GEYA GPS6 Series

Contents

GEYA GPS6 Series Din Rail Adjustable Voltage/Current Protector User Manual

Models: GPS6-VA5, GPS6-VAK, GPS6-VAWIFI

Adjustable Overvoltage, Undervoltage, Overcurrent Protection Device

1. Introduction

The GEYA GPS6 series is a range of advanced Din Rail-mounted protection devices designed to safeguard electrical circuits and equipment from voltage and current anomalies. These devices offer adjustable overvoltage, undervoltage, and overcurrent protection, ensuring stable and reliable power supply. The series includes models with Kilowatt-hour (KWH) metering for energy consumption monitoring and Wi-Fi connectivity for remote control and smart home integration.

This manual provides detailed instructions for the installation, operation, and maintenance of your GEYA GPS6 device. Please read it thoroughly before use to ensure proper functionality and safety.

2. Safety Information

WARNING: Electrical shock hazard. Installation and maintenance should only be performed by qualified personnel.

  • Only trained and qualified professionals should install, operate, and maintain this equipment.
  • During installation, operation, and maintenance, all local safety codes and relevant operating procedures must be strictly observed. Failure to do so may result in personal injury or equipment damage.
  • The safety precautions mentioned in this instruction manual are intended only as a supplement to local safety codes. GEYA assumes no liability for any violation of general safety requirements or safety standards for the design, manufacture, and use of the equipment.
  • Ensure the power supply is disconnected before any installation or wiring work.

3. Product Overview

The GEYA GPS6 series offers different models to suit various protection and monitoring needs:

  • GPS6-VA5: Adjustable Overvoltage, Undervoltage, and Overcurrent Protection.
  • GPS6-VAK: Adjustable Overvoltage, Undervoltage, and Overcurrent Protection with KWH Measuring.
  • GPS6-VAWIFI: Adjustable Overvoltage, Undervoltage, Overcurrent, and Electric Leakage Protection with Wi-Fi and Bluetooth control for remote monitoring and management.

Front-face Panel Indicators:

  • `>V`: Overvoltage Indicator
  • `
  • `>A`: Overcurrent Indicator
  • `POWER`: Normal Working Indicator (Green for Normal operation, Red for Fault condition - Voltage/Current)

Control Buttons:

  • `SET`: Enters setting mode and confirms selections.
  • `▲` (Digit+/Up): Increases values or navigates up in menus.
  • `▼` (Digit-/Down): Decreases values or navigates down in menus.
  • `ON/OFF` (or Power button): Toggles the device power.
GEYA GPS6-VA5 Adjustable Voltage/Current Protector front view with specifications
Figure 1: GPS6-VA5 Front Panel and Key Specifications
GEYA GPS6-VA5 and GPS6-VAK models side-by-side showing digital displays
Figure 2: Comparison of GPS6-VA5 (Voltage & Current) and GPS6-VAK (Voltage & Current & KWH)

4. Specifications

Parameter GPS6-VA5 GPS6-VAK GPS6-VAWIFI
Type Mini
Model Number GPS6 Voltage / Current Protector GPS6 Voltage / Current / KWH GPS6-VAWIFI
Rated Supply Voltage AC220V; DC85~300V AC220V AC 220V (Range: AC 80V-300V)
Rated Frequency 40~70Hz 50~60Hz 50/60Hz
Overvoltage (>V) Setting Range AC130~300V; DC130~300V AC130~300V 230-300V (Default: 270V)
Undervoltage ( AC80~210V; DC85~210V AC80~210V 110-210V (Default: 170V)
Max Operating Current 40A, 63A, 80A (selectable models)
Overcurrent Setting Range 0.1A-100A (P-9) 0.1-63.0A (Default: 63A)
Voltage Hysteresis 5V N/A
Overvoltage Trip Delay 0.5s (P-3) 1-30S/OFF (Default: OFF)
Voltage Accuracy <1% N/A
Reset Time (Recovery Delay) 1~900s (factory default: 30s) (P-2) N/A
Max. Operating Phase Voltage 350V 400V (Rated peak insulation voltage)
Altitude ≤2000m
Permissible Relative Humidity ≤50% at 40°C (without condensation)
Ambient Temperature -25°C~+55°C -10°C~+60°C
Size (L*W*H) 81*36*66mm 85*36*65mm
Output Contacts N/A 1NO
Electrical Life N/A 105
Mechanical Life N/A 105
Protection Level N/A IP20
Storage Temperature N/A -10°C~+55°C
Electric Leakage Protection N/A 10-100mA (Default: 10mA)
Product dimensions showing height 86mm, width 38mm, and depth 67.5mm
Figure 3: Product Dimensions

5. Installation

The GEYA GPS6 series devices are designed for Din Rail mounting. Ensure the installation location is dry, well-ventilated, and free from excessive vibration or extreme temperatures.

