1. Introduction
The SmartGen ACC5100 is a sophisticated controller designed for diesel-driven air compressors. It integrates advanced control features with RS485 CANBUS communication capabilities, providing comprehensive monitoring and management for optimal compressor performance. This manual provides detailed instructions for installation, operation, maintenance, and troubleshooting of the ACC5100 controller.

2. Setup and Installation
2.1. Installation Method
The ACC5100 controller is designed for panel built-in installation. It is fixed using four M4 screws and nuts, corresponding to the four screw holes on the controller.
2.2. Overall & Cutout Dimensions

Dimensions:
- Height: 180 mm
- Width: 145 mm
- Depth: 49 mm (front panel to back)
Cutout Dimensions:
- Height: 162 mm
- Width: 130 mm
2.3. Wiring Connection
Ensure all connections are correct and secure before commissioning. The controller requires a DC power supply, and its positive and negative terminals must be correctly connected.


Key Connection Details:
- Battery Voltage Input: The ACC5100 controller can support battery voltage environments of 8-35VDC. The negative of the battery must be connected with the engine shell. The diameter of wires connecting the power supply (B+ and B-) with battery positive and negative must be over 1.5mm².
- Speed Sensor Input: The speed sensor is the engine speed sensor installed in the starter for detecting flywheel teeth. The connection wires with controller should apply 2-core shielded line. The shielded layer should be connected to Terminal 32 in the controller and another side is hanging up in the air.
- Output and Expansion Relays: All controller outputs are relay contact output. If expansion relays are needed, please add freewheel diode to both ends of expansion relay's coils (when relay coils have DC current) or increase resistance-capacitance return circuit (when relay coils have AC current), in order to prevent disturbance to the controller or other equipment.
Table 1: Connection Terminals Description (Partial)
| No. | Type | Remark |
|---|---|---|
| 1 | Aux. Sensor 1 | Configure by user (Resistance/current/voltage type) |
| 2 | Aux. Sensor 2 | Configure by user (Resistance/current/voltage type) |
| 3 | Aux. Sensor 3 | Configure by user (Resistance/current/voltage type) |
| 4 | DC5V | Power supply for voltage type sensor. |
| 5 | Sensor COM (B-) | Common terminal of sensor. It is already connected with B- internally. |
3. Operating Instructions
3.1. Controller Panel Overview

3.2. Key Functions Description
The controller features several keys for operation and configuration:
| Icon | Keys | Function Description |
|---|---|---|
| Start | Press to start the air compressor when it is under stop status. | |
| Load/Unload | At idle speed status, press it and the load relay of controller will output; at normal running status, press it again and controller shall unload and the load relay stops output. | |
| Alarm Reset/Return | 1. In the home page, press it to enter the alarm page quickly, press it again to reset the alarm; after alarm is reset, press it again to exit from the alarm page. 2. In parameter setting page, press it to return the previous menu. | |
| Stop | 1. Stop the running air compressor at start status. 2. Press and hold it for 3s or longer, test whether panel indicators are normal (lamp test). | |
| Maintenance | Press it to enter the maintenance page; press it again and exit from the page; press and hold it in the page to enter the password interface; Enter the password and maintenance setting is entered. | |
| Up/Increase | 1. Scroll up. 2. Move up cursor or increase the value in setting menu. | |
| Down/Decrease | 1. Scroll down. 2. Move down cursor or decrease the value in setting menu. | |
| Set/Confirm | 1. In the home page, press it to enter the parameter setting menu. 2. Confirm the settings in the parameter settings. | |
| Power On/Off | Control the power supply of controller. | |
| High/Low Pressure | Select the high or low pressure. If low pressure is selected, the air compressor runs at low pressure value configured in the user parameter setting. If high pressure is selected, the air compressor runs at high pressure value configured in the user parameter setting. | |
| Emergency Stop | Press it to switch off the power of auxiliary output 1 (fuel relay output), auxiliary output 2 (start relay output), and stop the air compressor at the same time. |
3.3. Start/Stop Operation Sequence
- Press the Start key to start the air compressor.
- If pre-heat time is configured, then pre-heat relay outputs (if configured). LCD displays "pre-heat delay xx".
- After pre-heat delay is over, fuel relay outputs pre-fuel time before start (default 1s), then starting relay outputs; if air compressor crank doesn't fail during "crank time", then fuel relay and starting relay stop outputting, and enter "crank rest time", waiting for next start.
- After the pre-set start attempts, if air compressor doesn't succeed to start, then controller issues failed to start alarm, and meanwhile LCD alarm page displays "Failed to Start" alarm.
- During any one of the start attempts, if crank disconnect is fulfilled, then it enters "Safety On Delay", during which oil low pressure, water temperature high, under speed, and charging failure alarms are all inactive; after safety on delay it enters "Start Idle Delay" (if configured).
- After "Start Idle Time" it enters idling run; if load delay is present, then it enters "Warming Up Time" (if configured).
- To stop the compressor, press the Stop key.
3.4. DPF Regeneration
The controller supports DPF (Diesel Particulate Filter) regeneration. The DPF regeneration panel can be accessed via the controller menu.

