1. Introduction
This manual provides comprehensive instructions for the installation, operation, maintenance, and troubleshooting of your DATOUBOSS 24V 3300W Hybrid Solar Inverter. This multifunctional inverter/charger integrates an inverter, solar charger, and battery charger into a single unit, delivering uninterrupted power support in a portable form factor. Its comprehensive LCD display supports user-customizable settings, complemented by intuitive control buttons to adjust battery charging current, AC/solar charger priority, and acceptable input voltage according to varying application scenarios.


The inverter is compatible with 95% of household and office appliances, including lighting, fans, refrigerators, air conditioners, coffee machines, and other household appliances.

2. Setup and Installation
2.1. Product Overview and Components
Before beginning installation, familiarize yourself with the inverter's components and connections.

2.2. Initial Preparation
Before connecting any wiring, remove the bottom cover by unscrewing the screws.
2.3. Wiring Connections
DANGER: Touching the terminals of the mains or equipment may result in death by electric shock or fire! Do not touch terminals or conductors connected to the mains circuit. Pay attention to any instructions or safety documentation regarding grid connection.
NOTE: Some internal components will become hot during operation; please wear protective gloves.
2.3.1. Battery Connection
- Remove insulation sleeve 6 mm for positive and negative conductors.
- Check correct polarity of connection cable from battery modules and battery input connectors. Connect positive pole (+) of connection cable to positive pole (+) of BATTERY input connector. Connect negative pole (-) of connection cable to negative pole (-) of BATTERY input connector.
- Make sure the polarity of the wiring is correct and the connection is firm. Ensure there is no short circuit between the positive and negative electrodes.
2.3.2. AC Input (Grid-Connected) and AC Output (Uninterrupted Output) Connection
CAUTION: There are two terminal blocks with "INPUT" and "OUTPUT" markings. Please do NOT mis-connect input and output connectors.
- Before connecting to AC input power source, install a separate AC breaker between the inverter and AC input power source. This will ensure the inverter can be securely disconnected.
- Remove insulation sleeve 10mm for four conductors.
- Insert AC Input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor first.
- Then, insert AC output wires according to polarities indicated on the terminal block and tighten terminal screws.
WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.
2.3.3. PV Connection
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Check correct polarity of connection cable from PV modules and PV input connectors. Connect positive pole (+) of connection cable to positive pole (+) of SOLAR input connector. Connect negative pole (-) of connection cable to negative pole (-) of SOLAR input connector.
- Make sure the polarity of the wiring is correct and the connection is firm.

Important Wiring Notes:
- When connecting the battery and photovoltaic, pay attention to the positive and negative poles of the cable, and do not connect them reversely.
- If connecting a generator, start the generator first, then connect to the inverter mains input after it runs stably. If connecting to the output end of the generator, then start the inverter, and finally connect to the user equipment after the inverter becomes normal.
- It is recommended that the generator capacity is three times the inverter rated capacity.
2.4. Final Assembly
After connecting all wirings, put the bottom cover back by screwing the screws as shown in the product overview image.

3. Operation
3.1. Display Control Panel and Buttons
The display board is divided into three functional areas: LCD display area, LED display area, and Function key control area.
3.1.1. LED Indicators
| Name | Description |
|---|---|
| AC (Green) | On: The inverter works in the main state Flashing: The inverter AC input detection is normal, works in battery priority mode. Off: Other states |
| INV (Green) | On: The inverter is working in the inverter state. Off: Other states |
| CHG (Yellow) | On: Constant voltage charging, floating charging or fully charged Flashing: Constant current charging Off: Other states |
| FLUAT (Red) | On: Inverter self-protection Flashing: Fault occurs in the inverter Off: Works normally |
3.1.2. Button Functions
| Function keys | Description |
|---|---|
| DOWN | Parameter less or previous page |
| ESC | Without saving or Exit setup mode |
| ENTER | Confirm selection in setup mode or enter Save and exit setup mode |
| UP | Parameter more or next page |
3.2. LCD Screen Description
The LCD display includes icon display, working status display area, numerical display, and function setting area.
3.2.1. Icon Display
- Load and battery icons indicate the load and battery capacity. Each square represents 25% of the capacity.
