DATOUBOSS DT-2433M-A-EU

Contents

DATOUBOSS Hybrid Solar Inverter User Manual

Model: DT-2433M-A-EU

1. Introduction

This manual provides comprehensive instructions for the installation, operation, maintenance, and troubleshooting of your DATOUBOSS 24V 3300W Hybrid Solar Inverter. This multifunctional inverter/charger integrates an inverter, solar charger, and battery charger into a single unit, delivering uninterrupted power support in a portable form factor. Its comprehensive LCD display supports user-customizable settings, complemented by intuitive control buttons to adjust battery charging current, AC/solar charger priority, and acceptable input voltage according to varying application scenarios.

DATOUBOSS Hybrid Solar Inverter with key specifications
The DATOUBOSS Hybrid Solar Inverter, highlighting its 3300W AC output power, 80A maximum AC charging current, and 5000W maximum photovoltaic input power.
DATOUBOSS Hybrid Solar Inverter with key features
This image illustrates the inverter's key features, including 3300W AC output power, 80A maximum AC charging current, and 5000W maximum photovoltaic input power, emphasizing its role as a multifunctional inverter/charger.

The inverter is compatible with 95% of household and office appliances, including lighting, fans, refrigerators, air conditioners, coffee machines, and other household appliances.

Inverter powering various household appliances
The inverter is shown powering various household appliances, demonstrating its 3300W maximum AC power output and broad compatibility.

2. Setup and Installation

2.1. Product Overview and Components

Before beginning installation, familiarize yourself with the inverter's components and connections.

Exterior Diagram and Product Overview of the Hybrid Solar Inverter
Exterior Diagram/Product Overview: This diagram labels the key external components of the inverter, including the LCD display, LED indicator light, function keys (DOWN, ESC, ENTER, UP), power button, RS485-2 (BMS Communication) and RS485-1 (External Communication/WIFI) interfaces, Input Reproducible Insurance, AC Output (Standby Output/Uninterruptible Output) Terminal Block, AC Input (Grid-Connected) Terminal Block, PV input terminal block, Battery terminal, Grounding, Mains power input socket, and Load output socket. The Mains Input Control Switch is also indicated, showing its function for selecting AC terminal input.

2.2. Initial Preparation

Before connecting any wiring, remove the bottom cover by unscrewing the screws.

2.3. Wiring Connections

DANGER: Touching the terminals of the mains or equipment may result in death by electric shock or fire! Do not touch terminals or conductors connected to the mains circuit. Pay attention to any instructions or safety documentation regarding grid connection.

NOTE: Some internal components will become hot during operation; please wear protective gloves.

2.3.1. Battery Connection

  1. Remove insulation sleeve 6 mm for positive and negative conductors.
  2. Check correct polarity of connection cable from battery modules and battery input connectors. Connect positive pole (+) of connection cable to positive pole (+) of BATTERY input connector. Connect negative pole (-) of connection cable to negative pole (-) of BATTERY input connector.
  3. Make sure the polarity of the wiring is correct and the connection is firm. Ensure there is no short circuit between the positive and negative electrodes.

2.3.2. AC Input (Grid-Connected) and AC Output (Uninterrupted Output) Connection

CAUTION: There are two terminal blocks with "INPUT" and "OUTPUT" markings. Please do NOT mis-connect input and output connectors.

  1. Before connecting to AC input power source, install a separate AC breaker between the inverter and AC input power source. This will ensure the inverter can be securely disconnected.
  2. Remove insulation sleeve 10mm for four conductors.
  3. Insert AC Input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor first.
  4. Then, insert AC output wires according to polarities indicated on the terminal block and tighten terminal screws.

WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.

2.3.3. PV Connection

  1. Remove insulation sleeve 10 mm for positive and negative conductors.
  2. Check correct polarity of connection cable from PV modules and PV input connectors. Connect positive pole (+) of connection cable to positive pole (+) of SOLAR input connector. Connect negative pole (-) of connection cable to negative pole (-) of SOLAR input connector.
  3. Make sure the polarity of the wiring is correct and the connection is firm.
Wiring diagram for a complete operating system with solar panels, generator, inverter, battery, and loads
Complete Operating System Diagram: This diagram illustrates the connections between solar panels (PV), a generator, the inverter, batteries, and various household loads (light bulb, induction cooker, oven, washing machine, air conditioner). It shows how these components integrate to form a hybrid power system.

