1. Introduction
This manual provides essential information for the safe and effective use of your ELECTESLA Variable Frequency Drive (VFD) External Control Panel. It covers safety precautions, installation, operation, parameter settings, and troubleshooting. Please read this manual thoroughly before installation and operation.
2. Safety Information and Precautions
WARNING: Improper installation or operation can lead to severe electrical shock, burns, or equipment damage. Only authorized and qualified personnel should perform installation and maintenance.
2.1. Electrical Safety
- Extreme care must be taken at all times when working with the VFD or within its area.
- The voltages used in the VFD can cause severe electrical shock or burns and are potentially lethal.
- The VFD is NOT intended to be used for safety-related applications/functions. The electronic “STOP & START” control circuits within the VFD must not be relied upon for the safety of personnel.
- The mains power supply must be disconnected by an electrical safety isolation device before accessing the internal parts of the VFD.
2.2. Machine/System Design and Safety of Personnel
- Machine/system design, installation, commissioning, startups, and maintenance must be carried out by personnel with necessary training and experience.
- A safety risk assessment of the machine or process system using a VFD must be undertaken by the user or system integrator/designer.
- The system integrator/designer must ensure the complete system is safe and designed according to relevant safety standards.
2.3. Electrical Installation - Safety
- Electrical shock risk is always present within a VFD, including the output cable leading to the motor terminals.
- Where dynamic brake resistors are fitted externally, ensure cables are double insulated as DC voltages are typically 300VDC to 650VDC.
- A mains power supply isolation switch should be fitted to the VFD.
- The AC supply must be isolated at least 10 minutes before any work can be undertaken, allowing stored charge in the DC bus capacitors to discharge through internal bleed resistors.
- Always check the DC bus voltage with a VDC meter before accessing the VFD bridge.
3. Product Overview
The ELECTESLA VFD External Control Panel provides an intuitive interface for controlling and monitoring your Variable Frequency Drive. It is designed for ease of use and reliable performance.
3.1. Components




3.2. Operating Panel Layout

Key Functions:
| Item | Symbol | Function |
|---|---|---|
| Digital tube display | 8.8.8.8. | To display frequency or parameter etc using LED. |
| Parameter setting key | PRG | Used to read and modify each group of parameters, press to enter the parameter group or display the parameter value. |
| Enter keys | ENTER | Press this key to enter the next level menu. Confirm setting parameters. |
| Increment | ▲ | To increase parameter number or parameter set value. |
| Decrement | ▼ | To reduce parameter number or parameter set value. |
| RUN | RUN | Start the VFD when using the operating panel control mode. |
| STOP | STOP | Stop the VFD when the drive is in the RUNNING status. Perform a reset operation when the drive is in the FAULT status. |
| Speed control knob | ◎ | To adjust frequency. |
| Multifunction keys | FUNC | Default for VFD jog operation. |
| Shift keys | ▶▶ | The display parameters of operation/shutdown monitoring are cyclically switched; When setting data in programming state, you can change the modification bit of setting data. |
4. Specifications
4.1. Compatible VFD Specifications (Example)
The external control panel is compatible with various VFD models. Below are example specifications for VFDs that can be controlled by this panel.
| Power | Power Supply | Output Current (A) | Overall Dimension L*W*H (mm) | Installation Dimension L*W (mm) - Mounting Screw |
|---|---|---|---|---|
| 0.4KW | Single-phase AC 200V-240V 50Hz/60Hz | 2.1 | 170*79*127 | 160*60.5-M5 |
| 0.75KW | 3.8 | |||
| 1.5KW | 7 | 187*86*144 | 173*68-M4 | |
| 2.2KW | 9.0 | |||
| 3.0KW | 13 | 216*101*151 | 204*83.5-M4 | |
| 4.0KW | 15 | |||
| 5.5KW | Three-phase AC 200V-240V 50Hz/60Hz | 20 | 237*111*168 | 216*88-M5 |
| 0.4KW | 2.1 | |||
| 0.75KW | 3.8 | 170*79*127 | 160*60.5-M5 | |
| 1.5KW | 7 | |||
| 2.2KW | 9.0 | 187*86*144 | 173*68-M4 | |
| 3.0KW | 13 | |||
| 4.0KW | Three-phase AC 340V-440V 50Hz/60Hz | 15 | 237*111*168 | 216*88-M5 |
| 5.5KW | 20 | |||
| 0.4KW | 1.5 | 170*79*127 | 160*60.5-M5 | |
| 0.75KW | 2.1 | |||
| 1.5KW | 3.8 | 187*86*144 | 173*68-M4 | |
| 2.2KW | 5.1 | |||
| 3.0KW | Three-phase AC 340V-440V 50Hz/60Hz | 7.1 | 216*101*151 | 204*83.5-M4 |
| 4.0KW | 9.0 | |||
| 5.5KW | 12.6 | 237*111*168 | 216*88-M5 | |
| 7.5KW | 16.1 |
4.2. Package Dimensions and Weight
- Length: 10 cm
- Width: 5 cm
- Height: 5 cm
- Weight: 0.3 kg
5. Installation and Wiring
Proper installation and wiring are crucial for the safe and correct operation of the VFD and its external control panel. Refer to the wiring diagram and terminal instructions below.
5.1. Wiring Diagram

