1. Introduction
The LILYTECH ZL-R300A is an advanced temperature controller designed for air source heat pump water heaters. It features precise temperature control, electronic expansion valve management, and various protection functions to ensure efficient and reliable operation of your heat pump system. This manual provides detailed instructions for installation, operation, parameter settings, and troubleshooting.
2. Package Contents
The ZL-R300A package typically includes the following components:
- ZL-R300A Temperature Controller (Display Unit)
- ZL-R300A Main Control Board (V5.0)
- Water Temperature Sensor
- Ambient Temperature Sensor
- Pipe Temperature Sensor
- Coil Temperature Sensor
- Exhaust Temperature Sensor
- Connecting Cables
- Mounting Accessories (e.g., clips)
3. Setup and Wiring
Proper installation and wiring are crucial for the safe and correct operation of the ZL-R300A controller. Please follow the wiring diagram carefully.
3.1 Wiring Diagram
The following diagram illustrates the connections for the ZL-R300A controller. Ensure all connections are secure and correctly matched to avoid damage or malfunction.
- Power Supply: Connect 220VAC (Live and Neutral) to the designated terminals.
- Sensors: Connect the water temperature, ambient temperature, pipe temperature, coil temperature, and exhaust temperature sensors to their respective ports.
- Switches: Connect the high pressure switch and low pressure switch.
- Actuators: Connect the outdoor fan, four-way valve, electric heater, and compressor to their corresponding output terminals.
- Display Unit: Connect the display unit to the main board via the provided cable.
- Expansion Valve: Connect the electronic expansion valve.
Warning: Ensure power is disconnected before performing any wiring to prevent electric shock.
4. Operation
The ZL-R300A controller features an intuitive display and button interface for easy operation.
4.1 Control Panel Overview
The display unit shows current temperatures, operating status, and time. The buttons are used for navigation and setting parameters:
- Power Button (U): Turns the controller on/off.
- Mode Button (M): Switches between operating modes and navigates menu items.
- Set Button (S): Enters setting mode and confirms selections.
- Up Arrow (▲): Increases values or moves up in menus.
- Down Arrow (▼): Decreases values or moves down in menus.
4.2 Basic Operations
- Power On/Off:
- To power on: In the off state, long press the M button for 2 seconds.
- To power off: In the on state, long press the M button for 2 seconds (only the real-time clock will be displayed).
- Water Tank Temperature Setting:
- In the on state, press the S button. The setting temperature will flash.
- Use the ▲ or ▼ buttons to modify the value.
- Press the S button again to save and exit. (Factory default: 50°C).
- Set Real-time Clock:
- Press the S button. The hh:mm display will flash.
- Use the ▲ or ▼ buttons to modify the time.
- Press the S button again to save and exit.
- Forced Defrost:
- In the on state, simultaneously press the S and ▼ buttons for 3 seconds to initiate forced defrost.
- To exit forced defrost, simultaneously press the S and ▼ buttons for 3 seconds again.
- Manual Auxiliary Electric Heating:
- In the on state, simultaneously press the S and ▲ buttons for 3 seconds.
- If the water temperature is below the set temperature, auxiliary electric heating will turn on. It will turn off automatically when the water temperature reaches or exceeds the set temperature.
- Key Lock:
- Simultaneously press the ▲ and ▼ buttons to lock the keys. The '8' symbol will light up, and all key operations will be invalid.
- To unlock, simultaneously press the ▲ and ▼ buttons again.
- Restore Factory Default Parameters:
- In the on state, simultaneously press the S and M buttons for 3 seconds. The LCD will display "UnL".
- Press the ▲ button twice. The system will automatically restore factory default settings.
- Set Working Mode:
- In the on state, press the M button. The current working mode symbol will flash.
- Press the M button to cycle through the 4 available modes.
- After selecting, press the S button to confirm and exit.
Working Mode Symbols and Descriptions Symbol Mode Description A Automatic Heating Mode Controls heating based on set temperature, no time limit. A Automatic Cooling Mode Controls cooling based on set temperature, no time limit. S Economic Heating Mode Up to 3 heating cycles, temperature control within set range. S Economic Cooling Mode Up to 3 cooling cycles, temperature control within set range.
4.3 Parameter Settings
To access and modify advanced parameters, follow these steps:
- In the on state, long press the S button for 3 seconds. The display will show "00" prompting for a password.
- Use the ▲ or ▼ buttons to modify the password value (default: 11).
- Press the S button to confirm. If the password is correct, the temperature display area will show parameter code "01". If incorrect, it will exit.
- Press the S or M button to cycle through parameter codes.
- Use the ▲ or ▼ buttons to modify the parameter value.
- After setting, long press the S button for 3 seconds to exit and save parameters. If no button is pressed for 30 seconds, it will automatically exit without saving.
