1. Introduction
This manual provides detailed instructions for the assembly, installation, operation, and troubleshooting of the PowMr POW-SPH-6KW Hybrid Solar Inverter. Please read this manual carefully before installation and operation, and keep it for future reference.
1.1 Purpose
The PowMr POW-SPH-6KW Hybrid Solar Inverter is a multi-function inverter/charger designed for home and small commercial energy storage systems. It combines the functions of an inverter, solar charger, and battery charger to provide uninterruptible power support. The comprehensive LCD display allows for user-configurable and easy-accessible button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
1.2 Scope
This manual covers safety and installation guidelines, as well as information on tools and wiring for the POW-SPH-6KW model. It also details the operation of the unit, including LCD display settings, and provides troubleshooting steps.
1.3 Key Features
- Pure sine wave inverter output.
- IP65-rated waterproof and dustproof protection for worry-free stability in various environments.
- Smart Touch Display for intuitive interface and real-time data.
- Supports parallel operation of up to six units for system expansion, reaching a total of 36KW in single-phase or three-phase configurations.
- Dual MPPT inputs for flexible and efficient power generation, supporting 1.5 times PV oversizing (up to 9000W PV input).
- Wide PV input voltage range of 50-500VDC, with an open-circuit voltage up to 520V.
- Dual output design.
- Built-in Wi-Fi module for easy remote monitoring via a mobile app.
- Emergency Power Supply (EPS) mode for critical loads during power outages.
- Flexible Time-of-Use settings to optimize energy efficiency and reduce costs.
- Inverter and Battery BMS Communication, supporting lithium and lead-acid batteries, with features like lithium activation and battery balancing.
- Delivers 6kW of power at 230V.
2. Safety Instructions
This section contains important safety and operating instructions. Please read and keep this manual for future reference.
2.1 General Warnings
- Only qualified service personnel should service this device. If errors persist after troubleshooting, contact your local dealer or service center.
- This inverter is non-isolated. Only single crystalline, poly crystalline (Class A-rated), and CIGS modules are acceptable. Do not connect PV modules with possible current leakage to the inverter. Grounded PV modules will cause current leakage. Ensure no grounding when using CIGS modules.
- It is required to use a PV junction box with surge protection. Failure to do so may cause damage to the inverter during lightning strikes on PV modules.
2.2 Cautions
- To reduce the risk of injury, only charge deep-cycle lead-acid type rechargeable batteries. Other battery types may burst, causing personal injury and damage.
- Only qualified personnel can install this device with a battery.
- Never charge a frozen battery.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect reassembly may result in electric shock or fire.
- To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- For optimum operation, follow the required specifications to select appropriate cable sizes. Correct operation of this inverter/charger is crucial.
- Be very cautious when working with metal tools on or around batteries. Dropping a tool could spark or short-circuit batteries or other electrical parts, potentially causing an explosion.
- Strictly follow the installation procedure when disconnecting AC or DC terminals. Refer to the installation section of this manual for details.
- A 150A fuse is provided as over-current protection for the battery supply.
- This inverter/charger should be connected to a permanent grounded wiring system. Comply with local requirements and regulations for installation.
- Never short-circuit AC output and DC input. Do not connect to the mains when DC input short-circuits.
3. Product Overview
The PowMr POW-SPH-6KW Hybrid Solar Inverter is designed for robust performance and ease of use. Below are the key components and their functions, along with an overview of the display and system architecture.
3.1 Physical Overview
3.2 Product Components and Connections
- Backup indicator
- Grid indicator
- Charge indicator
- Fault indicator
- LCD display
- Function buttons
- Wall rack
- Lifting handle
- Power on/off switch
- PV switch
- PV1 and PV2 input
- Parallel port
- DRMS port
- WIFI communication
- Main output
- DRY/METER port
- Battery communication/RS-485 port /Current Transformer
- Battery input
- Generator
- Second output
- GRID
3.3 Basic System Architecture
The inverter can be integrated into various energy systems. A typical setup includes a battery, generator or utility power, and PV modules. This inverter is capable of powering a wide range of home and office appliances.
