1. Introduction
The KUAIQU KM511 and KM502C are high-quality insulation resistance testers, also known as megometers. These specialized instruments are designed for measuring the insulation resistance of various electrical equipment and insulating materials, such as large transformers, generators, high-voltage motors, power capacitors, power cables, and arresters. They are ideal for maintenance, repair, testing, and verification in electrical applications.
The KM502C offers a measuring range of 0.1 MΩ to 20 GΩ, while the KM511 ranges from 1 MΩ to 200 GΩ. Both models feature AC/DC voltage measurement from 10V to 600V.
Product Overview Video: This video demonstrates the unboxing and basic operation of the KM502C model, highlighting its components and some key features.
2. Safety Information
This series of insulation resistance testers is designed and produced according to the safety standard IEC1010, strictly following the safety standards of double insulation CAT III 1000V, CAT IV, and pollution degree 2. To protect your safety, please read this manual carefully before using the device.
2.1 Safety Symbols
- Caution! Refer to the user's manual before using this meter. Double Insulation.
- Warning! Dangerous Voltage (Risk of electric shock).
- Danger: To avoid serious or fatal damage that may be caused by certain states and wrong operations.
- Warning: Indicates avoiding the risk of electric shock.
- Caution: Indicates avoiding damage to the instrument and making accurate measurements.
2.2 General Precautions
- Do not test in flammable locations; sparks may cause an explosion.
- Do not operate the instrument if its surface is wet or if the operator's hands are wet.
- When testing voltage, there is a possibility of personal injury due to accidental short-circuit between metal parts and test leads.
- Do not exceed the maximum allowable range of the measuring range during measurement.
- Do not open the battery cover during measurement.
- When performing insulation measurement, do not touch the line under test.
- If the instrument is abnormal (e.g., broken casing, exposed metal parts), stop using it immediately.
- When test leads are connected to the circuit, do not press function buttons; first exit measurement, then change the test item.
- Do not install substitute parts or make any unauthorized changes to the instrument.
- Do not replace the battery when the instrument is wet.
- Make sure all test leads are securely connected to the meter's test sockets.
- Make sure the instrument is turned off before opening the battery cover.
- Before measuring, confirm that the function button is selected to the appropriate position.
- After use, press and hold the "OFF" button to turn off the unit. If not used for a long time, remove the battery for storage.
- Do not store in high temperature, humidity, places where condensation may occur, or in direct sunlight.
- Use a damp cloth or detergent to clean the instrument case; do not use abrasives or solvents.
- If the instrument is wet, dry it before use or storage.
- The long-term short-circuit of the measuring end shall not exceed 60 seconds.
- The continuous working time should not exceed 30 minutes.
3. Product Overview
3.1 Package Contents
The product package typically includes:
- Insulation resistance tester (KM511 or KM502C model)
- 1 pair of test leads
- 1 pair of alligator clips
- Instruction manual
- Storage bag
- Color box packaging
- 6x AA Batteries (may vary by package)

Figure 3.1: Product List - Contents of the KM511 package.
3.2 Device Layout (KM511 Model)

Figure 3.2: KM511 Device Layout - Key components and controls of the KM511 model.
3.3 Device Layout (KM502C Model)

Figure 3.3: KM502C Device Layout - Key components and controls of the KM502C model.
4. Specifications
The following tables detail the technical specifications for the KM511 and KM502C models.
4.1 General Specifications
| Feature | Description |
|---|---|
| DIY Supplies | Electrical |
| Origin | Mainland China |
| Certification | CE |
| Semi-finished product | No |
| Battery Included | No (Requires 6x AA batteries) |
| High-concerned chemical | None |
| Working conditions | 0°C~35°C, relative humidity ≤ 75%, 2000 meters above sea level |
| Working temperature and humidity | 0°C~40°C, relative humidity ≤ 85% |
| Short circuit current | Less than 1.8mA (KM502C), 1.8mA (KM511) |
| Low battery indication | Display shows "E3" |
| Withstand voltage | AC 2KV 50Hz 1 minute |
| Dimensions | 180 x 140 x 70 mm (approx. 7 x 5.5 x 2.8 inches) |
| Weight | Approx. 800g (including battery) |
4.2 KM511 Technical Parameters

Figure 4.1: KM511 Technical Parameters
4.3 KM502C Technical Parameters

Figure 4.2: KM502C Technical Parameters
4.4 Model Comparison

Figure 4.3: KM511 vs KM502C Feature Comparison
5. Setup
5.1 Battery Installation
If "E3" is displayed on the LCD during use, the battery capacity is insufficient, and you need to replace the batteries. Before replacing the battery, ensure the test leads are disconnected and the power is turned off.
- Stop all test work and disconnect the test leads from the item under test.
- Disconnect the test leads from the meter.
- Remove the battery cover from the back of the meter.
- Insert 8 AA / 1.5V batteries, paying attention to the correct position and polarity.
- Install the battery cover and screw on the battery cover.
5.2 Connecting Test Leads
Plug the red test lead into the meter's "L" input jack and the black test lead into the "E" input jack.
- Connect the wiring of the "E" end jack (black test lead with alligator clip) to one end of the object to be tested.
- Clip the wiring of the "L" end jack (red test lead with alligator clip) to the other end of the tested object.
- Alternatively, you can hold the test rod with one hand to make the test needle contact the other end of the object to be tested. When operating with one hand, the other hand or other parts of the body should not be in contact with any part of the test circuit.
- For accurate measurements and to prevent surface leakage from affecting the test impedance, connect the shielded wire (with a large test clip) from the "G" end jack of the instrument to the surface of the DUT.