Important Wiring Notes:

  • When connecting the battery and photovoltaic, pay attention to the positive and negative poles of the cable, and do not connect them reversely.
  • If connecting a generator, start the generator first, then connect to the inverter mains input after it runs stably. If connecting to the output end of the generator, then start the inverter, and finally connect to the user equipment after the inverter becomes normal.
  • It is recommended that the generator capacity is three times the inverter rated capacity.

2.4. Final Assembly

After connecting all wirings, put the bottom cover back by screwing the screws as shown in the product overview image.

Mains power input socket and electrical assembly cable
Mains power input socket and the included 16A angled plug electrical assembly cable (3x2.5mm², 2M).

3. Operation

3.1. Display Control Panel and Buttons

The display board is divided into three functional areas: LCD display area, LED display area, and Function key control area.

3.1.1. LED Indicators

NameDescription
AC (Green)On: The inverter works in the main state
Flashing: The inverter AC input detection is normal, works in battery priority mode.
Off: Other states
INV (Green)On: The inverter is working in the inverter state.
Off: Other states
CHG (Yellow)On: Constant voltage charging, floating charging or fully charged
Flashing: Constant current charging
Off: Other states
FLUAT (Red)On: Inverter self-protection
Flashing: Fault occurs in the inverter
Off: Works normally

3.1.2. Button Functions

Function keysDescription
DOWNParameter less or previous page
ESCWithout saving or Exit setup mode
ENTERConfirm selection in setup mode or enter Save and exit setup mode
UPParameter more or next page

3.2. LCD Screen Description

The LCD display includes icon display, working status display area, numerical display, and function setting area.

3.2.1. Icon Display

  • Load and battery icons indicate the load and battery capacity. Each square represents 25% of the capacity.
  • The Mute icon shows whether the buzzer is muted. Under normal circumstances, this icon is not displayed; press the ENTER key in any mode to display it. The inverter enters the mute state and the buzzer inhibit icon will be displayed.
  • The Fault icon only displays when in fault mode, and won't display in other situations.

3.2.2. Working Status Display Area

After starting up, this display area mainly displays the working status of the inverter, such as mains status, inverter status, grid connection status, etc.

3.2.3. Numerical Display and Function Setting Area

  • In non-function setting mode, this area displays inverter related information. Normal mode displays output information, check the operation up and down. The Inquiry key (UP or DOWN key) is used to display input voltage and output voltage, input frequency and output frequency, battery voltage and current, PV voltage and PV current, PV voltage and power, output power and output voltage, output apparent power and output Voltage, load percentage and output voltage related information. The fault mode displays the fault code.
  • In the function setting page, you can set the working mode, battery high and low voltage alarm, etc. by operating the ENTER key and the UP and DOWN keys.

3.3. ON/OFF Button Description

3.3.1. Switch On

Connect to battery or AC power supply (AC power needs to confirm the reasonable input range according to the output mode) or connect to PV power, then the inverter can switch on.

  • Switch on with Battery: After connecting with battery, press the on button. The inverter will establish working power supply, and waiting for a while, the inverter will be turned on and there will be AC output.
  • Switch on with AC: After connecting with AC, the inverter will establish working power supply automatically. Press the on button, the inverter will have AC output. If set to AC output priority mode, the AC will charge the battery and bypass the output.
  • Switch on with PV: After connecting with PV, the inverter will establish working power supply automatically and charge the battery. Press the on button, the inverter starts to invert and has AC output.

3.3.2. Switch Off

  • Switch Off with Battery: When working with battery, press the Off button. The machine will switch off the output and working power after a period of time.
  • Switch Off with AC: When working with AC, press the Off button. The machine will switch off the output and only maintain the working power, standby state, disconnect the AC, and the inverter turn off.
  • Switch Off with PV: When working with PV, press the Off button. The machine will switch off the output, maintain the working power and charge the battery, disconnect the PV, and the inverter turn off.

3.4. Operation in Alarm State

When the inverter has an alarm and the red LED fault indicator is on, it means that the inverter is working in an alarm state. You can observe the fault code displayed on the LCD display and compare it with the fault code table in the troubleshooting section for preliminary troubleshooting.

3.5. Function Setting Operation (A0-A28)

To enter the function setting page, press the ENTER key for 2 seconds. Use the UP/DOWN keys to navigate through functions and values. Press ENTER again to confirm selections. Press ESC to exit without saving.

3.5.1. Output Priority Setting (A0)

There are three choices: GRD (Mains priority), PV (PV priority), PBG (Battery priority). This can only be set in battery mode and takes effect immediately after saving.

