ZL-R300A Air Source Heat Pump Water Heater Temperature Controller

User Manual

1. Introduction

The LILYTECH ZL-R300A is an advanced temperature controller designed for air source heat pump water heaters. It features precise temperature control, electronic expansion valve management, and various protection functions to ensure efficient and reliable operation of your heat pump system. This manual provides detailed instructions for installation, operation, parameter settings, and troubleshooting.

2. Package Contents

The ZL-R300A package typically includes the following components:

  • ZL-R300A Temperature Controller (Display Unit)
  • ZL-R300A Main Control Board (V5.0)
  • Water Temperature Sensor
  • Ambient Temperature Sensor
  • Pipe Temperature Sensor
  • Coil Temperature Sensor
  • Exhaust Temperature Sensor
  • Connecting Cables
  • Mounting Accessories (e.g., clips)
ZL-R300A package contents including controller, main board, and sensors
Figure 1: ZL-R300A Controller, Main Board, and Sensors
Close-up of the ZL-R300A main control board
Figure 2: ZL-R300A Main Control Board

3. Setup and Wiring

Proper installation and wiring are crucial for the safe and correct operation of the ZL-R300A controller. Please follow the wiring diagram carefully.

3.1 Wiring Diagram

The following diagram illustrates the connections for the ZL-R300A controller. Ensure all connections are secure and correctly matched to avoid damage or malfunction.

Detailed wiring diagram for ZL-R300A heat pump controller, showing connections for high/low pressure switches, various temperature sensors (ambient, exhaust, pipe, water, coil), display, expansion valve, outdoor fan, four-way valve, electric heater, compressor, and 220VAC power supply.
Figure 3: ZL-R300A Wiring Diagram
  • Power Supply: Connect 220VAC (Live and Neutral) to the designated terminals.
  • Sensors: Connect the water temperature, ambient temperature, pipe temperature, coil temperature, and exhaust temperature sensors to their respective ports.
  • Switches: Connect the high pressure switch and low pressure switch.
  • Actuators: Connect the outdoor fan, four-way valve, electric heater, and compressor to their corresponding output terminals.
  • Display Unit: Connect the display unit to the main board via the provided cable.
  • Expansion Valve: Connect the electronic expansion valve.

Warning: Ensure power is disconnected before performing any wiring to prevent electric shock.

4. Operation

The ZL-R300A controller features an intuitive display and button interface for easy operation.

4.1 Control Panel Overview

ZL-R300A controller display showing temperature readings and control buttons
Figure 4: ZL-R300A Display Unit

The display unit shows current temperatures, operating status, and time. The buttons are used for navigation and setting parameters:

  • Power Button (U): Turns the controller on/off.
  • Mode Button (M): Switches between operating modes and navigates menu items.
  • Set Button (S): Enters setting mode and confirms selections.
  • Up Arrow (▲): Increases values or moves up in menus.
  • Down Arrow (▼): Decreases values or moves down in menus.

4.2 Basic Operations

  1. Power On/Off:
    • To power on: In the off state, long press the M button for 2 seconds.
    • To power off: In the on state, long press the M button for 2 seconds (only the real-time clock will be displayed).
  2. Water Tank Temperature Setting:
    • In the on state, press the S button. The setting temperature will flash.
    • Use the ▲ or ▼ buttons to modify the value.
    • Press the S button again to save and exit. (Factory default: 50°C).
  3. Set Real-time Clock:
    • Press the S button. The hh:mm display will flash.
    • Use the ▲ or ▼ buttons to modify the time.
    • Press the S button again to save and exit.
  4. Forced Defrost:
    • In the on state, simultaneously press the S and ▼ buttons for 3 seconds to initiate forced defrost.
    • To exit forced defrost, simultaneously press the S and ▼ buttons for 3 seconds again.
  5. Manual Auxiliary Electric Heating:
    • In the on state, simultaneously press the S and ▲ buttons for 3 seconds.
    • If the water temperature is below the set temperature, auxiliary electric heating will turn on. It will turn off automatically when the water temperature reaches or exceeds the set temperature.
  6. Key Lock:
    • Simultaneously press the ▲ and ▼ buttons to lock the keys. The '8' symbol will light up, and all key operations will be invalid.
    • To unlock, simultaneously press the ▲ and ▼ buttons again.
  7. Restore Factory Default Parameters:
    • In the on state, simultaneously press the S and M buttons for 3 seconds. The LCD will display "UnL".
    • Press the ▲ button twice. The system will automatically restore factory default settings.
  8. Set Working Mode:
    • In the on state, press the M button. The current working mode symbol will flash.
    • Press the M button to cycle through the 4 available modes.
    • After selecting, press the S button to confirm and exit.
    Working Mode Symbols and Descriptions
    Symbol Mode Description
    A Automatic Heating Mode Controls heating based on set temperature, no time limit.
    A Automatic Cooling Mode Controls cooling based on set temperature, no time limit.
    S Economic Heating Mode Up to 3 heating cycles, temperature control within set range.
    S Economic Cooling Mode Up to 3 cooling cycles, temperature control within set range.