Installation Steps:

  1. Ensure all power to the circuit is disconnected at the main breaker before beginning installation.
  2. Mount the device onto a standard 35mm Din Rail.
  3. Refer to the wiring diagram for correct connections.
  4. Connect the incoming Neutral (N) and Live (L) wires to the 'N' and 'L' terminals on the UP side of the device.
  5. Connect the outgoing Neutral (N) and Live (L) wires to the 'N' and 'L' terminals on the DOWN side of the device, leading to your load.
  6. Double-check all connections for tightness and correctness before restoring power.

6. Wiring Diagram

Wiring diagram showing a circuit breaker connected to the GEYA GPS6 device, which then connects to a load. N and L lines are clearly marked.
Figure 4: Standard Wiring Diagram for GPS6 Series

The diagram illustrates the connection of the GPS6 device in a single-phase circuit. The incoming power (N and L) connects to the upper terminals, and the protected load connects to the lower terminals. It is recommended to install a circuit breaker upstream of the protector for additional safety and isolation.

7. Operation

7.1. Initial Power-Up

After successful installation and wiring, restore power to the circuit. The device display will light up, showing real-time voltage and current readings. The POWER indicator will be green if operating normally.

7.2. Setting Parameters (GPS6-VA5 / GPS6-VAK)

To adjust protection parameters:

  1. Enter Setting Mode: Long press the `SET` button for approximately 5 seconds until the display changes to show parameter codes (e.g., P-1).
  2. Navigate Parameters: Use the `▲` (Up) and `▼` (Down) buttons to scroll through the parameter list (P-1 to P19).
  3. Select Parameter: Short press `SET` to select a parameter for adjustment. The value will start blinking.
  4. Adjust Value: Use the `▲` (Up) and `▼` (Down) buttons to change the value. Long press `▲` or `▼` for rapid adjustment.
  5. Save Setting: Short press `SET` again to confirm and save the new value. The display will return to the parameter code.
  6. Exit Setting Mode: Long press `SET` again, or wait for approximately 10 seconds of inactivity to automatically exit the setting mode.

Parameter List (GPS6-VA5 / GPS6-VAK):

  • `P-1`: Power-on delay time (Range: 1s-999s)
  • `P-2`: Recovery delay (Range: 1s-999s, factory default: 30s)
  • `P-3`: Overvoltage Setting (Range: AC130V-300V / DC130V-300V)
  • `P-4`: Overvoltage recovery value (Range: AC125V-295V / DC125V-295V)
  • `P-5`: Undervoltage Setting (Range: AC80V-210V / DC80V-210V)
  • `P-6`: Undervoltage recovery value (Range: AC85V-215V / DC85V-215V)
  • `P-7`: Voltage trip delay (Range: 0.1s-10s)
  • `P-8`: Voltage Correction (Range: -10%~+10%V)
  • `P-9`: Overcurrent Setting (Range: 0.1A-100A)
  • `P10`: Overcurrent trip delay (Range: 0.1s-10s)
  • `P11`: Overcurrent counter (Options: OFF, 0-20 times)
  • `P12`: Current adjustment (Range: -10%~+10%A)
  • `P13`: Frequency adjustment (Range: -2.5%~+2.5%Hz)
  • `P14`: Quick power down protection (Options: on/oFF)
  • `P15`: Display Mode Selection (1: Standard, 2: Manual, 3: Automatic)
    • Mode 2 (Manual): Press Up or Down button to display voltage (-U-), power (-P-), current (-A-), frequency (-H-).
    • Mode 3 (Automatic): Displays voltage (-U-), power (-P-), current (-A-), frequency (-H-) in turn.
  • `P16`: Automatic reset (Options: on/oFF)
  • `P17`: Switch mode (Options: On/oFF)
  • `P18`: Energy saving mode (Options: OFF/on/oFF)
  • `P19`: Password setting (Default: 112, Range: 000-999). Change the lock parameter after the initial password is changed. Set to initial password 112 to unlock.

Note: Under DC power, only voltage is displayed; current is not displayed.

7.3. Wi-Fi Control (GPS6-VAWIFI)

The GPS6-VAWIFI model offers remote control and monitoring via a smartphone application. This model also includes electric leakage protection.

Key Functions:

  • Remote control at any time from anywhere.
  • Schedule/Timer/Cycle Timer functions.
  • Energy monitoring (KWH).
  • Under voltage protection (110V-210V, adjustable, default: 170V).
  • Over voltage protection (230V-300V, adjustable, default: 270V).
  • Over current protection (0.1A-63A, adjustable, default: 63A).
  • Electric leakage protection (10-100mA, adjustable, default: 10mA).
  • Preset current/voltage thresholds by app: If real-time values reach thresholds, connected appliances will automatically turn off.

