SUMRY SP Series Hybrid Solar Inverter

Contents

SUMRY SP Series Hybrid Solar Inverter User Manual

Model: SP-3200 / SP-4200 / SP-7000

Brand: SUMRY

1. Introduction

This is a multi-function inverter/charger, combining functions of inverter, MPPT solar charger and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.

Features

  • Pure sine wave inverter
  • Programmable supply priority for PV, battery or Grid
  • High PV input voltage range (55~450VDC)
  • Built-in Max 110A MPPT solar charge
  • Compatible with lithium-ion battery
  • Support BMS communication with Lithium battery
  • Smart battery charge design to optimize battery life
  • Overload, high temperature, inverter output short circuit protection
  • Cold start function
  • Intelligent fan speed adjustment
  • WIFI (Optional)

Basic System Architecture

The following illustration shows basic application for this inverter/charger. It also includes following devices to have a complete running system: Generator or Utility, PV modules (option).

Consult with your system integrator for other possible system architectures depending on your requirements.

This inverter can power all kinds of appliances in home or office environment, including motor-type appliances such as tube light, fan, refrigerator and air conditioner.

Hybrid Power System Diagram
Figure 1: Hybrid Power System - Illustrates connections between solar panels, generator/utility, battery, inverter, and home appliances.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.
  2. CAUTION --To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION – Only qualified personnel can install this device with battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
  10. GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
  11. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
  12. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

3. Product Overview

The SUMRY Hybrid Solar Inverter features a clear LCD display, status indicators, and function buttons for easy operation and monitoring. Key components include AC input/output, PV input, battery input, and communication ports.

Product Overview Diagram
Product Overview: Labeled components of the inverter.

Components Description:

  1. LCD display
  2. Status Indicator
  3. Charging Indicator
  4. Fault Indicator
  5. Function buttons
  6. Power on/off switch
  7. AC input
  8. AC output
  9. PV input
  10. Battery input
  11. RS-232/RS485 communication port
  12. Safety (Earth) ground

4. Installation

4.1 Unpacking and Inspection

Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package: The unit x 1, User manual x 1.

4.2 Preparation

Before connecting all wirings, please take off bottom cover by removing two screws.

4.3 Mounting the Unit

Consider the following points before selecting where to install:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level in order to allow the LCD display to be read at all times.
  • The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.
  • Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Unit Mounting Diagram
Mounting the Unit: Recommended clearances for proper heat dissipation.

4.4 Battery Connection

CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable and terminal size as below.

ModelWire SizeCable mm²Ring Terminal D (mm)Ring Terminal L (mm)Torque Value
3.8KW 24V1*3AWG226.433.22 Nm
6.2KW 48V1*4AWG226.433.22 Nm

Please follow below steps to implement battery connection:

  1. Assemble battery ring terminal based on recommended battery cable and terminal size.
  2. Connect all battery packs as units requires.
Battery Connection Diagram
Battery Connection Diagram: Shows wiring for 4.2KVA and 7.0KVA systems.

3. Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the bolts are tightened with torque of 2-3 Nm. Make sure polarity at both the battery and the inverter/charger is correctly connected and ring terminals are tightly screwed to the battery terminals.

Battery Ring Terminal Connection
Battery Ring Terminal Connection: Proper insertion and tightening of terminals.

WARNING: Shock Hazard Installation must be performed with care due to high battery voltage in series.

CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring terminal. Otherwise, overheating may occur.

CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected tightly.

CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).

4.5 AC Input/Output Connection

CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is for 32A for 3.8KW, 50A for 6.2KW.

CAUTION!! There are two terminal blocks with “IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested cable requirement for AC wires:

ModelGaugeTorque Value
3.8KW12 AWG1.2~ 1.6 Nm
6.2KW8 AWG1.4~ 1.6Nm

Please follow below steps to implement AC input/output connection:

  1. Before making AC input/output connection, be sure to open DC protector or disconnector first.
  2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
  3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (yellow-green) first.

L→LINE (brown or black)
N→Neutral (blue)

WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.

4. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. Be sure to connect PE protective conductor (yellow-green) first.

