PowMr POW 4.2KW/6.2KW

Contents

PowMr 4.2KW/6.2KW Hybrid Solar Inverter User Manual

Models: POW-HVM6.2M-48V-N, POW-HVM4.2M-24V-N, POW-HVM3.6M-24V-N

1. Introduction

This manual describes the assembly, installation, operation, and troubleshooting of the PowMr multi-function hybrid inverter/charger. This unit combines the functions of an inverter, solar charger, and battery charger to provide uninterruptible power support in a compact size. Its comprehensive LCD display allows for user-configurable and easily accessible button operations, including battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.

1.1. Key Features

  • Pure sine wave output.
  • Configurable input voltage range for home appliances and personal computers via LCD settings.
  • Configurable battery charging current based on applications via LCD settings.
  • Configurable AC/Solar Charger priority via LCD settings.
  • Compatible with mains voltage or generator power.
  • Automatic restart while AC is recovering.
  • Overload, over temperature, and short circuit protection.
  • Smart battery charger design for optimized battery performance.
  • Cold start function.
  • WIFI/GPRS communication (optional).
  • Can connect to lithium batteries.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION: Only qualified personnel can install this device with a battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow the required specifications to select appropriate cable sizes. It is very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Refer to the INSTALLATION section of this manual for details.
  10. One piece of 150A fuse is provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  12. NEVER cause AC output and DC input short-circuited. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to a local dealer or service center for maintenance.

3. Product Overview

The PowMr Hybrid Inverter is designed for various applications, including RVs, home storage, camping, and solar power systems. It features a smart protection system with multiple protection modes to ensure safe and reliable operation.

PowMr Hybrid Solar Inverter front view with specifications
Front view of the PowMr Hybrid Solar Inverter, highlighting its 6.2KW/4.2KW power, 500Vdc Max PV Array Voltage, 120A MPPT Solar Charge, and DC 24V(4.2KW)/48V(6.2KW) Battery Voltage.
6.2KW Hybrid Solar Inverter specifications
Detailed specifications for the 6.2KW Hybrid Solar Inverter, including 6.2KW AC Output Power, 120A Max AC Charging Current, 500Vdc Max PV Array Open Circuit Voltage, 150V Starting Voltage, and 50W No-load Power Consumption.
Smart Protection System diagram
Diagram illustrating the Smart Protection System with multiple protection modes, including charge low/high temperature, discharge low/high temperature, discharge overcurrent, charging overcurrent, charging undervoltage, short-circuit, solar panel reverse connection, battery overvoltage, over temperature, and overload protection.

3.1. Basic System Architecture

The following illustration shows a basic application for this inverter/charger. It includes a solar power source, the solar inverter, external battery packs, and home appliances, with an option for a generator or utility connection.

Hybrid Power System Diagram
Diagram showing the hybrid power system architecture, connecting solar power, the inverter, external battery packs, and home appliances, with an optional generator or utility input. The inverter can provide up to 4200W Max AC Power.

4. Installation

4.1. Unpacking and Inspection

Before installation, inspect the unit. Ensure that nothing inside the package is damaged. You should have received the following items:

  • The unit x 1
  • User manual x 1

4.2. Preparation

Before connecting any lines, remove the screws under the machine and remove the bottom cover plate.

4.3. Mounting the Unit

Consider the following points before selecting where to install:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level in order to allow the LCD display to be read at all times.
  • For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the side and approximately 50 cm above and below the unit.
  • The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.
  • Make sure that other objects and surfaces are left with enough space from the machine to ensure adequate heat dissipation and that there is enough room to remove the wires.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing two screws. It's recommended to use M6 screws.

4.4. Battery Connection

CAUTION: For safety operation and regulatory compliance, it is requested to install a separate DC over-current protector or disconnect device between the battery and inverter. It may not be required to have a disconnect device in some applications, however, it is still requested to have over-current protection installed. Refer to the typical amperage in the table below for required fuse or breaker size.

