SmartGen ACC5100 Diesel Driven Air Compressor Controller User Manual

Model: ACC5100 | Brand: SmartGen

1. Introduction

The SmartGen ACC5100 is a sophisticated controller designed for diesel-driven air compressors. It integrates advanced control features with RS485 CANBUS communication capabilities, providing comprehensive monitoring and management for optimal compressor performance. This manual provides detailed instructions for installation, operation, maintenance, and troubleshooting of the ACC5100 controller.

Front view of the SmartGen ACC5100 diesel air compressor controller.
Figure 1: Front view of the ACC5100 Controller.

2. Setup and Installation

2.1. Installation Method

The ACC5100 controller is designed for panel built-in installation. It is fixed using four M4 screws and nuts, corresponding to the four screw holes on the controller.

2.2. Overall & Cutout Dimensions

Diagram showing the overall and cutout dimensions of the ACC5100 controller in millimeters.
Figure 2: Overall and Cutout Dimensions (Unit: mm).

Dimensions:

  • Height: 180 mm
  • Width: 145 mm
  • Depth: 49 mm (front panel to back)

Cutout Dimensions:

  • Height: 162 mm
  • Width: 130 mm

2.3. Wiring Connection

Ensure all connections are correct and secure before commissioning. The controller requires a DC power supply, and its positive and negative terminals must be correctly connected.

Back panel of ACC5100 controller showing various connection terminals.
Figure 3: ACC5100 Controller Back Panel with Connection Terminals.
Detailed wiring diagram for the ACC5100 controller showing connections for battery, sensors, outputs, and engine components.
Figure 4: ACC5100 Typical Application Diagram.

Key Connection Details:

  • Battery Voltage Input: The ACC5100 controller can support battery voltage environments of 8-35VDC. The negative of the battery must be connected with the engine shell. The diameter of wires connecting the power supply (B+ and B-) with battery positive and negative must be over 1.5mm².
  • Speed Sensor Input: The speed sensor is the engine speed sensor installed in the starter for detecting flywheel teeth. The connection wires with controller should apply 2-core shielded line. The shielded layer should be connected to Terminal 32 in the controller and another side is hanging up in the air.
  • Output and Expansion Relays: All controller outputs are relay contact output. If expansion relays are needed, please add freewheel diode to both ends of expansion relay's coils (when relay coils have DC current) or increase resistance-capacitance return circuit (when relay coils have AC current), in order to prevent disturbance to the controller or other equipment.

Table 1: Connection Terminals Description (Partial)

No.TypeRemark
1Aux. Sensor 1Configure by user (Resistance/current/voltage type)
2Aux. Sensor 2Configure by user (Resistance/current/voltage type)
3Aux. Sensor 3Configure by user (Resistance/current/voltage type)
4DC5VPower supply for voltage type sensor.
5Sensor COM (B-)Common terminal of sensor. It is already connected with B- internally.

3. Operating Instructions

3.1. Controller Panel Overview

Front panel of ACC5100 controller with labels for all buttons, indicators, and the display screen.
Figure 5: ACC5100 Front Panel.

3.2. Key Functions Description

The controller features several keys for operation and configuration:

IconKeysFunction Description
Start Key iconStartPress to start the air compressor when it is under stop status.
Load/Unload Key iconLoad/UnloadAt idle speed status, press it and the load relay of controller will output; at normal running status, press it again and controller shall unload and the load relay stops output.
Alarm Reset/Return Key iconAlarm Reset/Return1. In the home page, press it to enter the alarm page quickly, press it again to reset the alarm; after alarm is reset, press it again to exit from the alarm page.
2. In parameter setting page, press it to return the previous menu.
Stop Key iconStop1. Stop the running air compressor at start status.
2. Press and hold it for 3s or longer, test whether panel indicators are normal (lamp test).
Maintenance Key iconMaintenancePress it to enter the maintenance page; press it again and exit from the page; press and hold it in the page to enter the password interface; Enter the password and maintenance setting is entered.
Up/Increase Key iconUp/Increase1. Scroll up.
2. Move up cursor or increase the value in setting menu.
Down/Decrease Key iconDown/Decrease1. Scroll down.
2. Move down cursor or decrease the value in setting menu.
Set/Confirm Key iconSet/Confirm1. In the home page, press it to enter the parameter setting menu.
2. Confirm the settings in the parameter settings.
Power On/Off switch iconPower On/OffControl the power supply of controller.
High/Low Pressure switch iconHigh/Low PressureSelect the high or low pressure. If low pressure is selected, the air compressor runs at low pressure value configured in the user parameter setting. If high pressure is selected, the air compressor runs at high pressure value configured in the user parameter setting.
Emergency Stop button iconEmergency StopPress it to switch off the power of auxiliary output 1 (fuel relay output), auxiliary output 2 (start relay output), and stop the air compressor at the same time.

