ECGSOLAX Ecg-hvm6.5k-48V

ECGSOLAX 6.5KW Solar Hybrid Inverter User Manual

Model: Ecg-hvm6.5k-48V

1. Introduction

This manual provides detailed instructions for the assembly, installation, operation, and maintenance of the ECGSOLAX 6.5KW Solar Hybrid Inverter. This multifunctional inverter integrates an MPPT solar charge controller, a high-frequency pure sine wave inverter, and a UPS function module. It is designed for off-grid backup power and self-consumption applications and can operate with or without batteries.

The inverter features a built-in WiFi module for remote monitoring, allowing users to check the status of their PV system via mobile phone or website anytime, anywhere. It supports both lead-acid and lithium batteries and offers various configurable charging and output modes.

Hybrid Power System Diagram
Figure 1: Hybrid Power System Diagram. This diagram illustrates how the solar inverter integrates solar power, a generator, utility grid, and battery to supply power to home appliances.

2. Safety Instructions

WARNING! This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  • Battery System: Be clear about the type of battery system (lithium or lead-acid) you are using. Choosing the wrong system will prevent normal operation.
  • Read Instructions: Before using, read all instructions and cautionary markings on the unit, batteries, and all sections of this manual. The manufacturer is not responsible for damage caused by non-compliance with these instructions.
  • Qualified Personnel: All operations and connections must be performed by professional electrical or mechanical engineers.
  • Electrical Standards: All electrical installations must comply with local electrical safety standards.
  • PV Module Installation: When installing PV modules during the daytime, cover them with opaque materials to prevent dangerous high terminal voltage.
  • Battery Type: To reduce injury risk, charge only deep-cycle lead-acid or lithium rechargeable batteries. Other battery types may burst.
  • Disassembly: Do not disassemble the unit. Refer to a qualified service center for repairs. Incorrect re-assembly may result in electric shock or fire.
  • Disconnect Wiring: Disconnect all wirings before maintenance or cleaning to reduce electric shock risk. Turning off the unit alone is not sufficient.
  • Frozen Battery: NEVER charge a frozen battery.
  • Cable Size: Follow required specifications for appropriate cable size for optimum inverter operation.
  • Metal Tools: Be cautious when working with metal tools near batteries to avoid short circuits or explosions.
  • AC/DC Disconnection: Strictly follow installation procedures when disconnecting AC or DC terminals.
  • Grounding: The inverter must be connected to a permanent grounded wiring system, complying with local requirements.
  • Short Circuits: NEVER cause AC output and DC input short circuits. Do NOT connect to the mains if DC input is short-circuited.
  • Assembly: Ensure the inverter is completely assembled before operation.

Label Description

The following symbols are used on the inverter and in this manual to ensure user safety:

  • ! WARNING! A high level of potential danger, which, if not avoided, could result in death or serious injury to personnel.
  • ! CAUTION! A moderate or low level of potential danger, which, if not avoided, could result in moderate or minor injuries to personnel. In some bad situations, it could result in death or serious injury to personnel.
  • 4 Danger: High Voltage! Danger: Electrical Hazard!
  • 5min Start maintaining the INVERTER at least 5 minutes after the INVERTER disconnected from all external power supplies.
  • Read instructions carefully before performing any operation on the INVERTER.
  • Grounding: The system must be firmly grounded for operator safety.

3. Setup (Installation)

3.1 Unpacking and Inspection

Products are strictly tested before leaving the factory. Upon receipt, inspect the product for any damage. If the product or packaging is damaged, contact your local distributor immediately. Open the box to check for internal equipment damage.3.2 Installation Tools

The following tools are recommended for installation:

ToolDescription
Multi-meterFor electrical measurements.
Protective glovesFor safety during handling.
Insulated anti-smashing shoesFor foot protection.
Safety glassesFor eye protection.
ESD wrist strapTo prevent electrostatic discharge.
Hammer drillFor drilling mounting holes.
Electric screwdriverFor tightening screws.
Cross screwdriverFor tightening screws.
Rubber malletFor gentle adjustments.
Spirit levelFor ensuring level installation.
Wire cutter / stripperFor preparing cables.
Terminal crimping toolFor securing cable terminals.

