High-performance current vector frequency converter (Asynchronous)

Introduction

Thank you for purchasing the HLTNC EV210 series of high-performance current vector frequency converters. This manual provides essential information regarding the functional characteristics and usage methods of the EV210 series, including product selection, parameter setting, operation debugging, and maintenance inspection. Please read this user manual carefully before use to ensure safe and efficient operation.

The EV210 series is primarily designed to control and regulate the speed and torque of three-phase AC asynchronous motors. It supports various PG cards and is suitable for a wide range of applications such as textile machinery, paper production, wire drawing, machine tools, packaging, food processing, fans, pumps, and other automated production equipment.

HLTNC is committed to continuous product improvement, and features may be upgraded without prior notice. Illustrations in this manual are for reference and may differ slightly from the actual product.

1. Safety Information and Precautions

When installing, commissioning, and maintaining this system, users must carefully read and follow all safety precautions. The manufacturer is not responsible for any injury or loss resulting from the violation of operating procedures.

1.1 Marking and Definition of Safety Information

MarkingDefinition
⚠ DangerIndicates an accident that may result in death or serious injury if not performed as required.
⚠ WarningsIndicates that failure to operate as required will result in moderate personal injury or minor injury and some material loss.
△ NoteIndicates matters that need attention in operation or use.
⛔ ProhibitedIndicates something that is absolutely not allowed to be done.
ℹ CompulsionIndicates something that must be done.

1.2 Safety Matters

Installation Environment

  • Install in an indoor, well-ventilated location, generally vertically, to ensure optimal cooling. Horizontal installation may require additional ventilation.
  • Ambient temperature should be between -10°C and +40°C. If it exceeds 40°C, remove the top cover. If it exceeds 50°C, external forced cooling or derating is required. Avoid high-temperature environments to prolong lifespan.
  • Ambient humidity should be below 95% with no water droplets condensing.
  • Install in a place with vibration less than 0.5G to prevent drop damage. Avoid sudden impacts.
  • Install in an environment free from electromagnetic fields, flammable, and explosive substances.

Installation Safety Instructions

  • Do not work with wet hands.
  • Wiring work must not be done when the power is not fully disconnected.
  • Do not open the face cover or perform wiring while the inverter is powered on, as there is a risk of electric shock.
  • Wiring, inspection, and other operations must be carried out 10 minutes after the power is turned off to avoid electric shock.
  • Do not install a frequency converter with damaged or missing components.
  • Main circuit terminals must be securely connected to the cable to prevent damage to the inverter from poor contact.
  • For safety, grounding terminals must be reliably grounded. For multiple frequency converters, use one-point grounding to avoid common ground impedance interference.
Diagram showing correct and incorrect grounding methods for multiple frequency converters.
Figure 1-1: Correct Grounding Methods for Multiple Frequency Converters

Prohibitions and Warnings

  • Danger: Do not connect an AC power supply to the output terminals U, V, W of the inverter, as this will cause damage.
Diagram illustrating the prohibition of connecting AC power to inverter output terminals.
Figure 1-2: Prohibited AC Power Connection to Inverter Output
  • Mandatory: Install a fuseless circuit breaker on the input power side for circuit protection.
  • Note: Avoid installing electromagnetic contactors on the output side of the frequency converter, as this can cause operating overvoltage and damage. If necessary, configure for specific situations like energy-saving control, critical processes, or controlling multiple motors.
  • Warnings: Do not install capacitors or surge current absorbers (varistors) at the output end of the frequency converter, as this can cause tripping and damage. If already installed, remove them.
Diagram showing an output circuit with a surge current absorber, which is prohibited.
Figure 1-3: Prohibited Output Circuit with Surge Current Absorber
  • Note: Perform an insulation check on the motor before first use or after long storage. If using outside allowable voltage range, configure a step-up or step-down device. Derate by 10% for every 1000 meters of elevation above 1000 meters.

