SUMRY MPS VIII ECO

Contents

SUMRY Hybrid Inverter User Manual

Models: 3.6KW / 4.2KW / 6.2KW (MPS VIII ECO Series)

Version: 1.0

1. Introduction

This manual describes the assembly, installation, operation, and troubleshooting of the SUMRY Hybrid Inverter. This multi-function inverter/charger combines the functions of an inverter, solar charger, and battery charger to provide uninterruptible power support in a compact size. Its comprehensive LCD display allows for user-configurable and easy-accessible button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.

1.1 Features

  • Pure sine wave inverter
  • Configurable input voltage range for home appliances and personal computers via LCD setting
  • Configurable battery charging current based on applications via LCD setting
  • Configurable AC/Solar Charger priority via LCD setting
  • Compatible with mains voltage or generator power
  • Auto restart while AC is recovering
  • Overload/Over temperature/short circuit protection
  • Smart battery charger design for optimized battery performance
  • Cold start function
  • WIFI/GPRS (Optional)

1.2 Basic System Architecture

The inverter/charger is designed to integrate with a generator or utility power source and PV modules. It can power various appliances in home or office environments, including motor-type appliances like tube lights, fans, refrigerators, and air conditioners.

Basic System Architecture Diagram

Figure 1: Basic System Architecture showing solar panels, inverter, battery, generator/utility, and home appliances.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  3. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  4. CAUTION – Only qualified personnel can install this device with battery. NEVER charge a frozen battery.
  5. For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  6. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  7. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for the details.
  8. One piece of 150A fuse is provided as over-current protection for the battery supply.
  9. GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
  10. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
  11. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

3. Setup and Installation

This section provides detailed instructions for unpacking, preparing, mounting, and connecting your SUMRY Hybrid Inverter.

3.1 Unpacking and Inspection

Before installation, carefully inspect the unit. Ensure that nothing inside the package is damaged. The package should contain the unit itself and a user manual.

3.2 Preparation

Before connecting any lines, remove the screws under the machine and detach the bottom cover plate.

3.3 Mounting the Unit

Consider the following points when selecting an installation location:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level to allow the LCD display to be read easily.
  • For proper air circulation and heat dissipation, allow a clearance of approximately 20 cm to the sides and 50 cm above and below the unit.
  • The ambient temperature should be between 0°C and 55°C for optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.
  • Ensure sufficient space around the machine for adequate heat dissipation and wire removal.

WARNING: Suitable for mounting on concrete or other non-combustible surface only.

Install the unit by screwing two M6 screws.

3.4 Battery Connection

CAUTION: For safety and regulation compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. It is crucial to use appropriate cable sizes for battery connection to reduce the risk of injury.

WARNING! All wiring must be performed by qualified personnel.

Recommended battery cable size:

ModelWire SizeCable (mm²)Torque value (max)
3.6KW/4.2KW/6.2KW1 x 2AWG252 Nm

Steps for battery connection:

  1. Remove 18 mm of insulation sleeve for positive and negative conductors.
  2. Suggest putting bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Connect all battery packs as shown in the diagram below.
  4. Insert the battery wires flatly into the inverter's battery connectors and tighten the bolts with a torque of 2 Nm in a clockwise direction. Ensure correct polarity. Recommended tool: #2 Pozi Screwdriver.
Battery Compatibility Diagram

Figure 2: Inverter compatibility with various battery types (Flooded, Gel, Lithium-iron phosphate, Lithium-ion, AGM/Sealed, User custom Battery).

WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.

CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).

3.5 AC Input/Output Connection

CAUTION: Before connecting to AC input power source, install a separate AC breaker between the inverter and the AC input power source. This ensures secure disconnection during maintenance and over-current protection. Recommended AC breaker specs: 32A for 3.6KW/4.2KW and 50A for 6.2KW.

CAUTION: There are two terminal blocks with “IN” and “OUT” markings. Do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, use the proper recommended cable size as below.

Suggested cable requirement for AC wires:

ModelGaugeCable (mm²)Torque Value
3.6KW/4.2KW12 AWG41.2 Nm
6.2KW10 AWG61.2 Nm

Steps for AC input/output connection:

  1. Before making AC input/output connection, open the DC protector or disconnector first.
  2. Remove 10mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3 mm.
  3. Insert AC input wires according to polarities (L→LINE (brown or black), N→Neutral (blue)) indicated on the terminal block and tighten the terminal screws.
  4. WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.
  5. Then, insert AC output wires according to polarities indicated on the terminal block and tighten terminal screws.
  6. Make sure the wires are securely connected.