Network Connection (Smart Life App):

  1. Download App: Scan the QR code provided in the product packaging or search for "Smart Life" in your mobile application market (App Store/Google Play) to download and install the app.
  2. Prepare Device: Ensure your GPS6-VAWIFI device is powered on and in a network-ready state (often indicated by a blinking Wi-Fi LED).
  3. Connect Phone to Wi-Fi: Connect your mobile phone to your home Wi-Fi network (2.4GHz band is usually required).
  4. Register/Login: Open the "Smart Life" app, register a new account, or log in to an existing one.
  5. Add Device: In the app, click "Add Device" or the '+' icon. The system may automatically search for nearby devices.
  6. Select Device: Select your GPS6-VAWIFI device from the discovered list.
  7. Connect to Wi-Fi: The app will prompt you to select your home Wi-Fi network and enter the Wi-Fi password.
  8. Complete Setup: Follow the on-screen instructions to complete the pairing process. Once successfully added, you can use the app to control and monitor your device.

Parameter Settings via App (GPS6-VAWIFI):

Within the Smart Life app, you can access and modify the following parameters:

Option Option Code Setting Range Default Parameter
Over-voltage Uo 230-300V 270V
Under-voltage UL 110-210V 170V
Over-voltage delay ULt 1-30S/OFF OFF
Over-current Io 0.1-63.0A 63A
Leakage current Ir 10-100mA/OFF 10mA
Leakage current deviation value IrE -20-20mA 0mA
Over-current limit number Ioc 1-20/OFF OFF
Over-current delay Iot 1-30/OFF OFF
Power-on delay Irt 1-400S 5S
Cleanliness Clr 1-30000/OFF OFF

8. Troubleshooting

Problem Possible Cause Solution
Device not powering on/No display No power supply; Incorrect wiring; Device fault. Check main power supply. Verify N and L connections. If wiring is correct and power is present, contact support.
POWER indicator is Red Voltage or current fault detected (Overvoltage, Undervoltage, Overcurrent). Check the actual voltage/current of the circuit. Verify protection settings (P-3, P-5, P-9) are appropriate for your load. The device should automatically recover after the fault clears and recovery delay (P-2) expires.
Device trips frequently Protection settings are too sensitive; Unstable power supply; Overloaded circuit. Adjust protection thresholds (P-3, P-5, P-9) to be less sensitive if appropriate for your application. Check for power fluctuations. Reduce the load on the circuit.
Cannot enter setting mode SET button not held long enough; Device malfunction. Ensure you long-press the SET button for at least 5 seconds. If still unable, contact support.
GPS6-VAWIFI cannot connect to app Incorrect Wi-Fi password; 5GHz Wi-Fi network; Device not in pairing mode; App issues. Ensure correct Wi-Fi password. Use a 2.4GHz Wi-Fi network. Put the device into pairing mode (refer to app instructions). Restart the app and try again.

9. User Tips

  • Verify Settings: Always double-check your overvoltage, undervoltage, and overcurrent settings to ensure they match the requirements of your connected appliances and local electrical standards.
  • Recovery Delay: Utilize the recovery delay (P-2) to prevent rapid on/off cycling of equipment during transient power fluctuations, which can extend appliance lifespan.
  • Password Protection: For critical installations, consider setting a password (P19) to prevent unauthorized changes to the device's protection parameters.
  • Wi-Fi Signal (VAWIFI): For Wi-Fi models, ensure a strong 2.4GHz Wi-Fi signal at the installation location for reliable remote monitoring and control.
  • Load Matching: Select the appropriate current rating (40A, 63A, 80A) for your device based on the maximum expected load to ensure optimal protection and prevent nuisance tripping.

10. Maintenance

  • Regular Inspection: Periodically inspect the device and its connections for any signs of damage, loose wiring, or overheating.
  • Cleaning: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners.
  • Ventilation: Ensure adequate ventilation around the device to prevent overheating.
  • Firmware Updates (VAWIFI): For Wi-Fi models, check the Smart Life app periodically for any available firmware updates to ensure optimal performance and security.

11. Warranty and Support

Thank you for choosing GEYA products. We are committed to providing you with excellent products and support. For warranty information, technical assistance, or any inquiries regarding your GEYA GPS6 device, please refer to the official GEYA website or contact your local distributor.

A detailed user manual in PDF format is available for download: GEYA GPS6 User Manual (PDF)

GEYA company information including establishment year, turnover, product categories, and certifications like CE, CB, SAA, ISO9001, UKCA, RoHS.