3.3 Mounting Unit

When selecting a mounting location, consider the following:

  • Do not mount on flammable construction materials.
  • Mount on a solid surface.
  • Install at eye level for easy LCD display readability.
  • Ambient temperature should be between -10°C and 60°C for optimal operation.
  • Adhere to vertical wall installation.
  • Ensure sufficient heat dissipation and space for wiring.

WARNING! Inverter is suitable for mounting on concrete or other non-combustible surfaces only.

Installation Steps:

  1. Use an Ø8 drilling bit to drill holes on the mounting surface. The distance between the two holes should be 200mm. Insert M6 expansion screw tubes.
  2. Pick up the inverter vertically and align the screw holes at the top with the installed expansion screw tubes. Fix the inverter to the mounting surface with screws.
  3. Before connecting any wiring, remove the bottom cover by unscrewing the four screws.
Inverter Mounting and Views
Figure 2: Multiple views of the inverter, showing mounting points and connections.

3.4 AC Input / Output Connection

CAUTION! Before connecting to the AC input power source, install a separate AC breaker (recommended 40A) between the inverter and the AC input source for safety and overcurrent protection.

CAUTION! Do NOT mis-connect input and output connectors. There are three terminal blocks: 'AC IN', 'AC OUT1', 'AC OUT2'.

CAUTION! Ensure correct AC cable polarity (L and N wires). Reversed connections can cause utility short-circuits in parallel operation.

WARNING! All wiring must be performed by qualified personnel.

WARNING! Use appropriate cable sizes for AC input/output connections to ensure system safety and efficient operation.

Recommended Cable Sizes:

ConnectionGaugeCable (mm²)
AC Input10 AWG5.26
AC Output12 AWG4

WARNING! Disconnect AC power before connecting to the unit. All electrical connection procedures must comply with local laws and regulations.

AC Input (AC IN) Connection Steps:

  1. Open the AC circuit breaker.
  2. Remove 12mm of insulation from cable ends, shorten conductor to 10mm. Insert into tubular terminal and crimp tightly.
  3. Insert AC input cables into terminal blocks according to polarities (PE: yellow-green, L: brown/black, N: blue) and tighten screws. Connect PE protective cable first.
  4. Ensure cables are securely connected.

AC Output (OUT1/OUT2) Connection: Follow the same steps as AC input connection for L (LINE) and N (Neutral) cables.

CAUTION! Appliances like air conditioners require a 2-3 minute restart delay to balance refrigerant gas. If a power shortage occurs and recovers quickly, it can damage connected appliances. Check if your air conditioner has a time-delay function. Otherwise, the inverter may trigger an overload fault.

3.5 PV Connection

CAUTION! Install a separate DC circuit breaker between the inverter and PV modules.

WARNING! Do not ground positive or negative terminals of PV modules, as this can severely damage the inverter.

WARNING! Exposure to sunlight can generate lethal high voltages in photovoltaic strings. Adhere to safety precautions in photovoltaic string documents.

WARNING! Connect PV terminals to corresponding ports on the inverter. Reversing polarity can damage the inverter.

WARNING! All wiring must be performed by qualified personnel.

WARNING! Use appropriate cable for PV module connection. Recommended cable size: 10AWG (5.26 mm²).

PV Module Selection Parameters:

  • Open circuit Voltage (Voc) of PV modules must not exceed the max PV array open circuit voltage of the inverter (500VDC).
  • Open circuit Voltage (Voc) of PV modules should be higher than the start-up voltage (60VDC).
  • PV Array MPPT Voltage Range: 60VDC~450VDC.

WARNING! Do not connect any DC switches or AC/DC circuit breakers before completing electrical connections.