WARNING! All wiring must be performed by qualified personnel.

WARNING! It is very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce the risk of injury, please use the proper recommended cable as below.

Recommended Battery Cable Size
ModelWire SizeCable (mm²)Torque Value (max)
3.6KW/4.2KW/6.2KW1 x 2AWG252 Nm

Follow these steps to implement battery connection:

  1. Remove insulation sleeve 18 mm for positive and negative conductors.
  2. Suggest putting bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Connect all battery packs as shown in the diagram below.
  4. Insert the battery wires flatly into the battery connectors of the inverter and ensure the bolts are tightened with a torque of 2 Nm in a clockwise direction. Make sure polarity at both the battery and the inverter/charger is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.
Battery Connection Diagram
Diagram showing battery connections for 3.6KW/4.2KW and 6.2KW inverters, illustrating how multiple 12V batteries are connected in series to achieve the required 24V or 48V DC input.

WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.

CAUTION!! Before making the final DC connection or closing the DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).

4.5. AC Input/Output Connection

CAUTION!! Before connecting to an AC input power source, please install a separate AC breaker between the inverter and the AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from overcurrent of AC input. The recommended specification for the AC breaker is 32A for 3.6KW/4.2KW and 50A for 6.2KW.

CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by qualified personnel.

WARNING! It is very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce the risk of injury, please use the proper recommended cable as below.

Suggested Cable Requirement for AC Wires
ModelGaugeCable (mm²)Torque Value
3.6KW/4.2KW12 AWG41.2 Nm
6.2KW10 AWG61.2 Nm

Follow these steps to implement AC input/output connection:

  1. Before making AC input/output connection, be sure to open the DC protector or disconnector first.
  2. Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3 mm.
  3. Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. (L→LINE (brown or black), N→Neutral (blue)).
AC Input Wiring Diagram
Diagram illustrating the correct wiring for AC input, showing the connection points and the process of securing the wires.

WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.

  1. Then, insert AC output wires according to polarities indicated on the terminal block and tighten the terminal screws. (L→LINE (brown or black), N→Neutral (blue)).
  2. Make sure the wires are securely connected.

CAUTION: Appliances such as air conditioners require at least 2-3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check the manufacturer of the air conditioner if it's equipped with a time-delay function before installation. Otherwise, this inverter/charger will trigger an overload fault and cut off output to protect your appliance, but sometimes it still causes internal damage to the air conditioner.

4.6. PV Connection

CAUTION: Before connecting to PV modules, please install a separate DC circuit breaker between the inverter and PV modules.

WARNING! It is very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce the risk of injury, please use the proper recommended cable size as below.

Recommended Cable Requirement for PV Module Connection
ModelWire SizeCable (mm²)Torque Value (max)
3.6KW/4.2KW/6.2KW1 x 12AWG41.2 Nm

PV Module Selection:

When selecting proper PV modules, please be sure to consider the following parameters:

  1. Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
  2. Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
Inverter Model PV Specifications
INVERTER MODEL3.6KW/4.2KW6.2KW
Max. PV Array Open Circuit Voltage500Vdc
PV Array MPPT Voltage Range60Vdc~450Vdc

Follow these steps to implement PV module connection:

  1. Remove insulation sleeve 10 mm for positive and negative conductors.
  2. Suggest putting bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Check the correct polarity of wire connection from PV modules and PV input connectors. Then, connect the positive pole (+) of the connection wire to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection wire to the negative pole (-) of the PV input connector. Recommended tool: 4mm blade screwdriver.
PV Module Wire Connection Diagram
Diagram illustrating the correct wiring for PV module connection, showing the positive and negative terminals and the process of securing the wires.

4.7. Final Assembly

After connecting all wirings, please put the bottom cover back by screwing two screws.

4.8. Communication Connection

1. Wi-Fi Cloud Communication (Option):

Use the supplied communication cable to connect to the inverter and Wi-Fi module. Download the APP and install it from the APP store, and refer to the "Wi-Fi Plug Quick Installation Guideline" to set up the network and register. The inverter status will be shown by the mobile phone APP or computer webpage.

