1. Safety Notes and Warnings
READ, UNDERSTAND AND FOLLOW ALL INSTRUCTIONS: Before using or installing this product, fully read and understand all applicable instructions and documentation. Save all manuals and documentation for future reference.
- Wear safety equipment and use insulated tools.
- Installation should be carried out by a professional.
- Use the appropriate size.
- Ensure that the installation follows applicable local and national electrical codes.
- Ensure that the system is properly grounded.
- Ensure that the battery is installed in a location suitable for the electronic device.
- Please keep the battery within the safe temperature range for stable operation.
- Clean the battery with a suitable cleaner (e.g. sandpaper, dry cloth) and do not use any spray cleaners, liquids, aerosols or any solvents to clean the spray paint.
- Make sure all fasteners are properly tightened.
- Do not burn, crush or puncture the battery.
- Do not place the battery in a hazardous/flammable environment where it could come into contact with corrosive chemicals or vapours.
- Do not store or install this product in radiators, collectors, cookers or enclosures that may remain overheated.
- Do not immerse the product in liquid.
- Risk of fire, explosion and burns. If electrical odour or overheating occurs, safely disconnect circuit breakers and call the fire department.
- Keep away from damaged batteries and any liquid (electrolyte) or gas (flammable) leaking from batteries. If inadvertently inhaled, evacuate the contaminated area and seek medical assistance.
- If battery leakage/fluid comes into contact with eyes or skin, flush the affected area with running water for 15 minutes and seek medical attention.
- In the event of a fire, do not use water! Use only dry powder fire extinguishers. If possible, move the battery pack to a safe place before it catches fire.
2. Preparation for Shipment, Receipt and Installation
2.1 Shipment and Receipt
All-in-one batteries are made of lithium iron phosphate cells (LiFePO4) and are classified as Class 9 Dangerous Goods, so please be aware of the following matters regarding shipment and receipt:
- SHIPPING: All-in-one batteries should be packaged appropriately for transport in accordance with the handling and labelling rules for lithium batteries UN3480.
- RECEIVING: When receiving the all-in-one battery, please inspect it. If you find any damage to the packaging or the inside of the battery pack, take photos and videos and contact your dealer immediately.
Please keep the original box and packaging materials intact in case the all-in-one battery needs to be repacked or warranted in the future.
2.2 Preparation for Installation
Tools required for installation:
- Suitable size Phillips screwdriver / torque spanner / riveting pliers.
Connecting the battery using cables/lugs:
- Correct cable: a cable that meets the safe current for battery pack use.
- Correct lugs: conform to battery pack installation dimensions and safe current lugs.
3. Installation Instructions
3.1 Unpacking and Inspection
Inspect the unit before installation. Make sure there is no damage in the package. You should receive the following items in the package:
- All-In-One Home Energy Storage
- User Manual x1
3.2 Preparatory Work (Installation in the off state, it is recommended that the installation of equipment to find a professional electrician installation)
Wall-mounted Before selecting a mounting location, consider the following points:
- Use safety devices and insulated tools in accordance with applicable local and national electrical codes by a qualified person who has fully read, understands, and strictly adheres to all instructions in this manual.
- In applicable locations and environments:
- Do not install the product in harsh environments; ambient temperatures should be between 0° C and 55° C to ensure optimum operation.
- No hazardous/flammable or corrosive chemicals or vapours.
- There are no nearby heat sources such as radiators, collectors or furnaces to transfer heat to the battery or retain excess heat in the enclosure.
- No children or pets are present or likely to be present.
- Do not install the All-in-One on flammable building materials, vertical mounting on a solid wall is recommended.
- Ensure that other objects and surfaces shown at right are retained so that there is enough room for heat dissipation and enough room to remove wires.
- Mount the MFP at eye level so that the LCD display can be read at all times.
- Its properly grounded, twisted, tightened and wired.
! WARNING !
Requires the product to be installed with the power off and disconnected.
4. Specifications
Detailed dimensions of the DATOUBOSS All-in-One Home Solar System.
Product parameters table for model JC-1116.
