1. Introduction
The SONGGER R2100E Industrial Paperless Recorder is a panel-mounted data logging instrument designed for real-time monitoring and recording of industrial process parameters. It supports up to four universal input channels and provides data storage, relay alarm output, and RS485 Modbus RTU communication. This device is suitable for applications requiring continuous process monitoring and historical data analysis.
Important Note: The display interface of this recorder is only available in Chinese. There is no English language option provided for the on-screen display.
2. Specifications
2.1 General Specifications
| Parameter | Specification |
|---|---|
| Power Supply | AC 220V |
| Rated Voltage | AC 220V |
| Power Options | Single-phase AC supply |
| Dimensions | 160 × 80 mm |
| Display | 3-inch Monochrome LCD (128x64 Dot Matrix) |
| Input Channels | 1 to 4 selectable universal inputs |
| Output (Standard) | RS485 (Modbus RTU) + 2 Relay Outputs |
| Custom Output Options | 4–20mA analog output and up to 4 relay outputs |
| Power Feed Output | 1 × 24V DC feed output |
| Storage Capacity | 128MB internal memory |
| USB Interface | Supported (for data export) |
| Alarm Interval | Adjustable from 1 to 240 seconds |
| Protection Rating | IP65 (front panel) |
| Processor | High-speed RISC processor |
| Semi-finished product | No |
| Battery Included | No |
| High-concerned chemical | None |
| Origin | Mainland China |
2.2 Detailed Technical Specifications
For a comprehensive list of technical specifications, including input types, voltage ranges, and communication protocols, please refer to the detailed product specifications below:

Image: Detailed technical specifications for the R2100E recorder, including display, housing material, accuracy, processor, storage, input channels, voltage/current/resistance input, RTD types, thermocouple types, frequency input, tungsten-rhenium, transmitter power supply, alarm output, and communication ports.
- Display: 128×64 Dot Matrix Monochrome LCD
- Housing Material: ABS Plastic
- Display Accuracy: Real-Time: ±0.2% F.S., Memory Recall: ±0.2% F.S.
- Processor: High-performance 32-bit ARM Cortex-M3 RISC core; supports multi-channel acquisition, logging, display, and control
- Storage Module: Large-capacity NAND FLASH for historical data; Serial FRAM for configuration and key data
- Input Channels: Up to 4 universal analog inputs supported (Note: Other inputs like 0-10V or curves must be specified when ordering)
- Voltage Input: 0–5V, 1–5V, 0–20mV, 0–100mV
- Current Input: 0–10mA, 4–20mA
- Resistance Input: Res(0–4000Ω)
- RTD Types: PT100, Cu50, G53, Cu100, BA1, BA2
- Thermocouple Types: S, B, K, T, R, E, N, J
- Frequency Input Channels: F1, F2
- Tungsten-Rhenium: WRe3–25, WRe5–26
- Transmitter Power Supply: Supports 1 channel +24VDC, <60mA
- Alarm Output: Up to 4 relay outputs; rated AC250V/3A or DC30V/3A, programmable high/low/dual limit alarms
- Communication Ports: RS232C and RS485 optional, supports Modbus RTU protocol, baud rates: 1200, 4800, 9600, 19200, 38400, 57600
3. Product Overview
3.1 Instrument Appearance and Components

Image: Front view of the R2100E recorder, highlighting the 128x64 Dot Matrix Monochrome LCD Display, USB Port, Navigation Keys, Silicone Buttons, Confirm Key, Exit Key, and Menu Key. The casing is flame-retardant.
3.2 Key Features
- Flexible Multi-Channel Input: Supports 1 to 4 input channels for diverse monitoring needs.
- High-Speed RISC Processor: Ensures stable, real-time data processing.
- Multiple Display Modes: View data as curve graphs, digital readings, or bar charts.
- USB Data Transfer: Easily export data for reports and logging.
- Relay Output + 24V Power Feed: Includes 2 relay outputs and one 24V power supply by default; customizable up to 4 relay channels.
- IP65-Rated Terminal Protection: Sealed and isolated terminals with dustproof plugs for protection against environmental factors.
- Compact Design with Clear LCD: 3-inch LCD screen for sharp display quality.

Image: Visual representation of key features including Up to 4-Channel Alarm Output, High Cost Performance, Recording Interval Setting (1-240S), Multiple Data Display, RISC Core Processor, and Linear Transformer.
4. Installation
4.1 Panel Mounting
The R2100E recorder is designed for panel mounting. Ensure the panel opening is compatible with the device dimensions.
- Overall Dimensions: 160 × 80 mm
- Single Unit Panel Cut-out Size: 152.0 (+1) x 76.0 (+1) mm
- Grouped Panel Cut-out Dimensions: Minimum 180mm (horizontal), 190mm (vertical) spacing

Image: Detailed product dimensions (160x80mm front, 75mm depth) and panel cut-out sizes for single (152x76mm) and grouped installations (minimum 180mm horizontal, 190mm vertical spacing).
4.2 Wiring Connections
All wiring should be performed by qualified personnel. Ensure the power supply is disconnected before making any connections.
- Power Supply: Connect the AC 220V power supply to the designated terminals. Ensure proper grounding.
- Input Signals: Connect input signals (e.g., from flowmeters, pressure transmitters, temperature sensors) to the appropriate input channels according to your specific application.
- RS485 Communication: If remote monitoring is required, connect the RS485 communication lines.
- Relay Outputs: Verify relay wiring before energizing the system.

