GEYA VA5

Contents

GEYA 4P VA5 Overvoltage & Undervoltage Protector Instruction Manual

Model: VA5

1. Introduction

The GEYA 4P VA5 Overvoltage & Undervoltage Protector is a sophisticated device designed to safeguard electrical circuits in both home and industrial environments. It provides comprehensive protection against voltage fluctuations, including overvoltage, undervoltage, and phase sequence errors. This manual provides essential information for the safe and effective installation, operation, and maintenance of your device.

GEYA 4P VA5 Overvoltage & Undervoltage Protector front view
Front view of the GEYA 4P VA5 Protector, showing the digital display and control buttons.

2. Safety Precautions

Please read and adhere to the following safety guidelines to prevent injury or damage to the device:

  • Professional Installation: This equipment must be installed by qualified professionals.
  • Power Disconnection: Before any operation or maintenance, disconnect all power supplies to the device and ensure no terminal is live.
  • Terminal Verification: Always verify that terminals are properly connected according to the wiring diagram.
  • No Disassembly or Repair: Do not attempt to disassemble or repair the equipment yourself. Refer to qualified service personnel.
  • Environmental Conditions: Do not use the equipment in places that may be corroded by gas, exposed to strong sunlight, or rain.

3. Installation and Wiring

The GEYA 4P VA5 Protector is designed for DIN rail mounting. Ensure adequate space for ventilation and access to terminals.

3.1. Product Dimensions

Product dimensions and setup menu overview
Dimensions of the GEYA 4P VA5 Protector (90mm x 97mm x 70mm).

3.2. Wiring Diagram

Follow the diagram below for correct power and load connections. Ensure all connections are secure and properly insulated.

Wiring diagram for GEYA 4P VA5 Protector
Wiring connections for power (top) and load (bottom) terminals.
  • Power Input: Connect the neutral (N) and live phases (L1, L2, L3) from your power source to the corresponding top terminals.
  • Load Output: Connect the neutral (N) and live phases (L1, L2, L3) of your load to the corresponding bottom terminals.

4. Operation

The device features a digital display and control buttons for monitoring and setting parameters.

4.1. Display Panel

Detailed display panel and electrical symbols
Detailed view of the display panel, buttons, and electrical symbols.

The display shows real-time voltage (V) and current (A) for each phase (L1, L2, L3). The control buttons are:

  • SET: Enters/confirms settings.
  • UP/DOWN Arrows: Adjusts parameter values.
  • Hand Switch: Manual control (if applicable).
  • Menu Key: Navigates through menu options.

4.2. Product Status Indicators

  • Normal Operation: The operating voltage and current values are displayed.
  • Fault Detection: If a fault (voltage or current) is detected, the output relay turns off, and the fault indicating LED lights up.
  • Voltage Failure: If the input voltage trips back to the hysteresis value after a voltage failure, the relay will automatically reset/start the delay count, and the current value will flash.
  • Phase Sequence Error: If a phase fault occurs, 'L1-L2-L3' will be displayed, and the protector will disconnect from the output power supply.
  • Continuous Overcurrent: If a continuous overcurrent fault is detected, 'OFF' will be displayed. Disconnect the overloaded device and manually reset the protector.

4.3. Setup Menu (P-1 to P-15)

The device allows for customization of various protection parameters. Access the setup menu using the 'SET' and 'Menu' keys, and adjust values with the UP/DOWN arrows.

Parameter CodeDescriptionAdjustable Range
P-1Power-on delay time1s - 600s
P-2Protection recovery delay1s - 600s
P-3Overvoltage protection value230V - 300V
P-4Overvoltage recovery value265V - 295V
P-5Undervoltage protection value170V - 210V
P-6Undervoltage recovery value175V - 215V
P-7Voltage protection action delay0.1s - 10s
P-8Three-phase voltage unbalance value50V - 100V
P-9Three-phase voltage unbalance recovery value20V - 99V
P-10Three-phase voltage calibration-9.5V - 9.5V
P-11Phase-sequence switchOn/Off
P-12Overcurrent protection value63A, 100A
P-13Overcurrent protection action time0.5s - 10s
P-14Continuous overcurrent protectionOff / 0-20
P-15Three-phase current error calibration-9.5A - 9.5A

5. Maintenance

The GEYA 4P VA5 Protector is designed for long-term, reliable operation with minimal maintenance. To ensure optimal performance and longevity:

  • Cleaning: Keep the device clean and free from dust. Use a dry, soft cloth for cleaning.
  • Environment: Ensure the operating environment remains within specified temperature and humidity ranges, and free from corrosive gases.
  • No User Serviceable Parts: The device contains no user-serviceable parts. Any internal issues should be addressed by qualified technicians.

6. Troubleshooting

If the device is not functioning as expected, refer to the following common issues and solutions:

ProblemIndicationPossible CauseSolution
Device trips, fault LED onOutput relay OFF, fault LED ONOvervoltage, undervoltage, or overcurrent fault detected.Check input voltage/current. Device will automatically reset after conditions normalize (or manual reset for overcurrent).
Voltage failureInput voltage trips, current value flashesInput voltage dropped below undervoltage threshold.Device will automatically reset once voltage recovers to hysteresis value.
Phase fault'L1-L2-L3' displayed, output disconnectedPhase sequence error or phase loss.Check phase connections and power supply.
Continuous overcurrent'OFF' displayedLoad drawing excessive current.Disconnect overloaded device. Manually reset the protector.

7. Specifications

Below are the technical specifications for the GEYA 4P VA5 Overvoltage & Undervoltage Protector:

FeatureSpecification
Rated Supply VoltageAC380V
Operating Voltage RangeAC120V-300V
Rated Frequency40/50/60/70Hz
Lag (Overvoltage & Asymmetry)5V
Lag (Undervoltage)5V
Asymmetric Delay10s
Voltage Measurement Accuracy≤2% (On the whole spectrum)
Rated Insulation Voltage450V
Output Contact3NO
Electrical Life10⁵ cycles
Mechanical Life10⁵ cycles
Protection ClassIP20
Pollution Degree3
Altitude<2000m
Operating Temperature-5℃ to 40℃
Humidity≤50% or 40℃ (Condensation free)
Storage Temperature-25℃ to 55℃
TypeMoulded Case, Circuit Breaker
Is Smart DeviceYes
CertificationCE
Rated Current Options63A, 100A
Package Dimensions (L x W x H)10cm x 8cm x 5cm
Package Weight0.5kg

8. User Tips

  • Voltage Compatibility: While the device is rated for AC380V, always verify the specific voltage parameters (P-3 to P-6) are set correctly for your local grid, especially if operating on a 400V system. Consult a professional electrician if unsure.
  • Parameter Customization: Take advantage of the extensive setup menu (P-1 to P-15) to fine-tune protection thresholds and delays according to your specific application requirements.

9. Warranty and Support

For detailed warranty information, technical support, or further inquiries, please refer to the official documentation or contact GEYA customer service.

An electronic version of the user manual (PDF) is available for more in-depth information. You can typically find this document on the manufacturer's website or by searching for the product model number.

Reference: User manual (PDF)

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.