1. Overview
This manual contains instructions and safety terms that users must adhere to in order to ensure safe operation and maintenance of the instrument. Please read these operating instructions carefully before using the instrument.
The symbol "Δ" on the instrument indicates that users must follow the relevant safety instructions in this manual. Pay special attention to the safety rules and warning notes in this manual to avoid electric shock and damage to the instrument.
The T60 series pointer-type insulation testers include models such as T6015, T6010, and T6005. These devices feature a modern design, compact size, and portability. They are fully functional, highly accurate, and easy to operate reliably. The T6015 supports 3-range insulation testing and AC/DC voltage testing, the T6005 supports 500V insulation testing, and the T6010 supports 1000V insulation testing. These products are suitable for measuring the insulation resistance of various electrical equipment and insulating materials, such as transformers, motors, cables, switches, and appliances. They are ideal for routine maintenance, testing, and verification of electrical equipment.

2. Panel Diagram

Panel Components:
- Charging indicator light.
- Work indicator light.
- Gear position rotary switch (T6015 model, not present on T6005/T6010).
- EARTH input terminal (connected to the ground terminal of the circuit under test).
- LINE input terminal (connected to the circuit under test).
- Test button.
- Pointer zero adjustment.
- Insulation meter reading dial.
3. Electrical Symbols
- ACV: AC voltage
- DCV: DC voltage
- Δ: Warning
- Δ: High Voltage Hazard
- Δ: Auto Discharge
- Δ: Low resistance alarm
- Δ: Withstand voltage test
4. Features
- Wide measurement range, the measurement range can reach up to 2000MΩ, which is convenient for users to choose.
- T6010 and T6005 can measure AC voltage below 500V, and T6015 can measure AC and DC voltage below 500V (full-scale linear indication).
- Low resistance buzzer alarm, when the measured resistance is less than the alarm setting value, reminds the user to pay attention.
- The working indicator lights include battery undervoltage status prompt (red light), automatic shutdown after 15 minutes (single green light on) and continuous working indication (double green lights on).
- Uses a 3.7V-18650 rechargeable battery and Type-C charging interface, which is convenient for users to use.
- The wider dial design provides a wider indication range and allows users to read values more accurately.
- Automatic discharge function: automatically enters the discharge state after shutdown to avoid electric shock caused by residual charge in the circuit.
- Strong output load capacity and large output short-circuit current (refer to technical indicators).
- Transistor withstand voltage measurement scale, directly reads the withstand voltage value (load voltage) of the material being tested.
5. Technical Specifications
- Power Supply: 1 x 3.7V 18650 rechargeable lithium battery.
- Dimensions: 161 x 96 x 45 mm.
- Weight: Approximately 534 g (including accessories).
- Environmental Conditions:
- Operating Temperature: 0°C-40°C, Relative Humidity <75% (non-condensing).
- Storage Temperature: -10°C-50°C, Relative Humidity <85%.
- Calibration Temperature: 23°C ±5°C, Relative Humidity <70%.

| Parameter | T6015 | T6005 | T6010 |
|---|---|---|---|
| Rated Test Voltage | 1000V, 500V, 100V | 500V | 1000V |
| Low-Resistance Alarm | <2MΩ, <1MΩ, <200kΩ | <2MΩ | <2MΩ |
| Transistor Withstand Voltage Test | 1000V, 500V, 100V | 500V | 1000V |
| Output Short-Circuit Current | Max 0.75 mA | Max 0.65 mA | Max 1.3 mA |
| Measurement Range | 0-2000MΩ | 0-1000MΩ | 0-2000MΩ |
| Measurement Accuracy | 1M-2000MΩ ±10% | 1M-1000MΩ ±10% | 1M-2000MΩ ±10% |
| Voltage Measurement Range | DCV500V, 50V; ACV500V (50HZ) | ACV500V (50HZ) | ACV500V (50HZ) |
| Insulation Test Output Voltage | 90%-120% of Rated Voltage | ||
| Discharge Resistance | 10MΩ | ||
| Voltage Measurement Error | ±5% (Full Scale) | ||
| Battery Detection | 3.3V Low Voltage Indication | ||
| Insulation | Between the movement circuit and the case: >50MΩ | ||
6. Setup and Operation
6.1 Insulation Resistance Measurement
6.1.1 Mechanical Zero Adjustment
Before starting insulation measurement, check whether the pointer is consistent with the "∞" (zero position on the left) mark on the insulation meter scale. If not, use a screwdriver to rotate the "pointer zero adjustment" on the meter to adjust the zero position.
6.1.2 Test Lead Connection
Insert the red and black test leads into the L and E ports of the meter respectively.