To perform DPF manual regeneration:
- Configure an input port and set it as "DPF Manual Regeneration Request", and connect it with a button (non-latching) externally.
- Press the Set/Confirm key on the controller panel and enter the parameter setting menu.
- Scroll to and select "DPF Regeneration" to access the DPF regeneration panel.
- Press "DPF Manual Regeneration Request" button again. DPF regeneration response indicator lights on and DPF exhaust temperature indicator always lights on.
- When manual regeneration is completed, DPF regeneration response indicator and DPF exhaust temperature indicator both go out.
4. Maintenance
4.1. Maintenance Settings
The ACC5100 controller allows for configurable maintenance settings to ensure timely servicing of the air compressor.

Table 2: Maintenance Setting Parameters (Partial)
| Item | Content | Description |
|---|---|---|
| Enable Choose | 0: Disabled, 1: Enabled | Set maintenance function active or not. |
| Maintenance Time | (0-30000)h | It is the number of hours from the time the maintenance is enabled to when maintenance is required. |
| Maintenance Due Action | 0: No Action; 1: Warning; 2: Shutdown; 3: Indication. | Alarm action when maintenance left time is 0. |
| Maint. Timing Method | 0: Running Time; 1: Real Time Clock | The timing of maintenance. |
| Pre-maint. Time | (0-30000)h | Alarm action when pre-maintenance left time is 0. |
| Maintenance Date | Year (2000-2099) 2025; Month (1-12) 12; Day (1-31) 31 | The date for pre-maintenance if maintenance function is enabled. |
| Reset Maintenance | After maintenance completion, through this item reset maintenance time. | |
| Maintenance Description | The character string of maintenance description can be set by maintenance 8, 9 and 10. Users can input maintenance name, like Change Engine Oil. |
4.2. Parameter Setting
To access and modify parameters:
- Press the Set/Confirm key and enter the controller menu.
- Navigate to "Manufacturer Parameters" and input the correct password (default: 01234) to enter the manufacturer parameters setting interface.
- Use the Up/Increase and Down/Decrease keys to scroll through options and adjust values.
- Press the Set/Confirm key to confirm changes.
- Press the Alarm Reset/Return key to go back to the previous screen or exit the menu.
5. Troubleshooting
The ACC5100 controller provides various warnings and shutdown alarms to indicate operational issues. When an alarm occurs, the controller immediately stops the engine (for shutdown alarms) or issues a warning. Press the Alarm Reset/Return button to remove alarms.
5.1. Warnings
Warnings indicate potential issues that do not immediately stop the engine but require attention.

Table 3: Common Warnings (Partial)
| No. | Type | Description |
|---|---|---|
| 1 | Over Speed Warn | When controller detects speed is above the pre-set over speed warning threshold, it issues warning signal. |
| 2 | Under Speed Warn | When controller detects speed is below the pre-set under speed warning threshold, it issues warning signal. |
| 3 | Loss of Speed Signal | When controller detects speed is 0, and speed signal loss action is selected "Warning", it issues warning signal. |
| 4 | Failed to Stop | When engine stop delay is over and engine doesn't stop completely, controller issues warning signal. |
| 5 | Charging Failure | When controller detects engine charger voltage is less than pre-set threshold, it issues warning alarm signal. |
5.2. Shutdown Alarms
Shutdown alarms indicate critical issues that cause the engine to stop immediately to prevent damage.

Table 4: Common Shutdown Alarms (Partial)
| No. | Type | Description |
|---|---|---|
| 1 | Emergency Stop | When controller detects emergency stop alarm signal, it issues emergency stop alarm signal. |
| 2 | Overspeed Shut | When controller detects engine speed is over pre-set over speed stop threshold, it issues shutdown alarm signal. |
| 3 | Underspeed Shut | When controller detects engine speed is below pre-set under speed stop threshold, it issues shutdown alarm signal. |
| 4 | Loss of Speed Signal | When controller detects speed is 0 and speed signal loss action is selected "Shutdown", it issues shutdown alarm signal. |
| 5 | Failed to Start | When engine fails to start during pre-set start attempts, controller issues failed to start alarm signal. |
5.3. Sensor Setting
The controller allows for configuration of sensor curves. If a sensor needs to be changed, the sensor curve will be transferred into the standard value. For example, if the default temperature sensor is SGD, the sensor curve is SGD curve; if it is set SGX, the temperature sensor curve is SGX curve.

Table 5: Common Pressure Unit Conversion Table
| Item | N/m² (Pa) | kgf/cm² | Bar | (psi) |
|---|---|---|---|---|
| 1 KPa | 1.0x10³ | 0.0102 | 0.01 | 0.145 |
| 1 Bar | 1.0x10⁵ | 1.02 | 1 | 14.5 |
| 1 psi | 6.89x10³ | 0.0703 | 0.0689 | 1 |
6. Specifications
| Feature | Detail |
|---|---|
| Model Number | ACC5100 |
| Brand Name | SAIWEI (SmartGen) |
| Application | Diesel Driven Air Compressor Controller |
| Communication | RS485 CANBUS |
| Electrified | Yes |
| Origin | Mainland China |
| Power Supply | 8-35VDC |
| Dimensions (H x W x D) | 180 mm x 145 mm x 49 mm |
| Cutout Dimensions (H x W) | 162 mm x 130 mm |
7. User Tips
- Always ensure proper grounding for all electrical connections to prevent interference and ensure safety.
- Regularly check the wiring connections for tightness and signs of wear or corrosion.
- Familiarize yourself with the warning and shutdown alarm codes to quickly diagnose and address potential issues.
- When performing maintenance, always disconnect power to the controller and associated equipment.
- For optimal performance and longevity, adhere to the recommended maintenance schedules.