PowMr 6.2kW 48V Hybrid Solar Inverter User Manual

Model: POW-HVM6.2K-48V-E

Brand: PowMr

1. Introduction

This is a multi-function inverter/charger, combining functions of inverter, solar charger and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.

1.1 Features

  • Pure sine wave inverter output.
  • Configurable input voltage range for home appliances and personal computers via LCD setting.
  • Configurable battery charging current based on applications via LCD setting.
  • Configurable AC/Solar Charger priority via LCD setting.
  • Compatible to mains voltage or generator power.
  • Auto restart while AC is recovering.
  • Overload/ Over temperature/ short circuit protection.
  • Smart battery charger design for optimized battery performance.
  • Cold start function.
  • RS485 is used to communicate with BMS and adjust the charging current of inverter according to battery demand.
  • It can work with or without batteries.
  • Intelligent fan speed adjustment, which adjusts the fan speed according to temperature, load and charging current.
  • Built-in MPPT, operating voltage range 55V~450V, open circuit voltage 500Voc.
  • RGB lamp, which displays different colors according to inverter status (optional).
  • WIFI remote monitoring (optional).
  • Offline upgrade function, firmware can be upgraded through COM port.
  • Grid-connected.
  • Built-in anti-dust kit for harsh environment.
  • In battery-free mode, PV systems deliver a better user experience when powering loads.
  • Equipped with lithium battery activation function.

1.2 Product Overview

Front view of the PowMr 6.2kW Hybrid Solar Inverter with LCD display
Front view of the PowMr 6.2kW Hybrid Solar Inverter with LCD display and control buttons.
Rear and side views of the PowMr 6.2kW Hybrid Solar Inverter showing connection ports
Rear and side views of the inverter, highlighting various connection ports and ventilation.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.
  2. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  3. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  4. CAUTION - Only qualified personnel can install this device with battery.
  5. NEVER charge a frozen battery.
  6. For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  7. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  8. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
  9. One piece of 150A fuse is provided as over-current protection for the battery supply.
  10. GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
  11. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
  12. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

3. Installation

This section provides instructions for installing your PowMr Hybrid Solar Inverter. For a visual guide, please refer to the installation video below.

Installation video demonstrating mounting, wiring, and power-on sequence for the solar inverter.

3.1 Unpacking and Inspection

Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the unit and a user manual.

3.2 Preparation

Before connecting all lines, remove the screws under the machine and remove the bottom cover plate.

3.3 Mounting the Unit

Consider the following points before selecting where to install:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level in order to allow the LCD display to be read at all times.
  • For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
  • The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.
  • Make sure that other objects and surfaces are left with enough space from the machine to ensure adequate heat dissipation and that there is enough room to remove the wires.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing two M6 screws.

3.4 Battery Connection

CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable as below.

ModelWire SizeCable (mm²)Torque value (max)
4.2KW/6.2KW1 x 2AWG252 Nm

Please follow below steps to implement battery connection:

  1. Remove insulation sleeve 18 mm for positive and negative conductors.
  2. Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Connect all battery packs as shown in the diagram below.
  4. Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.
Diagram showing battery connection to the inverter
Diagram illustrating the connection of batteries to the inverter, including multiple battery types and a 120A fast charge capability.

WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.

CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).

3.5 AC Input/Output Connection

CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 32A for 4.2KW and 50A for 6.2KW.

CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.

ModelGaugeCable (mm²)Torque Value
4.2KW12 AWG41.2 Nm
6.2KW10 AWG61.2 Nm

Please follow below steps to implement AC input/output connection:

  1. Before making AC input/output connection, be sure to open DC protector or disconnector first.
  2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
  3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. (L→LINE (brown or black), N→Neutral (blue))

WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.

  1. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. (L→LINE (brown or black), N→Neutral (blue))
  2. Make sure the wires are securely connected.
Detailed view of AC input/output terminals on the inverter
Detailed view of the inverter's rear panel, showing AC input and output terminals for wiring.

CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it's equipped with time-delay function before installation. Otherwise, this inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.

3.6 PV Connection

CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.

ModelWire SizeCable (mm²)Torque value (max)
4.2KW/6.2KW1 x 12AWG41.2 Nm

PV Module Selection:

When selecting proper PV modules, please be sure to consider below parameters:

  1. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
  2. Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
INVERTER MODEL4.2KW6.2KW
Max. PV Array Open Circuit Voltage500Vdc
PV Array MPPT Voltage Range60Vdc~450Vdc
IMax.PV27A

Please follow below steps to implement PV module connection:

  1. Remove insulation sleeve 10 mm for positive and negative conductors.
  2. Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Check correct polarity of wire connection from PV modules and PV input connectors. Then, connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector. Recommended tool: 4mm blade screwdriver.
Hybrid Power System diagram showing PV connections
Diagram of a Hybrid Power System, illustrating how solar panels (PV array) connect to the inverter.