PV Module Connection Steps:

  1. Open the DC circuit breaker.
  2. Remove 12mm of insulation from cable ends, shorten conductor to 10mm. Insert into tubular terminal and crimp tightly.
  3. Use a multi-meter to check polarities.
  4. Insert PV cables into terminal block according to polarities (PV+: red, PV-: black) and tighten screws.
  5. Ensure cables are securely connected.

3.6 Battery Connection

Users can choose a proper capacity 48V lead-acid battery. Select battery type as 'AGM' or 'FLD (flooded)'.

CAUTION! Install a separate DC over-current protector or disconnect device (recommended 150A) between the battery and inverter for safety and regulation compliance.

WARNING! All wiring must be performed by qualified personnel.

WARNING! Use appropriate cable for battery connection. Recommended cable size: 2 AWG (25 mm²).

WARNING! Disconnect AC power before connecting to the unit. All electrical connection procedures must comply with local laws and regulations.

Lead-acid Battery Connection Steps:

  1. Unscrew pre-fixed screws on battery poles. Prepare 2 DT terminals suitable for AWG2 cables.
  2. Remove 12mm of insulation from cable ends, shorten conductor to 10mm. Insert into DT terminal and crimp tightly.
  3. Pass battery cable through the battery installation hole on the bottom shell. Tighten terminal screws. Ensure correct polarity at both battery and inverter/charge, and DT terminals are tightly screwed to battery terminals.
  4. Connect all battery packs as required. A minimum 200Ah capacity battery is suggested.

WARNING! Shock Hazard. Installation must be performed with care due to high battery voltage in series.

CAUTION! Do not place anything between the flat part of the inverter terminal and the DT terminal. Overheating may occur.

CAUTION! Do not apply anti-oxidant substance on terminals before connecting them tightly.

CAUTION! Before final DC connection or closing DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).

3.7 Lithium Battery Connection

If using a lithium battery, check protocol compatibility first. The inverter has two connectors for lithium battery: RJ45 port for BMS and power cable.

Lithium Battery Connection Steps:

  1. Follow section 3.6 to connect the power cable.
  2. Connect the RJ45 terminal of the battery communication cable to the BMS communication port of the inverter. The communication protocol should be RS485 or CAN.
  3. Insert the other end of the RJ45 cable to the battery communication port of the lithium battery.

Note: If using a lithium battery, ensure the BMS communication cable is connected between the battery and the inverter.

Lithium Battery Communication and Setting:

  • Set the battery type to 'LIb' or 'FEL' in Program 17 (Section 4.2.2).
  • Ensure the lithium battery BMS port connects to the inverter is Pin to Pin.

Inverter BMS Port Pin Assignment:

Pin numberBMS port
1RS485B
2RS485A
3-
4CANH
5CANL
6-
7-
8-

Communicating with battery BMS in parallel system: If using BMS communication in a parallel system, connect the BMS communication cable between the battery and one inverter of the parallel system.

3.8 Final Assembly

After connecting all wiring, replace the bottom cover by screwing in the four screws mentioned in Section 3.3.

3.9 Smart Communication Stick Connection (Optional)

The smart communication stick (WiFi) connects to the cloud platform. Insert the stick directly into the COM port. For models with built-in WiFi, refer to the solar APP quick configuration guide.

4. Operation

4.1 Power ON/OFF

Once the unit is properly installed and batteries are connected, press the ON/OFF switch (located on the bottom of the case) to turn on the unit.

4.2 Operation and Display Panel

The operation and display panel on the front of the inverter includes four indicators, four function keys, and an LCD display to show operating status and input/output power information.

Function Buttons:

ButtonDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm selection in setting mode or enter setting mode

4.3 LCD Display Icons and Information

The LCD display provides various information about the inverter's status. The display information can be switched using the 'UP' or 'DOWN' keys. If there is no operation for a long time, the daily PV power generation will be displayed at the bottom of the screen.

