Smartgen FPC2000

Contents

Smartgen FPC2000 Diesel Driven Fire Pump Controller User Manual

Model: FPC2000 | Brand: Smartgen

1. Overview

The Smartgen FPC2000 is a sophisticated diesel-driven fire pump controller designed for fire pump systems controlled by an engine. This manual provides essential information for the proper installation, operation, and maintenance of the FPC2000 controller to ensure reliable performance in critical fire protection applications.

Smartgen FPC2000 Controller Front View
Figure 1: Front view of the FPC2000 Diesel Driven Fire Pump Controller.
Smartgen FPC2000 User Manual Cover
Figure 2: Cover page of the FPC2000 Diesel Fire Pump Controller User Manual.

2. Performance Features

The FPC2000 controller offers a range of features to ensure efficient and reliable operation of diesel-driven fire pumps:

  • 7-inch large size color LCD screen with touch screen support.
  • Supports multiple types of sensors (resistive, current, voltage).
  • CANbus port for communication and parameter configuration.
  • USB Type-C port for parameter debugging and program upgrade.
  • Real-time alarm event recording, storing up to 500 pieces of data.
  • Timed recording function for system pressure, voltage, and current.
  • Accumulated total run time and pump running time.
  • Adjustable screen brightness.
  • Robust sealing gasket design for IP65 waterproof performance.
  • Modular structure design for easy installation.
User Manual Page 7: Performance Features
Figure 3: Excerpt from the manual detailing performance features.

3. Specifications

Key technical parameters for the FPC2000 controller:

ItemContent
Operating Voltage8VDC-35VDC, protection for DC reverse connection; Resolution: 0.1V; Precision: 1%
Power Consumption≤7W (Standby mode: ≤5W)
Analog SensorResistance input: Range: 0Ω - 6000Ω, Resolution: 0.1Ω, Precision: 1% (Below 380Ω); Voltage input: Range: 0V - 5V, Resolution: 0.01V, Precision: 1%; Current input: Range: 4mA - 20mA, Resolution: 0.1mA, Precision: 1%
Extension Digital Output 1-3Capacity 10A @ 250VAC, passive output
Extension Aux. Input 1-2Active when it is grounded (GND). Low threshold voltage is less than or equal to 1.0VDC, and maximum voltage input is 60VDC.
RS485 PortIsolated, half-duplex, baud rate at 9600, maximum communication distance at 1000m.
MSC-CAN PortIsolated, maximum communication distance at 250m, Belden 9841 cable or other equal rating cable is required.
CE/EMC CertificationEN 55022, EN 55024
Case Dimensions209mm×189mm×39mm
Panel Cutout188.5mm×165.5mm
Working Temperature(-25~+70)°C
Working Humidity(20~90)%RH
Storage Temperature(-30~+80)°C
IP RatingFront enclosure: IP65 when waterproof rubber gasket is installed between controller panel and enclosure. Back enclosure: IP20
Dielectric StrengthApply voltage of 2.2kV AC between AC high voltage terminal and low voltage terminal, and the leakage current is below 3mA in one minute.
Weight0.90kg
User Manual Page 9-10: Technical Specifications
Figure 4: Technical specifications table for FPC2000.

4. Installation and Setup

4.1 Panel Mounting

The FPC2000D is designed for panel-mounting. It is fixed by clamps during installation. Follow these steps:

  1. Screw out the screw of fixed metal clamp counter-clockwise to a proper position.
  2. Pull the metal clamps backward one by one to make all four fixed metal clamps fixed in the specified slots.
  3. Tighten the screw of the metal clamp clockwise and make sure it is fixed on the controller panel.
  4. Don't tighten the screws of metal clamps too tightly.

The FPC2000M is installed on the DIN rail, with a compact structure and convenient installation.

User Manual Page 51-52: Installation and Dimensions
Figure 5: Installation instructions and overall/cutout dimensions for FPC2000D and FPC2000M.

4.2 Wiring Connection

Refer to the terminal descriptions for proper wiring. Ensure all connections are secure and follow local electrical codes.

FPC2000 Controller Rear View with Terminals
Figure 6: Rear view of the FPC2000 controller showing terminal blocks for wiring.
No.Cable SizeRemarks
11.0mm²Ground terminal.
21.0mm²Connect with the negative of DC power supply.
31.0mm²Connect with the positive of DC power supply.
41.0mm²Common terminal of digital input.
51.0mm²It is used as the digital input of master control module.
61.0mm²It is used as the digital input of master control module.
71.0mm²Ground terminal of analog input.
81.0mm²It is used as the analog input of master control module.
91.0mm²It is used as the analog input of master control module.
100.5mm²Reserved ports.
110.5mm²120Ω impedance shielded twisted pair cable is recommended, and one end of the cable must be grounded. 120Ω termination resistor will be connected if Terminal 10 is connected with Terminal 12 directly.
120.5mm²(120Ω)
User Manual Page 26: Wiring Connection Table
Figure 7: Description of display module connection terminals.