Video: Product unboxing and demonstration of wiring connections for AC input/output, PV, and battery.

3.6 PV Connection

CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, use the proper recommended cable size as below.

Recommended PV module cable size:

ModelWire SizeCable (mm²)Torque value (max)
3.6KW/4.2KW/6.2KW1 x 12AWG41.2 Nm

PV Module Selection: When selecting proper PV modules, consider the following parameters:

  1. Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
  2. Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
INVERTER MODEL3.6KW/4.2KW6.2KW
Max. PV Array Open Circuit Voltage500Vdc
PV Array MPPT Voltage Range60Vdc~450Vdc

PV Module Wire Connection:

  1. Remove 10 mm of insulation sleeve for positive and negative conductors.
  2. Suggest putting bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Check correct polarity of wire connection from PV modules and PV input connectors. Connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector. Recommended tool: 4mm blade screwdriver.

3.7 Final Assembly

After connecting all wirings, replace the bottom cover by screwing the two screws back as shown in the unpacking section.

3.8 Communication Connection

The inverter supports Wi-Fi and GPRS cloud communication options for monitoring and control.

  1. Wi-Fi Cloud Communication (Option): Use the supplied communication cable to connect to the inverter and Wi-Fi module. Download the APP from the APP store and refer to the "Wi-Fi Plug Quick Installation Guideline" to set up the network and register. The inverter status will be shown on your mobile phone APP or computer webpage.
  2. GPRS Cloud Communication (Option): Use the supplied communication cable to connect to the inverter and GPRS module, then apply external power to the GPRS module. Download the APP from the APP store and refer to the "GPRS RTU Quick Installation Guideline" to set up the network and register. The inverter status will be shown on your mobile phone APP or computer webpage.

3.8.1 Battery Communication

Communication between the battery and the inverter is realized through the battery communication interface, allowing the inverter and lithium battery to exchange information (Baud rate: 9600).

If using a lithium battery with the inverter, only lithium batteries matched with BMS communication protocol are allowed.

  1. Connect the battery according to the recommended battery cable specifications.
  2. Insert the ring terminal of the battery cable into the inverter's battery connector flatly, ensuring bolts are tightened with a torque of 2-3 Nm. Ensure correct polarities.
  3. Connect one side of the RJ45 cable to the BMS communication port of the inverter.
  4. Insert the other side of the RJ45 cable into the RS485 communication port on the lithium battery.

NOTE:

  • If you choose a lithium battery, ensure to connect the battery and inverter with a BMS communication cable and select the battery type as "LIB-485" mode.
  • In "LIB-485" mode, press and hold the "ESC" button to view lithium battery information. The inverter display screen will show total battery voltage and remaining battery capacity.
  • Press the "DOWN" button to display data such as battery charging current, discharge current, rated battery capacity, battery charge cycles, minimum/maximum MOS temperature, single battery cell voltage, and battery cell temperature.

Communication And Setting Of Lithium Battery:

  1. Connect the RJ45 communication cable between the inverter and battery. Confirm that the lithium battery BMS port's PIN corresponds with the inverter BMS communication port.

Inverter BMS port PIN definition:

Pin numberPort definitions
1RS485B
2RS485A
3NG
4NG
5NG
6NG
7RS485A
8RS485B
Dual Communication Ports Diagram

Figure 3: Dual Communication Ports for Battery and WiFi communication.

CAUTION: When the battery type is set to "LIB-485", the setting items 12, 13, and 29 are displayed in percentage. The user cannot modify the maximum charging current. If communication fails, the inverter will cut off the output.

4. Operating Instructions

4.1 Power ON/OFF

Once the unit is properly installed and batteries are connected, simply press the On/Off switch (located on the button of the case) to turn on the unit.

4.2 Operation and Display Panel

The front panel of the inverter features an operation and display panel, including three indicators, four function keys, and an LCD display, which show the operating status and input/output power information.

LCD Display and Function Buttons

Figure 4: LCD Display, LED Indicators, and Function Buttons.

LED Indicator Messages:

LED IndicatorColorDescriptionMessages
INV/ACGreenSolid On
Flashing
Output is powered by utility in Line mode.
Output is powered by battery or PV in battery mode.
CHGGreenSolid On
Flashing
Battery is fully charged.
Battery is charging.
FAULTRedSolid On
Flashing
Fault occurs in the inverter.
Warning condition occurs in the inverter.