Key Display Information:

  • Battery Information: Battery icon, battery type (AGM, FLD, USER, Li-ion), charging stages (CC, CV, FLOAT), battery voltage, charging/discharging current.
  • AC Input Information: AC input icon, UPS or APP input mode, AC input voltage and frequency.
  • PV Input Information: PV input icon, PV power, PV voltage, PV current.
  • Output Information: Output voltage, apparent power (VA or kVA), active power (W or kW), output frequency.
  • Battery Capacity: Battery capacity indicator.
  • Load Capacity: Load capacity indicator, overload icon.
  • AC Output 2 Information: Second AC output icon, AC output 2 voltage.
  • Parameter Query, Function Setting or Fault/Alarm Information: System information, function settings, fault/alarm indicators.
  • Other Information: Mute, WiFi connected, PV + Grid status.

4.4 LCD Setting

To enter setting mode, press and hold the ENTER button for 2 seconds. Use 'UP' or 'DOWN' to select programs, then 'ENTER' to confirm or 'ESC' to exit.

Key Settings:

  • Program 01: Output voltage (Default: 230V, Adjustable: 208V, 220V, 230V, 240V)
  • Program 02: Output frequency (Default: 50Hz, Adjustable: 50Hz, 60Hz)
  • Program 03: Output source priority (Grid first, Solar first, PBG priority, MKS)
  • Program 04: Input mode (APP: Appliance, UPS: Computer/devices, GEN: Generator)
  • Program 05: Charger source priority (PNG: PV and Grid, OPV: Only PV, PVF: PV first)
  • Program 06: Grid charging current (Default: 60A, Adjustable: 2A-120A)
  • Program 07: Maximum charging current (Default: 100A, Adjustable: 2A-120A)
  • Program 08: Menu Default (ON/OFF for auto-return to first page)
  • Program 09: Auto restart when overload occurs (ON/OFF)
  • Program 10: Auto restart when over temperature occurs (ON/OFF)
  • Program 11: Main input cut warning (Enable/Disable Grid or PV loss alarm)
  • Program 12: Energy-saving mode (ON/OFF, inverter stops output if load < 25W)
  • Program 13: Overload transfer to bypass (ON/OFF, transfers to grid power output on overload)
  • Program 14: Silent mode setting (Enable/Disable buzzer sound)
  • Program 15: Battery return to grid voltage point (Adjustable based on battery type)
  • Program 16: Switching back to battery mode voltage points (Adjustable based on battery type)
  • Program 17: Battery type (AGM, Flooded, Lithium (Ternary), FEL (Lithium iron), User-Defined)
  • Program 18: Battery low voltage alarm setting (Adjustable based on battery type)
  • Program 19: Battery shutdown voltage point (Adjustable based on battery type)
  • Program 20: Constant voltage mode voltage point setting (Adjustable based on battery type)
  • Program 21: Floating charge mode voltage point setting (Adjustable based on battery type)
  • Program 22: Grid low voltage point setting (Adjustable based on input mode)
  • Program 23: Grid high voltage point setting (Adjustable based on input mode)
  • Program 24: Automatic turn off backlight (ON/OFF, backlight turns off after 1 minute of no button operation)
  • Program 25: Inverter soft start setting (ON/OFF, gradual output increase)
  • Program 26: Reset factory setting (Restores all settings to default)
  • Program 29: Battery Disconnection Alarm (Enable/Disable battery disconnection alarm)
  • Program 31: Equalization Voltage Point Setting (Adjustable for FEL, AGM/FLD/LIB/CUS battery types)
  • Program 32: Equalization Charging Time Setting (Function ON/OFF, duration 5-900 minutes)
  • Program 33: Equalization Delay Time Setting (Function ON/OFF, duration 5-900 minutes)
  • Program 34: Equalization Interval Time Setting (Default: 30 days, range: 1-90 days)
  • Program 35: Enable Equalization Immediately (ON/OFF)
  • Program 36: Grid-tie inverter function (Set whether inverter feeds to grid)
  • Program 37: Max Grid Tie Power (Setting output power to grid, Default: 6.0kW, range: 0-6.0kW)
  • Program 38: Battery dual output low voltage shutdown point (Adjustable, Default: 48V)
  • Program 39: Battery dual output duration (Default: OFF, range: 5-900 minutes or FUL for unlimited)
  • Program 40: Dual output battery mode cut-off SOC (Adjustable, Default: 20, range: 5-90 or OFF)
  • Program 44: BMS Communication Function (Set to specific BMS protocol or OFF)
  • Program 45: BMS ID (Setting BMS ID number, AtO or numerical value [0-15])
  • Program 46: Low SOC Shutdown (Adjustable, Default: 20, range: 5-50 or OFF)
  • Program 47: High SOC to Battery (Adjustable, Default: 90, range: 10-100 or OFF)
  • Program 48: Low SOC to Grid (Adjustable, Default: 50, range: 10-90 or OFF)
  • Program 61: Battery Max. Discharge Current (Default: OFF, range: 10-140A)

