Daxtromn AGH-8.2KW

Contents

Daxtromn 8.2KW Hybrid Solar Inverter User Manual

Model: AGH-8.2KW / AGH-10.2KW

1. Introduction

This manual provides detailed instructions for the assembly, installation, operation, and troubleshooting of the Daxtromn Hybrid Solar Inverter. It combines the functions of an inverter, solar charger, and battery charger to provide uninterruptible power support. Please read this manual carefully before installation and operation, and keep it for future reference.

The inverter features a comprehensive LCD display and easy-to-use buttons for configuring settings such as battery charging current, AC/solar charger priority, and acceptable input voltage ranges for various applications.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  • Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  • CAUTION: To reduce risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  • Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  • To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  • CAUTION: Only qualified personnel can install this device with battery.
  • NEVER charge a frozen battery.
  • For optimum operation, follow required specifications to select appropriate cable size.
  • Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  • Strictly follow installation procedures when disconnecting AC or DC terminals.
  • A 150A fuse is provided as over-current protection for the battery supply.
  • GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Comply with local requirements and regulations.
  • NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
  • WARNING: Only qualified service persons are able to service this device. If errors persist after troubleshooting, send the inverter/charger to a local dealer or service center.

3. Product Overview

The Daxtromn Hybrid Solar Inverter is a multi-function device designed for various power applications. It features a pure sine wave output, configurable input voltage ranges, adjustable battery charging current, and AC/solar charger priority settings. It is compatible with both mains voltage and generator power, includes auto-restart functionality upon AC recovery, and offers comprehensive protection against overload, over-temperature, and short circuits. The smart battery charger design optimizes battery performance, and a cold start function is included.

The inverter is equipped with a built-in 160A MPPT solar charger and an anti-dust kit for harsh environments. It also supports a dual AC output function and features touch buttons for user interaction.

Product Overview Diagram with numbered components

Figure 1: Product Overview Diagram

  1. LCD display
  2. Status indicator
  3. Charging indicator
  4. Fault indicator
  5. Touch Function buttons
  6. Power on/off switch
  7. AC input
  8. Main output
  9. Second output
  10. PV1 and PV2 input
  11. WIFI communication/RS-232 port
  12. Battery communication/RS-485 port
  13. Battery input
  14. Anti dust kit

This diagram illustrates the front and side views of the inverter, highlighting the LCD display, indicators, control buttons, and various input/output ports.

Product Display showing multiple views of the inverter

Figure 2: Product Display

Various views of the inverter, showcasing its design and physical layout from different angles.

Product Specifications with dimensions and weight

Figure 3: Product Dimensions and Weight

The inverter measures 500mm x 390mm x 136mm and has a net weight of 14.5kg (for 8.2KW model) or 14.7kg (for 10.2KW model).

4. Setup and Installation

4.1 Unpacking and Inspection

Before installation, carefully inspect the unit for any damage. The package should contain:

  • The inverter unit x 1
  • User manual x 1 (PDF version available at User manual (PDF))
  • Ring terminal x 1
  • MC4 terminal head x 2

4.2 Mounting the Unit

Select a suitable location for mounting the inverter, considering the following:

  • Mount on a solid, non-flammable surface.
  • Install at eye level for easy LCD display readability.
  • Ensure adequate air circulation: approximately 20 cm clearance to the sides and 50 cm above and below the unit for heat dissipation.
  • The ambient temperature should be between 0°C and 55°C for optimal operation.
  • The recommended installation position is vertically on a wall.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing two M4 or M5 screws into the wall.

4.3 Battery Connection

CAUTION: For safety and regulation compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. Refer to the table below for required fuse or breaker size.

WARNING: All wiring must be performed by qualified personnel. Use appropriate cable for battery connection to reduce risk of injury.

Recommended Battery Cable Size
Model Wire Size Cable (mm²) Torque value (max)
8.2KW/10.2KW 1 x 2AWG 25 2 Nm

Follow these steps for battery connection:

  1. Remove 18 mm of insulation from positive and negative conductors.
  2. Use bootlace ferrules on the ends of the wires with a proper crimping tool.
  3. Connect all battery packs as shown in the diagram below.
  4. Insert battery wires into inverter connectors and tighten bolts to 2 Nm. Ensure correct polarity at both the battery and inverter/charger.
Battery Connection Diagram showing 4x12V batteries in series connected to the inverter

Figure 4: Battery Connection Diagram

Illustrates connecting four 12V batteries in series to the inverter. Ensure correct polarity and use recommended cable sizes.

WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.

CAUTION: Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).

4.4 AC Input/Output Connection

CAUTION: Install a separate AC breaker between the inverter and AC input power source (recommended 63A for 8.2KW/10.2KW models). Do NOT mis-connect input and output connectors.

WARNING: All wiring must be performed by qualified personnel. Use appropriate cable for AC input connection.

Suggested Cable Requirement for AC Wires
Model Gauge Cable (mm²) Torque Value
8.2KW/10.2KW 10 AWG 6 1.2 Nm

Follow these steps for AC input/output connection:

  1. Before connecting, open the DC protector or disconnector.
  2. Remove 10mm insulation for six conductors. Shorten phase L and neutral conductor N by 3mm.
  3. Insert AC input wires according to polarities (Ground: yellow-green, L: brown/black, N: blue) and tighten terminal screws.
  4. Insert AC output wires according to polarities (L: brown/black, N: blue) and tighten terminal screws.
  5. Ensure all wires are securely connected.
AC Input/Output Connection Diagram showing terminal block wiring

Figure 5: AC Input/Output Connection Diagram

Detailed view of the terminal blocks for AC input and output, indicating proper wire connections and polarities.

4.5 PV Connection

CAUTION: Install a separate DC circuit breaker between the inverter and PV modules. Use appropriate cable for PV module connection.

Suggested Cable Requirement for PV Wires
Model Wire Size Cable (mm²) Torque Value
8.2KW/10.2KW 1 x 10AWG 6 1.2 Nm

When selecting PV modules, ensure the Open Circuit Voltage (Voc) does not exceed 500Vdc and is higher than the minimum battery voltage. The PV Array MPPT Voltage Range is 90Vdc~450Vdc.

CAUTION: Exceeding the maximum input voltage can destroy the unit! Check the system before wire connection.

PV Connection Diagram showing solar panels, inverter, battery, AC output, and home appliances

Figure 6: PV Connection Diagram

Illustrates the overall solar power system setup, including solar panels, inverter, battery, and connections to AC output and home appliances.

Note on PV input voltage requirements

Figure 7: PV Input Voltage Note

Important: If the solar inverter is used without an external battery, the PV input voltage must be above 120V for normal operation. If an external battery is connected, 90V is sufficient.

4.6 Communication Connection

The inverter supports Wi-Fi and GPRS cloud communication (optional) and battery communication.

  • Wi-Fi/GPRS Communication: Use the supplied communication cable to connect to the inverter and the Wi-Fi/GPRS module. Download the appropriate app and follow the "Wi-Fi Plug Quick Installation Guideline" or "GPRS RTU Quick Installation Guideline" for setup and registration. Inverter status can then be monitored via mobile app or computer webpage.
  • Battery Communication: Communication between the battery and inverter is achieved via the battery communication interface (Baud rate: 9600). The RJ45 connector of the communication cable connects to the BMS port of the inverter, and the other RJ45 connector connects to the RS485 port of the lithium battery. Ensure both lithium battery and inverter are turned off before connecting.
Lithium Battery Communication Cable Interface Diagram

Figure 8: Lithium Battery Communication Cable Interface

Shows the RJ45 connections for BMS communication between the inverter and lithium battery. A-01 connects to BMS port on inverter, A-02 connects to RS485 port of lithium battery.

To enable communication with a lithium battery BMS, press and hold the "ENTER" button, set battery type to "LIB-485" in program 05, then select the matching battery protocol (PYLON or PACE) in Program 43.

5. Operation

5.1 Power ON/OFF

Once the unit is properly installed and batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

5.2 Operation and Display Panel

The front panel of the inverter features an LCD display, three indicators, and four touch function keys for operation and monitoring.