Overall Parameters
| Parameter | Value |
|---|---|
| Product Model | JC-1116 |
| Battery Type | LiFePO4 Battery 314Ah |
| Battery Capacity | 16.07kWh |
| Dimensions (L x W x H) | 580×580×643mm |
| Nominal Voltage | 51.2V |
| Battery Cycle Life (25°C) | 8000 cycles, 70% SOH |
| Battery Cycle Life (45°C) | 3000 cycles, 70% SOH |
| Screen Type | LCD |
Input
| Parameter | Value |
|---|---|
| PV Charging Mode | MPPT |
| PV Input Power Max. | 2*7500W |
| Mppt Tracking Range | 90-500Vdc |
| Optimum Voltage | 360~430Vdc |
| Max PV Input Voltage | 500Vdc |
| Max PV Input Current | 18A/18A |
| PV Charging Current Max. | 150A |
| AC Charging Current Max. | 150A |
| Charging Current Max. | 150A |
| Input Format | L+N+PE |
| Rated Input Voltage | 220/230/240VAC |
| Voltage Range | 90-280VAC 3V (Normal Mode) 170-280VAC 3V (UPS Mode) |
| Frequency Range | 50Hz/60Hz (Adaptive) |
Output
| Parameter | Value |
|---|---|
| Output Rated Power (Battery Inverter) | 11000W |
| Output Rated Power (PV Inverter) | 12000W |
| Output Voltage | 220/230/240VAC ± 5% |
| Output Frequency | 50/60Hz ± 0.1% |
| Waveform | pure sine wave |
| Switching Time (Settable) | Computer equipment 10ms, household appliances 20ms |
| Peak Power | 22000VA |
| Overload Capacity | Battery mode: 11s@105%~150% Load; 2s@150%~200% Load; 400ms@>200% Load |
| Liquid Crystal Display | Display of operating modes/loads/inputs/outputs, etc. |
| Operating Temperature | -10~50℃ |
| Operating Environment Humidity | 20% ~ 95% (no condensation) |
| Storage Temperature | -15~60℃ |
| Altitude | Altitude should not exceed 1000m, derated above 1000m, up to 4000m, refer to IEC62040. |
| Noise Level | <50db |
5. Basic Operations
To turn on the power, please press the battery switch first, then press the inverter switch.
Basic operation buttons and their functions.
BATTERY ON/OFF
Press the “Battery Switch Button”, the work indicator and power indicator light up.
ON/OFF
BATERRAY
Inverter ON/OFF
Press the “Inverter Switch Button”, the inverter display lights up.
ON/OFF
INVERTER
1/2 PV ON/OFF
Turn on the PV switch and make sure the power is on and the PV cable is connected. Turn on the PV switch and the product starts PV charging. Turning the PV switch off stops the PV input.
1 PV 2 PV
ON/OFF ON/OFF
AC Input On/Off
Turn the AC Input switch on and make sure the power is turned on. The product starts AC charging. Turning the AC switch off stops the AC input.
AC IN ON/OFF
AC Output On/Off
Turn the AC Output switch on, the AC Output port is connected to an external load device and the product starts charging the external load device. Turning off the AC switch stops the AC output.
AC OUT ON/OFF
6. Wiring Hole Description
Wiring diagram for solar panels, grid, and home loads.
Port Descriptions:
- PV + Positive terminal port
- PV - Positive terminal port
- AC IN + Utility direct charge positive terminal port
- AC IN - Direct charging positive terminal for utility power
- AC IN Utility direct charging ground wire connector
- AC OUT + Inverter output positive terminal port
- AC OUT - Inverter Output Negative Terminal Port
- AC OUT Inverter output ground wire ground port
NOTE: Ensure that the installation follows applicable local and national electrical codes.
Communication Ports
RS 232 BMS/RS 485
Π Π Π
Debugging port BMS port
NC C NO
Ο Ο Ο
Dry contact
7. Product Overview (LED and LCD Displays)
Product function introduction with labeled components.
