DATOUBOSS 6200W Hybrid Inverter User Manual

Model: DT4862BF | Brand: DATOUBOSS

1. Introduction

1.1 Purpose and Scope

This manual describes the assembly, installation, operation, and troubleshooting of the DATOUBOSS 6200W Hybrid Inverter. Please read this manual carefully before installation and operation, and keep it for future reference. It provides safety and installation guidelines, as well as information on tools and wiring.

1.2 Key Features

  • Type: DC/AC Inverter
  • Capacity: 6200VA/6200W
  • Protection Degree: IP54 (Dustproof Model)
  • Max. PV Input Power: 8500W
  • Max. PV Input Voltage: 500VDC
  • MPPT Tracking Range: 60-500VDC
  • Full Load MPPT Range: 360-430VDC
  • Max Charging Current: 120A
  • Max Input Current: 36A
  • Maximum Main Load: 6200W
  • Waveform: Pure sine wave
  • Maximum Conversion Efficiency: 98%
  • Lightning and High-Voltage Protection
  • Input and Output Safety
  • Increased PV Input Current for more power
  • EMI Filtering Reduces Interference
  • Higher PV Utilization When PV and Mains are Complementary
  • Auto restart while AC is recovering
  • Overload/Over temperature/short circuit protection
  • Smart battery charger design for optimized battery performance
  • Cold start function

1.3 Basic System Architecture

The DATOUBOSS Hybrid Inverter combines functions of an inverter, solar charger, and battery charger to provide uninterruptible power support. It can be integrated with a generator or utility power source and PV modules to form a complete energy system. This inverter is capable of powering various home and environmental appliances, including motor-type appliances like tube lights, fans, refrigerators, and air conditioners.

System Diagram showing Power Grid, Solar, 48V Battery, and Load connections
Figure 1: Basic System Architecture. This diagram illustrates the connections between the power grid, solar panels, 48V battery, and various loads, all managed by the inverter.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION: To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION: Only qualified personnel can install this device with battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for the details.
  10. One piece of 150A fuse is provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  12. NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

3. Installation

3.1 Unpacking and Inspection

Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the unit and a user manual inside the package.

3.2 Mounting the Unit

Consider the following points before selecting where to install:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level in order to allow the LCD display to be read at all times.
  • For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the side and approximately 50 cm above and below the unit.
  • The ambient temperature should be between -10°C and 50°C to ensure optimal operation.
  • The recommended installation position is to adhere to the wall vertically.
  • Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing three screws:

  • 1, 2: Use M6*80mm expansion bolts.
  • 3: Use M4 or M5.
Front, Left, Right side views of the inverter with LCD display screen and back panel ports labeled.
Figure 2: Inverter views showing front, left, right sides, and the LCD display. The back panel includes ports for AC Input, RS232, BMS/RS485, Dry Contact, DC Input, PV Input, Main Out & Second Out, Parallel Connection, and Power ON/OFF Switch.
Product Introduction diagram with labeled ports and controls.
Figure 3: Product Introduction. This diagram labels the various ports on the back panel (AC Input, RS232, BMS/RS485, Dry Contact, DC Input, PV Input, Parallel Connection, Main Out & Second Out, Power ON/OFF Switch) and the touch screen controls (UP, ESC, ENTER, DOWN) and indicators (INV, CHG, AC, Fault).

3.3 Battery Connection

CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in the table below as required fuse or breaker size.

WARNING! All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable and terminal size as below.

Rated CapacityTypical AmperageBattery CapacityWire SizeCable (mm²)Ring Terminal D (mm)Ring Terminal L (mm)Torque Value
3KVA132A100AH1*4AWG226.433.22~3 Nm
3.6KVA165A200AH2*8AWG96.429.25 Nm
4KVA165A200AH2*4AWG258.433.25 Nm
5.5KVA121A200AH1*2AWG346.439.22~3 Nm
6.2KVA124A200AH1*2AWG388.439.25 Nm
11KVA228A250AH1*3/0AWG858.4545 Nm

Follow these steps to implement battery connection:

  1. Assemble battery ring terminal based on recommended battery cable and terminal size.
  2. Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with a torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charger is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.

WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.

CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).

3.4 AC Input/Output Connection

CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the Inverter can be disconnected during maintenance and fully protected from over current of AC input. The recommended spec of breaker is 32A for 24V system and 63A for 48V system.

CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested Cable Requirement for AC Wires:

Rated CapacityGaugeTorque Value
3KVA12AWG1.2~1.6Nm
3.6KVA12AWG1.2~1.6Nm
4KVA12AWG1.2~1.6Nm
5.5KVA10AWG1.4~1.6Nm
6.2KVA10AWG1.4~1.6Nm
11KVA8AWG1.4~1.6Nm

Please follow below steps to implement AC input/output connection:

  1. Before making AC input/output connection, be sure to open DC protector or disconnector first.
  2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N3 mm.
  3. Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (Ground) first.
  • Ground (yellow-green)
  • L (brown or black)
  • N (blue)

WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.

  1. Make sure the wires are securely connected.

CAUTION: Appliances such as air conditioners are required at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check the manufacturer of the air conditioner if it's equipped with a time-delay function before installation. Otherwise, this inverter/charger will trigger an overload fault and cut off output to protect your appliance, but sometimes it still causes internal damage to the air conditioner.

3.5 PV Connection (Only apply for the model with solar charger)

CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between the inverter and PV modules.

WARNING! All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.

Typical PV Cable Requirement:

Typical AmperageGaugeTorque Value
30A12AWG1.4~1.6Nm

PV Module Selection:

When choosing the right PV module, be sure to first consider the following requirements:

The open circuit voltage (Voc) of the PV modules does not exceed the maximum PV array open circuit voltage of the inverter. The maximum supply voltage of the PV modules should be close to the optimal PV access voltage range of the inverter for best performance. If one PV module cannot meet this requirement, it is necessary to connect multiple PV modules in series.

3.6 Final Assembly

After connecting all wirings, please put the bottom cover back by screwing the two screws.

4. Operation

4.1 Power ON/OFF

Once the unit has been properly installed and the batteries are connected, simply press the On/Off switch (located on the button of the case) to turn on the unit.

Steps to Start Up:

Connect the battery that meets the requirements (battery voltage needs to be beyond 23V) or AC (AC needs to confirm the suitable input range depending on the output mode), then you can start up the inverter.

  • Mains Power On: Connect to normal AC power, press the switch. The system will automatically turn on. If you set AC output power priority, after waiting for a period of time, the panel will display AC mode, indicating successful machine turn-on, and then enter AC mode.
  • Battery Boot: Connect to battery, press the power-on button to establish a working power source. The system will automatically turn on. After waiting for a period of time, the panel will display battery mode, indicating successful machine turn-on, and then enter battery mode.

Shutdown Steps:

When the system is in battery mode or AC mode output, press the switch again, then the system will be turned off.

4.2 LCD Display Icon

The operation and display panel is located on the front panel of the inverter. It includes RGB indicators and an LCD display.

Touch Color Screen with labeled controls and indicators.
Figure 4: Touch Color Screen. This image shows the inverter's touch screen with indicators for INV, CHG, AC, and Fault, along with navigation buttons (UP, ESC, ENTER, DOWN).

Home Screen:

The LCD is a touch screen. The upper part of the LCD screen displays overall information of the inverter.

  1. The absence of an icon in the center of the home screen indicates that the system is operating normally. If a gray icon and characters are displayed in the center of the main screen, it means that the inverter has an alarm, and the alarm information will be displayed in characters under this icon (detailed error information can be viewed in the instruction manual alarm menu). If a red icon and characters are displayed in the center of the main screen, it means that the inverter is faulty, and the fault information will be displayed in characters under this icon (detailed error information can be viewed in the instruction manual alarm menu).
  2. At the top of the screen is the time.
  3. System Settings icon: Press the Settings button to enter the system settings screen, including battery settings, system working mode, grid settings, basic settings, advanced features, device information.
  4. The main screen displays information including PV, mains, load, and battery. It also shows the direction of energy flow with arrows. Equivalent power. When approaching the limit value, the color on the panel will change from green to red, making the system information vividly displayed on the main screen.
  5. Photovoltaic power and load power are always positive.
  6. The mains power is connected negatively to the grid and obtained positively.