5. Maintenance

Regular maintenance ensures the longevity and optimal performance of your ECGSOLAX Solar Hybrid Inverter. Always ensure the inverter is disconnected from all external power supplies (AC, DC, and battery) for at least 5 minutes before performing any maintenance or cleaning tasks.

  • Cleaning: Keep the inverter's exterior clean and free from dust and debris to ensure proper ventilation and heat dissipation. Use a dry, soft cloth for cleaning. Do not use liquid cleaners.
  • Connections: Periodically check all electrical connections (AC input/output, PV, battery, communication cables) to ensure they are tight and free from corrosion. Loose connections can lead to poor performance or safety hazards.
  • Ventilation: Ensure that the inverter's ventilation openings are not blocked. Adequate airflow is crucial to prevent overheating.
  • Battery Health: Monitor battery voltage and performance regularly, especially for lead-acid batteries, and perform equalization as needed (refer to Section 7 for Battery Equalization).
  • Firmware Updates: Check the manufacturer's website or app for any available firmware updates to ensure your inverter has the latest features and bug fixes.

6. Troubleshooting

This section provides guidance on common issues and their solutions. For more complex problems, refer to the full user manual PDF or contact customer support.

6.1 Fault Reference Codes

If a fault occurs, the fault indicator will be solid red, and the buzzer will sound for 10 seconds then stop. The LCD will display a fault code. The system may attempt to restart automatically. If it fails after six attempts, it will remain in fault status. Power off the unit or wait 30 minutes to restart.

Fault CodeMeaningRelevant ActionTrigger ConditionsResume Conditions
1Bus boost failTurn fault modeGrid soft start process starts but bus voltage does not reach set valueRestore after reaching the set voltage for 15 seconds
2Bus over voltageTurn fault modeBus voltage is higher than set valueRestore after reaching the set voltage for 15 seconds
3Bus below voltageTurn fault modeBus voltage is lower than set valueCannot restore
4Battery over currentTurn fault modeBattery current is higher than set valueCannot restore
5System over temperatureTurn fault modePFC temperature is higher than set value or fan is not connectedRestore after temperature lower than set value and fan connected for 15 minutes
6Battery over voltageTurn fault modeBattery voltage is higher than set valueRestore after reaching the set voltage for 15 seconds
7Bus soft start failedTurn fault modeBattery soft start process starts but the bus voltage has not reached set valueRestore after reaching the set voltage for 15 seconds
8Bus short circuitTurn fault modeBus voltage is lower than set valueCannot restore
9Inverter soft start failedTurn fault modeInverter soft start process starts but the inverter voltage has not reached set valueRestore after reaching the set voltage for 15 seconds
11Inverter under voltageTurn fault modeThe inverter voltage is lower than the set value in battery modeRestore after reaching the set voltage for 15 seconds
12Inverter short circuitTurn fault modeInverter voltage is less than the set value and current is higher than the set valueRestore after reaching the set value for 15 seconds
13Inverter negative powerTurn fault modeThe inverter power is negative and exceeds the set value for a period of timeRestore after reaching the set value for 15 seconds
14Over loadTurn fault modeThe load current is higher than the set valueRestore after reaching the set value for 15 seconds
17Program updatingTurn fault modeInverter updating or OTARestore after updating
18PV reverse connectionTurn fault modePV reverse connectionRestore after connecting correctly for 15 seconds
26BMS faultTurn fault modeError code in BMS message.Restore after BMS fault resolved
29Inverter load abnormalTurn fault modeAbnormal inverter load leads to abnormal voltageRestore after voltage returning normal for 15 seconds