3.7 Final Assembly

After connecting all wirings, please put bottom cover back by screwing two screws.

3.8 Communication Connection

Wi-Fi cloud communication (optional):

Please use supplied communication cable to connect to inverter and Wi-Fi module. Download APP and installed from APP store, and Refer to "Wi-Fi Plug Quick Installation Guideline" to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.

GPRS cloud communication (optional):

Please use supplied communication cable to connect to inverter and GPRS module, and then applied external power to GPRS module. Download APP and installed from APP store, and Refer to "GPRS RTU Quick Installation Guideline" to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.

Battery communication and setting of Lithium Battery:

The communication between the battery and the inverter can be realized through the battery communication interface, so that the inverter and the lithium battery can exchange information (Baud rate: 9600).

  1. Connect the battery according to the recommended battery cable specifications.
  2. Insert the ring terminal of the battery cable into the battery connector of the inverter flatly, and ensure that the bolts are tightened with a torque of 2-3 Nm. Make sure that the polarities of the battery and inverter are connected correctly, and that the ring terminal is tightened with the battery terminal.
  3. Connect one side of RJ45 cable to the BMS communication port of inverter.
  4. Insert the other side of RJ45 cable into RS485 communication port on lithium battery.

NOTE:

If you choose a lithium battery, please make sure to connect the battery and inverter with BMS communication cable, and select the battery type as "LIB-485" mode.

In order to communicate with the lithium battery BMS, you should press the "ENTER" button for a long time, and set the battery type as "LIB-485" in program 05. Then select the matching battery protocol in Program 43.

4. Operation

4.1 Power ON/OFF

Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

4.2 Operation and Display Panel

The operation and display panel, shown below, is on the front panel of the inverter. It includes three indicators, four function keys and an LCD display, indicating the operating status and input/output power information.

LCD display and control buttons on the inverter
LCD display and control buttons (ESC, UP, DOWN, ENTER) for configuring settings.

LED Indicator

LED IndicatorMessages
INV/ACGreen Solid OnOutput is powered by utility in Line mode.
Green FlashingOutput is powered by battery or PV in battery mode.
CHGGreen Solid OnBattery is fully charged.
Green FlashingBattery is charging.
FAULTRed Solid OnFault occurs in the inverter.
Red FlashingWarning condition occurs in the inverter.

Function Keys

Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

4.3 Operating Mode Description

The inverter supports various operating modes, including Standby, Line Mode, and Grid-Tie operation. The LCD display will show different icons and information based on the current mode.

Diagram showing four charging modes and three load output working modes
Illustration of the four charging modes (Solar first, Utility first, Solar and Utility, Only Solar) and three load output working modes (Utility first, Solar first, SBU first).

4.4 Battery Equalization Description

Equalization function is added into charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize battery periodically.

How to Apply Equalization Function

You must enable battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in device by either one of following methods:

  1. Setting equalization interval in program 35.
  2. Active equalization immediately in program 36.

When to Equalize

In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter Equalize stage.

Equalize charging time and timeout

In Equalize stage, the controller will supply power to charge battery as much as possible until battery voltage raises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.

However, in Equalize stage, when battery equalized time is expired and battery voltage doesn't rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.

5. Maintenance

5.1 Clearance and Maintenance for Anti-Dust Kit

Every inverter is already installed with anti-dust kit from factory. Inverter will automatically detect this kit and activate internal thermal sensor to adjust internal temperature. This kit also keeps dust from your inverter and increases product reliability in harsh environment.

  1. Please loosen the screw in counterclockwise direction on the top of the inverter.
  2. Then, the dustproof case can be removed, and the air filter foam can be taken out.
  3. Clean the air filter foam and dustproof case. After clearance, re-assemble the dust-kit back to the inverter.

NOTICE: The anti-dust kit should be cleaned from dust every one month.

6. Troubleshooting

This section provides guidance for identifying and resolving common issues with the inverter.