Function Keys:

Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

4.3 LCD Display Icons

The LCD display uses various icons to convey information about the inverter's status and operation.

Input Source Information:

  • AC Input Icon Indicates the AC input.
  • PV Input Icon Indicates the PV input.
  • Input Voltage/Frequency Icon Indicates input voltage, input frequency, PV voltage, charger current (if PV in charging for 3.6KW models), charger power, battery voltage.

Configuration Program and Fault Information:

  • Setting Programs Icon Indicates the setting programs.
  • Warning/Fault Codes Icon Indicates the warning and fault codes.
  • Flashing Warning Code Icon Warning: Flashing with warning code.
  • Lighting Fault Code Icon Fault: Lighting with fault code.

Output Information:

  • Output Voltage/Frequency Icon Indicates output voltage, output frequency, load percent, load in VA, load in Watt, and discharging current.

Battery Information:

  • Battery Icon (Battery status is indicated here)

Load Information:

  • Overload Icon Indicates overload.

Mode Operation Information:

  • Mains Connection Icon Indicates unit connects to the mains.
  • PV Panel Connection Icon Indicates unit connects to the PV panel.
  • Utility Power Supply Icon Indicates load is supplied by utility power.
  • Utility Charger Working Icon Indicates the utility charger circuit is working.
  • DC/AC Inverter Working Icon Indicates the DC/AC inverter circuit is working.

Mute Operation:

  • Mute Alarm Icon Indicates unit alarm is disabled.

4.4 LCD Setting

After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use the “UP” or “DOWN” buttons to select setting programs, then press "ENTER" to confirm or "ESC" to exit. Key settings include:

  • Program 00: Exit setting mode (Escape, One-button restore setting options).
  • Program 01: Output source priority (Utility first, Solar first, SBU priority, MKS priority).
  • Program 02: Maximum charging current (10A to 120A options).
  • Program 03: AC input voltage range (Appliances, UPS).
  • Program 05: Battery type (AGM, Flooded, User Defined, LIB-485).
  • Program 06: Auto restart when overload occurs.
  • Program 07: Auto restart when over temperature occurs.
  • Program 09: Output frequency (50Hz, 60Hz).
  • Program 10: Output voltage (220V, 230V, 240V).
  • Program 11: Maximum utility charging current.
  • Program 12: Setting voltage point back to utility source when selecting "SBU priority" or "Solar first".
  • Program 13: Setting voltage point back to battery mode when selecting "SBU priority" or "Solar first".
  • Program 16: Charger source priority (Solar first, Solar and Utility, Only Solar).
  • Program 18: Alarm control (Alarm on, Alarm off).
  • Program 19: Auto return to default display screen.
  • Program 20: Backlight control (Backlight on, Backlight off).
  • Program 22: Beeps while primary source is interrupted (Alarm on, Alarm off).
  • Program 23: Overload bypass (Bypass disable, Bypass enable).
  • Program 25: Record Fault code (Record enable, Record disable).
  • Program 26: Bulk charging voltage (C.V voltage).
  • Program 27: Floating charging voltage.
  • Program 29: Low DC cut-off voltage.
  • Program 30: Battery equalization (Enable, Disable).
  • Program 31: Battery equalization voltage.
  • Program 33: Battery equalized time.
  • Program 34: Battery equalized timeout.
  • Program 35: Equalization interval.
  • Program 36: Equalization activated immediately.
  • Program 37: GRID-tie operation (Off grid, Hybrid).
  • Program 38: GRID-tie current.
  • Program 39: Led pattern light.
  • Program 41: Dual output (disable, use).
  • Program 42: Enter the dual output functional voltage point.
  • Program 43: Lithium battery protocol (PYLON, PACE).
  • Program 44: Delayed grid access (disable, enable).
  • Program 45: Maximum Second Load.

4.5 Operating Mode Description

The inverter can operate in different modes:

  • Standby Mode: The inverter is not turned on, but it can still charge batteries without AC output.
  • Line Mode: The unit provides output power from the mains and charges the battery.
  • Grid-Tie Operation: When working in Grid-Tie mode, the unit will flash every 3 seconds.
  • Battery Mode: The unit provides output power from the battery and solar power.

4.6 Battery Equalization

The equalization function reverses the buildup of negative chemical effects like stratification and removes sulfate crystals from battery plates, which can reduce battery capacity. It is recommended to equalize the battery periodically.