5. Operation

5.1 Panel of Controller

The FPC2000 controller features a user-friendly panel with a display and control buttons.

FPC2000 Controller Front Panel
Figure 8: FPC2000 Front Panel.
TypeInstruction
Running IndicatorIt lights up when it starts successfully by Battery I.
Running II IndicatorIt lights up when it starts successfully by Battery II.
Stop IndicatorIt lights up when the running of engine stops.
Test IndicatorIt lights up when the engine is under test.
User Manual Page 11: Panel Indicators
Figure 9: Table of indicator lights and their meanings.

5.2 Function of Buttons

IconButtonDescription
Start I Button IconStart IPress the button to start the engine by Battery I.
Start II Button IconStart IIPress the button to start the engine by Battery II.
Stop Button IconStopPress the button to manually stop the engine.
Test Button IconTestPress the button to open the bypass valve, so the sensor will detect the pressure drop.
User Manual Page 11: Button Descriptions
Figure 10: Table of button functions.

5.3 Start Methods

The FPC2000 supports various engine start methods:

  • Manual Start: In manual mode, press the fire pump engine start button.
  • Remote Manual Start: The fire pump engine can be started by closing the "Remote Manual Start" input.
  • Test Start: In auto mode, press the test button to open the bypass valve, which detects a pressure drop and starts the fire pump engine.
  • Auto Start: In auto mode, when the pressure drops below the start pressure, the controller automatically starts the fire pump engine.
  • Remote Auto Start: In auto mode, the fire pump engine can be started by opening the "Remote Auto Start" or "Deluge Valve Start" input.
  • Flow Start: In auto mode, the fire pump engine can be started by closing the "Flow/Zone Start" input.
  • Weekly Start: In auto mode, according to the set value of scheduled start parameters, the fire pump engine can be automatically started at a pre-programmed time.
  • Sequential Start: For multiple pumps, it is necessary to set an automatic start delay for all fire pump engines to prevent them from starting simultaneously when pressure drops.
  • Auto Start Sequence:
    1. When the conditions for auto start are satisfied, it will enter the "Start delay".
    2. After the start delay is over, the fuel relay will activate and the crank relay activates at the same time. If the pump unit does not start successfully within the "Crank Time", the fuel relay and the crank relay will deactivate. It will enter the "Crank Rest Time", and wait for the next start.
    3. At any start, if the pump unit starts successfully, the fuel relay continues to activate, while the crank relay deactivates, and the pump unit enters the normal running status.
    4. Within the set start times, if the pump unit does not start successfully, the controller will issue a start failure alarm. At the same time, the fuel relay and crank relay will deactivate, the ETS relay will activate, and it will deactivate after the stop detection time (10s) is over.
User Manual Page 12-13: Start Methods
Figure 11: Excerpt from the manual detailing various start methods and sequences.

5.4 Stop Methods

The FPC2000 supports various engine stop methods:

  • Manual Stop: In manual mode, press the stop button to remove the manual start signal.
  • Auto Stop: The fire pump engine can be automatically stopped after it has been started automatically and the automatic stop function is enabled. Once the automatic stop function is activated, if there are no other operation reasons, the fire pump engine will be automatically stopped when the pressure has recovered for 10 minutes (above the stop pressure set value).
  • Flow Stop: If the controller has been started by "Flow/Zone Start" input and the signal has returned to normal, the fire pump engine will be stopped if there are no any other operation reasons.
  • Stop Mode: Regardless of the present starting reason, once the controller is switched to stop mode, the fire pump engine will be stopped.
  • Stop Sequence: When all the start signals are removed or the controller is switched to stop mode, the controller will execute the stop process, the fuel relay will deactivate, the ETS relay will activate, and it will deactivate after the stop detection time (10s) is over. In auto mode, if the engine running signal is detected, the stop failure fault will be issued.
User Manual Page 13: Stop Methods
Figure 12: Excerpt from the manual detailing various stop methods and sequences.

5.5 Display Navigation

The FPC2000 features a comprehensive display for monitoring and configuration.