3.5.2. Battery Type and Parameter Settings (A1-A7)

If the battery pack is a lead-acid battery or a lithium battery without BMS communication, set A17 to Pb (lead-acid battery). The inverter operates according to the set values of battery parameters A1 to A7. If the battery pack is a lithium battery with BMS communication, set A17 to GRD/VLO/PYL/PAC according to the required BMS communication protocol.

  • A1: Average Charge Voltage Setting (e.g., 14.2V for 12V model)
  • A2: Float Voltage Setting (e.g., 13.8V for 12V model)
  • A3: Battery Low Voltage Protection Setting (e.g., 10.5V for 12V model)
  • A4: Battery Low Voltage Alarm Setting (e.g., 11.0V for 12V model)
  • A5: Recover Battery Voltage Setting (e.g., 13.0V for 12V model)
  • A6: Mains to Battery Mode Voltage Setting (e.g., 13.2V for 12V model)
  • A7: Battery to Mains Voltage Setting (e.g., 11.0V for 12V model)

3.5.3. Frequency Setting (A8)

Set the output frequency (50Hz or 60Hz). Default is 50Hz.

3.5.4. Output Voltage Setting (A9)

Set the output voltage (220V, 230V, 240V). Default is 230V.

3.5.5. Charging Priority Setting (A10)

Only settable in battery mode. Options: SNU (PV & mains charging), OSO (Only PV charging), CSO (PV Charging priority).

3.5.6. Non-Battery Mode Settings (A11)

Set whether the inverter is connected to the battery or not. Default is bC (connect battery), bNC (Disconnect battery).

3.5.7. Mains Charging Current Setting (A12)

Set the mains charging current. Default is 30A (range: 5A-65A).

3.5.8. Maximum Charging Current Setting (A13)

Set the maximum current for simultaneous charging of mains and photovoltaics. Default is 60A (range: 5A-100A).

3.5.9. Mains Input Voltage Range Setting (A14)

Set the mains input voltage range. Default is UPS (165V-280V), APL (120V-280V).

3.5.10. Working Mode Setting (A15)

Options: GRD (hybrid mode), GRE (grid-connected feed mode), DIS (off-grid mode).

3.5.11. Grid-Connected Current Setting (A16)

Set the current at AC INPUT when the grid is connected. Default is 0A. Range varies by power segment.

3.5.12. Lithium Battery BMS Communication Protocol Setting (A17)

Set the communication protocol for lithium batteries. Options: Pb (lead-acid battery), GRO (Growatt), VLO (Voltronic), PYL (Pylon), PAC (PACE).

3.5.13. BMS Communication Address Setting (A18)

Set the BMS communication address code (000-247). Default is 001.

3.5.14. Switch Off SOC Setting (A19)

Set the SOC value at which the inverter switches off in battery mode. Default is 5% (range: 1%-80%).

3.5.15. Low Voltage Recover SOC Setting (A20)

Set the SOC value at which the inverter recovers after low-voltage protection. Default is 15% (range: 1%-90%).

3.5.16. Inverter to Mains Battery SOC Setting (A21)

Set the SOC value at which the inverter switches from battery supply to mains supply. Default is 10% (range: 1%-80%).

3.5.17. Mains to Battery Mode SOC Setting (A22)

Set the SOC value at which the inverter switches from mains power supply to inverter power supply. Default is 80% (range: 1%-100%).

3.5.18. Charging Cut Off SOC (A23)

Set the SOC value at which the inverter stops charging. Default is 100% (range: 1%-100%).

3.5.19. Battery Low Voltage Restart Setting (A24)

Whether to automatically turn on the inverter output after battery low voltage protection. Default is BRE (Recover), BRD (Do not recover).

3.5.20. Overload Restart Setting (A25)

Whether to recover or not when the load is overloaded, and whether to automatically restore the power-on function after the inverter is overloaded. Default is LRD (Do not recover), LRE (Recover).

3.5.21. Recover After Over Temperature (A26)

Whether to recover the setting item when the temperature is too high. Default is TRD (Do not recover), TRE (Recover).

3.5.22. Inverter Computer Communication Address Setting (A27)

Set the computer communication address code (000-247). Default is 001.

3.5.23. Equipment Neutral Grounding Settings (A28)

Set whether the output neutral line is grounded in battery mode. Default is OFF (neutral line is not grounded), ON (neutral line is grounded).

3.5.24. Equipment Power Generation Reset (A29)

Inverter power generation reset item. Default is ESC (power generation is not cleared), CLR (power generation is cleared).

