1. Introduction
This manual describes the assembly, installation, operation, and troubleshooting of the PowMr 4.2KW Hybrid Solar Inverter. Please read this manual carefully before installation and operation. This multi-function inverter/charger combines the functions of an inverter, solar charger, and battery charger to offer uninterruptible power support in a portable size. Its comprehensive LCD display provides user-configurable and easy-accessible button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
1.1 Features
- Pure sine wave inverter output.
- Configurable input voltage range for home appliances and personal computers via LCD setting.
- Configurable battery charging current based on applications via LCD setting.
- Configurable AC/Solar Charger priority via LCD setting.
- Compatible with mains voltage or generator power.
- Auto restart while AC is recovering.
- Overload, over temperature, and short circuit protection.
- Smart battery charger design for optimized battery performance.
- Cold start function.
- RS485 is used to communicate with BMS and adjust the charging current of the inverter according to battery demand.
- Can work with or without batteries.
- Intelligent fan speed adjustment, which adjusts the fan speed according to temperature, load, and charging current.
- Built-in MPPT, operating voltage range 55V~450V, open circuit voltage 500Voc.
- RGB lamp, which displays different colors according to inverter status.
- WIFI remote monitoring (optional).
- Offline upgrade function, firmware can be upgraded through COM port.
- Grid-connected capability.
- Built-in anti-dust kit for harsh environments.
- In battery-free mode, PV systems deliver a better user experience when powering loads.
- Equipped with lithium battery activation function.
1.2 Basic System Architecture
The following illustration shows a basic application for this inverter/charger. It can power various appliances in home or office environments, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners.

2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION – Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
3. Installation & Setup
3.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items:
- The unit x 1
- User manual x 1
3.2 Preparation
Before connecting all lines, remove the screws under the machine and remove the bottom cover plate.
3.3 Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level in order to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the side and approximately 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Make sure that other objects and surfaces are left with enough space from the machine to ensure adequate heat dissipation and that there is enough room to remove the wires.
WARNING: SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two screws. It's recommended to use M6 screws.
3.4 Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable as below.
Recommended battery cable size:
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 4.2KW/6.2KW | 1 x 2AWG | 25 | 2 Nm |
Please follow below steps to implement battery connection:
- Remove insulation sleeve 18 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Connect all battery packs as shown in the diagram.
- Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with a torque of 2 Nm in a clockwise direction. Make sure polarity at both the battery and the inverter/charger is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.

WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
3.5 AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between the inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from overcurrent of AC input. The recommended spec of AC breaker is 32A for 4.2KW and 50A for 6.2KW.
CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires:
| Model | Gauge | Cable (mm²) | Torque Value |
|---|---|---|---|
| 4.2KW | 12 AWG | 4 | 1.2 Nm |
| 6.2KW | 10 AWG | 6 | 1.2 Nm |
Please follow below steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
- Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. (L→LINE (brown or black), N→Neutral (blue))

WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
- Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. (L→LINE (brown or black), N→Neutral (blue))

6. Make sure the wires are securely connected.
CAUTION: Appliances such as air conditioners require at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check the manufacturer of the air conditioner if it's equipped with a time-delay function before installation. Otherwise, this inverter/charger will trigger an overload fault and cut off output to protect your appliance, but sometimes it still causes internal damage to the air conditioner.
Wiring Guide Video:
3.6 PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between the inverter and PV modules.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for PV wires:
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 4.2KW/6.2KW | 1 x 12AWG | 4 | 1.2 Nm |
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
- Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
| INVERTER MODEL | 4.2KW | 6.2KW |
|---|---|---|
| Max. PV Array Open Circuit Voltage | 500Vdc | |
| PV Array MPPT Voltage Range | 60Vdc~450Vdc | |
| IMax.PV | 27A | |
Please follow below steps to implement PV module connection:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Check correct polarity of wire connection from PV modules and PV input connectors. Then, connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector. Recommended tool: 4mm blade screwdriver.