- The Mute icon shows whether the buzzer is muted. Under normal circumstances, this icon is not displayed; press the ENTER key in any mode to display it. The inverter enters the mute state and the buzzer inhibit icon will be displayed.
- The Fault icon only displays when in fault mode, and won't display in other situations.
3.2.2. Working Status Display Area
After starting up, this display area mainly displays the working status of the inverter, such as mains status, inverter status, grid connection status, etc.
3.2.3. Numerical Display and Function Setting Area
- In non-function setting mode, this area displays inverter related information. Normal mode displays output information, check the operation up and down. The Inquiry key (UP or DOWN key) is used to display input voltage and output voltage, input frequency and output frequency, battery voltage and current, PV voltage and PV current, PV voltage and power, output power and output voltage, output apparent power and output Voltage, load percentage and output voltage related information. The fault mode displays the fault code.
- In the function setting page, you can set the working mode, battery high and low voltage alarm, etc. by operating the ENTER key and the UP and DOWN keys.
3.3. ON/OFF Button Description
3.3.1. Switch On
Connect to battery or AC power supply (AC power needs to confirm the reasonable input range according to the output mode) or connect to PV power, then the inverter can switch on.
- Switch on with Battery: After connecting with battery, press the on button. The inverter will establish working power supply, and waiting for a while, the inverter will be turned on and there will be AC output.
- Switch on with AC: After connecting with AC, the inverter will establish working power supply automatically. Press the on button, the inverter will have AC output. If set to AC output priority mode, the AC will charge the battery and bypass the output.
- Switch on with PV: After connecting with PV, the inverter will establish working power supply automatically and charge the battery. Press the on button, the inverter starts to invert and has AC output.
3.3.2. Switch Off
- Switch Off with Battery: When working with battery, press the Off button. The machine will switch off the output and working power after a period of time.
- Switch Off with AC: When working with AC, press the Off button. The machine will switch off the output and only maintain the working power, standby state, disconnect the AC, and the inverter turn off.
- Switch Off with PV: When working with PV, press the Off button. The machine will switch off the output, maintain the working power and charge the battery, disconnect the PV, and the inverter turn off.
3.4. Operation in Alarm State
When the inverter has an alarm and the red LED fault indicator is on, it means that the inverter is working in an alarm state. You can observe the fault code displayed on the LCD display and compare it with the fault code table in the troubleshooting section for preliminary troubleshooting.
3.5. Function Setting Operation (A0-A28)
To enter the function setting page, press the ENTER key for 2 seconds. Use the UP/DOWN keys to navigate through functions and values. Press ENTER again to confirm selections. Press ESC to exit without saving.
3.5.1. Output Priority Setting (A0)
There are three choices: GRD (Mains priority), PV (PV priority), PBG (Battery priority). This can only be set in battery mode and takes effect immediately after saving.
3.5.2. Battery Type and Parameter Settings (A1-A7)
If the battery pack is a lead-acid battery or a lithium battery without BMS communication, set A17 to Pb (lead-acid battery). The inverter operates according to the set values of battery parameters A1 to A7. If the battery pack is a lithium battery with BMS communication, set A17 to GRD/VLO/PYL/PAC according to the required BMS communication protocol.
- A1: Average Charge Voltage Setting (e.g., 14.2V for 12V model)
- A2: Float Voltage Setting (e.g., 13.8V for 12V model)
- A3: Battery Low Voltage Protection Setting (e.g., 10.5V for 12V model)
- A4: Battery Low Voltage Alarm Setting (e.g., 11.0V for 12V model)
- A5: Recover Battery Voltage Setting (e.g., 13.0V for 12V model)
- A6: Mains to Battery Mode Voltage Setting (e.g., 13.2V for 12V model)
- A7: Battery to Mains Voltage Setting (e.g., 11.0V for 12V model)
3.5.3. Frequency Setting (A8)
Set the output frequency (50Hz or 60Hz). Default is 50Hz.
3.5.4. Output Voltage Setting (A9)
Set the output voltage (220V, 230V, 240V). Default is 230V.
3.5.5. Charging Priority Setting (A10)
Only settable in battery mode. Options: SNU (PV & mains charging), OSO (Only PV charging), CSO (PV Charging priority).