2. GPRS Cloud Communication (Option):

Use the supplied communication cable to connect to the inverter and GPRS module, and then apply external power to the GPRS module. Download the APP and install it from the APP store, and refer to the "GPRS RTU Quick Installation Guideline" to set up the network and register. The inverter status will be shown by the mobile phone APP or computer webpage.

3. Battery Communication

The communication between the battery and the inverter can be realized through the battery communication interface, allowing the inverter and the lithium battery to exchange information. Baud rate: 9600.

4. Lithium Battery and Inverter Connection:

Use power cables and communication cables for lithium batteries and inverters to connect.

Note: For lithium battery and inverter positive and negative positions, check the correct installation. The RJ45 connector of the communication cable connects to the BMS port of the inverter, and the other RJ45 connector connects to the RS485 port of the lithium battery. Before connecting, make sure the lithium battery and inverter are turned off. (It is recommended to install a circuit breaker for the power cables of the lithium battery and the inverter battery interface. Otherwise, a spark may occur.)

Lithium Battery Communication Diagram
Diagram illustrating the RJ45 connections for lithium battery communication, showing how the inverter's BMS port connects to the battery's RS485 port.

5. Operation

5.1. Power ON/OFF

Once the unit has been properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

5.2. Operation and Display Panel

The operation and display panel, located on the front panel of the inverter, includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.

LED Indicator Messages
LED IndicatorColorDescriptionMessages
INV/ACGreenSolid On
Flashing
Output is powered by utility in Line mode.
Output is powered by battery or PV in battery mode.
CHGGreenSolid On
Flashing
Battery is fully charged.
Battery is charging.
FAULTRedSolid On
Flashing
Fault occurs in the inverter.
Warning condition occurs in the inverter.
Function Keys
Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

5.3. LCD Display Icons

The LCD display provides various icons to indicate the inverter's status and operational information.

LCD Display Icons and Their Functions
IconFunction Description
AC Input IconIndicates the AC input.
PV Input IconIndicates the PV input.
Input/Output Voltage/Frequency/Current/PowerIndicates input voltage, input frequency, PV voltage, charger current (if PV in charging for 3.6KW models), charger power, battery voltage.
Setting Programs IconIndicates the setting programs.
Warning/Fault Codes IconIndicates the warning and fault codes. Flashing for warning, solid for fault.
Output InformationIndicates output voltage, output frequency, load percent, load in VA, load in Watt, and discharging current.
Battery InformationIndicates battery status.
Overload IconIndicates overload.
Mains Connection IconIndicates unit connects to the mains.
PV Panel Connection IconIndicates unit connects to the PV panel.
AC Bypass IconIndicates load is supplied by utility power.
Utility Charger Circuit IconIndicates the utility charger circuit is working.
DC/AC Inverter Circuit IconIndicates the DC/AC inverter circuit is working.
Mute Operation IconIndicates unit alarm is disabled.

5.4. LCD Setting

After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use the “UP” or “DOWN” buttons to select setting programs. Then, press the “ENTER” button to confirm the selection or the ESC button to exit.

The LCD settings allow configuration of various parameters, including:

  • Output Source Priority (Program 01): Configure how the load is powered (Utility first, Solar first, SBU priority, MKS priority).
  • Maximum Charging Current (Program 02): Set the total charging current for solar and utility chargers.
  • AC Input Voltage Range (Program 03): Define the acceptable AC input voltage range (Appliances or UPS).
  • Battery Type (Program 05): Select battery type (AGM, Flooded, User-Defined, LIB-485).
  • Auto Restart (Programs 06, 07): Enable/disable auto restart after overload or over temperature.
  • Output Frequency (Program 09): Set output frequency (50Hz/60Hz).
  • Output Voltage (Program 10): Set output voltage (220V/230V/240V).
  • Maximum Utility Charging Current (Program 11): Set the maximum charging current from utility.
  • Battery SOC Points (Programs 12, 13, 29): For LIB-485 mode, set battery SOC points for switching to utility/battery mode and low SOC shutdown.
  • Charger Source Priority (Program 16): Configure charger source priority (Solar first, Solar and Utility, Only Solar).
  • Alarm Control (Program 18): Enable/disable alarms.
  • Auto Return to Default Display Screen (Program 19): Set display behavior.
  • Backlight Control (Program 20): Turn backlight on/off.
  • Beeps while Primary Source is Interrupted (Program 22): Enable/disable beeps.
  • Overload Bypass (Program 23): Enable/disable transfer to line mode on overload.
  • Record Fault Code (Program 25): Enable/disable fault code recording.
  • Bulk Charging Voltage (Program 26): Set the bulk charging voltage (C.V voltage).
  • Floating Charging Voltage (Program 27): Set the floating charging voltage.
  • Low DC Cut-off Voltage (Program 29): Set the low DC cut-off voltage.
  • Battery Equalization (Program 30): Enable/disable battery equalization.
  • Battery Equalization Voltage (Program 31): Set the battery equalization voltage.
  • Battery Equalized Time (Program 33): Set the duration for battery equalization.
  • Battery Equalized Timeout (Program 34): Set the timeout for battery equalization.
  • Equalization Interval (Program 35): Set the interval between equalization cycles.
  • Equalization Activated Immediately (Program 36): Activate equalization immediately.
  • GRID-Tie Operation (Program 37): Select operation mode (Off grid, Hybrid).
  • GRID-Tie Current (Program 38): Set the GRID-Tie current.
  • Led Pattern Light (Program 39): Configure LED light pattern.
  • Dual Output (Program 41): Enable/disable dual output.
  • Dual Output Functional Voltage Point (Program 42): Set the voltage point for dual output function.
  • Lithium Battery Protocol (Program 43): Select lithium battery protocol (PYLON, PACE).
  • Delayed Grid Access (Program 44): Enable/disable delayed grid access.
  • Maximum Second Load (Program 45): Set the maximum second load percentage.

5.5. Operating Mode Description

The inverter supports various operating modes, each with specific behaviors for power supply and charging:

  • Standby Mode / Power Saving Mode: In standby, the inverter is not outputting but can charge batteries. In power saving mode, the output is off if the connected load is low.
  • Line Mode: The unit provides output power from the mains and charges the battery.
  • Grid-Tie Operation: When working in Grid-Tie mode, the unit can feed excess energy back to the grid.
  • Battery Mode: The unit provides output power from the battery and solar power.
Charging Mode Selection Diagram
Diagram illustrating different charging modes: Solar First (solar charges battery first, utility only when solar is unavailable), Solar and Utility (both charge battery simultaneously), and Only Solar Charging (solar is the only source, regardless of utility availability).
Charger and Output Source Priority Diagram
Diagram showing configurable charger source priorities (Utility/AC Power, Solar power, Solar+Utility, ONLY Solar) and output source priorities (Utility Source, Solar power, Solar+battery).

5.6. Battery Equalization

Battery equalization is a function added to the charge controller to reverse the buildup of negative chemical effects like stratification and to remove sulfate crystals from the plates. This process helps maintain the overall capacity of the battery and is recommended periodically.

How to Apply Equalization Function

You must enable the battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function by either:

  1. Setting the equalization interval in program 35.
  2. Activating equalization immediately in program 36.

When to Equalize

In the float stage, when the setting equalization interval (battery equalization cycle) is reached, or equalization is activated immediately, the controller will start to enter the Equalize stage.

Battery Equalization Diagram
Diagram illustrating the battery equalization process, showing the different stages: Bulk, Absorption, Float, and Equalize, and how voltage changes during these phases.

5.7. Mains and Lithium Battery Activation Function

  1. After 90 seconds of mains power connection to the inverter, the machine connects to the mains and starts to work.
  2. If the inverter is in lithium battery mode (item 05 is Llb or Llb-485), and the mains is connected but the battery is not, the mains activation function is automatically enabled.