3.7 Communication Connection
The communication between the battery and the inverter can be realized through the battery communication interface, so that the inverter and the lithium battery can exchange information (Baud rate: 9600).
Lithium battery and inverter connection:
If choosing a lithium battery for the inverter, only lithium batteries that have been matched with BMS communication protocol are allowed.
- Connect the battery according to the recommended battery cable specifications.
- Insert the ring terminal of the battery cable into the battery connector of the inverter flatly, and ensure that the bolts are tightened with a torque of 2-3 Nm. Make sure that the polarities of the battery and inverter are connected correctly, and that the ring terminal is tightened with the battery terminal.
- Connect one side of the RJ45 cable to the BMS communication port of the inverter.
- Insert the other side of the RJ45 cable into the RS485 communication port on the lithium battery.
NOTE: If you choose a lithium battery, please make sure to connect the battery and inverter with BMS communication cable, and select the battery type as "LIB-485" mode.
Communication And Setting Of Lithium Battery:
Connect the RJ45 communication cable between the inverter and battery. Please confirm that the lithium battery BMS port's PIN is correspond with the inverter BMS communication port. The inverter BMS port's PIN definition is as below:
| Pin number | Port definitions |
|---|---|
| 1 | RS485B |
| 2 | RS485A |
| 3 | NG |
| 4 | NG |
| 5 | NG |
| 6 | NG |
| 7 | RS485A |
| 8 | RS485B |

In order to communicate with the lithium battery BMS, you should press the "ENTER" button for a long time, and set the battery type as "LIB-485" in program 05. Then select the matching battery protocol in Program 43.
4. Operation
4.1 Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.
4.2 Operation and Display Panel
The operation and display panel, shown in the diagram below, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.

LED Indicators:
| LED Indicator | Color | Messages |
|---|---|---|
| INV/AC | Green | Solid On: Output is powered by utility in Line mode. Flashing: Output is powered by battery or PV in battery mode. |
| CHG | Green | Solid On: Battery is fully charged. Flashing: Battery is charging. |
| FAULT | Red | Solid On: Fault occurs in the inverter. Flashing: Warning condition occurs in the inverter. |
Function Keys:
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
4.3 LCD Display Icons
The LCD display provides various icons to indicate the status of the inverter. Here's a breakdown:
Input Source Information:
| Icon | Function description |
|---|---|
| AC input icon | Indicates the AC input. |
| PV input icon | Indicates the PV input. |
| 8.8.8 KW V Hz A | Indicates input voltage, input frequency, PV voltage, charger current, charger power, battery voltage. |
Configuration Program and Fault Information:
| Icon | Function description |
|---|---|
| 8.8.8 | Indicates the setting programs. |
| 8.8.8 | Indicates the warning and fault codes. |
| Warning: 8.8.8 | Flashing with warning code. |
| Fault: 8.8.8 | Lighting with fault code. |
Output Information:
| Icon | Function description |
|---|---|
| 8.8.8 KW VA % | Indicates output voltage, output frequency, load percent, load in VA, load in Watt, and discharging current. |
Battery Information:
| Icon | Function description |
|---|---|
| Battery icon | Indicates battery status. |
Load Information:
| Icon | Function description |
|---|---|
| OVER LOAD icon | Indicates overload. |
Mode Operation Information:
| Icon | Function description |
|---|---|
| Mains connection icon | Indicates unit connects to the mains. |
| PV panel connection icon | Indicates unit connects to the PV panel. |
| AC BYPASS icon | Indicates load is supplied by utility power. |
| Utility charger circuit icon | Indicates the utility charger circuit is working. |
| DC/AC inverter circuit icon | Indicates the DC/AC inverter circuit is working. |
Mute Operation:
| Icon | Function description |
|---|---|
| Mute icon | Indicates unit alarm is disabled. |
4.4 LCD Settings
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press the “UP” or “DOWN” button to select setting programs. Then, press the "ENTER" button to confirm the selection or the ESC button to exit.
The LCD allows configuration of various parameters including output source priority, charging current, input voltage range, power saving mode, battery type, auto restart settings, output frequency, output voltage, battery equalization settings, GRID-tie operation, and dual output function.
4.5 Operating Mode Description
The inverter supports various operating modes, including Standby mode, Line Mode, Grid-Tie operation, and Battery Mode. Each mode has specific behaviors regarding power flow and charging.
RGB Light (option):
- Inverter state: Green light
- Utility state: Blue light
- Failure state: Red light
4.6 Battery Equalization
Equalization function is added into the charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize the battery periodically.
How to Apply Equalization Function:
You must enable the battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in the device by either one of the following methods:
- Setting equalization interval in program 35.
- Active equalization immediately in program 36.
When to Equalize:
In the float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter the Equalize stage.