How to Apply Equalization Function:

Enable battery equalization in LCD setting program 30. Then, activate it by either:

  1. Setting the equalization interval in program 35.
  2. Activating equalization immediately in program 36.

When to Equalize:

In float stage, when the setting equalization interval is reached or equalization is active immediately, the controller will enter the Equalize stage.

Equalize Charging Time and Timeout:

In Equalize stage, the controller supplies power to charge the battery until it reaches the equalization voltage. Constant-voltage regulation maintains this voltage. The battery remains in Equalize stage until the set equalized time is reached. If the battery voltage doesn't rise to the equalization voltage point within the set time, the charge controller extends the equalized time. If the battery voltage is still lower than the equalization voltage when the equalized timeout setting is over, the charge controller stops equalization and returns to float stage.

4.7 Mains and Lithium Battery Activation Function

  1. After 90 seconds of mains power connection to the inverter, the machine connects to the mains and starts to work.
  2. If the inverter is in lithium battery mode (item 05 is Llb or Llb-485), and the mains are connected but the battery is not, the mains activation function is automatically enabled.

5. Maintenance

5.1 Clearance and Maintenance for Anti-Dust Kit

Every inverter comes with an anti-dust kit installed from the factory. This kit helps the inverter automatically detect and adjust internal temperature and prevents dust, increasing product reliability.

  1. Step 1: Loosen the screw in a counterclockwise direction on the top of the inverter.
  2. Step 2: Remove the dustproof case and take out the air filter foam.
  3. Step 3: Clean the air filter foam and dustproof case. After cleaning, re-assemble the dust-kit back to the inverter.

NOTICE: The anti-dust kit should be cleaned every one month.

6. Troubleshooting

This section provides information on fault reference codes, warning indicators, and a troubleshooting table to help diagnose and resolve common issues.

6.1 Fault Reference Code

When a fault occurs, the LCD display will show a specific fault code.

Fault CodeFault EventIcon on
01Fan is locked when inverter is off.01 ERROR
02Over temperature02 ERROR
03Battery voltage is too high03 ERROR
04Battery voltage is too low04 ERROR
05Output short circuited or over temperature is detected by internal converter components.05 ERROR
06Output voltage is too high.06 ERROR
07Overload time out07 ERROR
08Bus voltage is too high08 ERROR
09Bus soft start failed09 ERROR
51Over current or surge51 ERROR
52Bus voltage is too low52 ERROR
53Inverter soft start failed53 ERROR
55Over DC voltage in AC output55 ERROR
57Current sensor failed57 ERROR
58Output voltage is too low58 ERROR
59PV voltage is over limitation59 ERROR

6.2 Warning Indicator

The inverter provides audible alarms and flashing icons for various warning conditions.

Warning CodeWarning EventAudible AlarmIcon flashing
01Fan is locked when inverter is on.Beep three times every second01
03Battery is over-chargedBeep once every second03
04Low batteryBeep once every second04
07OverloadBeep once every 0.5 second07
10Output power deratingBeep twice every 3 seconds10
15PV energy is low.Beep twice every 3 seconds15
E9Battery equalizationNoneE9
bPBattery is not connectedNonebP

6.3 Troubleshooting Table

ProblemLCD/LED/BuzzerExplanation / Possible causeWhat to do
Unit shuts down automatically during startup process.LCD/LEDs and buzzer will be active for 3 seconds and then complete off.The battery voltage is too low (<1.91V/Cell)1. Re-charge battery.
2. Replace battery.
No response after power on.No indication.1. The battery voltage is far too low. (<1.4V/Cell)
2. Internal fuse tripped.
1. Contact repair center for replacing the fuse.
2. Re-charge battery.
3. Replace battery.
Input voltage is displayed as 0 on the LCD and green LED is flashing.Input protector is trippedCheck if AC breaker is tripped and AC wiring is connected well.
Mains exist but the unit works in battery mode.Green LED is flashing.Insufficient quality of AC power. (Shore or Generator)1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS/Appliance)
Green LED is flashing.Set "Solar First" as the priority of output source.Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly.LCD display and LEDs are flashingBattery is disconnected.Check if battery wires are connected well.
Buzzer beeps continuously and red LED is on.Fault code 07Overload error. The inverter is overload 110% and time is up.Reduce the connected load by switching off some equipment.
Output short circuited.Check if wiring is connected well and remove abnormal load.
Fault code 05Temperature of internal converter component is over 120°C.Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Fault code 02Internal temperature of inverter component is over 100°C.Return to repair center.
Fault code 03Battery is over-charged.Check if spec and quantity of batteries are meet requirements.
The battery voltage is too high.
Fault code 01Fan faultReplace the fan.
Fault code 06/58Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac)1. Reduce the connected load.
2. Return to repair center
Fault code 08/09/53/57Internal components failed.Return to repair center.
Fault code 51Over current or surge.Restart the unit, if the error happens again, please return to repair center.
Fault code 52Bus voltage is too low.
Fault code 55Output voltage is unbalanced.