3.5.6. Non-Battery Mode Settings (A11)
Set whether the inverter is connected to the battery or not. Default is bC (connect battery), bNC (Disconnect battery).
3.5.7. Mains Charging Current Setting (A12)
Set the mains charging current. Default is 30A (range: 5A-65A).
3.5.8. Maximum Charging Current Setting (A13)
Set the maximum current for simultaneous charging of mains and photovoltaics. Default is 60A (range: 5A-100A).
3.5.9. Mains Input Voltage Range Setting (A14)
Set the mains input voltage range. Default is UPS (165V-280V), APL (120V-280V).
3.5.10. Working Mode Setting (A15)
Options: GRD (hybrid mode), GRE (grid-connected feed mode), DIS (off-grid mode).
3.5.11. Grid-Connected Current Setting (A16)
Set the current at AC INPUT when the grid is connected. Default is 0A. Range varies by power segment.
3.5.12. Lithium Battery BMS Communication Protocol Setting (A17)
Set the communication protocol for lithium batteries. Options: Pb (lead-acid battery), GRO (Growatt), VLO (Voltronic), PYL (Pylon), PAC (PACE).
3.5.13. BMS Communication Address Setting (A18)
Set the BMS communication address code (000-247). Default is 001.
3.5.14. Switch Off SOC Setting (A19)
Set the SOC value at which the inverter switches off in battery mode. Default is 5% (range: 1%-80%).
3.5.15. Low Voltage Recover SOC Setting (A20)
Set the SOC value at which the inverter recovers after low-voltage protection. Default is 15% (range: 1%-90%).
3.5.16. Inverter to Mains Battery SOC Setting (A21)
Set the SOC value at which the inverter switches from battery supply to mains supply. Default is 10% (range: 1%-80%).
3.5.17. Mains to Battery Mode SOC Setting (A22)
Set the SOC value at which the inverter switches from mains power supply to inverter power supply. Default is 80% (range: 1%-100%).
3.5.18. Charging Cut Off SOC (A23)
Set the SOC value at which the inverter stops charging. Default is 100% (range: 1%-100%).
3.5.19. Battery Low Voltage Restart Setting (A24)
Whether to automatically turn on the inverter output after battery low voltage protection. Default is BRE (Recover), BRD (Do not recover).
3.5.20. Overload Restart Setting (A25)
Whether to recover or not when the load is overloaded, and whether to automatically restore the power-on function after the inverter is overloaded. Default is LRD (Do not recover), LRE (Recover).
3.5.21. Recover After Over Temperature (A26)
Whether to recover the setting item when the temperature is too high. Default is TRD (Do not recover), TRE (Recover).
3.5.22. Inverter Computer Communication Address Setting (A27)
Set the computer communication address code (000-247). Default is 001.
3.5.23. Equipment Neutral Grounding Settings (A28)
Set whether the output neutral line is grounded in battery mode. Default is OFF (neutral line is not grounded), ON (neutral line is grounded).
3.5.24. Equipment Power Generation Reset (A29)
Inverter power generation reset item. Default is ESC (power generation is not cleared), CLR (power generation is cleared).
3.5.25. Restore Factory Settings (A30)
One-click restore factory defaults. Default is ESC (parameters are not restored), RES (parameters are restored).
3.6. Output Priority and Working Modes
The inverter will continue to detect the fluctuation of the current power grid for about 1 minute. If the power grid fluctuation does not exceed the inverter's mains input range during this time, the inverter will be connected to the mains, otherwise it will not be connected to the mains. This prevents frequent switching to the mains when the power grid is unstable.
3.6.1. Grid-Tie Mode (A.Grid-Tie mode)
Mains power and PV provide power to the load simultaneously. The battery only provides power when mains power is unavailable. PV is prioritized for charging the battery, and excess energy feeds the grid.
- With PV and Mains Power: Mains power prioritizes load energy; PV charges the battery. If PV energy is insufficient, mains supplement. If PV generation exceeds load and charging needs, excess feeds the grid.
- With PV, No Mains Power: PV prioritizes load energy, remaining energy charges the battery. If PV energy is insufficient, the battery discharges to supplement.