3.3. Start/Stop Operation Sequence

  1. Press the Start key to start the air compressor.
  2. If pre-heat time is configured, then pre-heat relay outputs (if configured). LCD displays "pre-heat delay xx".
  3. After pre-heat delay is over, fuel relay outputs pre-fuel time before start (default 1s), then starting relay outputs; if air compressor crank doesn't fail during "crank time", then fuel relay and starting relay stop outputting, and enter "crank rest time", waiting for next start.
  4. After the pre-set start attempts, if air compressor doesn't succeed to start, then controller issues failed to start alarm, and meanwhile LCD alarm page displays "Failed to Start" alarm.
  5. During any one of the start attempts, if crank disconnect is fulfilled, then it enters "Safety On Delay", during which oil low pressure, water temperature high, under speed, and charging failure alarms are all inactive; after safety on delay it enters "Start Idle Delay" (if configured).
  6. After "Start Idle Time" it enters idling run; if load delay is present, then it enters "Warming Up Time" (if configured).
  7. To stop the compressor, press the Stop key.

3.4. DPF Regeneration

The controller supports DPF (Diesel Particulate Filter) regeneration. The DPF regeneration panel can be accessed via the controller menu.

DPF Regeneration Panel with icons for engine fault, NCD status, exhaust temperature, manual request, inhibition, response, and driver alarm indicators.
Figure 6: DPF Regeneration Panel.

To perform DPF manual regeneration:

  1. Configure an input port and set it as "DPF Manual Regeneration Request", and connect it with a button (non-latching) externally.
  2. Press the Set/Confirm key on the controller panel and enter the parameter setting menu.
  3. Scroll to and select "DPF Regeneration" to access the DPF regeneration panel.
  4. Press "DPF Manual Regeneration Request" button again. DPF regeneration response indicator lights on and DPF exhaust temperature indicator always lights on.
  5. When manual regeneration is completed, DPF regeneration response indicator and DPF exhaust temperature indicator both go out.

4. Maintenance

4.1. Maintenance Settings

The ACC5100 controller allows for configurable maintenance settings to ensure timely servicing of the air compressor.

Table showing various maintenance settings like Enable Choose, Maintenance Time, Maintenance Due Action, and their descriptions.
Figure 7: Table 15 Maintenance Setting.

Table 2: Maintenance Setting Parameters (Partial)

ItemContentDescription
Enable Choose0: Disabled, 1: EnabledSet maintenance function active or not.
Maintenance Time(0-30000)hIt is the number of hours from the time the maintenance is enabled to when maintenance is required.
Maintenance Due Action0: No Action; 1: Warning; 2: Shutdown; 3: Indication.Alarm action when maintenance left time is 0.
Maint. Timing Method0: Running Time; 1: Real Time ClockThe timing of maintenance.
Pre-maint. Time(0-30000)hAlarm action when pre-maintenance left time is 0.
Maintenance DateYear (2000-2099) 2025; Month (1-12) 12; Day (1-31) 31The date for pre-maintenance if maintenance function is enabled.
Reset MaintenanceAfter maintenance completion, through this item reset maintenance time.
Maintenance DescriptionThe character string of maintenance description can be set by maintenance 8, 9 and 10. Users can input maintenance name, like Change Engine Oil.