Figure 5.1: KM511 Insulation Resistance Test Setup

Figure 5.2: KM502C Insulation Resistance Test Setup
6. Operating Instructions
6.1 Power On/Off
- To turn on: Press and hold the power button (
) for more than 2 seconds. - To turn off: Press and hold the power button for more than 2 seconds.
6.2 Insulation Resistance Measurement
- Voltage Selection: Press the "SELECT" button to choose the appropriate test voltage (e.g., 50V, 100V, 250V, 500V, 1000V, 2000V, 2500V, 5000V depending on the model). The selected voltage will be displayed in the lower right corner of the screen.
- Initiate Test: Connect the test leads to the object under test. Press the "TEST" button. The test light will emit a red warning, and the insulation resistance test voltage will be displayed. The measurement time is shown at the bottom left, and the resistance value in the middle.
- End Test: Press the "TEST" button again to end the measurement. The test light will turn off, and the measured value will remain on the display.
Important Notes:
- Before testing, ensure there is no electricity in the circuit and do not measure live equipment.
- After measurement, do not touch the circuit with your hands, as stored capacitance can cause electric shock.
6.3 DAR (Dielectric Absorption Ratio) Automatic Calculation
When the insulation resistance measurement time exceeds 1 minute, press the "PI/DAR" button. The display will show the "DAR" symbol, and the instrument will automatically calculate and display the absorption ratio (ratio of insulation resistance at 1 minute to 30 seconds) in the lower left corner.

Figure 6.1: KM511 DAR Automatic Calculation
6.4 PI (Polarization Index) Automatic Calculation
After the insulation resistance measurement time exceeds 10 minutes, press the "PI/DAR" button until the display shows the "PI" symbol. The instrument will automatically calculate and display the polarization index value (ratio of insulation resistance at 10 minutes to 1 minute) in the lower left corner.

Figure 6.2: KM511 PI Automatic Calculation
6.5 AC/DC Voltage Test
The AC/DC voltage measuring range for both KM511 and KM502C is 10V to 600V.
- Select Mode: After powering on, press the "SELECT" button to choose either AC voltage measurement (display shows "AC" unit symbol V) or DC voltage measurement (display shows "DC" unit symbol V).
- Connect Leads: Insert the plug end of the red test lead into the "AC/DC 600V" jack, and the plug end of the black test lead into the "G" input jack.
- Measure: Touch the two test leads to the two ends of the voltage to be measured. The measured AC or DC voltage in volts will be displayed.
Note:
- The measured voltage should not exceed 600V AC/DC.
- For AC voltage, the frequency range is 40Hz to 70Hz. Measurements outside this range may exceed technical specifications.
- After completing measurements, disconnect the test leads from the circuit and then from the instrument.
6.6 Data Hold and Backlight Operation
- Backlight: Press and hold the "HOLD/*" button for more than 2 seconds to turn the backlight on. Press and hold again for more than 2 seconds to turn it off.
- Data Hold: Short press the "HOLD/*" button to hold the current data on the display. Short press again to exit data hold.
6.7 Data Storage, Recall, and Deletion
The device can store up to 100 sets of data.
- Store Data: After measuring insulation resistance, short press the "HOLD/*" button to hold the data (display shows "HOLD" symbol). Then, press the "MEM READ" button to save the data (display shows "MEM" symbol). Long press the "MEM READ" button to exit storage.
- Recall Data: After powering on, short press the "MEM READ" button. The "READ" symbol will be displayed. Use the "UP/DOWN" arrow buttons to scroll through stored data. Long press "MEM READ" to exit data reading.
- Delete Data: In data reading mode, short press the "SELECT" button to delete the current displayed data. The display will show "--". Use the arrow buttons to navigate and delete other data. To delete all data, long press the "PI/DAR" button.

Figure 6.3: KM511 Data Storage and Recall
7. Maintenance
7.1 Cleaning
Use a damp cloth or mild detergent to clean the instrument case. Do not use abrasive cleaners or solvents, as these can damage the casing and accessories. If the instrument becomes wet, ensure it is completely dry before use or storage.
7.2 Battery Replacement
Refer to section 5.1 for detailed instructions on battery replacement.
8. Troubleshooting
- "E3" Displayed: This indicates low battery. Replace the batteries as described in section 5.1.
- Abnormal Instrument Behavior: If the instrument shows any abnormal behavior, such as a broken casing or exposed metal parts, immediately stop using it. Do not attempt to repair it yourself.
- Inaccurate Readings: Ensure test leads are properly connected and not twisted. Verify the correct voltage range is selected. In contaminated or humid environments, connect the Guard Terminal (G) to eliminate surface leakage errors.
9. User Tips
- Always remember to set the corresponding voltage range before initiating any measurement to ensure accuracy and prevent damage.
- The PI (Polarization Index) button is crucial for evaluating the aging and moisture content of electrical equipment's insulation.
- The DAR (Dielectric Absorption Ratio) button helps quickly assess the insulation condition and moisture level.
- For measurements in contaminated or humid environments, always connect the Guard Terminal (G) to the test object to minimize surface leakage errors and ensure reliable results.
10. Support
For more detailed information, please refer to the full user manual PDF available from the seller.
If you encounter any issues or have questions, please contact KUAIQU customer service. Although there may be time differences, your inquiries will be prioritized. KUAIQU is committed to providing a great experience.