2. Technical Specifications

2.1 Naming Rules

The model number EV210-0007G-T4 indicates:

  • EV210: Product Line
  • 0007: Power Code (e.g., 0.75kW)
  • G: General-Purpose
  • T4: Voltage Rating (e.g., Three-Phase 380V)

2.2 General Technical Specifications

ItemSpecification
Input voltageThree-phase AC380V ±10%; Single-phase AC220V ±10%
Input frequency50/60Hz
Output voltage0 to input voltage
Output frequencyVector control: 0-500Hz; V/F control: 0-500Hz
Overload capacity150% rated current for 60 seconds; 180% rated current 3 seconds
Control modeV/F control, sensorless vector control (SVC)
Frequency setting resolution (Analog input)Maximum frequency x0.025%
Frequency setting resolution (Digital Settings)0.01 Hz
Protection gradeIP20
Cooling methodAir-cooled with fan control
Installation methodWall-mounted, cabinet

2.3 Chassis and Keyboard Dimensions

Drawing Parameters for EV210 VFD showing installation and peripheral dimensions.
Drawing Parameters: EV210 VFD Dimensions
Voltage levelModelInstallation dimensions (mm)Peripheral dimensions (mm)R (mm)
ABWHD
Single-phase 220V0.4 kW to 2.2 kW63.0136.5721461052.3
Three-phase 380V0.75 kW to 2.2 kW78.0172.5871831272.3
4 kW to 5.5 kW106.0229.01182411542.8
7.5 kW, 15 kW

2.4 Rated Output Ammeter

Inverter modelPower capacity KVAInput current AOutput Current ACompatible motor kW
EV210-0015G-S23.014.07.01.5
EV210-0022G-S24.023.09.62.2
EV210-0015G-T43.05.03.81.5
EV210-0022G-T44.05.85.12.2

2.5 Brake Resistor Selection Table

Inverter modelBrake resistor specificationsBraking torque 10%ED
WΩ
EV210-0015G-S2100100125
EV210-0022G-S210070125
EV210-0015G-T4300400125
EV210-0022G-T4300250125

Note:

  1. Please select the resistance value specified by our company.
  2. The Company is not responsible for damage caused by using non-Company provided brake resistors.
  3. Brake resistor installation must consider safety and flammability, maintaining at least 100mm distance from the frequency converter.
  4. Parameters in the table are for reference only and not standard.

3. Setup and Installation

3.1 Storage

Before installation, keep the product in its packing box. When storing, ensure the following:

  • Dust-free, dry location.
  • Ambient temperature: -20°C to +65°C.
  • Relative humidity: 0% to 95%, no condensation.
  • Free of corrosive gases and liquids.
  • Store on a shelf and in packaging. For long-term storage (over one year), power on once every six months for at least 5 hours, gradually increasing input voltage with a regulator.

3.2 Installation Location and Environment

Environmental conditions affect inverter service life. Install in locations with:

  • Ambient temperature: -10°C to +40°C with good ventilation.
  • No dripping and low temperature.
  • No direct sunlight, high temperatures, or heavy dust.
  • Free of corrosive gases, liquids, oil vapor, and metal shavings.
  • Vibration-free, easy to maintain and inspect.
  • Free from electromagnetic noise.

3.3 Installation Space and Orientation

  • Leave sufficient space around the inverter for maintenance.
  • Install vertically for good cooling and air circulation.
  • Ensure secure installation. If installed on a loose plane, stress may damage internal components.
  • Mounting wall should be made of non-combustible materials (e.g., iron plates).
  • When installing multiple inverters in the same cabinet, ensure proper spacing. If installed up and down, add a baffle or offset their alignment.

4. Wiring

4.1 Main Circuit Wiring Diagram

The inverter wiring consists of the main circuit and the control circuit. Users must connect them accurately according to the following diagrams after lifting the housing cover.

Basic operation wiring diagram for the EV210 inverter, showing connections for power input, multifunctional input terminals, potentiometer, analog output, RS485 communication, and relay output.
Basic Operation Wiring Diagram

4.2 Terminal Diagram

The control loop terminal arrangement and jumper settings are critical for proper operation.

Control Loop Terminal Arrangement

Terminals include: 10V, GND, AI, AO, 485+, 485-, X1, X2, X3, X4, COM, TA, TC.

