteresis (U11).
  • Heating Mode (U10 = HE):
    • R1 is energized when Room Temp. ≥ Set-point - Hysteresis (U11).
    • R1 is de-energized when Room Temp. ≤ Set-point - Hysteresis (U11).

Delay Protection for R1: After power is supplied, R1 will energize only after the delay protection time (U12) has passed. Similarly, after R1 de-energizes, it will only energize again after U12 has passed.

4.6 Timer 1 (R3 and R4 Outputs) for Egg Turning

Timer 1 is controlled by parameters U20 to U24.

  • R3/R4 Switching Counter: The counter tracks the switching cycles. If U24 is set to 0, R3/R4 will switch continuously. If U24 is set to a value greater than 0, R3/R4 will stop switching once the counter reaches U24.
  • To check the counter value, press CNT. The value will display for 2 seconds, and the 'Set' lamp will blink at 2Hz.
  • Manually Switching R3/R4: Keep T1% (Up arrow) pressed for 5 seconds to manually switch the R3 and R4 outputs. After manual switching, the next automatic switch will occur after the full set time (U20 to U23) has elapsed.

4.7 Timer 2 / Over Temperature Protection (R5 Output)

The R5 output has multiple functions, configured by parameter U34.

  • As Timer 2 Output (U34 = 1 or 3): R5 will be energized during the time set by U32 and U33. It will de-energize when the time is up.
  • As High Temperature Protecting Output (U34 = 2 or 3, only in heating mode): If the room temperature is greater than or equal to (Set-point + U16) for the duration of U19, R5 will be energized. If the temperature drops below (Set-point + U16 - U17), R5 will de-energize, stopping the high temperature protection.

4.8 Temperature Warning

Temperature warnings are active when U40 is set to 1. If U40 is 0, no buzzing warning will occur.

  • High Temperature Warning: If Room Temp. ≥ Set-point + U14, the controller will beep and display "Hi" alternately. The warning stops when Room Temp. < Set-point + U14.
  • Low Temperature Warning: If Room Temp. ≤ Set-point - U15, the controller will beep and display "Lo" alternately. The warning stops when Room Temp. > Set-point - U15.
  • Warning Delay: After power is supplied, the temperature warning will not be effective until the 1st Temp. warning delay time (U18) has passed.

4.9 Buzzer Warning

When U40 = 1, the buzzer will sound for warnings. Press any key to stop the beeping sound.

5. Maintenance

5.1 Restore to Factory Default Settings

To restore all settings to their factory defaults:

  1. Keep the P key and T1% (Up arrow) key depressed simultaneously for 3 seconds. The controller will display "UnL".
  2. Press the P key once. All settings will be restored to the factory default values (refer to the System Parameter Tables for default values).

5.2 Sensor Calibration

If the measured temperature is not accurate, you can calibrate it by adjusting parameter U13 (Temperature calibration). Ensure the sensor is properly connected and not damaged before attempting calibration.

6. Troubleshooting

The controller provides display codes to indicate certain issues:

  • E1: Sensor failure (short circuit or open circuit). Check sensor connections and the sensor itself. Replace if damaged.
  • Hi: High temperature alarming. The measured temperature has exceeded the high temperature warning threshold (Set-point + U14).
  • Lo: Low temperature alarming. The measured temperature has fallen below the low temperature warning threshold (Set-point - U15).

If the sensor is not connected or is broken, the display will show "E1". Ensure the sensor is correctly wired to terminals 9 and 10.

7. User Tips

  • Initial Setup: Always perform a fast check of the outputs after initial wiring to ensure they respond as expected.
  • Temperature Calibration: If you suspect temperature inaccuracies, use a reliable external thermometer to verify the incubator temperature and calibrate the controller using parameter U13 if necessary.
  • Timer Settings: Carefully review and set parameters U20-U24 for Timer 1 (egg turning) and U30-U33 for Timer 2 (R5 output) to match your specific incubation requirements.
  • Safety First: Double-check all wiring connections before powering on the device to prevent damage to the controller or connected equipment.
  • Environmental Conditions: Ensure the controller operates within its specified working conditions (-10~45°C, 5~85%RH without dew) for longevity and accuracy.

8. Warranty and Support

This ZL-7815A Incubator Controller comes with a 1-Year Warranty from the date of purchase, covering manufacturing defects. Please retain your proof of purchase for warranty claims.

For technical support or warranty inquiries, please contact your retailer or the manufacturer's customer service. Provide your product model number (ZL-7815A) and a detailed description of the issue to facilitate assistance.