L→LINE (brown or black)
N→Neutral (blue)

5. Make sure the wires are securely connected.

CAUTION: Important Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.

CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it's equipped with time-delay function before installation. Otherwise, this inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.

4.6 PV Connection

CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested cable requirement for PV wires:

ModelWire SizeCable (mm²)Torque value (max)
3.8KW/6.2KW1 x 12AWG41.2 Nm

PV Module Selection:

When selecting proper PV modules, please be sure to consider below parameters:

  1. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
  2. Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
INVERTER MODEL3.8KW6.2KW
Max. PV Array Open Circuit Voltage450Vdc450Vdc
PV Array MPPT Voltage Range55Vdc~450Vdc55Vdc~450Vdc

Take 250Wp PV module as an example. After considering above two parameters, the recommended module configurations are listed as below table.

Solar Panel Spec. (reference)SOLAR INPUT (Min in serial: 6 pcs, max. in serial: 12 pcs)Q'ty of panelsTotal input power
250Wp, Vmp: 30.1Vdc, Imp: 8.3A, Voc: 37.7Vdc, Isc: 8.4A, Cells: 602 pcs in serial2 pcs500W
6 pcs in serial6 pcs1500W
8 pcs in serial8 pcs2000W
12 pcs in serial12 pcs3000W
13 pcs in serial13 pcs3250W
8 pieces in serial and 2 sets in parallel16 pcs4000W
10 pieces in serial and 2 sets in parallel20 pcs5000W

Please follow below steps to implement PV module connection:

  1. Remove insulation sleeve 10 mm for positive and negative conductors.
  2. Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
Solar Panel Wiring in Series
Solar Panel Wiring in Series: Example for increasing voltage.
Solar Panel Wiring in Series/Parallel
Solar Panel Wiring Methods: Series for voltage increase, Parallel for current increase.

3. Make sure the wires are securely connected.

4.7 Final Assembly

After connecting all wirings, put the bottom cover back by screwing two screws.

5. Operation

5.1 Power ON/OFF

Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

5.2 Operation and Display Panel

The operation and display panel, shown below, is on the front panel of the inverter. It includes three indicators, four function keys and an LCD display, indicating the operating status and input/output power information.

LCD Display and Function Keys
LCD Display and Function Keys: Overview of the inverter's control panel.

LED Indicator:

LED IndicatorColorStateMessages
AC/INVGreenSolid OnOutput is powered by utility in Line mode.
FlashingOutput is powered by battery or PV in battery mode.
CHGGreenSolid OnBattery is fully charged.
FlashingBattery is charging.
FAULTRedSolid OnFault occurs in the inverter.
FlashingWarning condition occurs in the inverter.

Function Keys:

Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

5.3 LCD Display Icons

The LCD display provides various icons to indicate input source, configuration, output information, and battery status.

LCD Function Description
LCD Function Description: Detailed explanation of each icon on the display.

Input Source Information:

IconFunction description
ACIndicates the AC input.
PVIndicates the PV input.
888.8Indicate input voltage, input frequency, PV voltage, battery voltage and charger current.

Configuration Program and Fault Information:

IconFunction description
88Indicates the setting programs.
88.8Indicates the warning and fault codes.
Warning: 88.8 (flashing)Flashing with warning code.
Fault: 88.8 (lighting)Lighting with fault code.

Output Information:

IconFunction description
888.8Indicate output voltage, output frequency, load percent, load in VA, load in Watt and discharging current.

Battery Information:

IconFunction description
CHARGINGIndicates battery level by 0-24%, 25-49%, 50-74% and 75-100% in battery mode and charging status in line mode.

In AC mode, it will present battery charging status.

StatusBattery voltageLCD Display
Constant Current mode<2V/cell4 bars will flash in turns.
2 ~ 2.083V/cellBottom bar will be on and the other three bars will flash in turns.
Constant Voltage mode2.083 ~ 2.167V/cellBottom two bars will be on and the other two bars will flash in turns.
> 2.167 V/cellBottom three bars will be on and the top bar will flash.
Floating modeBatteries are fully charged.4 bars will be on.

In battery mode, it will present battery capacity.