Main Circuit Terminals

  • Single-phase 0.4kW-2.2kW, three-phase 0.75-2.2kW: R, S/L1, T/L2, U, V, W
  • Three-phase 4kW-15kW: R, S, T, P+, PB, U, V, W

Jumper Settings for the Main Control Board

JumperSettingDescription
J1BlockMain control board is grounded.
OFF stopMain control board is grounded open (default open).
J2AVO settingAnalog AO output voltage signal, 0-10V.
ACO stopAnalog AO output current signal, 0-20mA.
J4P-I rangeSelection of built-in keyboard potentiometer (default).
P-E modeSelection of external keyboard potentiometer.
J5AVI stopAnalog AI input voltage signal, 0-10V.
ACI stopAnalog AI input current signal, 0-20mA.

4.3 Wiring Precautions

Main Circuit Wiring

  • Wire diameter specifications must comply with electrical regulations.
  • Use isolation wires or conduits for power wiring, grounding them at both ends.
  • Install an air circuit breaker (NPB) between the power supply and input terminals (R, S, T). For leakage circuit breakers, use one with high-frequency countermeasure.
  • Power lines and control lines should be separated, not in the same conduit.
  • Do not connect AC power to the inverter's output terminals (U, V, W).
  • Output wiring must not touch metal parts of the inverter housing to prevent ground short circuits.
  • Do not use phase-shifting capacitors, LC, RC noise filters, etc., at the inverter output.
  • Keep main circuit wiring away from other control devices.
  • For long distances between inverter and motor (over 50m for 220V, 100m for 380V), high dv/dt can damage motor coil insulation. Use an AC motor dedicated to the inverter or install a reactor on the inverter side.
  • For long distances, reduce carrier frequency. Higher carrier frequency increases high-order harmonic leakage current, affecting the inverter and other equipment.

Control Circuit Wiring (Signal lines)

  • Signal lines must not be placed in the same wire slot as main circuit wiring to avoid interference.
  • Shield signal lines and ground them at one end (0.5-2mm² diameter).
  • Use 1mm² shielded wire for control lines.
  • Use control terminals on the control panel as needed.

Ground Wire

  • Grounding terminal E should be grounded in the third type of grounding (below 10Ω).
  • Use grounding wire according to technical length and electrical equipment dimensions.
  • Avoid sharing grounding electrodes with large electrical equipment (e.g., welding machines).
  • Keep grounding wires away from power lines of large electrical equipment.
  • For multiple frequency converters, use one-point grounding.
  • Grounding wiring must be as short as possible.
  • Ground terminal E must be properly grounded and never connected to the neutral wire.

4.4 Specific Application Precautions

Reactor Installation

When connecting to a large capacity power transformer (600kVA or more) or switching input capacitors, excessive peak current can damage the converter. Install a DC or AC reactor to prevent this and improve power factor. If the same power supply system is connected to thyristor converters, DC or AC reactors must be used.

Inverter Capacity

Ensure motor rated current does not exceed inverter rated output current. For multiple induction motors in parallel, the inverter capacity should be such that 1.1 times the combined rated current of the motors is less than the inverter's rated output current.

Starting Torque

Starting and acceleration characteristics are limited by the combined overload rated current of the frequency converter. If higher starting torque is needed, increase inverter capacity by one size or increase both motor and inverter capacity.

Emergency Stop

While protection functions will stop output upon inverter failure, the motor may not stop suddenly. Set up mechanical stop/hold structures on equipment requiring emergency stops.

Precautions for Motor Use

  • Existing Standard Motors: Driving a standard motor with a frequency converter increases losses. Cooling is worse at low speeds, increasing motor temperature. Reduce load torque at low speeds. For 100% continuous torque at low speeds, consider a motor dedicated to frequency converters.
  • Motors with Brakes: If the brake circuit is directly connected to the inverter output, the brake may not open at startup due to lower voltage. Use an independent brake power supply connected to the power side of the inverter. Noise may increase at low speeds.
  • Power Transmission Structure (Reducer, Belt, Chain): Oil lubrication may be poor at continuous low-speed operation. High-speed operation (above 60Hz) can cause noise, reduced lifespan, and strength issues due to centrifugal force.