Image: Rear view of the R2100E recorder, indicating the Serial Port, RJ45 Port, Power Wiring, Side Ventilation Holes, and Wiring Terminals. A detailed wiring diagram is visible on the back panel.
4.3 Wiring Diagrams
Refer to the following diagrams for specific wiring configurations:

Image: Comprehensive wiring diagrams for various sensor types. Includes Thermocouple Input Control Circuit (2-Wire System) with shielded compensating wires, RTD Input Control Circuit (2-Wire / 3-Wire System) requiring equal resistance for all three wires (≤ 15Ω), and Voltage and Current Wiring Circuits supporting 2-wire, 3-wire, and 4-wire configurations.
5. Operation
5.1 Initial Power-Up and Configuration
- Power On: After ensuring all wiring connections are secure, power on the device.
- Channel Configuration: Select the required input channel configuration within the system settings.
- Alarm & Communication Settings: Configure alarm thresholds, relay outputs, and communication parameters as needed.
5.2 Data Reading and Display Modes
The R2100E offers multiple ways to view process values:
- Curve Mode: Displays data trends over time.
- Digital Display Mode: Shows real-time numerical values.
- Bar Graph Mode: Provides a visual representation of current values.

Image: The R2100E recorder displaying flow, temperature, and pressure data on its 4-inch monochrome LCD, showing multiple parameters on the same screen.

Image: The R2100E recorder displaying a single channel flow measurement (18.12 Kg/h) on its monochrome LCD. The image also highlights the LCD display, touch keys, and terminal connections.

Image: The R2100E recorder displaying multiple channels of data (e.g., temperature, kPa, percentage) on its monochrome LCD, showing its capability for multi-channel data visualization.

Image: Examples of multiple display modes available on the R2100E, including curve, numeric, and bar graph interfaces, demonstrating customizable layouts for data visualization.
5.3 Data Export
Historical data can be exported via the USB interface for report generation and analysis. Insert a compatible USB storage device to enable data export.
5.4 Alarm Functionality
Relay outputs will activate automatically according to the configured alarm conditions.
6. Precautions and Safety
- Ensure installation is performed by qualified personnel.
- Confirm that the power supply matches AC 220V before connection.
- Do not operate the device in environments exceeding its specified temperature or humidity limits.
- Avoid exposure to corrosive gases or conductive dust.
- Ensure correct polarity and terminal assignment to prevent damage.
- Do not insert or remove wiring while the device is powered.
- Use only properly rated cables and connectors.
- If using the 24V feed output, ensure the connected load does not exceed the rated capacity.
6.1 Warning Information (EU Market Reference)
WARNING! Risk of electric shock. Internal circuits operate at hazardous voltage levels.
- Disconnect power supply before installation, maintenance, or wiring.
- Ensure proper grounding to prevent electric shock and electromagnetic interference.
- Do not use the device in explosive atmospheres unless certified for such use.
- Keep out of reach of children.
- Proper disposal: Follow WEEE Directive requirements for electronic waste disposal.
Note: This warning information is for reference only. Final warning language must comply with the official language requirements of the destination EU country.
7. Storage and Maintenance
- Disconnect power before cleaning.
- Clean the front panel using a soft, dry cloth. Do not use solvents or abrasive cleaners.
- Store the device in a dry and dust-free environment when not in use.
- Periodically inspect terminal connections for looseness or corrosion.
- Back up stored data regularly to prevent accidental loss.
8. Troubleshooting
This section provides basic troubleshooting steps. For more complex issues, please contact technical support.
| Problem | Possible Cause | Solution |
|---|---|---|
| Device does not power on | No power supply; incorrect wiring; faulty power source. | Check power connections and voltage. Ensure proper wiring. Test power outlet. |
| No data displayed | Incorrect input channel configuration; sensor not connected; faulty sensor. | Verify input channel settings. Check sensor connections. Test sensor functionality. |
| Data export fails via USB | Incompatible USB device; USB device full; incorrect export settings. | Use an industrial-grade USB disk (1GB-32GB). Check available space. Verify export settings. |
| Relay output not activating | Incorrect alarm thresholds; faulty relay wiring; relay malfunction. | Review alarm threshold settings. Check relay wiring. Test relay functionality. |
9. User Tips
- For optimal data integrity, always use an industrial-grade USB disk (1GB-32GB) for data backup and transfer.
- Regularly back up your recorded data to prevent accidental loss, especially before any maintenance or configuration changes.
- While the device is robust, avoid operating it in direct sunlight or environments with extreme temperature fluctuations to ensure longevity and accuracy.
- When connecting RTD sensors, ensure all three wires have equal resistance and each wire is ≤ 15Ω for accurate readings.
10. Warranty and Support
For warranty information, technical support, or bulk orders, please contact the manufacturer or your local distributor. This document is provided for product instruction purposes only and does not constitute legal advice. The seller is responsible for ensuring compliance with destination market regulations, including CE marking, EMC Directive, and Low Voltage Directive where applicable.