3.4 Product Video Overview
4. Setup (Installation)
Proper installation is crucial for the safe and efficient operation of your inverter. Follow these steps carefully.
4.1 Unpacking and Inspection
Before installation, inspect the unit for any damage. Ensure all items are present in the package:
- Inverter Unit: 1
- User Manual: 1
- Wall Rack: 1
- WIFI Module: 1
- Current Transformer: 1
- Ring Terminal: 9
- Parallel Communication Line: 1
4.2 Preparation
Before connecting any lines, remove the screws under the machine and detach the bottom cover plate.
4.3 Mounting the Unit
Consider the following points when selecting an installation location:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install the inverter at eye level for easy reading of the LCD display.
- For proper air circulation and heat dissipation, allow approximately 20 cm clearance on the sides and 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C for optimal operation.
- The recommended installation position is vertically on a wall.
- Ensure sufficient space around the machine for adequate heat dissipation and wire removal.
CAUTION: Suitable for mounting on concrete or other non-combustible surfaces only.
The wall hanger should be fixed to the wall using six screws. Then, hang the inverter unit onto the wall hanger from top down. M5 screws are recommended.
4.4 Battery Connection
For safety and compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. Refer to the table below for typical amperage and recommended fuse/breaker size.
WARNING: All wiring must be performed by qualified personnel. Use appropriate cables for battery connection to ensure system safety and efficient operation.
| Model | Wire size | Cable(mm²) | Torque value(max) |
|---|---|---|---|
| 6KW/8KW | 1x 2AWG | 25 | 2N·m |
| 10KW/12KW | 1x 0AWG | 53 | 2N·m |
Steps for Battery Connection:
- Remove 18 mm of insulation sleeve from positive and negative conductors.
- It is recommended to use bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Connect all battery packs as shown in the diagram below.
- Insert the battery wires flatly into the inverter's battery connectors and ensure the bolts are tightened to a torque of 2 N·m in a clockwise direction. Verify correct polarity at both the battery and the inverter/charger, and ensure conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.
CAUTION: Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).
WARNING: Installation must be performed with care due to high battery voltage in series.
4.5 AC Input/Output Connection
CAUTION: Before connecting to the AC input power source, install a separate AC breaker between the inverter and the AC input power source. This ensures the inverter can be securely disconnected during maintenance and is protected from overcurrent. Recommended AC breaker specs: 50A for 6KW, 65A for 8KW, 85A for 10KW, 100A for 12KW. There are two terminal blocks labeled "IN" and "OUT". Do NOT mis-connect input and output connectors.
WARNING: All wiring must be performed by qualified personnel. Use appropriate cables for AC input connection for system safety and efficient operation.
| Model | Wire size | Cable(mm²) | Torque value(max) |
|---|---|---|---|
| 6KW/8KW | 10AWG | 6 | 1.2N·m |
| 10KW/12KW | 8AWG | 6 | 1.2N·m |
Steps for AC Input/Output Connection:
- Before making AC input/output connections, ensure the DC protector or disconnector is open.
- Remove 10mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3mm.
- Insert AC input wires according to the polarities indicated on the terminal block and tighten the terminal screws. Ensure the PE protective conductor (Ground) is connected first.
- Then, insert AC output wires according to the polarities indicated on the terminal block and tighten the terminal screws.
- Ensure all wires are securely connected.
CAUTION: Appliances like air conditioners require 2-3 minutes to restart to balance refrigerant gas. If a power shortage occurs and recovers quickly, it can damage connected appliances. Check if your air conditioner has a time-delay function. Otherwise, the inverter may trigger an overload fault and cut off output, but internal damage to the appliance may still occur.
4.6 PV Connection
CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules. It is required to use a PV junction box with surge protection.