- With Mains Power, No PV: Mains power supplies load and charges the battery. If mains power is lost, the battery discharges until low voltage, then switches to standby.
3.6.2. PV Power Priority (2. PV power priority)
PV power is prioritized for the load. Excess energy charges the battery and then feeds the grid. The battery provides power only when PV power is insufficient or unavailable.
- With PV and Mains Electricity: PV power prioritizes load, excess charges battery. If battery voltage reaches grid connection condition, remaining PV energy feeds into the grid. If PV energy is insufficient for load, mains power supplements.
- With PV, No Mains Power: PV power prioritizes load, excess charges battery. If PV energy is insufficient, battery discharges to supplement.
- With Mains Power, No PV: Mains power supplies load and charges battery. If mains power is lost, battery discharges until low voltage, then switches to standby.
3.6.3. Battery Priority (3. Battery priority - Off-grid operation mode)
PV power prioritizes supplying power to the load. If PV power is insufficient or unavailable, batteries supplement the load. When battery discharge voltage reaches the set value, it switches to mains to supply power to the load.
- With PV and Mains Electricity: Inverter works in inverter state, PV power prioritizes load, excess charges battery. If PV energy is insufficient, battery discharges to supplement. If battery discharges to low voltage, it switches to mains bypass and starts charging.
- With PV, No Mains Electricity: PV power prioritizes load, excess charges battery. If PV energy is insufficient, battery discharges to supplement.
- With Mains Power, No PV: Prioritizes battery discharge for load. If battery discharges to low voltage, it switches to mains bypass and starts charging. If mains power is lost, battery discharges until low voltage, then switches to standby.
3.6.4. No Battery Operation Mode (D. No battery operation mode)
If no battery is configured, the inverter must be set to bNC (A11). Output priority cannot be set to battery output priority; the inverter will operate in grid-connected or hybrid mode.
- Grid-Tie Mode: PV solar energy prioritizes load. If PV generation is insufficient, mains supplement. If PV generation exceeds load, excess feeds the grid. If mains power is unavailable, PV inverter carries the load.
- Hybrid Mode: PV power energy prioritizes load. If PV generation is insufficient, mains supplement. If mains power is unavailable, PV inverter carries the load.
- Off-Grid Mode (Not Recommended): If PV power is insufficient, the output will be turned off. Only PV can be turned on and loaded; mains power is invalid.
4. Maintenance
4.1. General Maintenance Precautions
DANGER:
- Before any maintenance work, first disconnect the inverter from the electrical grid and then disconnect the DC side electrical connection.
- Wait at least 5 minutes until the internal components are discharged before proceeding with maintenance work.
- Any fault affecting the safety performance of the inverter must be eliminated before it can be turned on again. Contact maintenance center if needed.
- Do not disassemble or assemble internal components without authorization.
4.2. Battery Maintenance
The inverter requires minimal maintenance. The lifespan of the battery can be preserved by frequent charging.
- Batteries should be charged every three months if the inverter is long-term unused.
- Battery lifespan is typically three to five years. Replace in advance if any battery is in poor state. Replacement should be done by a professional.
- Batteries should be wholly replaced per supplier instructions.
- Every three months, batteries should be discharged (until the inverter shuts down) and recharged. Each charge should last at least 12 hours.
- In high-temperature areas, batteries should be discharged and recharged every two months.
NOTE:
- Shut down the inverter, then disconnect AC input and PV input before replacing batteries.
- Do not wear metal jewelry such as rings or watches.
- Use a screwdriver with an insulated handle and avoid placing tools or metal objects on batteries.
- Avoid short circuits or reverse connections.
WARNING:
- Battery must not be put in fire, which may cause explosion.
- Do not open or damage the battery. Electrolyte released will cause harm to eyes and skin and even intoxication.
4.3. Dust Filter Assembly and Cleaning
To clean the dust filter, remove the 2 screws fixing the dust filter cover on the left and right sides. Then take off the dust filter cover and dust filter. After cleaning, install the dust filter and its cover in the order shown in the figure, and then use the 2 removed screws to fix the left and right dust filter covers on the inverter.