Load PercentageBattery VoltageLCD Display
Load >50%< 1.717V/cell
1.717V/cell ~ 1.8V/cell
1.8 ~ 1.883V/cell
> 1.883 V/cell
50%> Load > 20%< 1.817V/cell
1.817V/cell ~ 1.9V/cell
1.9 ~ 1.983V/cell
> 1.983
Load < 20%< 1.867V/cell
1.867V/cell ~ 1.95V/cell
1.95 ~ 2.033V/cell
> 2.033

Load Information:

IconFunction description
OverloadIndicates overload.
Load Level (0-100%)Indicates the load level by 0-24%, 25-50%, 50-74% and 75-100%.

Mode Operation Information:

IconFunction description
Mains connectionIndicates unit connects to the mains.
PV panel connectionIndicates unit connects to the PV panel.
BYPASSIndicates load is supplied by utility power.
Utility chargerIndicates the utility charger circuit is working.
DC/AC inverterIndicates the DC/AC inverter circuit is working.

Mute Operation:

IconFunction description
MuteIndicates unit alarm is disabled.

5.4 LCD Setting

After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press "UP" or "DOWN" button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to exit.

Setting Programs:

ProgramDescriptionSelectable option
00Exit setting modeEscape (00 ESC)
01Output source priority: To configure load power source priority
  • 01 SU6 (default): Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, utility energy will supply power to the loads at the same time.
  • 01 S60: Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time.
  • Utility priority: Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or the setting point in program 12.
02Maximum charging current: To configure total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current)10A, 20A, 30A, 40A, 50A, 60A, 70A, 80A (default), 90A, 100A, 110A
03AC input voltage range
  • 03 APL (Appliances, default): If selected, acceptable AC input voltage range will be within 90-280VAC.
  • 03 UPS (UPS): If selected, acceptable AC input voltage range will be within 170-280VAC.
04Power saving mode enable/disable
  • 04 Sd5 (Saving mode disable, default): If disabled, no matter connected load is low or high, the on/off status of inverter output will not be effected.
  • 04 SEN (Saving mode enable): If enabled, the output of inverter will be off when connected load is pretty low or not detected.
05Battery type
  • 05 AGO (AGM, default)
  • 05 FLd (Flooded)
  • 05 USE (User-Defined): If "User-Defined" is selected, battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29.
06Auto restart when overload occurs
  • 06 Ltd (Restart disable, default)
  • 06 LHE (Restart enable)
07Auto restart when over temperature occurs
  • 07 ttd (Restart disable, default)
  • 07 tHE (Restart enable)
08Output voltage
  • 08 220 (220V)
  • 08 230 (230V, default)
  • 08 240 (240V)
09Output frequency
  • 09 50 (50Hz, default)
  • 09 60 (60Hz)
11Maximum utility charging current10A, 20A, 30A, 40A, 50A, 60A, 70A, 80A
12Setting voltage point back to utility source when selecting "SBU priority"Available options in 24V models: 22.0V, 22.5V, 23.0V (default), 23.5V, 24.0V, 24.5V, 25.0V, 25.5V. Available options in 48V models: 44V, 45V, 46V (default), 47V, 48V, 49V, 50V, 51V.
13Setting voltage point back to battery mode when selecting "SBU priority"Available options in 24V models: Battery fully charged, 24V, 24.5V, 25V, 25.5V, 26V, 26.5V, 27V (default), 27.5V, 28V, 28.5V, 29V. Available options in 48V models: Battery fully charged, 48V, 49V, 50V, 51V, 52V, 53V, 54V (default), 55V, 56V, 57V, 58V.
16Charger source priority: To configure charger source priority
  • 16 C50 (Solar first): Solar energy will charge battery as first priority. Utility will charge battery only when solar energy is not available.
  • 16 SNU (Solar and Utility, default): Solar energy and utility will charge battery at the same time.
  • 16 050 (Only Solar): Solar energy will be the only charger no matter utility is available or not. If this inverter/charger is working in Battery mode or Power saving mode, only solar energy can charge battery. Solar energy will charge battery if it's available and sufficient.
18Alarm control
  • 18 600 (Alarm on, default)
  • 18 LOF (Alarm off)
19Auto return to default display screen
  • 19 ESP (Return to default display screen, default): If selected, no matter how users switch display screen, it will automatically return to default display screen (Input voltage /output voltage) after no button is pressed for 1 minute.
  • 19 HEP (Stay at latest screen): If selected, the display screen will stay at latest screen user finally switches.
20Backlight control
  • 20 LON (Backlight on, default)
  • 20 LOF (Backlight off)
22Beeps while primary source is interrupted
  • 22 AON (Alarm on, default)
  • 22 AOF (Alarm off)
23Overload bypass: When enabled, the unit will transfer to line mode if overload occurs in battery mode.
  • 23 69d (Bypass disable, default)
  • 23 69E (Bypass enable)
25Record Fault code
  • 25 FEN (Record enable)
  • 25 Fd5 (Record disable, default)
26Bulk charging voltage (C.V voltage)24V model default setting: 28.2V. 48V model default setting: 56.4V. If user-defined battery type is selected (program 05), setting range is from 24.0V to 29.2V for 24V model and 48.0V to 58.4V for 48V model. Increment of each click is 0.1V. 24V model default to 27.0V.
27Floating charging voltage48V model default setting: 54.0V. If user-defined battery type is selected (program 05), setting range is from 24.0V to 29.2V for 24V model, 48.0V to 58.4V for 48V model. Increment of each click is 0.1V.
29Low DC cut-off voltage24V model default setting: 21.0V. 48V model default setting: 42.0V. If user-defined battery type is selected (program 05), setting range is from 20.0V to 24.0V for 24V model, 40.0V to 48.0V for 48V model. Increment of each click is 0.1V. Low DC cut-off voltage will be fixed to setting value no matter what percentage of load is connected.
31Solar power balance: When enabled, solar input power will be automatically adjusted according to connected load power
  • Enable (default): If selected, solar input power will be automatically adjusted according to the following formula: Max. input solar power = Max. battery charging power + Connected load power.
33Battery equalizationIf "Flooded" or "User-Defined" is selected in program 05, this program can be set up.
34Battery equalization voltage3.8KW default setting: 29.2V. 6.0KW default setting: 58.4V. Setting range is from 24V to 29.5V (24V models) and 50V to 59V (48V models). Increment of each click is 0.1V.
35Battery equalized time60min (default). Setting range is from 5min to 900min. Increment of each click is 5min.
36Battery equalized timeout120min (default). Setting range is from 5min to 900 min. Increment of each click is 5 min.
37Equalization interval30days (default). Setting range is from 0 to 90 days. Increment of each click is 1 day.
39Equalization activated immediately
  • Enable: If equalization function is enabled in program 33, this program can be set up. If "Enable" is selected in this program, it's to activate battery equalization immediately and LCD main page will show "EQ".
  • Disable (default): If "Disable" is selected, it will cancel equalization function until next activated equalization time arrives based on program 37 setting. At this time "EQ" will not be shown in LCD main page.