WARNING: This inverter is non-isolated. Only single crystalline, poly crystalline (Class A-rated), and CIGS modules are acceptable. Do not connect PV modules with possible current leakage to the inverter. Ensure no grounding when using CIGS modules. Use appropriate cables for PV module connection.
| Model | Wire size | Cable(mm²) | Torque value(max) |
|---|---|---|---|
| 6KW/8KW/10KW/12KW | 1x 10AWG | 6 | 1.2N·m |
PV Module Selection: When selecting PV modules, consider the following parameters:
- Open circuit Voltage (Voc) of PV modules must not exceed the inverter's maximum PV array open circuit voltage (520Vdc).
- Open circuit Voltage (Voc) of PV modules should be higher than the minimum battery voltage.
| Inverter Model | 6KW/8KW/10KW/12KW |
|---|---|
| Max. PV Array Open Circuit Voltage | 520Vdc |
| PV Array MPPT Voltage Range | 50Vdc~500Vdc |
PV Module Wire Connection Steps:
- Check the input voltage of PV array modules. The acceptable input voltage of the inverter is 50 VDC ~520VDC. Ensure the maximum current load of each PV input connector is 18A.
- Disconnect the DC circuit breaker.
- Assemble provided PV connectors with PV modules.
- Check correct polarity of connection cable from PV modules and PV input connectors. Connect positive pole (+) of connection cable to positive pole (+) of PV input connector, and negative pole (-) of connection cable to negative pole (-) of PV input connector.
CAUTION: Exceeding the maximum input voltage can destroy the unit! Check the system before wire connection.
4.7 Current Transformer Connection
Connect the CT connector at the bottom of the machine. Connect the left terminal to the positive terminal and the right terminal to the negative terminal.
4.8 Final Assembly
After all wires are connected, replace the bottom cover and tighten the screws.
4.9 Dry Contact Signal
There is one dry contact (3A/250VAC) available on the rear panel. It can be used to deliver a signal to an external device when the battery voltage reaches a warning level.
| Unit Status | Condition | NC&C | NO&C |
|---|---|---|---|
| Power Off | Unit is off and no output is powered | Close | Open |
| Power On | Mains mode | Close | Open |
| Non-mains mode (Battery voltage < stop discharge voltage or stop discharge SOC) | Open | Close | |
| Non-mains mode (Battery voltage > Re-discharge voltage or Re-discharge SOC) | Close | Open |
5. Operation
This section details how to operate your PowMr Hybrid Solar Inverter, including power control and LCD display navigation.
5.1 Power ON/OFF
Once the unit is properly installed, press the power switch (located on the bottom of the case) to turn on the unit.
5.2 Operation and Display Panel
The front panel of the inverter features an LCD display, second indicators, and four function keys. These provide information on operating status and input/output power.
Indicator Lights:
| Indicator Light | Messages |
|---|---|
| BACKUP (Green Solid On) | Output is powered by battery or PV in battery mode. |
| GRID (Green Solid On) | Output is powered by utility in Line mode. |
| CHG (Green Solid On) | Battery is fully charged. |
| CHG (Green Flashing) | Battery is charging. |
| FAULT (Red Solid On) | Fault occurs in the inverter. |
Function Keys:
| Function key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
5.3 LCD Display Icons
The LCD is a touchscreen display showing overall inverter information. The main screen includes icons for PV (left up), grid (right up), load (right bottom), and battery (left bottom), displaying energy flow direction by moving dots.
Icon Descriptions:
- System Status Icon: Indicates if the system is under normal operation, displaying "ON".
- PV Input Icon: Indicates PV input voltage, current, and power.
- Battery Icon: Indicates battery voltage, current, and power.
- Grid Icon: Indicates grid voltage, current, and power.
- Load Icon: Indicates load voltage, current, and power.
- Generator Icon: Indicates generator voltage, current, and power (not displayed if generator voltage is below 50V).
- History Error Icon: Click to enter the History Error Page and view error codes.
- Date and Time: Displays the data and local time, which must be set during commissioning.