LED Indicator Functions:

CodeMachine StateColorEffectDisplay
1Stand by/Self-testColorfulGradient color displayBreath light
2Under DC modeBlueMonochrome display (one light keeps flashing)NO
3Under AC/Full charge under AC modeGreenMonochrome displayNO
4Charging under AC modeGreenMonochrome displayYES
5Solar chargingYellowMonochrome displayYES
6Full charge under solar powerYellowMonochrome displayNO
7Under the alarmRedMonochrome displayYES (recoverable)
8Solar energy and AC charging at the same timeHalf and half (yellow on top, green on bottom)Monochrome displayYES

4.3 Touch Screen Operation Instructions

The touch screen allows for detailed monitoring and configuration of the inverter's parameters. The main menu provides access to various sub-pages:

  • Inverter Page: Displays machine type, inverter type, driver version, LCD version, temperatures (boosting, machine, MPPT, inverter, MOS), IAP status.
  • PV Page: Shows PV input voltage, current, power for PV1 and PV2, and records daily, monthly, yearly, and total PV power generation.
  • Battery Page: Displays battery type, BMS communication function status, battery voltage, charge current, discharge current, bus voltage, and Li Battery Active status.
  • BMS Page: Details BMS 485 protocol, SOC, charge/discharge current, BMS temperature, discharge/charge limit voltage, and charge limit current.
  • Load Page: Shows dual status, output, load percent, active power, and apparent power.
  • Mains Page: Displays AC input frequency, input voltage, and AC input power.
  • External CT Detail Page: Shows frequency, input voltage, and AC input power at the CT detection point.
  • System Settings Menu: Accesses various settings categories:
    • System Work Mode: Configures ECO function, output priority (SUB, SBU), output type (SIG, PAL, 3P1, 3P2, 3P3), clear generation, and reset factory settings.
    • Grid Setting: Configures input voltage range (APL/UPS), grid-connected regulation mode, grid feed enable/current, external CT function, zero export to CT, AC CHA open/stop time.
    • Charge Setting: Configures charge source priority (CSO, SNU, OSO), max utility charge current, max charge current, solar supply priority.
    • Basic Setting: Configures output voltage/frequency, alarm control, overload bypass/restart, MIP cut off buzzer, over temp restart, auto back menu.
    • Battery Setting: Configures battery type (AGM/FLD/USE/LIA/PYL/TQF/GRO/LIB/LIC), bulk charging voltage, float charging voltage, battery cut-off voltage, battery low voltage, BMS function switch, BMS SOC settings, battery equalization settings.
    • Advanced Function: Configures dual mode, dual output, output open/stop time, DC to AC voltage, AC to DC voltage.
    • Device Info: Displays system time, backlight settings, and RGB switch.

5. Maintenance

Regular maintenance is crucial for the longevity and optimal performance of your DATOUBOSS Hybrid Inverter. Always ensure the unit is disconnected from all power sources (AC, DC, PV) before performing any maintenance tasks.

  • Cleaning: Periodically clean the exterior of the inverter to prevent dust buildup, especially around ventilation openings. Use a dry, soft cloth. Do not use liquid cleaners.
  • Ventilation: Ensure that the inverter's ventilation openings are clear and unobstructed to allow for proper heat dissipation. Maintain the recommended clearances around the unit as specified in the installation section.
  • Wiring Inspection: Periodically check all wiring connections (battery, AC input/output, PV) for tightness and signs of wear or damage. Loose connections can lead to overheating and system malfunctions.
  • Battery Health: Monitor battery voltage and performance through the LCD display. Ensure batteries are not frozen and are charged according to recommended parameters.
  • Firmware Updates: Check the manufacturer's website for any available firmware updates to ensure your inverter is running with the latest features and bug fixes.