6.2 Alarm Reference Codes

If an alarm occurs, the inverter does not enter fault mode, but the red LED light flashes, and the LCD displays an alarm code. The buzzer sounds every one second for 1 minute, then stops.

Alarm CodeMeaningRelevant ActionTrigger ConditionsResume Conditions
50Battery openAlarmBattery disconnected for no more than 10 minutesRestore after battery connected and charging for 2 minutes
51Battery under voltageAlarm, battery low voltage shutdown or cannot power onBattery voltage is lower than BAU set valueRestore after the battery voltage exceeding the BAU set value by 2V
52Battery low voltageAlarmBattery voltage is lower than BAL set valueRestore after the battery voltage exceeding the BAL set value by 2V
53Battery charge short circuitAlarm, battery does not chargeBattery voltage is less than 24V and the charging current exists.Restore after a maximum of 1 minute when the short circuit is eliminated.
56BMS lossAlarmCommunication failure after BMS communication function is enabledRestore after communication function disabled or communication success
58Fan errorAlarm, fan operation in full speedNo fan speed signal detectedRestore after fan speed signal detected
59EEPROM errorAlarmEEPROM read/write exceptionCannot restore
60OverloadAlarmThe mains current/battery discharge current/load power is higher than the rated value.Restore after the mains current/battery discharge current/load power is less than the rated value.
62PV energy weakAlarm, Turn off the PV output to the load, but keep the PV charging the batteryWhen the battery is not connected, the bus voltage is lower than the set valueRestore after battery connected or grid connected, or 10 minutes later.
68Battery under SOC shutdownAlarm, turn to standby modeBMS reports SOC lower than BSU set valueRestore after meeting one of the following three conditions: 1. Disable low SOC shutdown function 2. Disable BMS communication function 3. SOC is higher than the set value by 5%
69Battery below SOC warningAlarm, if it is in standby mode, it will remain in standby mode.Lithium battery SOC is lower than set value+5% (grid mode or battery mode), lower than set value+10% (standby mode)Restore after meeting one of the following three conditions: 1. Disable low SOC shutdown function 2. Disable BMS communication function 3. SOC is higher than the set value by 10%
72Battery can not startupAlarmDuring standby, battery voltage is lower than the allowed startup voltageRestore after the battery voltage is higher than the allowed startup voltage
77Grid power is unstableAlarmLost of grid power three times within 5 minutesRestore after 5 mins

6.3 General Troubleshooting

Problem: LED screen display fault code 5 (Over temperature)

  • What to do: Check if the fan is connected or if there are loose wiring issues. If the fan is not connected for more than 5 minutes, the machine will report fault code 5.

Problem: LED screen display fault code 12 (Inverter short circuit)

  • What to do: 1. Check for a short circuit at the output terminals (e.g., a screw piercing through and causing an L-N short circuit). 2. Verify if the inverter voltage and current meet the triggering conditions.

Problem: LED screen display fault code 58 (Fan malfunction)

  • What to do: 1. Check if the fan is connected properly or if there are any loose connections. 2. If the fan is properly connected: a) Check for issues with the fan detection circuit (often due to excessive soldering under the control board socket). b) Check if the fan itself is damaged.

Problem: Unable to start (Battery)

  • What to do: 1. Check if the battery voltage sampling is functioning properly and if the battery voltage has been calibrated. 2. Use a multimeter to measure the voltage at the battery terminals (using a DC power supply or a real battery) to see if it reaches the minimum voltage of 11.5V per cell for startup. Note: It is crucial to configure the battery voltage according to the machine model. Connecting the wrong battery voltage can cause capacitor explosion.