4.3 Parameter Settings

To access and modify advanced parameters, follow these steps:

  1. In the on state, long press the S button for 3 seconds. The display will show "00" prompting for a password.
  2. Use the ▲ or ▼ buttons to modify the password value (default: 11).
  3. Press the S button to confirm. If the password is correct, the temperature display area will show parameter code "01". If incorrect, it will exit.
  4. Press the S or M button to cycle through parameter codes.
  5. Use the ▲ or ▼ buttons to modify the parameter value.
  6. After setting, long press the S button for 3 seconds to exit and save parameters. If no button is pressed for 30 seconds, it will automatically exit without saving.
Working Parameters Table
No. Code Setting Function Setting Range Description Factory Default
1t1Water tank hysteresis temperature1-10°C5
2t2Water tank electric auxiliary heating start ambient temperature-5-25°C12
3t3Water tank electric auxiliary heating0: Off 1: On0
4t4Set temperature upper limit15-99°C70
5t5Set temperature lower limit9-t410
6t6Water temperature sensor calibration-9.9-9.9°C0
7d1Defrost start time0-180 minutes0: Disable defrost45
8d2Defrost start temperature-20-20°C-5
9d3Defrost end temperature2-30°C10
10d4Maximum defrost time0-30 minutes0: Disable defrost8
11d5When external coil temperature sensor fails, defrost starts at ambient temperature-10-20°C1
12d6Compressor start/stop during defrost0-10: Compressor does not stop 1: Compressor starts/stops1
13P1Exhaust protection temperature0-130°C0: Disable exhaust high temperature protection110
14P2High pressure switch0-10: Disconnect alarm 1: Close alarm1
15P3Low pressure switch0-10: Disconnect alarm 1: Close alarm1
16F1Electronic expansion valve manual opening80-500 steps350
17F2Electronic expansion valve cycle0-20: Disabled 1: Automatic EEV adjustment 2: Manual EEV adjustment2
18F3Electronic expansion valve minimum opening0-480 steps80
19F4Electronic expansion valve adjustment cycle1-120 seconds30
20F5Target superheat-10-10 degrees1
21F6Coarse adjustment steps0-20 steps12
22F7Fine adjustment steps0-20 steps4
23F8Micro adjustment steps0-20 steps1
24U1Compressor delay protection1-30 minutes3
25U2Four-way valve mode0-10: Heating off, cooling on 1: Heating on, cooling off0
26U3Power-off memory function0-10: Off 1: On1
27U4Buzzer alarm0-10: Off 1: On1
28U9Password0-9911
Page from ZL-R300A manual showing detailed parameter settings table
Figure 5: Parameter Settings Table (Page 3/6 of Manual)
Page from ZL-R300A manual showing detailed operation instructions for power, temperature, clock, defrost, auxiliary heat, key lock, factory reset, and mode settings
Figure 6: Operation Instructions (Page 4/6 of Manual)

5. Maintenance

To ensure the longevity and optimal performance of your ZL-R300A controller, consider the following general maintenance guidelines:

  • Regular Cleaning: Keep the display unit and main board free from dust and debris. Use a soft, dry cloth for cleaning.
  • Connection Checks: Periodically inspect all wiring connections to ensure they are secure and free from corrosion.
  • Sensor Integrity: Ensure temperature sensors are properly installed and not damaged.
  • Environmental Conditions: Operate the controller within its specified environmental limits (temperature and humidity) to prevent damage.

6. Troubleshooting

The ZL-R300A controller includes self-diagnostic capabilities and displays error codes to help identify issues. Refer to the table below for common fault codes and their solutions.

Fault Codes and Actions
Fault Name Code Cause of Fault Action Description
Water tank temperature sensor faultE01Sensor short circuit or open circuitStop cooling, heatingAutomatic
External coil temperature sensor faultE02Sensor short circuit or open circuitStop cooling, heatingAutomatic
Ambient temperature sensor faultE03Sensor short circuit or open circuitStop cooling, heatingAutomatic
Exhaust temperature sensor faultE04Sensor short circuit or open circuitStop cooling, heatingAutomatic
High pressure switch input alarmEPHHigh pressure switch signal abnormalStop cooling, heatingAutomatic or manual
Low pressure switch input alarmEPLLow pressure switch signal abnormalStop cooling, heatingAutomatic or manual
Exhaust temperature too highEWHExhaust temperature too highStop cooling, heatingResets automatically when exhaust temperature drops
Communication faultE09Communication fault between control panel and main boardAutomatic
Communication dropE10Communication drop between control panel and main boardAutomatic
Auxiliary electric temperature sensor faultE11Sensor short circuit or open circuitAutomatic

Note: Manual reset method for alarms: Power off the controller, then power on again.

Page from ZL-R300A manual showing fault codes, causes, and actions
Figure 7: Fault Codes and Troubleshooting (Page 6/6 of Manual)

7. Specifications

Feature Specification
ModelZL-R300A
DIY SuppliesElectrical
ElectronicNo
High-concerned chemicalNone
OriginMainland China
Power Supply220VAC, 50/60Hz
Temperature Sensor TypeNTC 10K/3470
Temperature Measurement Range-10 to 50°C
Control Accuracy±1°C
Display Resolution0.1°C
Operating EnvironmentTemperature: -10 to 50°C, Humidity: 20-85% RH (non-condensing)
Compressor Relay Output30A/250VAC
Electric Heater Relay Output10A/250VAC
Other Relay Outputs5A/250VAC
EEV Drive12VDC/300mA, 1-2 phase, 50pps

8. User Tips

No specific user tips are available from provided reviews or Q&A. However, general best practices for temperature controllers include:

  • Always ensure sensors are correctly placed and insulated for accurate readings.
  • Regularly check for any loose connections, especially after initial installation or maintenance.
  • Familiarize yourself with the parameter settings to optimize your heat pump's performance for your specific needs.

9. Warranty and Support

For warranty information and technical support, please contact your retailer or the manufacturer directly. Keep your purchase receipt as proof of purchase.

For technical inquiries, you may contact the seller via:

  • Email: ed18773098526@163.com
  • WhatsApp: +8613667399620

10. Product Video

Watch this video for a visual overview of the ZL-R300A controller and its components.