5.5 Display Setting

The LCD display information will be switched in turns by pressing "UP" or "DOWN" key. The selectable information is switched as below order: input voltage, input frequency, PV voltage, MPPT charging current, MPPT charging power, battery voltage, output voltage, output frequency, load percentage, load in VA, load in Watt, DC discharging current, main CPU Version and second CPU Version.

Selectable information and LCD display:

Selectable informationLCD display
Input voltage/Output voltage (Default Display Screen)Input Voltage=230V, output voltage=230V
Input frequencyInput frequency=50Hz
PV voltagePV voltage=360V
MPPT Charging currentCurrent ≥ 10A or Current < 10A
MPPT Charging powerMPPT charging power=500W
Battery voltage/ DC discharging currentBattery voltage=25.5V, discharging current=1A
Output frequencyOutput frequency=50Hz
Load percentageLoad percent=70%
Load in VAWhen connected load is lower than 1kVA, load in VA will present xxxVA. When load is larger than 1kVA, load in VA will present x.xkVA.
Load in WattWhen load is lower than 1kW, load in W will present xxxW. When load is larger than 1kW, load in W will present x.xkW.
Main CPU version checkingMain CPU version SR 26.00

5.6 Operating Mode Description

Operation modeDescriptionLCD display
Standby mode / Power saving modeNo output is supplied by the unit but it still can charge batteries.Charging by utility and PV energy. Charging by utility. Charging by PV energy. No charging.
Fault modeErrors are caused by inside circuit error or external reasons such as over temperature, output short circuited and so on. PV energy and utility can charge batteries.Charging by utility and PV energy. Charging by utility. Charging by PV energy. No charging.
Line ModeThe unit will provide output power from the mains. It will also charge the battery at line mode.Charging by utility and PV energy. Charging by utility.
Battery ModeThe unit will provide output power from battery and PV power.Power from battery and PV energy. Power from battery only.