Problem: Unable to start (Utility power)

  • What to do: 1. Check for any short circuits at the mains terminal (e.g., a screw piercing through and causing a short circuit between live and neutral). 2. Check for any wiring errors, such as mistakenly connecting the mains input to the output terminals.

Problem: Unable to start (PV)

  • What to do: 1. Check if the PV input voltage is too close to the critical threshold. 2. For low voltage versions, check if the software version numbers of the main control are compatible. If they differ significantly, the machine may not activate.

Problem: PV not charging

  • What to do: Connecting the wrong battery voltage can result in damage to the auxiliary power supply on the PV side, causing a loss of power and inability to communicate with the main control.

7. Specifications

The ECGSOLAX 6.5KW Solar Hybrid Inverter (Model Ecg-hvm6.5k-48V) offers robust performance for various solar energy applications. Below are the detailed specifications:

Detailed Inverter Specifications Table
Figure 3: Detailed Specifications for ECG-HVM5K-24V and ECG-HVM6.5K-48V models.
CategoryParameterECG-HVM6.5K-48V
AC InputPhase1-phase
Rated Input Voltage (VAC)208/220/230/240 (1+N) PE
Voltage Range (VAC)90-280 (APP mode); 170-280 (UPS mode)
AC OutputRated Capacity (kW)6.5 kW (Output Power rating will be reduced to 90% when setting the Output Voltage to 208V)
Surge Power (kVA)12 kVA
Voltage (VAC)208/220/230/240
Power Factor (PF)1
Frequency (Hz)50/60 ± 0.1%
Switch Time (ms)10 (APP/UPS mode) / 20 (GEN mode)
Wave FormPure sine wave
Charger (PV/AC)Solar Charger TypeMPPT
Max PV Input Current27A
Max PV Input Power9000W
MPPT Range @ Operating Voltage (VDC)60-450V
PV Start-up Voltage60VDC
Max PV Open Circuit Voltage (VDC)500VDC
BatteryNormal Voltage (VDC)48VDC
Floating Charge Voltage (VDC)54VDC
Overcharge Protection (VDC)61VDC
General DataHMILCD
InterfaceRS485/RS232/USB
MonitoringBuilt-in WIFI
Ingress ProtectionIP21
Operating Temperature-10°C - 60°C
Relative Humidity5% - 95% (Non-condensing)
Storage Temperature-15°C - 60°C
Dimensions (W*H*D)410mm * 336mm * 110mm
WeightNet Weight (kg)10kg
CertificationCECE

8. Warranty and Support

For detailed warranty information, including terms, conditions, and duration, please refer to the official product documentation provided by the seller or contact ECGSOLAX customer support directly. The user manual PDF (available at ECGSOLAX Inverter User Manual PDF) may contain additional warranty details.

For technical support, troubleshooting assistance beyond this manual, or inquiries regarding parts and service, please contact your authorized ECGSOLAX dealer or the manufacturer's customer service department.

9. User Tips

  • Optimal Placement: Ensure the inverter is installed in a well-ventilated area, away from direct sunlight and moisture, to maximize its lifespan and efficiency.
  • Cable Management: Use appropriate cable gauges and ensure all connections are secure and properly insulated to prevent energy loss and potential hazards.
  • Regular Monitoring: Utilize the built-in WiFi monitoring feature to regularly check system performance, battery status, and energy production. This helps in early detection of any issues.
  • Battery Compatibility: Always verify battery compatibility and settings (e.g., voltage points, charging current) in the LCD menu to match your specific battery type (lead-acid or lithium) for safe and efficient operation.
  • Consult Professionals: For complex installations or persistent issues, always consult with a qualified electrician or solar professional.
Documents - ECGSOLAX – Ecg-hvm6.5k-48V

no relevant documents