Equalize charging time and timeout:
In the Equalize stage, the controller will supply power to charge the battery as much as possible until the battery voltage raises to the battery equalization voltage. Then, constant-voltage regulation is applied to maintain the battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until the setting battery equalized time is arrived.
However, in the Equalize stage, when the battery equalized time is expired and the battery voltage doesn't rise to the battery equalization voltage point, the charge controller will extend the battery equalized time until the battery voltage achieves the battery equalization voltage. If the battery voltage is still lower than the battery equalization voltage when the battery equalized timeout setting is over, the charge controller will stop equalization and return to the float stage.
4.7 Mains and Lithium Battery Activation Function
- After 90s of mains power connection to the inverter, the machine is connected to the mains and starts to work.
- The inverter is in lithium battery mode (item 05 is Llb or Llb-485). After the mains is connected, the battery is not connected, and the mains activation function is automatically enabled.
5. Maintenance
5.1 Clearance and Maintenance for Anti-Dust Kit
Every inverter is already installed with an anti-dust kit from the factory. The inverter will automatically detect this kit and activate an internal thermal sensor to adjust the internal temperature. This kit also keeps dust out of your inverter and increases product reliability in harsh environments.
- Please loosen the screw in a counterclockwise direction on the top of the inverter.
- Then, the dustproof case can be removed, and the air filter foam can be taken out as shown in the diagram.