LED Display Description
The front panel features LED indicators for system status:
a ON/OFF Ο Ο 100%
b RUN Ο Ο 75%
c ALM Ο Ο 50%
d RESET Ο Ο 25%
- Switching Indicator
- Operation Indicator
- Alarm Indicator
- Reset Button
- Battery Indicator
Table 1: LED Display Description
| State of system | Event | ON/OFF | RUN | ALARM | Battery Indicator LED | Instruction | |
|---|---|---|---|---|---|---|---|
| Power Off | Dormant | ON | ON | ON | ON ON ON ON | All LEDs turn off | |
| Static State | Normal | Always On | Flash1 | ON | Based on battery indicator | Standby Status | |
| Alarm | Bright | Flash1 | Flash3 | Module Low Voltage | |||
| Normal | Bright | Bright | ON | Based on power indication (Power indicator LED flashes up to 2) | Maximum charge LED flashing (flash 2), overcharge alarm ALM not flashing | ||
| Charging | Alarm | Bright | Bright | Flash3 | The over-voltage alarm does not flash | ||
| Overcharge protection | Bright | Bright | ON | Bright Bright Bright Bright | If there is no utility power, the indicator is in standby mode. | ||
| Temperature, overcurrent, failure protection | Bright | ON | Bright | ON ON ON ON | Stop charging | ||
| Discharging | normal | Bright | Flash3 | ON | Based on battery indicator | / | |
| Alarm | Bright | Flash3 | Flash3 | ||||
| Undervoltage protection | Bright | ON | ON | ON ON ON ON | Stop Discharge | ||
| Temperature, overcurrent, short-circuit, reverse connection, failure protection | Bright | ON | Bright | ON ON ON ON | Stop Discharge | ||
| Lose Efficacy | Bright | ON | Bright | ON ON ON ON | Stop charging/discharging | ||
Table 2: SOC Display Description
| State | SOC(%) | Charging | Discharge | ||||||
|---|---|---|---|---|---|---|---|---|---|
| LED4 | LED3 | LED2 | LED1 | LED4 | LED3 | LED2 | LED1 | ||
| LED | 0~25% | ON | ON | ON | Flash2 | ON | ON | ON | Bright |
| 25~50% | ON | ON | Flash2 | Bright | OFF | OFF | Bright | Bright | |
| 50~75% | ON | Flash2 | Bright | Bright | ON | Bright | Bright | Bright | |
| 75~100% | Flash2 | Bright | Bright | Bright | Bright | Bright | Bright | Bright | |
| RUN_LED | Bright | Flash3 | |||||||
Table 3: LED Flash Description
| Flash Mode | ON | OFF |
|---|---|---|
| Flash1 | 0.25S | 3.75S |
| Flash2 | 0.5S | 0.5S |
| Flash3 | 0.5S | 1.5S |
8.1 Product Overview (LCD Display)
The LCD screen provides a comprehensive overview of the system's operation.
Machine operation data display
Photovoltaic Solar Display
Battery Display
Date & Time Display
System Setup
Utility display
Output Load Display
1. The absence of an icon in the centre of the main screen indicates that the system is in normal operation. If the centre of the main screen displays a grey icon and characters, this means that the inverter has issued an alarm, and the alarm message will be displayed as a character under the no icon (details of the error message can be found in the annunciator alarm menu). If a red icon and character are displayed in the centre of the main screen, this means that the inverter is faulty and the fault message will be displayed as a character under this icon (details of the error message can be found in the manual alarm menu).
OFF
03
Battery is over charged
Example: Battery is over charged alarm.
OFF
60
PV voltage is over limitation
Example: PV voltage is over limitation alarm.
8. Touch Screen Operating Instructions
8.2 Touch Screen Display Flow Chart
The touch screen interface allows navigation through various settings and information pages.
Home screen
├── Inverter page
├── Photovoltaic page
├── Battery page
├── Load page
├── Utility page
└── System setup
├── Battery setup
├── System work setup
├── Utility setup
├── Basic setup
├── Charge settings
├── Advanced Functions
└── Equipment Information
8.3 Touch Screen Main Interface Page Content Instructions
Inverter Data Details Page
This page shows in detail the machine model, machine type, boost tube temperature, internal temperature, MPPT temperature, inverter temperature, whether the underlying program is normal or not, the version number of the colour screen, the version number of the centralised control board, and the version number of the machine control board.