5.2. Terminal Function Instruction
| Terminal | Function | Setting and Instruction |
|---|---|---|
| R, S, T | VFD: Three-phase 220V/380V Model connect with R, S, T terminals. Single-phase 220V Model connect with L, N terminals. | Air switch should be used as the over-current protection device in front of the VFD power. If there is LCDI, and it is afraid of breakdown, please choose the LCDI whose sensitivity level is above 200mA and reaction period last more than 100ms. |
| U, V, W | VFD output, connected with electrical machine. | In order to reduce the leakage of current, the connection wire should not be over 50 meters. |
| P+, PB | Connected with braking resistor. | According to the list of braking resistors, choose an appropriate one. |
| PE | Connected with the ground. | The VFD should be connected with the ground well. |
| X1 | Digital input X1 | Set according to parameter F5.02, and factory set defaults to be FWD. |
| X2 | Digital input X2 | Set according to parameter F5.03, and factory set defaults to be REV. |
| X3 | Digital input X3 | Set according to parameter F5.04, and factory set defaults to be the first one of multistage speed. |
| X4/485+ | Digital input X4 RS485+ | If it is not the RS485-, it set according to parameter F5.05, and factory set defaults to be the second one of multistage speed. |
| X5/485- | Digital input X5 RS485- | If it is not the RS485+, it set according to parameter F5.06, and factory set defaults to be external RST. |
| GND | Signal public terminal | Zero potential of analog input signal. |
| AVI | 0-10V signal input | 0-10V, input resistance: >50KΩ. |
| 10V | Frequency Setting potentiometer power source | +10V, the maximum is 10mA. |
| ACI | 0-20mA analog input | 0-20mA, input resistance: 100Ω. |
| AO | Analog output | Set according to parameter F6.10. |
| TA, TB, TC | Relay output | Set according to parameter F5.07. Contact rating: AC 250V/3A, DC 24V/2A. |
6. Operating Instructions
6.1. Basic Panel Operation
The VFD control panel allows for direct control and monitoring. The digital tube display shows frequency or parameter values.

Parameter Setting and Navigation:
- Use the PRG key to enter the parameter group or display the parameter value.
- Press the ENTER key to enter the next level menu or confirm settings.
- Use the Increment (▲) and Decrement (▼) keys to adjust parameter numbers or set values.
- The Shift (▶▶) keys switch the display units (units, tens, hundreds, thousands) of the digital tube.
- After setting parameters, return to the original interface by powering off and on again, or by pressing the PRG button twice or three times.
6.2. VFD Running Command Mode Setting
The VFD operation command mode is set by parameter F0.02. There are three types:
(1) Panel Control Start and Stop (F0.02=0)
- To start the VFD, press the green RUN button on the panel.
- To stop the VFD, press the red STOP button.
- The VFD defaults to forward rotation. Forward and reverse rotation can be set through input terminals X1-X5 (reverse setting is 2).
(2) Terminal Start/Stop (F0.02=1)
This mode uses external terminals for control. Two-wire and three-wire control modes are available.