- Clean the air filter foam and dustproof case. After cleaning, re-assemble the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.
6. Troubleshooting
6.1 Fault Reference Code
If the inverter experiences an issue, a fault code may be displayed. Refer to the table below for common fault codes and their corresponding events and solutions.
| Fault Code | Fault Event | What to do |
|---|---|---|
| 01 | Fan is locked when inverter is off. | Replace the fan. |
| 02 | Over temperature | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. |
| 03 | Battery voltage is too high | Check if spec and quantity of batteries are meet requirements. |
| 04 | Battery voltage is too low | 1. Re-charge battery. 2. Replace battery. |
| 05 | Output short circuited or over temperature is detected by internal converter components. | Check if wiring is connected well and remove abnormal load. |
| 06 | Output voltage is too high. | Return to repair center. |
| 07 | Overload time out | Reduce the connected load by switching off some equipment. |
| 08 | Bus voltage is too high | Restart the unit, if the error happens again, please return to repair center. |
| 09 | Bus soft start failed | Restart the unit, if the error happens again, please return to repair center. |
| 51 | Over current or surge | Restart the unit, if the error happens again, please return to repair center. |
| 52 | Bus voltage is too low | Restart the unit, if the error happens again, please return to repair center. |
| 53 | Inverter soft start failed | Restart the unit, if the error happens again, please return to repair center. |
| 55 | Over DC voltage in AC output | Restart the unit, if the error happens again, please return to repair center. |
| 57 | Current sensor failed | Return to repair center. |
| 58 | Output voltage is too low | 1. Reduce the connected load. 2. Return to repair center. |
| 59 | PV voltage is over limitation | Return to repair center. |
6.2 Warning Indicator
The inverter provides warning indicators for various conditions. Refer to the table below for warning codes, events, audible alarms, and icon flashing patterns.
| Warning Code | Warning Event | Audible Alarm | Icon flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second | 01 (flashing) |
| 03 | Battery is over-charged | Beep once every second | 03 (flashing) |
| 04 | Low battery | Beep once every second | 04 (flashing) |
| 07 | Overload | Beep once every 0.5 second | 07 (flashing) |
| 10 | Output power derating | Beep twice every 3 seconds | 10 (flashing) |
| 15 | PV energy is low. | Beep twice every 3 seconds | 15 (flashing) |
| 16 | AC voltage is over limitation | Beep twice every 3 seconds | 16 (flashing) |
| E9 | Battery equalization | None | E9 (flashing) |
| 6P | Battery is not connected | None | 6P (flashing) |
7. Specifications
Detailed technical specifications for the PowMr 4.2KW Hybrid Solar Inverter are provided in the tables below.
7.1 Line Mode Specifications
| INVERTER MODEL | 4.2KW | 6.2KW |
|---|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) | |
| Nominal Input Voltage | 230Vac | |
| Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) | |
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) | |
| High Loss Voltage | 280Vac±7V | |
| High Loss Return Voltage | 270Vac±7V | |
| Max AC Input Voltage | 300Vac | |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | |
| Low Loss Frequency | 40±1Hz | |
| Low Loss Return Frequency | 42±1Hz | |
| High Loss Frequency | 65±1Hz | |
| High Loss Return Frequency | 63±1Hz | |
| Output Short Circuit Protection | Circuit Breaker | |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | |
7.2 Inverter Mode Specifications
| INVERTER MODEL | 4.2KW | 6.2KW |
|---|---|---|
| Rated Output Power | 4.2KW | 6.2KW |
| Output Voltage Waveform | Pure Sine Wave | |
| Output Voltage Regulation | 230Vac±5% | |
| Output Frequency | 50Hz | |
| Peak Efficiency | 93% | |
| Overload Protection | 3s@≥150% load; 30s@101%~150% load | |
| Surge Capacity | 2* rated power for 5 seconds | |
| Nominal DC Input Voltage | 24Vdc | 48Vdc |
| Cold Start Voltage | 23.0Vdc | 46.0Vdc |
| No Load Power Consumption | 25W | 50W |
| Saving Mode Power Consumption | < 10W | < 15W |
7.3 Two Load Output Power
| INVERTER MODEL | 4.2KW | 6.2KW |
|---|---|---|
| Full Load | 4200W | 6200W |
| Maximum Main Load | 4200W | 6200W |
| Second Load Range | 840W~2940W | 1240W~4340W |
| Main Load Cut Off Voltage | 22VDC | 44VDC |
| Main Load Return Voltage | 26VDC | 52VDC |
7.4 Charge Mode Specifications
| INVERTER MODEL | 4.2KW | 6.2KW |
|---|---|---|
| Utility Charging Mode | ||
| Charging Algorithm | 3-Step | |
| AC Charging Current (Max) | 100Amp | |
| Bulk Charging Voltage (Flooded Battery) | 29.2 | 58.4 |
| Bulk Charging Voltage (AGM / Gel Battery) | 28.2 | 56.4 |
| Floating Charging Voltage | 27Vdc | 54Vdc |
| MPPT Solar Charging Mode | ||
| Max. PV Array Power | 6200W | 8000W |
| Nominal PV Voltage | 240Vdc | 360Vdc |
| PV Array MPPT Voltage Range | 60Vdc~450Vdc | |
| Max. PV Array Open Circuit Voltage | 500Vdc | |
| Max Charging Current (AC charger plus solar charger) | 120Amp | |
7.5 General Specifications
| Parameter | Value |
|---|---|
| Safety Certification | CE |
| Operating Temperature Range | -10°C to 50°C |
| Storage temperature | -15°C~60°C |
| Humidity | 5% to 95% Relative Humidity (Non-condensing) |
| Dimension (D*W*H), mm | 423x344x112 |
| Net Weight, kg | 7.2 |
8. User Tips
- The inverter can operate without solar panels connected, relying on battery or AC input. This allows for flexible setup and use, even before a full solar array is installed.
- Always ensure all connections (battery, AC, PV) are secure and follow polarity guidelines to prevent damage and ensure safe operation.
- Regularly check the LCD display for any warning or fault codes and consult the troubleshooting section for appropriate actions.
9. Warranty & Support
All PowMr products come with a 1-year warranty from the date of purchase. For any service or repair needs, please contact your local dealer or an authorized service center. Do not attempt to disassemble the unit yourself, as this may void the warranty and pose a risk of electric shock or fire.