5.7 Battery Equalization Description

Equalization function is added into charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize battery periodically.

How to Apply Equalization Function:

You must enable battery equalization function in monitoring LCD setting program 33 first. Then, you may apply this function in device by either one of following methods:

  1. Setting equalization interval in program 34.
  2. Active equalization immediately in program 39.

When to Equalize:

In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter Equalize stage.

Equalize charging time and timeout:

In Equalize stage, the controller will supply power to charge battery as much as possible until battery voltage raises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.

However, in Equalize stage, when battery equalized time is expired and battery voltage doesn't rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.

6. Troubleshooting

6.1 Fault Reference Code:

Fault CodeFault EventIcon on
01Fan is locked when inverter is off.01
02Over temperature02
03Battery voltage is too high03
04Battery voltage is too low04
05Output short circuited or over temperature is detected by internal converter components.05
06Output voltage is too high.06
07Overload time out07
08Bus voltage is too high08
09Bus soft start failed09
11Main relay failed11
51Over current or surge51
52Bus voltage is too low52
53Inverter soft start failed53
55Over DC voltage in AC output55
56Battery connection is open56
57Current sensor failed57
58Output voltage is too low58

6.2 Warning Indicator:

Warning CodeWarning EventAudible AlarmIcon flashing
01Fan is locked when inverter is on.Beep three times every second01
03Battery is over-chargedBeep once every second03
04Low batteryBeep once every second04
07OverloadBeep once every 0.5 second07
10Output power deratingBeep twice every 3 seconds10
12Solar charger stops due to low battery.12
13Solar charger stops due to high PV voltage.13
14Solar charger stops due to overload.14

6.3 Troubleshooting Guide:

ProblemLCD/LED/BuzzerExplanation / Possible causeWhat to do
Unit shuts down automatically during startup process.LCD/LEDs and buzzer will be active for 3 seconds and then complete off.The battery voltage is too low (<1.91V/Cell)1. Re-charge battery. 2. Replace battery.
No response after power on.No indication.1. The battery voltage is far too low. (<1.4V/Cell) 2. Battery polarity is connected reversed.1. Check if batteries and the wiring are connected well. 2. Re-charge battery. 3. Replace battery.
Input voltage is displayed as 0 on the LCD and green LED is flashing.Input protector is trippedCheck if AC breaker is tripped and AC wiring is connected well.
Mains exist but the unit works in battery mode.Green LED is flashing.Insufficient quality of AC power. (Shore or Generator)1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS→Appliance)
Green LED is flashing.Set "Solar First" as the priority of output source.Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly.LCD display and LEDs are flashingBattery is disconnected.Check if battery wires are connected well.
Fault code 07Overload error. The inverter is overload 110% and time is up.Reduce the connected load by switching off some equipment.
Buzzer beeps continuously and red LED lights up.Output short circuited.Check if wiring is connected well and remove abnormal load.
Fault code 05Temperature of internal converter component is over 120°C.Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Fault code 02Internal temperature of inverter component is over 100°C.Return to repair center.
Fault code 03Battery is over-charged.Check if spec and quantity of batteries meet requirements.
The battery voltage is too high.Replace the fan.
Fault code 01Fan fault1. Reduce the connected load. 2. Return to repair center.
Fault code 06/58Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac)Return to repair center.
Fault code 08/09/53/57Internal components failed.Restart the unit, if the error happens again, please return to repair center.
Fault code 51Over current or surge.If the battery is connected well, please return to repair center.
Fault code 52Bus voltage is too low.
Fault code 55Output voltage is unbalanced.
Fault code 56Battery is not connected well or fuse is burnt.