6. Clearance and Maintenance for Anti-Dust Kit

6.1. Overview

Every inverter is already installed with an anti-dust kit from the factory. The inverter will automatically detect this kit and activate an internal thermal sensor to adjust the internal temperature. This kit also keeps dust out of your inverter and increases product reliability in harsh environments.

6.2. Clearance and Maintenance

  1. Step 1: Loosen the screw in a counterclockwise direction on the top of the inverter.
  2. Step 2: The dustproof case can then be removed, and the air filter foam taken out.
  3. Step 3: Clean the air filter foam and dustproof case. After cleaning, re-assemble the dust-kit back to the inverter.

NOTICE: The anti-dust kit should be cleaned from dust every one month.

7. Specifications

This section details the technical specifications for the PowMr Hybrid Inverter, covering line mode, inverter mode, two-load output power, MPPT solar charging, grid-tie operation, and general characteristics.

Table 1: Line Mode Specifications
INVERTER MODEL3.6KW4.2KW6.2KW
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS); 90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS); 100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)
Output Power Derating Graph
Graph showing output power derating: When AC input voltage drops to 170V, the output power will be derated.
Table 2: Inverter Mode Specifications
INVERTER MODEL3.6KW4.2KW6.2KW
Rated Output Power3.6KW4.2KW6.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency50Hz
Peak Efficiency93%
Overload Protection3s@≥150% load; 5s@101%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage24Vdc48Vdc
Cold Start Voltage23.0Vdc46.0Vdc
Low DC Warning Voltage @load < 50%22.0Vdc44.0Vdc
Low DC Warning Voltage @load ≥ 50%21.0Vdc42.0Vdc
Low DC Warning Return Voltage @load < 50%22.5Vdc45.0Vdc
Low DC Warning Return Voltage @load ≥ 50%22.0Vdc44.0Vdc
Low DC Cut-off Voltage @load < 50%20.5Vdc41.0Vdc
Low DC Cut-off Voltage @load ≥ 50%20.0Vdc40.0Vdc
High DC Recovery Voltage32Vdc62Vdc
High DC Cut-off Voltage33Vdc63Vdc
No Load Power Consumption30W35W50W
Table 3: Two Load Output Power
INVERTER MODEL3.6KW4.2KW6.2KW
Full Load3600W4200W6200W
Maximum Main Load3600W4200W6200W
Maximum Second Load (battery model)1400W1400W2066W
Main Load Cut Off Voltage26VDC52VDC
Main Load Return Voltage27VDC54VDC
Table 4: MPPT Solar Charging Mode
INVERTER MODEL3.6KW4.2KW6.2KW
Max. PV Array Power6200W6500W6500W
Nominal PV Voltage240Vdc360Vdc360Vdc
PV Array MPPT Voltage Range60Vdc~450Vdc90Vdc~500Vdc90Vdc~500Vdc
Max. PV Array Open Circuit Voltage500Vdc
Max Charging Current (AC charger plus solar charger)120Amp120Amp120Amp
Table 5: Grid-Tie Operation
INVERTER MODEL3.6KW4.2KW6.2KW
Nominal Output Voltage220/230/240 VAC
Feed-in Grid Voltage Range195~253VAC
Feed-in Grid Frequency Range50±1Hz/60±1Hz
Nominal Output Current15.7A18.2A26.9A
Power Factor Range>0.99
Maximum Conversion Efficiency (DC/AC)97%
Table 6: General Specifications
INVERTER MODEL3.6KW4.2KW6.2KW
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm358×442×116
Net Weight, kg8.08.08.9

8. Troubleshooting

This section provides guidance for common issues you might encounter with your PowMr Hybrid Inverter. Refer to the tables below for fault codes, warning indicators, and suggested solutions.