  • First Start Up: When the controller is started for the first time, the "First Start Up" page appears. Click the "User Login", then enter the valid password. After logging in, the icon in front of the "User Login" is unlocked and the unlock level will be displayed.
  • Power Information Confirm: After logging in, click the "Power" button. Verify the voltage of chargers and batteries matches the actual value. If everything is normal, click the "Confirm" button to confirm the power information and return to the First Start page.
  • Pressure Information Confirm: Click the "Pressure" button, verify the pressure reading on the screen matches the reading on the calibrated pressure meter installed beside the sensor.
  • Date & Time Setting: Adjust date and time via the "Date & Time" button.
  • Home Page: Displays AC voltage, charger voltage, battery voltage, charging current and charging status, engine start/stop status, start reason, starter status, fuel output status, engine temperature status and engine oil pressure status.
  • Configuration Page: Access parameters for setting, language, password, and factory reset.
  • Alarms Page: Displays real-time alarm events.
  • History Page: Displays event records, pressure, power, and total run time.
  • About Page: Displays product model, display module number, software release date, company name, LOGO, website, address, phone number, etc.
User Manual Page 14-15: Display Navigation
Figure 13: Excerpt from the manual showing display screens for First Start Up, Power Information, and Engine Start Test.
User Manual Page 21-22: Configuration and Calibration
Figure 14: Excerpt from the manual showing Configuration Page, Date & Time Setting, and Screen Calibration Page.
User Manual Page 23-24: Alarms and History
Figure 15: Excerpt from the manual showing Alarms Page, History Page, Regular Pressure Record Page, and Regular Power Record Page.
User Manual Page 25: About Page
Figure 16: Excerpt from the manual showing the About Page with product information.

6. Maintenance

Regular maintenance is crucial for the longevity and reliable operation of your FPC2000 controller. While specific maintenance schedules are typically detailed in the full user manual, general practices include:

  • Regular Inspections: Periodically check all wiring connections for tightness and signs of corrosion.
  • Environmental Checks: Ensure the controller's operating environment remains within specified temperature and humidity ranges.
  • Cleaning: Keep the controller's exterior clean and free from dust and debris. Use a soft, dry cloth. Do not use abrasive cleaners or solvents.
  • Software Updates: Check for and apply any available software updates or firmware upgrades as recommended by Smartgen to ensure optimal performance and security.
  • Battery Health: Monitor the health and charge of the connected batteries, as they are critical for starting the engine.

7. Troubleshooting

This section provides guidance on common issues you might encounter with the FPC2000 controller. For more detailed troubleshooting, refer to the complete user manual.

7.1 Alarm Events

The controller's "Alarms Page" displays real-time alarm events. Warning alarms are general alarm events that automatically cancel when the condition no longer exists. Faults are serious alarm events that are latched and will not automatically clear. They are displayed with a red alarm icon.

  • Clearing Alarms:
    • "Alarm Reset" button: Resets the alarm of the display module and master control module.
    • "Alarm Mute" button: Mutes the alarm sound of the display module and master control module.
    • Click again to cancel the mute operation.
    • "Alarm Test" button: Sends an alarm test command to the master control module to test the alarm bell of the master control module, and click again to cancel the alarm test.
User Manual Page 23: Alarms Page
Figure 17: Alarms Page showing alarm indicators and controls.

7.2 Common Issues and Solutions

  • Controller Not Powering On:
    • Check DC power supply connections (Terminals 2 and 3) for proper voltage (8VDC-35VDC).
    • Verify battery connections and charge level.
  • Engine Fails to Start:
    • Check the "Start I" or "Start II" buttons.
    • Ensure the "Remote Manual Start" input is correctly activated if using remote start.
    • Verify fuel supply and engine health.
    • Check for any active alarms on the display that might prevent starting.
  • Incorrect Sensor Readings:
    • Verify sensor wiring connections (Analog Input terminals).
    • Ensure the correct sensor type is configured in the controller settings.
    • Perform screen calibration if touch input is inaccurate.
  • Communication Failure (CANbus/RS485):
    • Check cable connections for CANbus (Terminals 10, 11, 12) and RS485.
    • Ensure proper termination resistors are in place for CANbus.
    • Verify baud rate settings for RS485.

8. User Tips

  • Password Management: Remember to change the default password for configuration settings to enhance security. The default password is often 664213.
  • Data Backup: Regularly save event history information and regular history record information to a USB flash drive for easy viewing and problem analysis.
  • Environmental Protection: Ensure the controller is installed in an environment that protects it from excessive moisture and extreme temperatures to maintain its IP65 rating for the front enclosure.

9. Warranty and Support

For warranty information and technical support, please contact your supplier or the manufacturer directly. Keep your purchase records, including the date of purchase and seller information, as these will be required for any warranty claims or support inquiries.

The "About Page" on the controller's display provides information such as the product model, display module number (DPD), master control module number (MPO), software release date, company name, LOGO, website, address, and phone number. This information can be useful when seeking support.

User Manual Page 25: About Page
Figure 18: About Page displaying product information for support.

10. Product Video

Video showcasing a generator set, providing a general view of the type of equipment the FPC2000 controller is designed to manage.

© 2024 Smartgen. All rights reserved.

Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.