7. Specifications

7.1 Line Mode Specifications

INVERTER MODEL3.6KW4.2KW6.2KW
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS); 90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS); 100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)

7.2 Inverter Mode Specifications

INVERTER MODEL3.6KW4.2KW6.2KW
Rated Output Power3.6KW4.2KW6.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency50Hz
Peak Efficiency93%
Overload Protection3s@≥150% load; 5s@101%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage24Vdc48Vdc
Cold Start Voltage23.0Vdc46.0Vdc
Low DC Warning Voltage @load < 50%22.0Vdc44.0Vdc
Low DC Warning Voltage @load ≥ 50%21.0Vdc42.0Vdc
Low DC Warning Return Voltage @load < 50%22.5Vdc45.0Vdc
Low DC Warning Return Voltage @load ≥ 50%22.0Vdc44.0Vdc
Low DC Cut-off Voltage @load < 50%20.5Vdc41.0Vdc
Low DC Cut-off Voltage @load ≥ 50%20.0Vdc40.0Vdc
High DC Recovery Voltage32Vdc62Vdc
High DC Cut-off Voltage33Vdc63Vdc
No Load Power Consumption30W35W50W

7.3 Two Load Output Power

INVERTER MODEL3.6KW4.2KW6.2KW
Full Load3600W4200W6200W
Maximum Main Load3600W4200W6200W
Second Load Range720W~2520W840W~2940W1240W~4340W
Main Load Cut Off Voltage22VDC44VDC
Main Load Return Voltage26VDC52VDC

7.4 Charge Mode Specifications

Utility Charging Mode

INVERTER MODEL3.6KW4.2KW6.2KW
Charging Algorithm3-Step
AC Charging Current (Max)100Amp (@VI/P=230Vac)
Bulk Charging Voltage (Flooded Battery)29.258.4
Bulk Charging Voltage (AGM / Gel Battery)28.256.4
Floating Charging Voltage27Vdc54Vdc

MPPT Solar Charging Mode

INVERTER MODEL3.6KW4.2KW6.2KW
Max. PV Array Power6200W6500W
Nominal PV Voltage240Vdc360Vdc
PV Array MPPT Voltage Range60Vdc~500Vdc
Max. PV Array Open Circuit Voltage500Vdc
Max Charging Current (AC charger plus solar charger)120Amp120Amp120Amp

7.5 Grid-Tie Operation

INVERTER MODEL3.6KW4.2KW6.2KW
Nominal Output Voltage220/230/240 VAC
Feed-in Grid Voltage Range195~253VAC
Feed-in Grid Frequency Range50±1Hz/60±1Hz
Nominal Output Current15.7A18.2A26.9A
Power Factor Range>0.99
Maximum Conversion Efficiency (DC/AC)97%

7.6 General Specifications

INVERTER MODEL3.6KW4.2KW6.2KW
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm358×442×116
Net Weight, kg8.08.08.9

8. User Tips

  • Voltage Selection: The SUMRY ECO series inverters are available in different voltage configurations (e.g., 110V, 120V, 220V). Always confirm the specific voltage model you have purchased to ensure compatibility with your electrical system and appliances. Refer to the product label and your order details.
  • Battery Type: Ensure your battery type (Flooded, Gel, Lithium-ion, AGM/Sealed, or custom) is correctly configured in the LCD settings (Program 05) for optimal performance and longevity.
  • Monitoring: Utilize the optional WiFi or GPRS module and the SmartESS App for remote monitoring and control of your inverter's status and performance.

9. Warranty and Support

All SUMRY products come with a 1-year warranty from the date of purchase. For any technical support or service inquiries, please contact your local dealer or service center. Our team aims to provide a 24-hour response time for customer queries.

Note: Only qualified service personnel should attempt repairs. Incorrect re-assembly or unauthorized service may void your warranty and pose safety risks.