NOTE: When using the inverter in areas with poor environment, the dust filter is easily blocked by air particles. Disassemble and clean the dust filter regularly to avoid affecting the air volume and flow rate inside the inverter and triggering the over-temperature protection of components. Failure will affect power supply usage and the service life of the inverter.
5. Troubleshooting
When the inverter has a fault alarm, the red LED light flashes; when there is fault protection, the LED red light is on, and the LCD displays the fault code. For specific fault code descriptions and solutions, refer to the following sheet:
5.1. Fault Code Sheet
| Fault code | Fault message | Remedy (Rx) |
|---|---|---|
| 40 | EEPROM Read and write fault | Please contact the supplier |
| 41 | Communication failure with the main controller | Please contact the supplier |
| 42 | Abnormal parameter setting | Please check whether the set parameters are incorrect or can restore the factory settings |
| 43 | Abnormal reference voltage | The internal power supply is unstable, restart the machine to recover |
| 44 | BUS soft start fault | Please check whether the battery voltage or other input voltage is too low |
| 45 | Hardware over flow | Please check whether the output is overloaded or has an excessively large non-linear load. |
| 46 | Short circuit fault | Please check the output for a short circuit to exclude the abnormal load |
| 47 | Inverter fault | Please check whether the inductive load has too much impact, turn off the power and then power on the inverter again. If it does not recover, please contact the supplier |
| 48 | Battery over voltage alarm | Please check whether the battery voltage is too high, whether the number of battery cells is correct, and whether the voltage of each battery cell is normal. |
| 49 | Battery over voltage protection | Please check whether the battery voltage is too high, whether the number of battery cells is correct, and whether the voltage of each battery cell is normal. |
| 50 | Battery low voltage protection | Please check whether the battery voltage is too low, whether the number of battery cells is correct, and whether the voltage of each battery cell is normal. |
| 51 | Battery low voltage alarm | Please check whether the battery voltage is too low, whether the number of battery cells is correct, and whether the voltage of each battery cell is normal. |
| 52 | BUS high voltage fault | Please check whether the battery or input voltage is too high |
| 53 | BUS low voltage fault | Please check whether the battery or input voltage is too low |
| 54 | Overload alarm | Please check whether the output load is overloaded and reduce the load appropriately |
| 55 | High temperature of the inverter radiator | Please check whether the cooling fan is normal, whether the ambient temperature is too high, and whether the inverter vent is blocked. |
| 56 | DC/DC, the radiator at high temperature | Please check whether the cooling fan is normal, whether the ambient temperature is too high, and whether the inverter vent is blocked |
| 57 | MPPT radiator with high temperature | Please check whether the cooling fan is normal, whether the ambient temperature is too high, and whether the inverter vent is blocked |
| 58 | PV1 high voltage | Please check whether the PV input voltage of PV1 exceeds the operating range. |
| 59 | PV2 high voltage | Please check whether the PV input voltage of PV2 exceeds the working range |
| 60 | Mains high voltage | Please check whether the input mains voltage is too high |
| 61 | Abnormal frequency | Please check whether the mains frequency is normal |
| 62 | Remote shutdown | Please determine if a remote shutdown command was sent |
| 63 | Abnormal communication with the lithium battery | Please check whether the inverter and the lithium battery communication protocol correspond, and whether the connection line is correct |
| 64 | Lithium battery single cell or total voltage is too high | Please check whether the single-section cell voltage and total voltage of the lithium battery are too high |
| 65 | Lithium battery single cell or total voltage is too low | Please check whether the single-section cell voltage and total voltage of the lithium battery are too low |
| 66 | Lithium battery discharge overcurrent | Please check whether the load power is too large |
| 67 | Lithium battery charge overcurrent | Please appropriately reduce the maximum charging current set by the inverter |
| 68 | Lithium battery temperature is abnormal | Please check whether the lithium battery is overheated, shut down and wait for recover after restarting |
6. Technical Specifications
The following table details the technical specifications of the DATOUBOSS Hybrid Solar Inverter (Model: DT-2433M).