LED Indicator Messages
LED Indicator Color State Message
INV/AC Green Solid On Output is powered by utility in Line mode.
Flashing Output is powered by battery or PV in battery mode.
CHG Green Solid On Battery is fully charged.
Flashing Battery is charging.
FAULT Red Solid On Fault occurs in the inverter.
Flashing Warning condition occurs in the inverter.
Function Keys
Function Key Description
ESC To exit setting mode
UP To go to previous selection
DOWN To go to next selection
ENTER To confirm the selection in setting mode or enter setting mode

5.3 LCD Display Icons

The LCD displays various icons to indicate the inverter's status and information:

  • Input Source Information: Icons for AC input and PV input. Displays input voltage, frequency, PV voltage, charger current, charger power, and battery voltage.
  • Configuration Program and Fault Information: Indicates setting programs, warning codes (flashing), and fault codes (lighting).
  • Output Information: Displays output voltage, frequency, load percentage, load in VA, load in Watt, and discharging current.
  • Battery Information: Shows battery status.
  • Load Information: Overload indicator.
  • Mode Operation Information: Indicates connection to mains, PV panel, load supplied by utility, utility charger circuit working, DC/AC inverter circuit working.
  • Mute Operation: Indicates unit alarm is disabled.

5.4 LCD Settings

To enter setting mode, press and hold the "ENTER" button for 3 seconds. Use "UP" or "DOWN" to select programs, and "ENTER" to confirm or "ESC" to exit.

Output Source Priority LCD Setting (Program 01)

Figure 9: Output Source Priority Setting (Program 01)

This setting configures how the inverter prioritizes power sources for the load. Options include Utility first (01 USB), Solar first (01 SUB, default), SBU priority (01 SBU), and MKS priority (01 ntS).

Off-Grid or Hybrid Mode LCD Setting (Program 37)

Figure 10: Off-Grid or Hybrid Mode Setting (Program 37)

This setting determines the inverter's operational mode. "37 OFF" (default) means the inverter operates only in off-grid mode, with solar energy as first priority for loads and then charging. "37 HYd" means hybrid mode, where solar energy provides power to loads first, then charging, and excess energy can be fed to the grid.

Key configurable programs include:

  • Program 00: Exit setting mode (GOE for one-button restore, GOK to exit).
  • Program 01: Output source priority (Utility first, Solar first (default), SBU priority, MKS priority).
  • Program 02: Maximum charging current (10A to 160A).
  • Program 03: AC input voltage range (APL for Appliances 90-280VAC, UPS for UPS 170-280VAC).
  • Program 05: Battery type (AGM, Flooded, User Defined, LIB). If "LIB-485" is selected, specific battery settings (12, 13, 29) are displayed as percentages.
  • Program 06/07: Auto restart when overload/over temperature occurs (enable/disable).
  • Program 09/10: Output frequency (50Hz/60Hz) and voltage (220V/230V/240V).
  • Program 11: Maximum utility charging current.
  • Program 12/13: Battery SOC points for switching to utility/battery mode in SBU/Solar first modes.
  • Program 26/27/29: Bulk charging voltage, floating charging voltage, and low DC cut-off voltage (or low SOC shutdown point for LIB-485).
  • Program 30-36: Battery equalization settings (enable/disable, voltage, time, timeout, interval, immediate activation).
  • Program 37: GRID-tie operation mode (Off-grid or Hybrid).
  • Program 41/42/45: Dual output function settings (enable/disable, functional voltage point, maximum second load percentage).
  • Program 43: Lithium battery protocol (PYLON or PACE).

5.5 Operating Mode Description

The inverter supports various working modes, including operation without a battery connected and operation with a battery connected. These modes dictate how power is sourced and distributed to connected loads.

Various Working Modes Diagram

Figure 11: Various Working Modes

This diagram illustrates different power flow scenarios for the inverter, both with and without a battery connected, showing how solar, generator, utility, and battery power are utilized to supply home appliances.

The inverter also features RGB lights to indicate the current operating mode:

  • Battery Mode: Red Light
  • Utility Mode: Blue Light
  • PV Mode: Purple Light

5.6 Battery Equalization

The equalization function helps reverse the buildup of negative chemical effects like stratification and removes sulfate crystals from battery plates, optimizing battery performance and lifespan. It is recommended to equalize batteries periodically.

To apply equalization, enable the function in LCD setting program 30. You can then set an equalization interval in program 35 or activate equalization immediately in program 36. The controller will enter the Equalize stage when the set interval is reached or immediately activated.