7. Specifications

The SUMRY SP Series Hybrid Solar Inverter is available in various models, each with specific technical parameters to suit different power requirements. Below are the detailed specifications for Line Mode, Inverter Mode, Charge Mode, and General Specifications.

Product Parameters Table
Product Parameters: Overview of different SP series models including rated power, MAX PV array power, surge power, and MAX charging current.

7.1 Line Mode Specifications:

INVERTER MODEL3.8KW 24V6.2KW 48V
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS)
90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS);
100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionLine mode: Circuit Breaker
Battery mode: Electronic Circuits
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS);
20ms typical (Appliances)

7.2 Inverter Mode Specifications:

INVERTER MODEL3.8KW 24V6.2KW 48V
Rated Output Power4.2KVA/3.8KW7.0KVA/6.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency60Hz or 50Hz
Peak Efficiency94%
Overload Protection5s@≥150% load; 10s@110%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage24Vdc48Vdc
Cold Start Voltage23.0Vdc46.0Vdc
Low DC Warning Voltage @load < 20%22.0Vdc44.0Vdc
@20% ≤ load < 50%21.4Vdc42.8Vdc
@load ≥ 50%20.2Vdc40.4Vdc
Low DC Warning Return Voltage @load < 20%23.0Vdc46.0Vdc
@20% ≤ load < 50%22.4Vdc44.8Vdc
@load ≥ 50%21.2Vdc42.4Vdc
Low DC Cut-off Voltage @load < 20%21.0Vdc42.0Vdc
@20% ≤ load < 50%20.4Vdc40.8Vdc
@load ≥ 50%19.2Vdc38.4Vdc
High DC Recovery Voltage29Vdc58Vdc
High DC Cut-off Voltage31Vdc62Vdc
No Load Power Consumption<25W<50W
Saving Mode Power Consumption<10W<15W

7.3 Charge Mode Specifications:

Utility Charging Mode:

INVERTER MODEL3.8KW 24V6.2KW 48V
Charging Current (UPS) @Nominal Input Voltage80A80A
Bulk Charging Voltage (Flooded Battery)29.258.4
Bulk Charging Voltage (AGM / Gel Battery)28.256.4
Floating Charging Voltage27Vdc54Vdc
Charging Algorithm3-Step

Solar Charging Mode:

INVERTER MODEL3.8KW 24V6.2KW 48V
Rated Power6000W6000W
PV Charge Current110A110A
Efficiency98.0% max.
Max. PV Array Open Circuit Voltage450Vdc
PV Array MPPT Voltage Range55-450Vdc
Min battery voltage for PV charge
Standby Power Consumption2W
Battery Voltage Accuracy+/-0.3%
PV Voltage Accuracy+/-2V
Charging Algorithm3-Step

7.4 General Specifications:

INVERTER MODEL3.8KW 24V6.2KW 48V
Safety CertificationCE
Operating Temperature Range0°C to 55°C
Storage temperature-15°C~60°C
Dimension (D*W*H), mm423.4*290.4*100.7(mm)423.4*290.4*115.7(mm)
Net Weight, kg6.8KG7.8KG

8. User Tips

  • Battery Requirement: The SUMRY SP Series Hybrid Solar Inverter requires a connected battery to operate. It cannot function without a battery.
  • WIFI Monitoring: For remote monitoring, ensure you download the SmartESS app for iOS or Android using the provided QR codes.
  • Inductive Loads: For running inductive loads for extended periods, it is recommended to use a pure sine wave inverter.
  • Sizing: Ensure the inverter's power rating is higher than the appliance you intend to power (at least 10% to 20% more than the maximum load). If running multiple appliances simultaneously, refer to the total wattage.

9. Frequently Asked Questions (FAQ)

Q: Does this inverter work without batteries?
A: No, the SUMRY SP Series Hybrid Solar Inverter requires a battery to operate. It must run with a connected battery.

10. Warranty and Support

For warranty information, technical support, or service inquiries, please contact your local SUMRY dealer or authorized service center. Keep your purchase receipt and product serial number handy for all support requests.

A user manual in PDF format is available for download: User Manual (PDF)