6.3. VFD Frequency Setting Method Selection
The VFD frequency setting mode is configured via parameter F0.03:
- F0.03=4: Running frequency set by potentiometer.
- F0.03=2: Running frequency input by AVI (0-10V, can be connected to a potentiometer).
- F0.03=3: Running frequency input by ACI (0-20mA).
- F0.03=1: Controlled by external terminal (digital value set to increase/decrease frequency).
7. Function Parameter Specifications
The VFD has a comprehensive set of parameters organized into groups (F0-FA, FB, FC) to customize its operation. Detailed tables for these parameters are available in the full user manual. Below is a summary of key parameter groups:
- F0 Group: Basic Running Parameters (e.g., VF Power, Control Mode, Running order channel selection, Frequency given source channel, Max frequency output, Upper limit frequency)
- F1 Group: V/F Control Parameters (e.g., V/F curve set, Torque boost, PWM Carrier frequency)
- F2 Group: Vector Control Parameters (e.g., ASR Low speed Kp/Ki, Electric slip compensation gain)
- F3 Group: Auxiliary Operation Parameters (e.g., Start-up mode, Start DC braking current, Stop mode)
- F4 Group: Auxiliary Operation 2 Parameters (e.g., Jog forward running frequency, Multi-function key, Jump frequencies)
- F5 Group: Digital Input and Output Parameters (e.g., FWD/REV mode, Input X1-X5 Function, Relay output settings)
- F6 Group: Analog Input and Output Parameters (e.g., Lower/Upper limit voltage/current for AVI/ACI, AO1 output selection)
- F7 Group: PLC, Multi-speed Parameters (e.g., Multi-speed frequencies, PLC run mode selections)
- F8 Group: PID Control, MPPT And PV Pump Parameters (e.g., PID feedback trait selection, Water shortage detection, Swing frequency control)
- F9 Group: Motor Parameters (e.g., Motor rated power, voltage, current, frequency, stator/rotor resistance)
- FA Group: Protect Parameters (e.g., Motor overload protection, Overvoltage protection level, Overcurrent/Overvoltage suppression)
- FB Group: Display And Special Parameters (e.g., Running/Stop monitoring parameters, Motor speed display coefficient, Malfunction records)
- FC Group: Communication Control Function Parameter (e.g., Communication baud rate, Modbus data format, 485 communication address)
For a complete list and detailed descriptions of all parameters, please refer to the official PDF user manual: ELECTESLA VFD External Control Panel User Manual (PDF).
8. Troubleshooting
This section provides common fault codes, their possible reasons, and suggested troubleshooting steps.
| Fault Code | Fault Description | Possible Reasons | Troubleshooting |
|---|---|---|---|
| OU1(1) | Over voltage in Acc process | Abnormal supply voltage; Driver restarted with rotating motor | Check power supply; Start after setting as DC braking or rotational |
| OU1(2) | Over voltage in Dec process | Too short Dec time; Abnormal supply voltage | Prolong the Dec time; Check power supply |
| OCC1(4) | Hardware Over-current in Acc process | Too short Acc time; VFD power too small; V/F curve not suitable; IGBT module damaged | Prolong the Acc time; Select higher power drive; Adjust V/F curve or torque boost; Contact suppliers for service |
| LU(13) | Undervoltage | Abnormal input voltage; Contactor does not pick up | Check power supply voltage; Contact suppliers for service |
| OH(14) | Overheat | Ambient temperature too high; Small space around VFD; Air duct blocked; Cooling fan does not run | Improve environment; Adjust space; Clean and unclog airways; Check fan's power supply and fan itself |
| EFO(10) | Power module failure | VFD instantaneous overcurrent; Control board abnormal or serious interference; Damaged power device | Refer to overcurrent countermeasures; Contact suppliers for service |
| ELH | Water shortage malfunction | Wiring from inverter to motor is abnormal | Troubleshoot wiring |
| SPO | Output phase loss fault | Three-phase output of inverter is unbalanced; Abnormal drive board; Module Abnorma | Check three-phase winding of motor; Contact suppliers for service |
9. Maintenance
Regular maintenance ensures the longevity and optimal performance of your VFD External Control Panel.
- Cleaning: Keep the panel and surrounding area clean and free from dust and debris. Use a soft, dry cloth for cleaning. Do not use harsh chemicals or abrasive materials.
- Inspection: Periodically inspect all wiring connections for tightness and signs of wear or damage. Ensure the panel is securely mounted.
- Environmental Conditions: Ensure the operating environment is within the specified temperature and humidity ranges to prevent damage.
- Firmware Updates: Check with ELECTESLA for any available firmware updates for your VFD model to ensure optimal performance and security.
10. User Tips
No specific user tips were available from reviews or Q&A for this product at this time. Always refer to the detailed parameter settings in the full manual for advanced configurations.
11. Manufacturer Overview
ELECTESLA is a professional manufacturer specializing in frequency converters and various instruments. The factory utilizes advanced equipment and technology, adhering to strict quality control processes to ensure high-quality products. Every product undergoes multiple inspections before being placed in the warehouse.
12. Warranty and Support
For technical support, warranty information, or service inquiries, please contact ELECTESLA Official Store directly. Refer to your purchase documentation for specific contact details.
You can also find the full user manual in PDF format here: ELECTESLA VFD External Control Panel User Manual (PDF).