6.1 Fault Reference Code

Fault CodeFault EventIcon on
01Fan is locked when inverter is off.01 ERROR
02Over temperature02 ERROR
03Battery voltage is too high03 ERROR
04Battery voltage is too low04 ERROR
05Output short circuited or over temperature is detected by internal converter components.05 ERROR
06Output voltage is too high.06 ERROR
07Overload time out07 ERROR
08Bus voltage is too high08 ERROR
09Bus soft start failed09 ERROR
51Over current or surge51 ERROR
52Bus voltage is too low52 ERROR
53Inverter soft start failed53 ERROR
55Over DC voltage in AC output55 ERROR
57Current sensor failed57 ERROR
58Output voltage is too low58 ERROR
59PV voltage is over limitation59 ERROR

6.2 Warning Indicator

Warning CodeWarning EventAudible AlarmIcon flashing
01Fan is locked when inverter is on.Beep three times every second01
03Battery is over-chargedBeep once every second03
04Low batteryBeep once every second04
07OverloadBeep once every 0.5 second07
10Output power deratingBeep twice every 3 seconds10
15PV energy is low.Beep twice every 3 seconds15
16AC voltage is over limitationBeep twice every 3 seconds16
E9Battery equalizationNoneE9
bPBattery is not connectedNonebP

7. Specifications

7.1 Line Mode Specifications

INVERTER MODEL4.2KW6.2KW
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS); 90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS); 100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)

7.2 Inverter Mode Specifications

INVERTER MODEL4.2KW6.2KW
Rated Output Power4.2KW6.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency50Hz
Peak Efficiency93%
Overload Protection3s@≥150% load; 30s@101%~150% load
Surge Capacity2* rated power for 3 seconds
Nominal DC Input Voltage24Vdc48Vdc
Cold Start Voltage23.0Vdc46.0Vdc
Low DC Warning Voltage @load < 50%22.0Vdc44.0Vdc
Low DC Warning Voltage @load ≥ 50%21.0Vdc42.0Vdc
Low DC Warning Return Voltage @load < 50%22.5Vdc45.0Vdc
Low DC Warning Return Voltage @load ≥ 50%22.0Vdc44.0Vdc
Low DC Cut-off Voltage @load < 50%20.5Vdc41.0Vdc
Low DC Cut-off Voltage @load ≥ 50%20.0Vdc40.0Vdc
High DC Recovery Voltage32Vdc62Vdc
High DC Cut-off Voltage33Vdc63Vdc
No Load Power Consumption25W50W
Saving Mode Power Consumption< 10W< 15W

7.3 Two Load Output Power

INVERTER MODEL4.2KW6.2KW
Full Load4200W6200W
Maximum Main Load4200W6200W
Second Load Range840W~2940W1240W~4340W
Main Load Cut Off Voltage22VDC44VDC
Main Load Return Voltage26VDC52VDC

7.4 Charge Mode Specifications

4.2KW6.2KW
Utility Charging Mode
Charging Algorithm3-Step
AC Charging Current (Max)100Amp (@VI/P=230Vac)
Bulk Charging Flooded Battery29.258.4
Voltage AGM / Gel Battery28.256.4
Floating Charging Voltage27Vdc54Vdc
MPPT Solar Charging Mode
Max. PV Array Power6200W8000W
Nominal PV Voltage240Vdc360Vdc
PV Array MPPT Voltage Range60Vdc~450Vdc
Max. PV Array Open Circuit Voltage500Vdc
Max Charging Current (AC charger plus solar charger)120Amp

7.5 General Specifications

INVERTER MODEL4.2KW6.2KW
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm423×344×112
Net Weight, kg7.28.2

7.6 Approximate Back-up Time Table

ModelLoad (W)Backup Time @ 24Vdc 100Ah (min)Backup Time @ 24Vdc 200Ah (min)
4.2KW3004491100
600222525
900124303
120095227
150068164
180056126
210048108
24003594
27003174
32002867
36002560
42002253
6.2KW5006131288
1000268613
1500158402
2000111271
250090215
320076182
350065141
400050112
450044100
50004090
62003680

Note:

  1. Backup time depends on the quality of the battery, age of battery and type of battery. Specifications of batteries may vary depending on different manufacturers.
  2. The final interpretation right of this product belongs to the company.

8. User Tips

  • Ensure all components are received and inspected upon delivery. Verify correct model and voltage (e.g., 48V for 6.2kW) before installation.
  • Proper wiring and adherence to specifications are crucial for optimal performance and safety.
  • Thoroughly check the package contents immediately upon arrival and contact the seller promptly if any discrepancies are found.
  • If you order the 6.2 kW at 48 volts, confirm that the model POW-HVM6.2K-48V-E is received.

9. Warranty and Support

9.1 Warranty

All products come with a 1-year warranty from our store.

9.2 Contact Information

For technical support or inquiries, please contact:

  • Tel/Fax: +86755-28219903
  • Email: support@powmr.com
  • Website: www.powmr.com
  • Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China

10. Frequently Asked Questions (FAQ)

Q: Is the 6.2 kW inverter compatible with 48V systems?
A: Yes, the 6.2kW model (POW-HVM6.2K-48V-E) is specifically designed for 48V systems. Please confirm the model number when ordering.
Q: How can I confirm the inverter's voltage and power?
A: The model number POW-HVM6.2K-48V-E indicates 6.2kW power and 48V system voltage. Always verify the product details upon receipt.