3.5.25. Restore Factory Settings (A30)

One-click restore factory defaults. Default is ESC (parameters are not restored), RES (parameters are restored).

3.6. Output Priority and Working Modes

The inverter will continue to detect the fluctuation of the current power grid for about 1 minute. If the power grid fluctuation does not exceed the inverter's mains input range during this time, the inverter will be connected to the mains, otherwise it will not be connected to the mains. This prevents frequent switching to the mains when the power grid is unstable.

3.6.1. Grid-Tie Mode (A.Grid-Tie mode)

Mains power and PV provide power to the load simultaneously. The battery only provides power when mains power is unavailable. PV is prioritized for charging the battery, and excess energy feeds the grid.

  • With PV and Mains Power: Mains power prioritizes load energy; PV charges the battery. If PV energy is insufficient, mains supplement. If PV generation exceeds load and charging needs, excess feeds the grid.
  • With PV, No Mains Power: PV prioritizes load energy, remaining energy charges the battery. If PV energy is insufficient, the battery discharges to supplement.
  • With Mains Power, No PV: Mains power supplies load and charges the battery. If mains power is lost, the battery discharges until low voltage, then switches to standby.

3.6.2. PV Power Priority (2. PV power priority)

PV power is prioritized for the load. Excess energy charges the battery and then feeds the grid. The battery provides power only when PV power is insufficient or unavailable.

  • With PV and Mains Electricity: PV power prioritizes load, excess charges battery. If battery voltage reaches grid connection condition, remaining PV energy feeds into the grid. If PV energy is insufficient for load, mains power supplements.
  • With PV, No Mains Power: PV power prioritizes load, excess charges battery. If PV energy is insufficient, battery discharges to supplement.
  • With Mains Power, No PV: Mains power supplies load and charges battery. If mains power is lost, battery discharges until low voltage, then switches to standby.

3.6.3. Battery Priority (3. Battery priority - Off-grid operation mode)

PV power prioritizes supplying power to the load. If PV power is insufficient or unavailable, batteries supplement the load. When battery discharge voltage reaches the set value, it switches to mains to supply power to the load.

  • With PV and Mains Electricity: Inverter works in inverter state, PV power prioritizes load, excess charges battery. If PV energy is insufficient, battery discharges to supplement. If battery discharges to low voltage, it switches to mains bypass and starts charging.
  • With PV, No Mains Electricity: PV power prioritizes load, excess charges battery. If PV energy is insufficient, battery discharges to supplement.
  • With Mains Power, No PV: Prioritizes battery discharge for load. If battery discharges to low voltage, it switches to mains bypass and starts charging. If mains power is lost, battery discharges until low voltage, then switches to standby.

3.6.4. No Battery Operation Mode (D. No battery operation mode)

If no battery is configured, the inverter must be set to bNC (A11). Output priority cannot be set to battery output priority; the inverter will operate in grid-connected or hybrid mode.

  • Grid-Tie Mode: PV solar energy prioritizes load. If PV generation is insufficient, mains supplement. If PV generation exceeds load, excess feeds the grid. If mains power is unavailable, PV inverter carries the load.
  • Hybrid Mode: PV power energy prioritizes load. If PV generation is insufficient, mains supplement. If mains power is unavailable, PV inverter carries the load.
  • Off-Grid Mode (Not Recommended): If PV power is insufficient, the output will be turned off. Only PV can be turned on and loaded; mains power is invalid.

4. Maintenance

4.1. General Maintenance Precautions

DANGER:

  • Before any maintenance work, first disconnect the inverter from the electrical grid and then disconnect the DC side electrical connection.
  • Wait at least 5 minutes until the internal components are discharged before proceeding with maintenance work.
  • Any fault affecting the safety performance of the inverter must be eliminated before it can be turned on again. Contact maintenance center if needed.
  • Do not disassemble or assemble internal components without authorization.

4.2. Battery Maintenance

The inverter requires minimal maintenance. The lifespan of the battery can be preserved by frequent charging.

  • Batteries should be charged every three months if the inverter is long-term unused.
  • Battery lifespan is typically three to five years. Replace in advance if any battery is in poor state. Replacement should be done by a professional.
  • Batteries should be wholly replaced per supplier instructions.
  • Every three months, batteries should be discharged (until the inverter shuts down) and recharged. Each charge should last at least 12 hours.
  • In high-temperature areas, batteries should be discharged and recharged every two months.