5.7 Mains and Lithium Battery Activation Function

  • After 90 seconds of mains power connection, the inverter will connect to the mains and begin operation.
  • If the inverter is in lithium battery mode (Program 05 set to LIB or LIL) and the mains are connected but the battery is not, the mains activation function will automatically enable.

6. Maintenance

6.1 Clearance and Maintenance for Anti-Dust Kit

The inverter comes with a pre-installed anti-dust kit to protect against dust and increase product reliability. The inverter automatically detects this kit and adjusts its internal thermal sensor to manage temperature.

Procedure:

  1. Loosen the screw on the top of the inverter in a counterclockwise direction.
  2. Remove the dustproof case and take out the air filter foam.
  3. Clean the air filter foam and dustproof case. Re-assemble the dust-kit back to the inverter.

NOTICE: The anti-dust kit should be cleaned from dust every one month.

7. Troubleshooting

This section provides guidance for common issues, fault codes, and warning indicators. For persistent errors, contact a qualified service person.

7.1 Fault Reference Codes

When a fault occurs, the LCD will display a fault code. Refer to the table below for explanations and corrective actions.

Common Fault Codes
Fault Code Fault Event What to do
01Fan is locked when inverter is off.Return to repair center.
02Over temperatureCheck air flow, ambient temperature.
03Battery voltage is too highCheck battery specifications.
04Battery voltage is too lowRe-charge or replace battery.
05Output short circuited or over temperature detected by internal converter components.Check wiring, reduce load.
06Output voltage is too high.Return to repair center.
07Overload time outReduce connected load.
08Bus voltage is too highReturn to repair center.
09Bus soft start failedReturn to repair center.
51Over current or surgeRestart unit, if error persists, return to repair center.
52Bus voltage is too lowRestart unit, if error persists, return to repair center.
53Inverter soft start failedReturn to repair center.
55Over DC voltage in AC outputReturn to repair center.
57Current sensor failedReturn to repair center.
58Output voltage is too lowReturn to repair center.
59PV voltage is over limitationReturn to repair center.

7.2 Lithium Battery Fault Codes

Lithium Battery Specific Fault Codes
Fault Code Fault Event Fault Condition
02The battery temperature is too highLithium battery charging temperature ≥65°C; Discharge temperature ≥70°C.
03The battery voltage is too highLithium battery maximum single cell voltage >3.65V; Total voltage of lithium battery >54.6V (48V lithium battery).
04The battery voltage is too lowMinimum voltage of a lithium battery cell <2.71V; Total voltage of lithium battery <40.4V (48V lithium battery).

7.3 Warning Indicators

Warning events are indicated by audible alarms and flashing icons. Refer to the table below for details.

Warning Events and Indicators
Warning Code Warning Event Audible Alarm
01Fan is locked when inverter is on.Beep three times every second
03Battery is over-chargedBeep once every second
04Low batteryBeep once every second
07OverloadBeep once every 0.5 second
10Output power deratingBeep twice every 3 seconds
15PV energy is low.Beep twice every 3 seconds
E9Battery equalizationNone
6PBattery is not connectedNone
Lithium Battery Specific Warning Codes
Warning Code Warning Event Warning Condition
04The battery voltage is too lowMinimum voltage of a lithium battery cell <2.85V; Total voltage of lithium battery <42V (48V lithium battery).
05The battery voltage is too highLithium battery maximum single cell voltage >3.55V; Total voltage of lithium battery >54V (48V lithium battery).
06The battery is low warningRemaining battery capacity ≤10%

8. Specifications

The following tables detail the technical specifications for the Daxtromn Hybrid Solar Inverter (8.2KW and 10.2KW models).

Product Label with detailed specifications

Figure 12: Product Label Specifications

A detailed view of the product label, listing key specifications for the inverter charger, including PV input, Grid/AC output, two load output power, AC input, and battery parameters.