- Settings Icon: Accesses pages for Battery Setting (1, 2, 3), Work Mode, Time Of Use, Grid Setting, Basic Setting, and History Error.
- SUB (Work Mode): Indicates the current work mode.
System Status Clarifications:
- PV power will always be positive.
- In a single inverter system, load power will always be positive.
- A negative Grid power means energy is being exported to the grid (sold), while positive means energy is being imported from the grid (purchased).
- Negative battery power means charge, positive means discharge.
5.4 LCD Display Settings
The LCD allows configuration of various parameters. To access settings, you may need to enter a password (default: 123456).
Key Settings Include:
- Battery Settings (Page 1, 2, 3): Configure battery type (User-Define, PACE_485, PYLON_485), equalization, BMS error handling, lithium activation, EPS mode, and communication protocol. Adjust constant voltage, float voltage, maximum charging current, grid charging current, maximum charging SOC, battery equalization voltage and timeout, equalization interval, discharging current, under voltage/SOC, stop discharge voltage/SOC, re-discharge voltage/SOC, and EPS off voltage/SOC.
- Work Mode Settings: Select between SUB (Solar Utility Battery), SBU (Solar Battery Utility), MKS (PV first, then SBU/SUB), and Selfuse (PV and battery supply loads simultaneously).
- Time Of Use Settings: Program specific periods for grid charging and battery discharge to power loads.
- Basic Settings: Set date and time, clear PV/Load/Grid data, reset to default, enable/disable LCD sleep, and control buzzer sound.
- Grid Settings: Select country, output frequency (50Hz/60Hz), output voltage (220V/230V/240V), enable/disable feed-in to grid, GFCI check, CT enable, and CT radio adjustment.
- History Error Page: View software version and historical error codes.
6. Parallel Function
The PowMr Hybrid Solar Inverter supports parallel operation to increase total output power and meet higher load demands. It can operate in single-phase or three-phase configurations.
6.1 Introduction
- Parallel operation in single phase supports up to 6 units, with a maximum output power of 36 KW/36 KVA.
- Three-phase parallel operation supports up to three units working together.
6.2 Mounting the Unit for Parallel Operation
When installing multiple units, ensure proper spacing for air circulation and heat dissipation. Allow approximately 20 cm clearance on the sides and 50 cm above and below each unit. All units should be installed at the same level.
6.3 Wiring Connection for Parallel Operation
WARNING: It is REQUIRED to connect a battery for parallel operation. Ensure all battery cables are of the same length to avoid voltage differences that could prevent parallel inverters from working.
CAUTION: Install breakers at the battery and AC input sides to ensure secure disconnection during maintenance and protection from overcurrent.
For multiple units, use a connector or bus-bar as a joint to connect battery cables. The cable size from the joint to the battery should be X times the cable size listed in the tables (where X is the number of inverters in parallel). The same principle applies to AC input and output wiring.
6.4 Parallel Operation in Single Phase
The FLW-SPH-6KW offers powerful scalability, supporting up to six inverters in parallel with a total capacity of 36kW to easily meet higher load demands. This allows for flexible deployment, enhancing single-phase output.
Example Power Connections:
Similar diagrams are available in the full PDF manual for 4, 5, and 6 units in parallel.
6.5 Support 3-Phase Equipment
For three-phase applications, one inverter is used per phase. This configuration allows for forming a three-phase system to suit industrial and commercial applications.
Important Notes for 3-Phase Setup:
- All inverters must be connected to the “PARALLEL” port to avoid malfunction or damage.
- If increasing the number of inverters in a phase, add them in parallel as described above, and connect additional cables directly to that phase line.
- Ensure at least one inverter per phase is present for normal output.
- Single-phase parallel supports up to six units; three-phase parallel supports up to three units.
- The first and last parallel inverter's communication board's “SW1” switch should be set to ON.
7. Wi-Fi Connection Instructions
The inverter features a built-in Wi-Fi module for remote monitoring via a mobile application.