NOTE:

  • Shut down the inverter, then disconnect AC input and PV input before replacing batteries.
  • Do not wear metal jewelry such as rings or watches.
  • Use a screwdriver with an insulated handle and avoid placing tools or metal objects on batteries.
  • Avoid short circuits or reverse connections.

WARNING:

  • Battery must not be put in fire, which may cause explosion.
  • Do not open or damage the battery. Electrolyte released will cause harm to eyes and skin and even intoxication.

4.3. Dust Filter Assembly and Cleaning

To clean the dust filter, remove the 2 screws fixing the dust filter cover on the left and right sides. Then take off the dust filter cover and dust filter. After cleaning, install the dust filter and its cover in the order shown in the figure, and then use the 2 removed screws to fix the left and right dust filter covers on the inverter.

Dust filter assembly diagram
Diagram showing the dust net and net cover components for the inverter's dust filter assembly.

NOTE: When using the inverter in areas with poor environment, the dust filter is easily blocked by air particles. Disassemble and clean the dust filter regularly to avoid affecting the air volume and flow rate inside the inverter and triggering the over-temperature protection of components. Failure will affect power supply usage and the service life of the inverter.

5. Troubleshooting

When the inverter has a fault alarm, the red LED light flashes; when there is fault protection, the LED red light is on, and the LCD displays the fault code. For specific fault code descriptions and solutions, refer to the following sheet:

5.1. Fault Code Sheet

Fault codeFault messageRemedy (Rx)
40EEPROM Read and write faultPlease contact the supplier
41Communication failure with the main controllerPlease contact the supplier
42Abnormal parameter settingPlease check whether the set parameters are incorrect or can restore the factory settings
43Abnormal reference voltageThe internal power supply is unstable, restart the machine to recover
44BUS soft start faultPlease check whether the battery voltage or other input voltage is too low
45Hardware over flowPlease check whether the output is overloaded or has an excessively large non-linear load.
46Short circuit faultPlease check the output for a short circuit to exclude the abnormal load
47Inverter faultPlease check whether the inductive load has too much impact, turn off the power and then power on the inverter again. If it does not recover, please contact the supplier
48Battery over voltage alarmPlease check whether the battery voltage is too high, whether the number of battery cells is correct, and whether the voltage of each battery cell is normal.
49Battery over voltage protectionPlease check whether the battery voltage is too high, whether the number of battery cells is correct, and whether the voltage of each battery cell is normal.
50Battery low voltage protectionPlease check whether the battery voltage is too low, whether the number of battery cells is correct, and whether the voltage of each battery cell is normal.
51Battery low voltage alarmPlease check whether the battery voltage is too low, whether the number of battery cells is correct, and whether the voltage of each battery cell is normal.
52BUS high voltage faultPlease check whether the battery or input voltage is too high
53BUS low voltage faultPlease check whether the battery or input voltage is too low
54Overload alarmPlease check whether the output load is overloaded and reduce the load appropriately
55High temperature of the inverter radiatorPlease check whether the cooling fan is normal, whether the ambient temperature is too high, and whether the inverter vent is blocked.
56DC/DC, the radiator at high temperaturePlease check whether the cooling fan is normal, whether the ambient temperature is too high, and whether the inverter vent is blocked
57MPPT radiator with high temperaturePlease check whether the cooling fan is normal, whether the ambient temperature is too high, and whether the inverter vent is blocked
58PV1 high voltagePlease check whether the PV input voltage of PV1 exceeds the operating range.
59PV2 high voltagePlease check whether the PV input voltage of PV2 exceeds the working range
60Mains high voltagePlease check whether the input mains voltage is too high
61Abnormal frequencyPlease check whether the mains frequency is normal
62Remote shutdownPlease determine if a remote shutdown command was sent
63Abnormal communication with the lithium batteryPlease check whether the inverter and the lithium battery communication protocol correspond, and whether the connection line is correct
64Lithium battery single cell or total voltage is too highPlease check whether the single-section cell voltage and total voltage of the lithium battery are too high
65Lithium battery single cell or total voltage is too lowPlease check whether the single-section cell voltage and total voltage of the lithium battery are too low
66Lithium battery discharge overcurrentPlease check whether the load power is too large
67Lithium battery charge overcurrentPlease appropriately reduce the maximum charging current set by the inverter
68Lithium battery temperature is abnormalPlease check whether the lithium battery is overheated, shut down and wait for recover after restarting

6. Technical Specifications

The following table details the technical specifications of the DATOUBOSS Hybrid Solar Inverter (Model: DT-2433M).

