1. Introduction
The Linecome 820 Series VFD AC Drive Driver is a versatile and reliable solution designed for driving and controlling asynchronous motors in various industrial applications. Featuring an advanced DSP chip and PID algorithm, this frequency converter delivers high performance and precision. It includes 15-speed segments, automatic programs, and frequency control capabilities, enhancing reliability, adaptability, and usability. This product is certified according to international standards, ensuring quality and safety.
Video: Overview of the Linecome 820 Series VFD AC Drive Driver, highlighting its features and applications.
2. Important Safety Warnings
Failure to follow these instructions may result in serious injury or death.
- Read the user's manual before the inverter is opened.
- Do not connect AC power to output terminals U, V, W.
- Ground (PE) must always be connected.
- Do not open this front cover while power is applied or within 10 minutes after power has been removed.

Image: Front panel of the VFD unit, showing critical safety warnings.
3. Specifications
General Specifications
| Attribute | Value |
|---|---|
| Name | General-purpose Frequency Converter |
| Model | LNC820-4T2500G/4T2800P |
| Brand | LINECOME |
| Material | Iron |
| Color | White grey |
| Power Range | 250kW |
| Input Voltage | Three phase 380V |
| Output Voltage | Three phase 380V |
| Output Frequency | 0-500Hz |
| Origin | Mainland China |
| Control Mode | V/F |
| Nominal Voltage | 380 V |
| Power Phase Number | Three Phase |
| Rated Power | 250KW |
| Place of Origin | Jiangsu, China |
| IP Level | IP20 |
| Size (L*W*H) | 862*600*455mm |
| Installation Size | 400*832mm |
| Weight | 134kg |
| Certification | CE, ISO |
| Customized | Yes |
| OEM | Accepted |
| MOQ | 1pcs |
| Display | LED Display |
Model-Specific Electrical Ratings
| Model | Input/Output Voltage (V) | Rated Power (kW) | Rated Input Current (A) | Rated Output Current (A) |
|---|---|---|---|---|
| LNC820-4T2500G/4T2800P | Three Phase 380V±15% / Three Phase 380V±15% | 250 | 468 | 465 |

Image: Model number explanation and power adaptation table for LNC820 series.

Image: Dimensional drawing of the VFD unit.
4. Key Features and Components
The Linecome 820 Series VFD AC Drive Driver is built with high-quality components to ensure stable performance and durability.

Image: Internal components and their features.
- Fan: Provides efficient cooling, dust-proof operation, and noise reduction.
- PCB Board: Features special protective paint for acid and alkali resistance and enhanced aging resistance.
- Control Board: Designed for low frequency, high torque applications, with automatic voltage regulation.
- Keypad: Simplified design for easy operation and clear digital display.

Image: High-quality components ensuring stable performance.
5. Installation and Setup
Installation of the VFD AC Drive Driver should be performed by qualified personnel only. Ensure all power is disconnected before beginning any installation or wiring procedures.
5.1 Mounting
- Mount the unit in a well-ventilated area, free from excessive dust, moisture, and corrosive gases.
- Ensure adequate clearance around the unit for proper airflow and heat dissipation. Refer to the dimensions (862x600x455mm) and installation size (400x832mm) for cabinet integration.
- Securely fasten the VFD to a stable surface using appropriate mounting hardware.
5.2 Wiring
- Power Input: Connect the three-phase 380V AC power supply to the R, S, T input terminals of the frequency converter.
- Motor Output: Connect the three-phase asynchronous motor to the U, V, W output terminals of the frequency converter.
- Grounding: The Ground (PE) terminal must always be connected to a reliable earth ground.
- Brake Unit: If a brake unit is used, connect it to the P+ and PB terminals.
- Ensure all wiring connections are tight and secure to prevent loose contacts and potential hazards.
- Verify correct voltage and current ratings for all connected components.
For detailed wiring diagrams and specific connection instructions, please consult the full user manual (PDF) which can be obtained from the manufacturer or seller.
6. Operation
The VFD features a simplified keypad and digital display for easy operation. After proper installation and power-up, the unit is ready for configuration and control.
6.1 Basic Control
- Use the keypad to set desired output frequency (0-500Hz) and other operational parameters.
- The VFD supports V/F control mode, suitable for general-purpose applications.
- Utilize the 15-speed segments and automatic programs for complex control sequences.
6.2 Advanced Functions
The advanced DSP chip and PID algorithm enable precise control and optimization for various motor loads. Refer to the comprehensive manual for detailed programming and parameter adjustments for specific application requirements.
7. Maintenance
Regular maintenance ensures the longevity and optimal performance of your Linecome VFD AC Drive Driver. Always disconnect power before performing any maintenance.
- Cleaning: Periodically clean the cooling fan and ventilation openings to prevent dust accumulation, which can lead to overheating.
- Inspection: Regularly inspect all wiring connections for tightness and signs of wear or damage.
- Environment: Ensure the operating environment remains within specified temperature and humidity ranges, and free from corrosive substances. The PCB board is designed with protective paint for acid and alkali resistance, but extreme conditions should be avoided.
- Firmware Updates: Check with the manufacturer for any available firmware updates to improve performance or address known issues.
8. Troubleshooting
This section provides general guidance for common issues. For complex problems, consult the full user manual or contact technical support.
Common Issues:
- No Power/Display: Check input power connections, fuses, and ensure the unit is properly grounded.
- Motor Not Running: Verify motor connections (U, V, W), check VFD output frequency settings, and ensure no fault codes are displayed.
- Overheating: Clean cooling fan and vents. Ensure adequate ventilation and ambient temperature.
- Fault Codes: Refer to the user manual for a list of fault codes and their corresponding troubleshooting steps.
9. User Tips
- Quality Assurance: The production process is ISO9001-certified with dedicated QC departments (IQC, IPQC, OQC, FQC) and fully automatic testing equipment. Each product has unique codes for traceability, ensuring high quality.
- Customization: The manufacturer offers customization options to meet specific requirements, leveraging patented appearance and a professional technical and quality management team.
- Voltage Support: The VFD supports various voltage configurations, including single-phase 220V input/output, single-phase 220V input/three-phase 220V output, three-phase 220V input/three-phase 220V output, single-phase 220V input/three-phase 380V output, and three-phase 380V input/three-phase 380V output.
10. Warranty and Support
The Linecome 820 Series VFD AC Drive Driver comes with an 18-month warranty.
For technical support, inquiries, or warranty claims, please contact the manufacturer or seller directly. You may reach out via:
- WhatsApp: +86 15211483492
- Email: 3251620464@qq.com
Please have your product model number (LNC820-4T2500G/4T2800P) and serial number ready when contacting support.
11. Typical Applications
The Linecome 820 Series VFD AC Drive Driver is suitable for a wide range of industrial applications, including but not limited to:
- Pumping Units
- Water Pumps
- Solar Energy Systems
- Conveyor Belts
- Textile Machines
- Printing and Dyeing Machines
- Crushers
- CNC Lathes
- Automated Workshops
- Compressors
- Industrial Equipment