5. Operations and Displays

5.1 Instructions for the Operation Panel

Diagram of the EV210 VFD operation panel with key instructions and indicator light descriptions.
EV210 Operation Panel: Key Instructions and Indicator Lights

Key Instructions

Key SymbolNameFeature Description
PRGProgramming keysMenu entry or exit, parameter modification
ENTERDetermine keyGo to the menu and confirm parameter settings
▲Incrementing keysIncrement data or function code
▼Decrement keyDecrement data or function code
RUN/►Run keysRun/Shift operations in keyboard operation mode
STOP/RESETStop/Reset keyUsed as a shift key to view displayed content when main interface is stopped

Indicator Light Instructions

Indicator Light NameInstructions
REVInverter reverse indicator light (on indicates reverse operation)
FWDForward rotation indicator light (on indicates forward rotation operation)
ALMConstantly lit: torque control; Fast-flashing: fault; Slow-flashing: tuning
HzFrequency unit
AUnits of current
VVoltage units

Functional Indicator Light Combinations

Indicator light combination methodLED shows meaningSymbols
Hz+AMotor speedr/min
A+VTime (seconds)s
Hz+VPercentage actual value%
Hz+A+VTemperature°C

5.2 Operating Procedures

Parameter Settings

The menu structure has three levels:

  1. Function Code group number (first-level menu)
  2. Function code labels (secondary menu)
  3. Function code Settings (Level 3 menu)

Note: In the third-level menu, press PRG or ENTER to return to the second-level menu. ENTER saves parameters and moves to the next function code. PRG returns without saving and stays on the current function code.

If a parameter has no flashing bit in the third-level menu, it cannot be modified. Reasons include: unmodifiable parameter (e.g., detection/record parameters) or operation in progress (requires shutdown).

Fault Reset

After a fault, the inverter displays fault information. Use the STOP/RESET key on the keyboard or terminal function to reset. After reset, the inverter enters standby mode. If not reset, it remains in protection mode and will not operate.

Motor Parameter Self-Learning

For vector control operation, accurately input motor nameplate parameters. Vector control performance relies heavily on precise motor parameters. Obtain accurate parameters of the controlled motor for optimal control.

5.3 Product Startup and Operation Demonstration

Watch this video for a demonstration of product startup and operation, including setting parameters for a 400Hz, 24000RPM motor.

Video: Product Startup and Operation Demonstration

6. Maintenance and EMC Guidelines

6.1 EMC (Electromagnetic Compatibility)

Definitions

Electromagnetic compatibility refers to the ability of electrical equipment to operate stably in an electromagnetic environment without causing or being affected by interference.

Introduction to EMC Standards

The inverter complies with national standard GB/T12668.3 and international standard IEC/EN61800-3:2004, covering both electromagnetic interference and anti-electromagnetic interference. This includes tests for radiated interference, conducted interference, harmonic interference, conducted immunity, radiated immunity, surge immunity, rapid burst immunity, ESD immunity, and low-frequency power supply immunity.

EMC Guidance

  • Harmonics Effects: Higher harmonics in the power supply can damage the frequency converter. In areas with poor grid quality, installing an AC input reactor is recommended.
  • Electromagnetic Interference and Installation Precautions:
    • Grounding wire of the frequency converter and other electrical products should be well grounded.
    • Power input/output lines and weak current signal lines should not be arranged in parallel; arrange vertically if possible.
    • For output power lines, use shielded cables or steel pipe shielded power lines, with reliable grounding. For disturbed equipment, use twisted-pair shielded control lines with reliable grounding.
    • For motor cables longer than 100 meters, install an output filter or reactor.
  • Methods for Dealing with Interference from Peripheral Equipment: If the inverter malfunctions due to interference from relays, contactors, or electromagnetic brakes:
    • Install a surge suppressor on the interfering device.
    • Install a filter at the input of the frequency converter.
    • Use shielded cables for control signal and detection lines, with reliable grounding.
  • How to Deal with Interference from the Inverter to Peripheral Equipment: This includes radiated and conducted interference.
    • For sensitive instruments/sensors: Keep them away from the inverter, avoid parallel routing of signal and power lines, shield and ground signal/power lines, add ferrite rings to the output side of the frequency converter (30-1000MHz, 2-3 turns), or install an EMC output filter.
    • If interfered equipment and inverter share the same power supply: Install an EMC filter between the inverter and the power supply.
    • Ground peripheral equipment separately to eliminate leakage current interference.
  • Leakage Current and Handling: Two forms exist: leakage current to ground and between lines.
    • To Ground: Caused by distributed capacitance. Reduce distance between inverter and motor. Lower carrier frequency (but increases motor noise). Installing a reactor is also effective.
    • Between Lines: Caused by distributed capacitance and higher harmonics. Lower carrier frequency or install an output reactor. Do not install a thermal relay between the frequency converter and the motor; use the electronic overcurrent protection function.
  • Notes for Installing an EMC Input Filter:
    • Use the filter strictly according to rated values.
    • The metal casing of the Class I electrical appliance filter must have good contact with the metal ground of the installation cabinet for electrical continuity, preventing electric shock and affecting EMC.
    • The filter ground must be connected to the same common ground as the PE terminal ground of the frequency converter.
    • Install the filter as close as possible to the power input of the inverter.

