1. Introduction
This manual provides detailed instructions for the installation, operation, and maintenance of the CC305N Chiller Heat Pump Controller PCBA Control Board. This controller is designed for use with air source swimming pool heat pump systems, offering precise control over temperature and system functions. Please read this manual thoroughly before installation and operation to ensure safe and efficient use of the product.
2. Safety Information
Always observe the following safety precautions to prevent injury or damage to the product:
- Ensure the power supply is disconnected before any installation, wiring, or maintenance work.
- All electrical connections must be performed by a qualified electrician in accordance with local and national electrical codes.
- Do not expose the control board or display panel to water or excessive moisture.
- Verify that the voltage supply matches the product specifications (220V AC).
- Keep children away from the control unit during operation.
- Do not attempt to modify or repair the unit yourself. Contact qualified personnel for service.
3. Package Contents
The CC305N Chiller Heat Pump Controller package typically includes the following components:
- CC305N PCBA Control Board
- Digital Display Panel
- Power Transformer
- Protective Casing for Control Board
- Multiple NTC Temperature Sensors (e.g., for condenser, outdoor, suction, evaporator, inlet/outlet water)
- Various Wiring Harnesses and Cables


4. Specifications
| Attribute | Specification |
|---|---|
| Model | CC305N |
| Material | Aluminum alloy |
| Product Name | Swimming Pool Heat Pump Controller |
| Application | Swimming Pool Machine |
| Voltage | 220±10%(VAC), 50/60Hz |
| Size | 150*95*35mm |
| Sensor Type | NTC(5KΩ/25°c, B Value 3470K) |
| Relay Output Capacity | 5A/240VAC, 20A/250VAC |
| Testing | AOI Test |
| PCBA Service | Support Customization |
5. Setup and Installation
Careful installation is crucial for the proper functioning of the CC305N controller. Follow these steps:
5.1 Mounting the Control Board and Display
- Mount the PCBA Control Board securely within its protective casing in a dry, well-ventilated area, away from direct sunlight and heat sources.
- Install the Digital Display Panel in an easily accessible location for user interaction. Ensure the connecting cable between the display and the control board is routed safely and is not subject to strain or damage.
5.2 Wiring Connections
Refer to the wiring diagram below for all electrical connections. Ensure all connections are tight and secure to prevent loose contacts and potential hazards.

- Power Input: Connect the L (Live) and N (Neutral) 220V AC input to the designated terminals on the control board.
- Circular Pump Output (OUT2): Connect the circular pump to the OUT2 terminal.
- Compressor Output (OUT1): Connect the compressor to the OUT1 terminal.
- 4-Way Valve Output (OUT3): Connect the 4-way valve to the OUT3 terminal.
- Fan Output (OUT4): Connect the fan to the OUT4 terminal.
- Electrical Heater Output (OUT5): Connect the electrical heater to the OUT5 terminal.
- 12V Output: This output provides 12V power for auxiliary components if needed.
- Indicator Light (LED): Connect the indicator light to the LED terminals.
- Display Connection: Connect the display panel to the dedicated 'display' port using the provided cable.
- Sensor Connections: Connect the NTC sensors to their respective ports:
- Condenser Temp Sensor
- Outdoor Temp Sensor
- Suction Temp Sensor
- Evaporator Temp Sensor
- Outlet Water Temp Sensor
- Inlet Water Temp Sensor
- Switch Connections: Connect the following switches to their designated ports:
- ON/OFF Switch
- Water Flow Switch
- High Pressure Switch
- Low Pressure Switch
After all connections are made, double-check them against the diagram before applying power.
6. Operating Instructions
The digital display panel provides an intuitive interface for controlling the heat pump. Below are the basic operating procedures:

6.1 Display Overview
The display shows current temperature (TEMP), humidity (HUM), fan status (FAN AUTO), and ON/OFF indicators. Various icons represent different modes (snowflake for cooling, sun for heating, fan for ventilation, water droplet for humidity, etc.).
6.2 Button Functions
- Power Button (⏻): Press to turn the unit ON or OFF.
- Mode Button (M): Press to cycle through different operating modes (e.g., Heating, Cooling, Auto, Fan Only).
- Up (▲) / Down (▼) Buttons: Use these buttons to adjust temperature settings or navigate menu options.
- SET Button: Press to enter settings mode or confirm a selection.
- AUX Button: Activates auxiliary functions, if configured.
6.3 Basic Operation
- Power On/Off: Press the Power button to switch the controller on or off.
- Select Mode: Press the 'M' button repeatedly until the desired operating mode icon is displayed (e.g., sun for heating, snowflake for cooling).
- Set Temperature: In heating or cooling mode, use the Up/Down buttons to adjust the target temperature. Press 'SET' to confirm.
- Fan Control: The 'FAN AUTO' indicator shows the fan's operating status. Specific fan speed adjustments may be available through the 'SET' menu or 'AUX' button, depending on configuration.
7. Maintenance
Regular maintenance ensures the longevity and optimal performance of your CC305N controller:
- Cleaning: Gently wipe the display panel and control board casing with a soft, dry cloth. Do not use abrasive cleaners or solvents.
- Inspection: Periodically check all wiring connections for tightness and signs of wear or damage. Ensure sensors are clean and properly positioned.
- Environment: Keep the control unit free from dust, debris, and excessive humidity.
8. Troubleshooting
If you encounter issues with your CC305N controller, try the following troubleshooting steps:
- No Power: Check the main power supply to the unit. Ensure the transformer is correctly connected and functioning. Verify all power input wiring.
- Display Not Working: Check the cable connection between the control board and the display panel. Ensure the control board has power.
- Incorrect Temperature Readings: Verify that all NTC sensors are correctly connected and not damaged. Ensure sensors are properly placed in their respective locations (e.g., water sensors in water flow).
- Heat Pump Not Responding: Check all output wiring (compressor, fan, pump, heater). Ensure the selected operating mode is appropriate. Verify that pressure switches and flow switches are not indicating a fault condition.
- System Error Codes: If the display shows an error code, consult the specific error code list (if provided separately by the manufacturer) or contact technical support.
9. User Tips
- Always ensure proper ventilation around the control board to prevent overheating.
- For optimal performance, calibrate temperature sensors periodically if your system allows.
- Keep a record of your system's normal operating parameters to quickly identify any deviations.
10. Warranty and Support
For warranty information, technical support, or service inquiries, please refer to the contact information provided by your retailer or the product manufacturer. Keep your purchase receipt as proof of purchase.