Machine Type: 6248
Inverter Type: HPVINV04
Boosting Temp: 31°C
Machine Temp: 51°C
MPPT Temp: 25℃
MOS Temp: 39°C
IAP Status: Norma
Lcd Version:V10.01
Driver Version:V10.01
Main Version:V10.03
Photovoltaic Data Detail Page
This page shows the input voltage, current, and power of the PV solar panel in detail. It also records today's PV power, this month's PV power, this year's PV power, and total PV power.
PV1 Input: 262.6 V 7.0 A
PI1 Input Power: 1855 W
PV2 Input: 0.0 V 0.1 A
PV2 Input Power: 0 W
Today: 0.000KWh Month : 0.0KWh
Year: 0.0KWh Total: 0.0KWh
Battery Detail Page
This page shows in detail the battery type, BMS current communication status, battery voltage, BAT charge current, BAT discharge current and BUS bus voltage and lithium activation status.
Battery Type: AGM
BMS COM Function: OFF
Battery Voltage: 54.0 V
Charge Current: 12 A
Discharge Current: 0 A
Bus Voltage: 428 V
Li Battery Active: OFF
BMS Detail Page
This page details the BMS current usage protocol, BMS current SOC value, BMS charging current, BMS discharging current, BMS temperature, BMS discharging limit voltage, BMS charging limit voltage, and BMS charging limit current.
BMS 485 Protocol: NULL
SOC: 100 %
Charge Current: 0.0 A
Discharge Current: 0.0 A
BMS Temper: 0.0 C
Discharge Limit Voltage: 0.0 V
Charge Limit Voltage: 0.0 V
Charge Limit Current: 100.0 A
System Setup Menu Page
This is the System Settings page, including Battery Settings, System Operation Mode, Battery Settings, Utility Settings, Charging Settings, Basic Settings, Advanced Functions, and Device Information.
Basic Setup Menu Page
This page allows you to set:
- Inverter voltage: 220/230/240V (default 230V)
- Inverter frequency: 50/ HZ (default 50HZ)
- Buzzer: ON/OFF
- Bypass switch: ON/OFF
- Overload restart: ON/OFF
- Input source prompt function: ON/OFF
- Over-temperature restart function: ON/OFF
Battery Setting Menu Page
This page allows you to set:
- Battery type: AGM/FLD/USE/LIA/PYL/TQF, /GRO/LIB/LIC
- TRONG CHARGE VOLTAGE: This procedure can be set if Custom is selected for Battery Type. The setting range for 24V system models is 24.0V to 30.0V, 48V system models have a setting range of 48-0V to 60.0V. OV, 48V system models have a setting range of 48–0V to 60.0V
- Float Charging Voltage: 27V/54V
- Low Power Cutoff Voltage: If battery power is the only available source, the inverter will shut down.
- BMS function switch: whether to enable the BMS communication function or not
- BMS Soc Lockout: When the SOC value of the BMS falls below the set value, the inverter switches off to protect the battery.
- BMS Soc to AC: When the inverter's mode of operation is set to Battery Priority Mode, the inverter will be forced to enter power charging when the SOC of the BMS falls below the set value.
- BMS Soc to DC: When the inverter's operating mode is set to Battery Priority Mode, the inverter will return to DC operating mode when the SOC of the BMS is higher than the set value. Battery Soc Restart: When the inverter is switched on, the SOC must be higher than the set value to work normally.
- Battery balancing: If you select "liquid battery" in the battery type or "user-defined", you can set up the program.
- Battery equalization voltage: 24V system models default 29.2V, 48V system models default 58-4V
- Battery equalization time: Setting range from 5 minutes to 900 minutes.