7. Troubleshooting

If an anomaly occurs during operation, the inverter will block PWM output and enter fault protection, displaying a flashing fault code and lighting the ALM indicator. Refer to the tables below for diagnosis and countermeasures. If the problem persists, contact customer service.

7.1 Fault Diagnosis and Countermeasures (Table 8-1 Excerpt)

Faults NameOperation Panel DisplayTroubleshootingTroubleshooting Countermeasures
Inverter unit protectionFU011. Short circuit in output circuit
2. Long wiring between motor and inverter
3. Module overheating
4. Loose wiring
5. Main control board abnormality
6. Driver board abnormality
7. Inverter module abnormality
1. Eliminate peripheral faults
2. Install reactor or output filter
3. Check/clear blocked air duct, fan
4. Plug in all wires
5. Seek technical support
Accelerate overcurrentFU021. Ground/short circuit in output circuit
2. Vector control, no parameter identification
3. Short acceleration time
4. Manual torque boost or inappropriate V/F curve
5. Low voltage
6. Start a rotating motor
7. Sudden load increase
8. Inverter too small
1. Eliminate peripheral faults
2. Perform motor parameter identification
3. Increase acceleration time
4. Adjust manual boost torque or V/F curve
5. Adjust voltage to normal range
6. Select speed tracking start or wait for motor to stop, then restart
7. Cancel sudden load
8. Use larger power rating inverter
Under-voltage faultFU091. Momentary power outage
2. Input voltage out of range
3. Abnormal bus voltage
4. Rectifier bridge/buffer resistor malfunction
5. Driver board abnormality
6. Control board abnormality
1. Reset faults
2. Adjust voltage to normal range
3-6. Seek technical support

7.2 Common Faults and How to Handle Them (Table 8-2 Excerpt)

Serial NumbersFault phenomenonPossible causesSolution
1No display when powered on
  • No grid voltage or too low
  • Switching power supply failure
  • Rectifier bridge damaged
  • Inverter buffer resistor damaged
  • Control board, keyboard failure
  • Connection between control board, driver board, and keyboard broken
  • Check input power
  • Check bus voltage
  • Seek manufacturer service
2Power-on display "P.OFF"
  • Poor contact between driver board and control board
  • Related components on control board damaged
  • Short circuit to ground in motor or motor wire
  • Hall fault
  • Grid voltage too low
  • Seek manufacturer service
3Inverter shows normal, then "P.OFF" and stops immediately
  • Fan damaged or blocked
  • Short circuit in peripheral control terminal wiring
  • Replace fan
  • Rule out external short circuit faults
5Motor doesn't turn after inverter is running
  • Motors and motor wires
  • Parameters set incorrectly
  • Poor contact between driver board and control board
  • Driver board failure
  • Reconfirm connection
  • Replace motor or clear mechanical faults
  • Check and reset motor parameters

8. User Tips

  • For optimal motor performance, especially with 400Hz motors, ensure parameters P0-10, P0-12, P1-04, and P1-05 are correctly set according to your motor's specifications (e.g., P0-10=400, P0-12=400, P1-04=400, P1-05=24000 for a 400Hz, 24000RPM motor).
  • Always double-check wiring connections, particularly for the control card or USB interface board, to prevent operational issues.
  • If experiencing frequent overheating faults (FU14), verify that the cooling fan is functioning correctly and that air ducts are not blocked. Consider reducing the carrier frequency (P0-15) if necessary.

9. Warranty and Support

If you encounter any problems using our products that cannot be resolved with this manual, please contact your regional agents or our customer service center directly for assistance.

For a detailed PDF version of the user manual, please refer to the official documentation: HLTNC EV210 Frequency Converter User Manual (PDF).