Fault Reference Code
Fault CodeFault EventIcon on
01Fan is locked when inverter is off.01 ERROR
02Over temperature02 ERROR
03Battery voltage is too high03 ERROR
04Battery voltage is too low04 ERROR
05Output short circuited or over temperature is detected by internal converter components.05 ERROR
06Output voltage is too high.06 ERROR
07Overload time out07 ERROR
08Bus voltage is too high08 ERROR
09Bus soft start failed09 ERROR
51Over current or surge51 ERROR
52Bus voltage is too low52 ERROR
53Inverter soft start failed53 ERROR
55Over DC voltage in AC output55 ERROR
57Current sensor failed57 ERROR
58Output voltage is too low58 ERROR
59PV voltage is over limitation59 ERROR
Warning Indicator
Warning CodeWarning EventAudible AlarmIcon flashing
01Fan is locked when inverter is on.Beep three times every second01
03Battery is over-chargedBeep once every second03
04Low batteryBeep once every second04
07OverloadBeep once every 0.5 second07
10Output power deratingBeep twice every 3 seconds10
15PV energy is low.Beep twice every 3 seconds15
E9Battery equalizationNoneE9
6PBattery is not connectedNone6P
Troubleshooting Guide
ProblemLCD/LED/BuzzerExplanation / Possible causeWhat to do
Unit shuts down automatically during startup process.LCD/LEDs and buzzer will be active for 3 seconds and then complete off.The battery voltage is too low (<1.91V/Cell)1. Re-charge battery.
2. Replace battery.
No response after power on.No indication.1. The battery voltage is far too low. (<1.4V/Cell)
2. Internal fuse tripped.
1. Contact repair center for replacing the fuse.
2. Re-charge battery.
3. Replace battery.
Input voltage is displayed as 0 on the LCD and green LED is flashing.Input protector is trippedCheck if AC breaker is tripped and AC wiring is connected well.
Mains exist but the unit works in battery mode.Green LED is flashing.Insufficient quality of AC power. (Shore or Generator)1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS/Appliance)
Green LED is flashing.Set "Solar First" as the priority of output source.Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly.LCD display and LEDs are flashingBattery is disconnected.Check if battery wires are connected well.
Fault code 07Overload error. The inverter is overload 110% and time is up.Reduce the connected load by switching off some equipment.
Fault code 05Output short circuited.Check if wiring is connected well and remove abnormal load.
Fault code 02Temperature of internal converter component is over 120°C. Internal temperature of inverter component is over 100°C.Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Buzzer beeps continuously and red LED is on.Fault code 03Battery is over-charged.Return to repair center.
Fault code 01Fan faultReplace the fan.
Fault code 06/58Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac)1. Reduce the connected load.
2. Return to repair center.
Fault code 08/09/53/57Internal components failed.Return to repair center.
Fault code 51Over current or surge.Restart the unit, if the error happens again, please return to repair center.
Fault code 52Bus voltage is too low.
Fault code 55Output voltage is unbalanced.

9. User Tips

  • Model Variants: The PowMr Hybrid Inverter comes in different models, specifically designed for either 24V or 48V battery systems (e.g., 4.2KW for 24V, 6.2KW for 48V). Ensure you select the correct model that matches your battery voltage. The inverter itself is configured for one or the other, not both simultaneously.
  • Battery Requirement: This inverter requires a connected battery to function. It is not designed to operate without a battery.
  • Generator Compatibility: The inverter is compatible with both mains voltage and standard generator power. This means it can work with a gasoline generator, not just an inverter generator, for charging or providing backup power.
  • Regular Maintenance: Clean the anti-dust kit monthly to ensure optimal performance and longevity of the inverter, especially in dusty environments.

10. Warranty and Support

For technical support, warranty claims, or service, please contact PowMr directly using the information below:

  • Company: SHENZHEN HEHEJIN INDUSTRIAL CO.,LTD
  • Tel/Fax: +86755-28219903
  • Email: support@powmr.com
  • Web: www.powmr.com
  • Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China

The final interpretation rights of this product belong to the company.

A detailed user manual in PDF format is also available for download. Please refer to the official product page or contact support for the link.