- Battery balancing timeout: Setting ranges from 5 minutes to 900 minutes. Equalization interval: Setting range from 0 to 90 days
- DC to AC voltage: 22V-25.5V/44V-51VAC
- AC to DC voltage: 24V-29/48V-58V
System Working Mode Setting Menu Page
This page allows you to set:
- ECO function: When the load is low in battery mode, the system will temporarily stop.
- Output priority: Output source priority options
- SUB: Solar energy is the first priority for loads. If solar energy is not enough to power all connected loads, utility grid energy will supply power to the loads at the same time. Solar energy provides power as the first priority for load output source priority selection.
- SBU: If solar energy is not enough to power all connected loads, battery energy will power the loads at the same time. The mains supply power to the load only when the battery voltage drops to a low warning voltage or when solar energy and batteries are insufficient.
- Output type: SIG/PAL/3P1/3P2/3P3
- Restore factory settings: To restore default values, check the box and click the "YES" button.
Mains Grid Setting Menu Page
This page allows you to set:
- Input voltage range: APL\UPS
- Photovoltaic energy source type: Mode 01\Mode 02\Mode 03 Mode 04
- Grid connection mode: Disabled\Enable
- Municipal power parallel network current: default 20A
- Start time for charging mains grid: settable range 0-23
- Power grid charging shutdown time: settable range 0-23
Charge Setting Menu Page
This page allows you to set:
- Charging priority: Configure charging priority
- CSO: Solar energy will give priority to charging batteries. AC power charges the battery only when solar energy is not available.
- SNU: Solar and mains power will charge the battery at the same time.
- OSO: Solar will be the only source of chargers, AC or not.
Note: If the inverter/charger is operating in battery mode, only solar energy will charge the battery. If there is sufficient solar energy, solar energy will charge the batteries.
- Maximum AC current: Note: If the set value in the maximum charging current is less than the set value in the maximum AC current, the inverter will use the charging current in the maximum charging current to charge the AC charger.
- Maximum charging current: Configure total charging current for solar and AC chargers.
Advanced Functions
This page allows you to set:
- The second output battery voltage: On/Off Off Second output battery voltage: 44V/22V, if the battery voltage is lower than the inverter setting, the second output is cut off.
- Turn off the second output capacity: The default is 20%. If the battery capacity is lower than the SOC setting, the second output will be cut off.
- Restoring the second output battery voltage: The default is 52V/26V. If the battery voltage is higher than the battery voltage setting, the second output will resume.
- Restoring the capacity of the second output battery: The default is 50%. If the battery capacity is higher than the SOC setting, the second output will be restored.
- Second output discharge time: 0-990min Configure the discharge time to turn off the second output and wait time to turn on the second output when the inverter returns to line mode or the battery is in a charged state.
- Second output recovery delay time: Configure the second output recovery delay. Even if the conditions for restoring the voltage of the second output battery and restoring the capacity of the second output battery are met, it is still necessary to wait for the recovery delay to end to restore the second output, and the value range is 0-66 minutes
- Second output turn-on time: Values range from 0 to 23.
- Second output turn-off time: Values range from 0 to 23.
- Output open time: Values range from 0 to 23.
- Output stop time: Values range from 0 to 23.
Product Information Setting Menu Page (Device Info)
This page can set the system time: Year/month/day/hour/minute/second.
Screen brightness: from dark to bright.
RGB switch: on/off.
9. Description of Functions and Alarms
When the BMS/485 communication interface is externally connected, as shown in the following figure:
RJ45
1-------485B
2-------485A
3/4/5/6/7/8--NC
8.4.1 Description of the Fault
Fault: The inverter enters the fault mode, the red LED is always on and the LCD displays the fault code. Fault reference code.
| Error code | Fault event |
|---|---|
| 01 | When the inverter is turned off, the fan is locked. |
| 02 | High temperature or poor NTC connection. |
| 03 | Battery voltage too high. |
| 04 | Battery voltage too low. |
| 05 | Output short circuit or overheating detected inside the product. |
| 06 | Output voltage too high |
| 07 | Overload timeout. |
| 08 | Bus voltage too high. |
| 09 | Bus soft start failed. |
| 51 | Excessive current or power surge. |
| 52 | Bus voltage too low |
| 53 | Inverter soft start failed. |
| 55 | The DC voltage in the AC output too high. |
| 57 | Current sensor failed. |
| 58 | The output voltage too low. |
| 59 | PV voltage exceeds limit. |
8.4.2 Warning Description
WARNING: The LCD displays a warning code and the inverter does not enter fault mode.