| Category | Parameter | Value |
|---|---|---|
| PV Input | Max PV Input Power | 2500W |
| MPPT Tracking Voltage Range | 30VDC-240VDC | |
| Rated Voltage | 180VDC | |
| Max PV Input Voltage Voc (at lowest temperature) | 300VDC | |
| Max PV Input Current | 15A | |
| Battery & Charging | Battery Type | Lead-acid Battery/Lithium Battery (Customizable) |
| Rated Battery Voltage | 12VDC | |
| Battery Voltage Range | 10.5-15VDC (default) | |
| Max Charging Current (PV/AC) | 100A (PV), 65A (AC) | |
| On-Grid Output (AC) | Rated Output Power | 1800W |
| Rated Output Voltage | 220VAC/230VAC/240VAC | |
| Grid Voltage Range | 187VAC-264VAC | |
| Frequency Range | 47Hz-52Hz (50Hz), 57Hz-62Hz (60Hz) | |
| Power Factor | >0.98 | |
| Off-Grid Output (AC) | Rated Input Voltage | 220V/230V/240V |
| Mains Input Voltage Range | 165VAC-280VAC / 120VAC-280VAC (settable) | |
| Rated Output Power | 1800W | |
| Rated Output Voltage | 220V/230V/240V | |
| Output Voltage Accuracy | ±2% | |
| Output Wave | Pure Sine Wave | |
| General | Maximum Conversion Efficiency (Battery Discharge) | 94% (peak value) |
| MPPT Tracking Efficiency | ≥99.9% | |
| Transfer Time | 10ms (typical value) | |
| Display | LCD+LED | |
| Cooling Method | Cooling fan in intelligent control | |
| Communication | RS485/Mobile APP (WIFI Monitoring) (Optional) | |
| Protection Degree | IP20 | |
| Environment | Operating Temperature | -10°C~50°C |
| Storage Temperature | -15°C~60°C | |
| Noise | ≤55dB | |
| Elevation | 2000m (More than derating) | |
| Humidity | 0%~95% (No condensation) | |
| Dimensions & Weight | Product Size (L*W*Hmm) | 310x250x91 |
| Package Size (L*W*Hmm) | 385x305x156 | |
| N.W. (kg) | 4.0 | |
| G.W. (kg) | 5.0 |
Note: The above parameters are subject to change without prior notice!

7. Warranty and Support
7.1. Warranty Information
Please retain your warranty card as proof of maintenance. The warranty period is 1 year from the date of purchase. During the warranty period, under normal use and maintenance, if damage is caused by the product's own quality, the company will provide free repair and replacement parts after verification. The company reserves the right to maintain and interpret all contents.
Free maintenance will not be given under the following circumstances:
- Damage caused by manipulation that does not follow the requests of the manual.
- The product has been repaired, modified by technicians other than our company's, and any internal parts of the product have been replaced by users.
- The product number has been altered or the product is inconsistent with the warranty card.
- Damage caused by careless use, penetration of water or other substances into the product.
- Damage caused by accident or natural disaster.
7.2. Communication Interfaces
7.2.1. RS485 Communication Interface
The inverter features RS485-1 (External communication/WIFI) and RS485-2 (BMS communication) ports. Refer to the product overview diagram for pin definitions.
7.2.2. WIFI Communication Port (Optional)
A WIFI module (optional, not standard) can be connected for remote monitoring/control via mobile phones or web pages. Operating data of the inverter can be uploaded to a server via WiFi. Users can choose to use the web or APP for monitoring and reading as needed. Register an account and bind the device using the WiFi serial number and QR code affixed to the packaging box/WiFi data collector.
- Website: https://solar.siseli.com/
- APP: Android phone users search "Solar of Things" in the App Store. iOS users search "Solar of Things" in the AppStore.
For detailed instructions on the WIFI data collector, please refer to its instruction manual.
7.3. User Manual (PDF)
A detailed user manual in PDF format is available for further reference. This document contains comprehensive instructions and specifications not fully detailed here. You can view the PDF manual here.
8. User Tips
- On-Grid Functionality: This inverter supports on-grid functionality, allowing it to feed excess solar power back into the grid. Ensure your local regulations and utility company requirements are met before enabling this feature.
- Indoor Use Only: The inverter is not waterproof and is recommended for use in indoor waterproof environments.
- Regular Dust Filter Cleaning: To maintain optimal performance and prevent overheating, regularly clean the dust filter, especially in dusty environments.