6. Troubleshooting

6.1 Fault and Alarm Description

The inverter provides various fault and alarm codes to help diagnose issues. Alarms typically cause the red LED to flash and display a code on the LCD, but the inverter does not enter fault mode. Faults indicate a more serious issue, causing the red LED to stay on and the inverter to enter fault mode.

Warning Codes:

Warning CodeWarning EventAudible Alarm
01Fan locked when inverter startsBeeps three times every 1 second
02Over temperatureNone
03Battery overchargeBeeps once every 1 second
04Low batteryBeeps once every 1 second
07OverloadBeeps once every 0.5 seconds
10Output power deratingBeeps twice every 3 seconds
15Low PV energyBeeps twice every 3 seconds
16High AC input during bus soft start (>280VAC)None
60Power feedback protectionNone
61Communication interruption (Battery)Beeps immediately if communication fails after successful connection.
69Battery status does not allow chargingNone
70Battery status requires chargingNone
71Battery status does not allow dischargingNone

Fault Codes:

Fault CodeFault EventExplanation/Possible CauseAction
01Fan locked when inverter shuts downFan malfunctionReplace fan.
02Over temperature or poor NTC connectionInternal temperature too highCheck for blocked airflow or high ambient temperature.
03Battery overvoltageBattery voltage too highCheck battery specifications and quantity.
04Battery undervoltageBattery voltage too lowCharge battery or replace battery.
05Output short circuit or internal overheating detectedOutput short circuit or internal converter component temperature exceeds 120°CCheck wiring, remove abnormal loads.
06Output overvoltageOutput voltage too highReturn to service center.
07Overload timeoutInverter overloaded (105%), or derated output power exceeded by load.Reduce connected load.
08Bus overvoltageBus voltage too highReturn to service center.
09Bus soft start failureBus soft start failedReturn to service center.
51Overcurrent or surgeOvercurrent detectedRestart device. If error persists, return to service center.
52Bus undervoltageBus voltage too lowReturn to service center.
53Inverter soft start failureInverter soft start failedReturn to service center.
55DC voltage in AC outputDC component detected in AC outputReturn to service center.
57Current sensor faultCurrent sensor malfunctionReturn to service center.
58Output undervoltageOutput voltage too lowReturn to service center.
59PV voltage out of limitPV input voltage exceeds specificationsReduce the number of series PV modules.

7. Technical Specifications

The following table provides detailed technical specifications for the DATOUBOSS 6200W Hybrid Inverter (Model DT4862BF).

FeatureSpecification
InputInput TypeL+N+PE
Rated Input Voltage220/230/240VAC
Voltage Range90-280VAC±3V (APL Mode), 170-280VAC±3V (UPS Mode)
Frequency Range50Hz/60Hz (Auto-adaptive)
Rated Power (Battery Inverter)6200W
OutputRated Power (PV Inverter)8500W
Output Voltage220/230/240VAC±5%
Output Frequency50/60Hz±0.1%
WaveformPure Sine Wave
Peak Power12400VA
Grid-tied OperationFeed-in Grid Voltage Range170-265VAC
Feed-in Grid Frequency Range49-51Hz/59-61Hz
EfficiencyNominal Output Current26.9A
Power Factor Range>0.99
Maximum Conversion Efficiency (DC/AC)98%
BatteryRated Voltage48Vdc
Constant Voltage Charging (Adjustable)56.4Vdc
Float Charging Voltage (Adjustable)54Vdc
ChargerPV Charging MethodMPPT
Max. PV Input Power8500W
MPPT Input Voltage Range60-500Vdc
Max. PV Input Voltage500Vdc
Max. PV Input Current27A
Max. Charging Current120A
GeneralWeight23.2KG
Operating Temperature-10°C to 50°C
Protection DegreeIP54

8. Warranty and Support

For warranty information, technical support, or service inquiries, please contact DATOUBOSS Official Store directly. Ensure you retain your purchase records for any warranty claims.

A detailed user manual in PDF format is available for download. Please refer to the official product page or contact customer support for the PDF link: User Manual (PDF)