| Warning Codes | Warning Events | Audible alarms |
|---|---|---|
| 01 | The fan is locked when the inverter is on. | Three beeps every second. |
| 02 | overheating | None |
| 03 | Battery overcharging | One beep every second. |
| 04 | low power | One beep every second. |
| 07 | Overload | One beep every 0.5 seconds. |
| 10 | Output power derate | Two beeps every 3 seconds. |
| 15 | PV low energy | Two beeps every 3 seconds |
| 16 | High AC input during bus soft start (>280VAC) | None |
| E9 | Battery balancing | None |
| 6P | Battery not connected | None |
8.4.3 Code Reference
The relevant information code will be displayed on the LCD screen. Please check the operation of the inverter LCD screen.
| Code | Instructions |
|---|---|
| 60 | If the battery status does not allow charging and discharging after successful communication between the inverter and the battery, it will display code 60, Stop battery charging and discharging. |
| 61 | Communications interruption
|
| 69 | If the battery status does not allow charging after successful communication between the inverter and the battery, it will display code 69, stop charging the battery. |
| 70 | If the battery state must be charged after successful communication between the inverter and the battery, it will display code 70, Charge Battery. |
| 71 | If the battery status does not allow discharging after successful communication between the inverter and the battery, it will display code 71, Stop Battery Discharge. |
10. Troubleshooting (Incident Handling)
| Problems | Liquid Crystal Display/Light Emitting Diode/Buzzer | Explanation/possible reasons | How to do. |
|---|---|---|---|
| Product automatically switches off during start-up | The LCD/LED and buzzer will activate for 3 seconds and then turn off completely. | Battery voltage too low (<1.91V/battery) | 1. Charge the battery 2. Replace the battery |
| Internal fuse tripped. | 1. Replace the fuse. | ||
| No response after power on | No instructions | 1. Battery voltage is too low. (<1.4V battery) | 2. Charge the battery. 3. Replace batteries. |
| 2. Internal fuse tripped. | Check that the AC circuit breaker has not tripped and that the AC wiring is well connected. | ||
| Battery disconnected. | Check that battery leads are well connected. | ||
| Internal relay repeatedly opens and closes when the unit is switched on | liquid crystal screen | Overload error. It's time to overload the inverter by 105%. | Reduce the load on the connection by switching off some devices. |
| Buzzer beeps continuously | Error code 07 | If the PV input voltage is higher than the specification, the output power will be reduced. In this case, if the connected load is higher than the derated output power, an overload will result. | Reduce the number of PV components or connected loads in series. |
| Output short circuit. | Check that the unit airflow is not obstructed or that the ambient temperature is not too high. | ||
| Error code 05 | Internal converter assembly temperature exceeds 20° C | Check that the unit airflow is not obstructed or that the ambient temperature is not too high. | |
| Error code 02 | The internal temperature of the inverter module exceeds 100° C. | Check that the specifications and quantity of batteries meet the requirements. | |
| Error code 03 | The battery is overcharged. | Check that the specifications and quantity of batteries meet the requirements. | |
| Battery voltage is too high. | Replace the fan | ||
| Error code 01 | fan failure | 1. Reduce the connected load. 2. Return to the repair centre. | |
| Error code 06/58 | Output abnormality (inverter voltage below 190Vac or above 260Vac) | Return to the repair centre. | |
| Error code 08/09/53/57 | Internal components have failed. | Restart the device and if the error occurs again, return to the repair centre. | |
| Error code 51 | Overcurrent or power surge. | Reduce the number of PV assemblies in series. | |
| Error code 52 | Bus voltage too low. | ||
| Error code 55 | Output voltage unbalance. | ||
| Error code 59 | PV input voltage out of specification. |