| No. | Code | Setting Function | Setting Range | Description | Factory Default |
|---|---|---|---|---|---|
| 1 | t1 | Water tank hysteresis temperature | 1-10°C | 5 | |
| 2 | t2 | Water tank electric auxiliary heating start ambient temperature | -5-25°C | 12 | |
| 3 | t3 | Water tank electric auxiliary heating | 0: Off 1: On | 0 | |
| 4 | t4 | Set temperature upper limit | 15-99°C | 70 | |
| 5 | t5 | Set temperature lower limit | 9-t4 | 10 | |
| 6 | t6 | Water temperature sensor calibration | -9.9-9.9°C | 0 | |
| 7 | d1 | Defrost start time | 0-180 minutes | 0: Disable defrost | 45 |
| 8 | d2 | Defrost start temperature | -20-20°C | -5 | |
| 9 | d3 | Defrost end temperature | 2-30°C | 10 | |
| 10 | d4 | Maximum defrost time | 0-30 minutes | 0: Disable defrost | 8 |
| 11 | d5 | When external coil temperature sensor fails, defrost starts at ambient temperature | -10-20°C | 1 | |
| 12 | d6 | Compressor start/stop during defrost | 0-1 | 0: Compressor does not stop 1: Compressor starts/stops | 1 |
| 13 | P1 | Exhaust protection temperature | 0-130°C | 0: Disable exhaust high temperature protection | 110 |
| 14 | P2 | High pressure switch | 0-1 | 0: Disconnect alarm 1: Close alarm | 1 |
| 15 | P3 | Low pressure switch | 0-1 | 0: Disconnect alarm 1: Close alarm | 1 |
| 16 | F1 | Electronic expansion valve manual opening | 80-500 steps | 350 | |
| 17 | F2 | Electronic expansion valve cycle | 0-2 | 0: Disabled 1: Automatic EEV adjustment 2: Manual EEV adjustment | 2 |
| 18 | F3 | Electronic expansion valve minimum opening | 0-480 steps | 80 | |
| 19 | F4 | Electronic expansion valve adjustment cycle | 1-120 seconds | 30 | |
| 20 | F5 | Target superheat | -10-10 degrees | 1 | |
| 21 | F6 | Coarse adjustment steps | 0-20 steps | 12 | |
| 22 | F7 | Fine adjustment steps | 0-20 steps | 4 | |
| 23 | F8 | Micro adjustment steps | 0-20 steps | 1 | |
| 24 | U1 | Compressor delay protection | 1-30 minutes | 3 | |
| 25 | U2 | Four-way valve mode | 0-1 | 0: Heating off, cooling on 1: Heating on, cooling off | 0 |
| 26 | U3 | Power-off memory function | 0-1 | 0: Off 1: On | 1 |
| 27 | U4 | Buzzer alarm | 0-1 | 0: Off 1: On | 1 |
| 28 | U9 | Password | 0-99 | 11 |
5. Maintenance
To ensure the longevity and optimal performance of your ZL-R300A controller, consider the following general maintenance guidelines:
- Regular Cleaning: Keep the display unit and main board free from dust and debris. Use a soft, dry cloth for cleaning.
- Connection Checks: Periodically inspect all wiring connections to ensure they are secure and free from corrosion.
- Sensor Integrity: Ensure temperature sensors are properly installed and not damaged.
- Environmental Conditions: Operate the controller within its specified environmental limits (temperature and humidity) to prevent damage.
6. Troubleshooting
The ZL-R300A controller includes self-diagnostic capabilities and displays error codes to help identify issues. Refer to the table below for common fault codes and their solutions.
| Fault Name | Code | Cause of Fault | Action | Description |
|---|---|---|---|---|
| Water tank temperature sensor fault | E01 | Sensor short circuit or open circuit | Stop cooling, heating | Automatic |
| External coil temperature sensor fault | E02 | Sensor short circuit or open circuit | Stop cooling, heating | Automatic |
| Ambient temperature sensor fault | E03 | Sensor short circuit or open circuit | Stop cooling, heating | Automatic |
| Exhaust temperature sensor fault | E04 | Sensor short circuit or open circuit | Stop cooling, heating | Automatic |
| High pressure switch input alarm | EPH | High pressure switch signal abnormal | Stop cooling, heating | Automatic or manual |
| Low pressure switch input alarm | EPL | Low pressure switch signal abnormal | Stop cooling, heating | Automatic or manual |
| Exhaust temperature too high | EWH | Exhaust temperature too high | Stop cooling, heating | Resets automatically when exhaust temperature drops |
| Communication fault | E09 | Communication fault between control panel and main board | Automatic | |
| Communication drop | E10 | Communication drop between control panel and main board | Automatic | |
| Auxiliary electric temperature sensor fault | E11 | Sensor short circuit or open circuit | Automatic |
Note: Manual reset method for alarms: Power off the controller, then power on again.
7. Specifications
| Feature | Specification |
|---|---|
| Model | ZL-R300A |
| DIY Supplies | Electrical |
| Electronic | No |
| High-concerned chemical | None |
| Origin | Mainland China |
| Power Supply | 220VAC, 50/60Hz |
| Temperature Sensor Type | NTC 10K/3470 |
| Temperature Measurement Range | -10 to 50°C |
| Control Accuracy | ±1°C |
| Display Resolution | 0.1°C |
| Operating Environment | Temperature: -10 to 50°C, Humidity: 20-85% RH (non-condensing) |
| Compressor Relay Output | 30A/250VAC |
| Electric Heater Relay Output | 10A/250VAC |
| Other Relay Outputs | 5A/250VAC |
| EEV Drive | 12VDC/300mA, 1-2 phase, 50pps |
8. User Tips
No specific user tips are available from provided reviews or Q&A. However, general best practices for temperature controllers include:
- Always ensure sensors are correctly placed and insulated for accurate readings.
- Regularly check for any loose connections, especially after initial installation or maintenance.
- Familiarize yourself with the parameter settings to optimize your heat pump's performance for your specific needs.
9. Warranty and Support
For warranty information and technical support, please contact your retailer or the manufacturer directly. Keep your purchase receipt as proof of purchase.
For technical inquiries, you may contact the seller via:
- Email: ed18773098526@163.com
- WhatsApp: +8613667399620
10. Product Video
Watch this video for a visual overview of the ZL-R300A controller and its components.