4.2. Parameter Setting

To access and modify parameters:

  1. Press the Set/Confirm key and enter the controller menu.
  2. Navigate to "Manufacturer Parameters" and input the correct password (default: 01234) to enter the manufacturer parameters setting interface.
  3. Use the Up/Increase and Down/Decrease keys to scroll through options and adjust values.
  4. Press the Set/Confirm key to confirm changes.
  5. Press the Alarm Reset/Return key to go back to the previous screen or exit the menu.

5. Troubleshooting

The ACC5100 controller provides various warnings and shutdown alarms to indicate operational issues. When an alarm occurs, the controller immediately stops the engine (for shutdown alarms) or issues a warning. Press the Alarm Reset/Return button to remove alarms.

5.1. Warnings

Warnings indicate potential issues that do not immediately stop the engine but require attention.

Table listing various warnings and their descriptions for the ACC5100 controller.
Figure 8: Table 6 Warnings.

Table 3: Common Warnings (Partial)

No.TypeDescription
1Over Speed WarnWhen controller detects speed is above the pre-set over speed warning threshold, it issues warning signal.
2Under Speed WarnWhen controller detects speed is below the pre-set under speed warning threshold, it issues warning signal.
3Loss of Speed SignalWhen controller detects speed is 0, and speed signal loss action is selected "Warning", it issues warning signal.
4Failed to StopWhen engine stop delay is over and engine doesn't stop completely, controller issues warning signal.
5Charging FailureWhen controller detects engine charger voltage is less than pre-set threshold, it issues warning alarm signal.

5.2. Shutdown Alarms

Shutdown alarms indicate critical issues that cause the engine to stop immediately to prevent damage.

Table listing various shutdown alarms and their descriptions for the ACC5100 controller.
Figure 9: Table 7 Shutdown Alarms.

Table 4: Common Shutdown Alarms (Partial)

No.TypeDescription
1Emergency StopWhen controller detects emergency stop alarm signal, it issues emergency stop alarm signal.
2Overspeed ShutWhen controller detects engine speed is over pre-set over speed stop threshold, it issues shutdown alarm signal.
3Underspeed ShutWhen controller detects engine speed is below pre-set under speed stop threshold, it issues shutdown alarm signal.
4Loss of Speed SignalWhen controller detects speed is 0 and speed signal loss action is selected "Shutdown", it issues shutdown alarm signal.
5Failed to StartWhen engine fails to start during pre-set start attempts, controller issues failed to start alarm signal.

5.3. Sensor Setting

The controller allows for configuration of sensor curves. If a sensor needs to be changed, the sensor curve will be transferred into the standard value. For example, if the default temperature sensor is SGD, the sensor curve is SGD curve; if it is set SGX, the temperature sensor curve is SGX curve.

Graph showing a sensor curve setting with KPa vs. Ohm values.
Figure 10: Sensor Curve Setting (Figure 7 from manual).

Table 5: Common Pressure Unit Conversion Table

ItemN/m² (Pa)kgf/cm²Bar(psi)
1 KPa1.0x10³0.01020.010.145
1 Bar1.0x10⁵1.02114.5
1 psi6.89x10³0.07030.06891

6. Specifications

FeatureDetail
Model NumberACC5100
Brand NameSAIWEI (SmartGen)
ApplicationDiesel Driven Air Compressor Controller
CommunicationRS485 CANBUS
ElectrifiedYes
OriginMainland China
Power Supply8-35VDC
Dimensions (H x W x D)180 mm x 145 mm x 49 mm
Cutout Dimensions (H x W)162 mm x 130 mm

7. User Tips

  • Always ensure proper grounding for all electrical connections to prevent interference and ensure safety.
  • Regularly check the wiring connections for tightness and signs of wear or corrosion.
  • Familiarize yourself with the warning and shutdown alarm codes to quickly diagnose and address potential issues.
  • When performing maintenance, always disconnect power to the controller and associated equipment.
  • For optimal performance and longevity, adhere to the recommended maintenance schedules.

8. Warranty and Support

For warranty information, technical support, or service inquiries, please contact your authorized SmartGen dealer or the manufacturer directly. Keep your purchase records and model number handy for faster assistance.

9. Product Overview Video

Video showcasing a diesel generator set, illustrating the type of equipment the ACC5100 controller is designed to manage.
Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.