CNC YCQ4-100R/4P

Contents

CNC YCQ4-100R 4P Dual Power Automatic Transfer Switch User Manual

Model: YCQ4-100R/4P

1. Introduction

The CNC YCQ4-100R 4P Dual Power Automatic Transfer Switch (ATS) is a micro household power switch designed to ensure continuous and reliable power supply. It automatically switches between a main power source and a standby power source (e.g., generator) when an abnormality is detected in the main supply.

This product is specifically designed for domestic track installation and is suitable for PZ30 distribution boxes. It operates on 50 or 60Hz rated 400V AC emergency power supply systems. The ATS features a solid structure, reliable conversion, easy installation, and long operational life. It is widely used in applications where power continuity is critical, offering both automatic and manual operation modes. The ATS is composed of a Transfer Switching Equipment (TSE) and a controller, complying with GB/T14048.11 and IEC60947-6-1 standards for low-voltage switching and control devices.

2. Product Features

  • Fast Switching Speed: Achieves switching within 0.008 seconds (8ms) for minimal power interruption.
  • Reliable Performance: Engineered for consistent and dependable operation.
  • Solid Structure: Durable design for long-term use.
  • Easy Installation and Maintenance: Designed for straightforward setup and upkeep.
  • Dual Operation Modes: Supports both automatic and manual power transfer.
  • Compliance: Meets IEC60947-6-1 and GB/T14048.11 standards.
Image highlighting features of the YCQ4-100R ATS including fast switching speed and reliable performance, along with dimensions.
Figure 1: Product Features and Dimensions (Dimensions: 142mm width, 100mm height, 76mm depth)

3. Specifications

AttributeValue
Model NumberYCQ4-100R/4P
TypeMini Automatic Transfer Switch
Poles Number4P
Rated Current (Ie)63A, 100A (selectable)
Rated Working Voltage220V AC
Insulation Voltage (Ui)690VAC
Impact-resistant Voltage8kV
Tse ClassPC (Can be manufactured withstood without short circuit current)
Frequency50/60Hz
StandardIEC60947-6-1
CertificationCE
Utilization CategoryAC-33iB, AC-31B
Weight (4P)2.6 kg
Electrical Life2000 times
Manual Operation Life5000 times
Rated Short Circuit Current (Iq)50kA
Short Circuit Protection Device (Fuse)RT16-00-63A
Rated Control Voltage (Us)AC220/50Hz
Normal Working Conditions (Control Voltage)85-110% Us
Auxiliary Circuit2 relays, each with two sets of contact converter contact capacity: AC200V/50Hz le=5y
Conversion Time of Contactor< 50ms
Operation Conversion Time< 50ms
Return Conversion Time< 50ms
Power Off Time< 50ms
Detailed specification table for the YCQ4-100R ATS, including current ratings, voltages, and operational timings.
Figure 2: Detailed Specifications

4. Safety Information

WARNING: Electrical shock hazard. Installation and servicing should only be performed by qualified personnel.

  • Always disconnect power from both main and standby sources before installing or servicing the ATS.
  • Ensure all wiring connections are secure and comply with local electrical codes.
  • Do not operate the switch if it appears damaged.
  • Verify correct voltage and current ratings before connecting to any power source.
  • Keep children and unauthorized personnel away from electrical installations.

5. Installation

The YCQ4-100R/4P ATS is designed for domestic track installation, typically within a PZ30 distribution box.

5.1 Mounting

  • Mount the ATS securely onto a standard DIN rail within your distribution box.
  • Ensure adequate clearance around the switch for ventilation and access to terminals.
Front view of the YCQ4-100R/4P Automatic Transfer Switch mounted on a DIN rail, showing its compact design.
Figure 3: ATS Mounted on DIN Rail

5.2 Wiring Diagram

Refer to the wiring diagram below for proper connection of the main power (Source A), standby power (Source B), control lines, and load output.