Table 1: Line Mode Specifications
Feature 8.2KW 10.2KW
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage (UPS)170Vac±7V
Low Loss Voltage (Appliances)90Vac±7V
Low Loss Return Voltage (UPS)180Vac±7V
Low Loss Return Voltage (Appliances)100Vac±7V
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time (UPS)10ms typical
Transfer Time (Appliances)20ms typical
Table 2: Inverter Mode Specifications
Feature 8.2KW 10.2KW
Rated Output Power8.2KW10.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency50Hz
Peak Efficiency93%
Overload Protection3s@≥150% load; 5s@101%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage48Vdc
Cold Start Voltage46.0Vdc
Low DC Warning Voltage (<50% load)44.0Vdc
Low DC Warning Voltage (≥50% load)42.0Vdc
Low DC Warning Return Voltage (<50% load)45.0Vdc
Low DC Warning Return Voltage (≥50% load)44.0Vdc
Low DC Cut-off Voltage (<50% load)41.0Vdc
Low DC Cut-off Voltage (≥50% load)40.0Vdc
High DC Recovery Voltage62Vdc
High DC Cut-off Voltage63Vdc
No Load Power Consumption70W75W
Table 3: Two Load Output Power
Feature 8.2KW 10.2KW
Full Load8200W10200W
Maximum Main Load8200W10200W
Second Load Range1640W~5740W2040W~7140W
Main Load Cut Off Voltage52VDC
Main Load Return Voltage54VDC
Table 4: Charge Mode Specifications
Feature 8.2KW 10.2KW
Charging Algorithm3-Step
AC Charging Current (Max)140Amp140Amp
Bulk Charging Flooded Battery58.4V
Voltage AGM / Gel Battery56.4V
Floating Charging Voltage54Vdc
MPPT Solar Charging Mode IMax.PV (PV1 Channel)18A
MPPT Solar Charging Mode IMax.PV (PV2 Channel)18A
Nominal PV Voltage360Vdc
PV Array MPPT Voltage Range90Vdc~450Vdc
Max. PV Array Open Circuit Voltage500Vdc
Max Charging Current (AC charger plus solar charger)160Amp
Table 5: Grid-Tie Operation Specifications
Feature 8.2KW 10.2KW
Nominal Output Voltage220/230/240 VAC
Feed-in Grid Voltage Range195~253VAC
Feed-in Grid Frequency Range50±1Hz/60±1Hz
Nominal Output Current35.6A44.3A
Power Factor Range≥0.99
Maximum Conversion Efficiency (DC/AC)98%
Table 6: General Specifications
Feature 8.2KW 10.2KW
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage Temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm500*390*136mm
Net Weight, kg14.514.7

8.1 Approximate Back-up Time Table

The following table provides approximate backup times based on load and battery capacity. Note that actual backup time depends on battery quality, age, and type.

Approximate Back-up Time Table @ 48Vdc
Model Load (W) Backup Time @ 100Ah (min) Backup Time @ 200Ah (min)
8.2KW / 10.2KW5006131288
1000268613
1500158402
2000111271
250090215
320076182
350065141
400050112
450044100
50004090
10.2KW62003680
72003270
82002860
92002450
102002040

9. User Tips

  • Grid Feedback: This inverter is a hybrid solar inverter and can feed power back to the grid. Ensure local regulations are met for grid-tie operation.
  • PV Panel Flexibility: You can connect two strings of solar panels with different specifications to this inverter.
  • BMS Compatibility: For optimal battery life and safety, ensure both your inverter and external battery have BMS (Battery Management System) functions to allow communication and automatic parameter adjustments. Supported BMS protocols include PACE and PYLON.
  • PV Input Voltage (No Battery): If operating the inverter without an external battery, the voltage from the solar panels must be above 120VDC for the inverter to function correctly.
  • PV Input Voltage (With Battery): If operating with an external battery, the PV input voltage can be as low as 90VDC.
  • Dual AC Output: The inverter has a dual AC output function. If the main AC input/grid is unavailable and the battery voltage is low, the main AC output will automatically cut off, and only the second AC output will be powered by the battery or PV. DO NOT CONNECT THE SECOND OUTPUT TO THE GRID.
  • Parallel/Series Connection: This inverter does not support parallel or series connection with other inverters.

10. Warranty and Support

The Daxtromn Hybrid Solar Inverter comes with a 1-year warranty.

For detailed technical support, troubleshooting beyond the scope of this manual, or warranty claims, please contact your local dealer or authorized service center.

A comprehensive user manual in PDF format is available for download: User manual (PDF).