6.1.3 Insulation Measurement Start and Shutdown
Press and hold the "test button" for 1 second to turn on the meter. The green "working" indicator light on the upper right corner of the dial will light up. After normal startup, it will automatically shut down after 15 minutes. Press the "test button" three times within 5 seconds after powering on, the meter switches to continuous working state, and the two green indicators in the upper right corner light up, and the automatic shutdown function is canceled. You can manually shut down the meter 5 seconds after powering on, and press and hold for 1 second to shut down. When working in the undervoltage state, the working indicator light is red, and it will automatically shut down after 15 minutes.
6.1.4 Reading Insulation Measurement
After the insulation measurement is started, the test leads touch the insulator to be measured and read the measured value according to the pointer scale.
6.2 AC and DC Voltage Measurement
- The T6015 needs to be switched to the corresponding voltage range for measurement, while the T6010 and T6005 can be measured directly.
- Confirm that no insulation measurement has been started, i.e. the working indicator light is not on.
- Use the test leads to touch the two ends of the voltage to be measured.
- Read the measured value according to the pointer scale.
Note: When T6015 measures DC voltage, insert the red test lead into "+" and the black test lead into "-".

6.3 Transistor Withstand Voltage Measurement
- Connect the transistor to be tested to the meter according to polarity.
- Press the test button to directly read the BV(V) voltage scale. The read value is the withstand voltage of the transistor (the DC load voltage value L(V) at both ends of the material being tested).
- The maximum withstand voltage measurement value of T6015 and T6010 insulation meters is 1000V. The maximum withstand voltage measurement value of T6005 insulation meter is 500V.
6.4 Charging and Replacing Batteries
- To prevent electric shock, please remove the test leads from the instrument.
- When the instrument is working normally, the working indicator light is green, indicating that the battery is sufficient. When the working indicator light is red, it means that the battery power supply is undervoltage, prompting that charging or replacement of batteries is required.
- Use 5V USB power supply (including power bank and car charger, etc.), and the charging interface of the instrument is Type-C.
- The charging indicator light turns red during charging and automatically turns green when fully charged.
- Do not start the test during charging.
- If the battery fails, please replace it with a battery of the same specification.

7. Safety Rules and Precautions
- Read this manual carefully before use.
- Do not use the instrument if the battery cover is not securely closed, as this poses an electric shock hazard.
- Before use, ensure the test leads' insulation is intact and undamaged.
- To avoid damaging the instrument, perform insulation measurements only on disconnected circuits.
- Do not press the "Test Button" when measuring voltage.
- To avoid electric shock, do not touch the test leads or the circuit being tested during measurement.
- Avoid touching the tested circuit immediately after testing, as residual charge may cause electric shock.
8. Maintenance
This instrument is a precision electronic device and should be maintained with care.
- If the instrument is not used for an extended period, recharge it every two months.
- Store the instrument in a dry place and avoid humid environments.
- Avoid strong vibrations or impacts, as they may damage the meter head or circuitry.
- Do not modify the internal circuitry. If a malfunction occurs, contact us for assistance.
9. Package Contents
- T60 Series Insulation Resistance Tester x 1
- Portable Tool Bag x 1
- Insulation Resistance Tester Test Leads × 1 pair
- User Manual x 1 (Refer to the provided PDF for full details: User Manual PDF)
- 18650 Rechargeable Lithium Battery × 1
- USB Charging Cable × 1

10. User Tips
- This device is suitable for measuring the earth resistance of a house, providing a reliable tool for home electrical safety checks.
- Always perform the mechanical zero adjustment before critical insulation resistance measurements to ensure accuracy.
- The Type-C charging port makes it convenient to charge the device using common power banks or car chargers.
- Pay attention to the working indicator light: green indicates sufficient battery, red indicates low battery and prompts for charging.
- The magnetic back allows for convenient attachment to metal surfaces, freeing up hands during testing.