Wiring diagram for the YCQ4R(4P) Automatic Transfer Switch, illustrating connections for City Power (Source A), Generator (Source B), control lines, and load output.
Figure 4: Wiring Diagram for YCQ4R(4P)

Wiring Instructions:

  1. Source A (City Power) Connection: Connect the main power supply to the terminals labeled 'Source A' (R, S, T, N).
  2. Source B (Generator) Connection: Connect the standby power supply (e.g., generator) to the terminals labeled 'Source B' (R, S, T, N).
  3. Load Output: Connect your household load to the 'Load Output' terminals.
  4. Control Lines:
    • Connect the 'Common Control Line' to the appropriate terminals for Source A and Source B.
    • Connect the 'Standby Control Line' to the designated terminals for Source B.
    • Ensure control wiring for Source A (NO C NC AR AN) and Source B (NO C NC BR BN) are correctly connected as per the diagram.
  5. Double-check all connections for tightness and correctness before applying power.

6. Operation

The YCQ4-100R/4P ATS offers both automatic and manual operation modes.

Detailed view of the YCQ4-100R/4P switch showing the Manual/Auto selector switch and product specifications.
Figure 5: Manual/Auto Selector Switch

6.1 Automatic Mode

  • Set the selector switch (red rotary knob) to the "Auto" position.
  • In this mode, the ATS will continuously monitor the main power supply (Source A).
  • If Source A fails or its voltage drops below acceptable levels, the switch will automatically transfer the load to the standby power supply (Source B).
  • Once Source A is restored, the switch will automatically transfer the load back to Source A.

6.2 Manual Mode

  • To operate the switch manually, set the selector switch (red rotary knob) to the "Manual" position.
  • In manual mode, you can use the rotary knob to switch between Source A and Source B as needed.
  • Important Note: Manual operation must be performed carefully. Ensure the switch is in the 'Manual' position before attempting to switch sources manually.

7. Maintenance

The YCQ4-100R/4P ATS is designed for low maintenance. However, regular checks can ensure optimal performance and longevity.

  • Visual Inspection: Periodically inspect the switch for any signs of physical damage, loose connections, or overheating (discoloration).
  • Terminal Tightness: Ensure all wiring terminals remain tight. Loose connections can cause resistance, heat, and potential failure.
  • Dust and Debris: Keep the switch free from dust and debris, which can impede operation or cause overheating. Use a dry, soft cloth or compressed air for cleaning.
  • Functional Test: Periodically test the automatic transfer function by simulating a main power failure (if safe to do so and with proper precautions).
  • Professional Inspection: For complex issues or annual checks, it is recommended to have the unit inspected by a qualified electrician.

8. Troubleshooting

If you encounter issues with your ATS, consider the following common troubleshooting steps:

  • No Power Transfer:
    • Check if both main (Source A) and standby (Source B) power supplies are active and within their normal operating voltage range.
    • Ensure the selector switch is in the "Auto" position for automatic transfer.
    • Verify all control wiring connections are secure and correct according to the wiring diagram.
  • Intermittent Operation:
    • Inspect all power and control wiring for loose connections.
    • Check for stable voltage from both power sources. Fluctuations might cause erratic behavior.
  • Overheating:
    • Ensure the switch is not overloaded beyond its rated current (63A or 100A).
    • Check for proper ventilation around the unit.
    • Tighten any loose power connections.
  • Manual Operation Failure:
    • Ensure the selector switch is firmly in the "Manual" position before attempting to switch sources manually.
    • Do not force the rotary knob if it feels stuck; inspect for obstructions.

If the problem persists after these steps, contact qualified technical support.

9. User Tips

No specific user tips were available from reviews or Q&A for this product. Always follow the installation and operation guidelines provided in this manual.

10. Support and Contact

For technical assistance, warranty information, or further inquiries, please contact the manufacturer or your authorized dealer.

  • Brand: CNC Electric
  • Model: YCQ4-100R/4P
  • Manufacturer: CNC Electric Group Co., Ltd.

Please have your product model number and any relevant details ready when contacting support.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.