Detailed Specifications label on the side of the inverter
Detailed specifications as printed on the product label.
CategoryParameterValue
PV InputMax PV Input Power2500W
MPPT Tracking Voltage Range30VDC-240VDC
Rated Voltage180VDC
Max PV Input Voltage Voc (at lowest temperature)300VDC
Max PV Input Current15A
Battery & ChargingBattery TypeLead-acid Battery/Lithium Battery (Customizable)
Rated Battery Voltage12VDC
Battery Voltage Range10.5-15VDC (default)
Max Charging Current (PV/AC)100A (PV), 65A (AC)
On-Grid Output (AC)Rated Output Power1800W
Rated Output Voltage220VAC/230VAC/240VAC
Grid Voltage Range187VAC-264VAC
Frequency Range47Hz-52Hz (50Hz), 57Hz-62Hz (60Hz)
Power Factor>0.98
Off-Grid Output (AC)Rated Input Voltage220V/230V/240V
Mains Input Voltage Range165VAC-280VAC / 120VAC-280VAC (settable)
Rated Output Power1800W
Rated Output Voltage220V/230V/240V
Output Voltage Accuracy±2%
Output WavePure Sine Wave
GeneralMaximum Conversion Efficiency (Battery Discharge)94% (peak value)
MPPT Tracking Efficiency≥99.9%
Transfer Time10ms (typical value)
DisplayLCD+LED
Cooling MethodCooling fan in intelligent control
CommunicationRS485/Mobile APP (WIFI Monitoring) (Optional)
Protection DegreeIP20
EnvironmentOperating Temperature-10°C~50°C
Storage Temperature-15°C~60°C
Noise≤55dB
Elevation2000m (More than derating)
Humidity0%~95% (No condensation)
Dimensions & WeightProduct Size (L*W*Hmm)310x250x91
Package Size (L*W*Hmm)385x305x156
N.W. (kg)4.0
G.W. (kg)5.0

Note: The above parameters are subject to change without prior notice!

Dimensions of the Hybrid Solar Inverter
The inverter's dimensions are 375mm (height), 275mm (width), and 108mm (depth).

7. Warranty and Support

7.1. Warranty Information

Please retain your warranty card as proof of maintenance. The warranty period is 1 year from the date of purchase. During the warranty period, under normal use and maintenance, if damage is caused by the product's own quality, the company will provide free repair and replacement parts after verification. The company reserves the right to maintain and interpret all contents.

Free maintenance will not be given under the following circumstances:

  • Damage caused by manipulation that does not follow the requests of the manual.
  • The product has been repaired, modified by technicians other than our company's, and any internal parts of the product have been replaced by users.
  • The product number has been altered or the product is inconsistent with the warranty card.
  • Damage caused by careless use, penetration of water or other substances into the product.
  • Damage caused by accident or natural disaster.

7.2. Communication Interfaces

7.2.1. RS485 Communication Interface

The inverter features RS485-1 (External communication/WIFI) and RS485-2 (BMS communication) ports. Refer to the product overview diagram for pin definitions.

7.2.2. WIFI Communication Port (Optional)

A WIFI module (optional, not standard) can be connected for remote monitoring/control via mobile phones or web pages. Operating data of the inverter can be uploaded to a server via WiFi. Users can choose to use the web or APP for monitoring and reading as needed. Register an account and bind the device using the WiFi serial number and QR code affixed to the packaging box/WiFi data collector.

  • Website: https://solar.siseli.com/
  • APP: Android phone users search "Solar of Things" in the App Store. iOS users search "Solar of Things" in the AppStore.

For detailed instructions on the WIFI data collector, please refer to its instruction manual.

7.3. User Manual (PDF)

A detailed user manual in PDF format is available for further reference. This document contains comprehensive instructions and specifications not fully detailed here. You can view the PDF manual here.

8. User Tips

  • On-Grid Functionality: This inverter supports on-grid functionality, allowing it to feed excess solar power back into the grid. Ensure your local regulations and utility company requirements are met before enabling this feature.
  • Indoor Use Only: The inverter is not waterproof and is recommended for use in indoor waterproof environments.
  • Regular Dust Filter Cleaning: To maintain optimal performance and prevent overheating, regularly clean the dust filter, especially in dusty environments.
Hybrid solar inverter setup with solar modules, inverter, battery, and household loads
A typical hybrid solar inverter setup, showing solar modules connected to the inverter, which in turn powers household loads and charges a battery. Note: The inverter is not waterproof and is recommended for indoor use.