7.1 APP Download
You can download the "SUN WISE" app using one of the following methods:
- Scan the QR code provided in the manual.
- Scan the QR code on the film of the collector.
- Search for "SUN WISE" in your application market.
7.2 Registered Account
On the App home page, click "Sign Up", fill in the required information, and complete the registration.
7.3 Supporting Network and Adding Device
Wi-Fi Collector Connection Router:
- After the PWR indicator on the collector is on, enable Bluetooth on your mobile phone and open the SUN WISE App. Click the “Wi-Fi Configuration” button to enter the “Searching” page. The app will automatically display nearby Bluetooth devices.
- Select the collector to be distributed, enter the matching webpage, and click the search icon to choose the Wi-Fi hotspot name.
Add Device:
- On the App homepage, click “+” in the upper right corner to enter the device adding page. Bring your mobile phone close to the device, and the app will automatically scan for the device.
- After scanning, select the ID that matches the collector tag ID and click “Add”. (Note: Confirm the collector ID before scanning. If the ID is not on the machine surface, view it on the matching page.)
- Alternatively, you can manually add the device by entering the collector ID, name, and other information.
- You can also scan the QR code ID number on the collector film to add the device.
7.4 Collector Fault Diagnose and Indicator Light Judgment
After the device distribution network is completed or fails, you can diagnose the fault by clicking "Diagnose" in the upper right corner of the app.
Indicator Light Status:
- PWR (Power Indicator Light):
- On: Normal power supply.
- Off: Abnormal power supply.
- COM (Serial Port Transmission Indicator):
- Off: No data interaction.
- Off for 0.3 seconds, on for 0.9 seconds: Serial output data.
- Off for 0.3 seconds, on for 0.3 seconds: Serial receiving data.
- On: Bi-directional transfer.
- Net (Network Status Indicator):
- Off for 0.3 seconds, on for 3 seconds: STA mode connects the upper router.
- Off for 0.3 seconds, on for 0.3 seconds: STA is not connected to the upper router.
- SRV (Server Connection Indicator):
- On: Connected to the server.
- Off: Uninterrupted to the server.
8. Specifications
Detailed technical specifications for the PowMr POW-SPH-6KW Hybrid Solar Inverter.
8.1 Line Mode Specifications
| Parameter | Specification (6KW) |
|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) |
| Nominal Input Voltage | 230Vac |
| Low Loss Voltage | 170Vac±7V(UPS) |
| Low Loss Return Voltage | 180Vac±7V(UPS) |
| High Loss Voltage | 280Vac±7V |
| High Loss Return Voltage | 258Vac±7V |
| Max AC Input Voltage | 300Vac |
| Nominal Input Frequency | 50Hz/60Hz (Auto detection) |
| Low Loss Frequency | 45±1Hz |
| Low Loss Return Frequency | 46±1Hz |
| High Loss Frequency | 65±1Hz |
| High Loss Return Frequency | 63±1Hz |
| Output Short Circuit Protection | Circuit Breaker |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) |
| Transfer Time | 10ms typical (Single mode) |
8.2 Inverter Mode Specifications
| Parameter | Specification (6KW) |
|---|---|
| Rated Output Power | 6000W |
| Output Voltage Waveform | Pure Sine Wave |
| Output Voltage Regulation | 230Vac±5% |
| Output Frequency | 50Hz/60Hz |
| Peak Efficiency | 93% |
| Overload Protection | 3s @ ≥ 150% load; 5s @ 101%~150% load |
| Surge Capacity | 2* rated power for 5 seconds |
| Nominal DC Input Voltage | 48.0Vdc |
| Cold start Voltage | 46.0Vdc |
| Low DC Cut-off Voltage @ load < 50% | 41.0Vdc |
| Low DC Cut-off Voltage @ load ≥ 50% | 40.0Vdc |
| High DC Recovery Voltage | 62.0Vdc |
| High DC Cut-off Voltage | 63.0Vdc |
| No Load Power Consumption | 75W |
8.3 Two Load Output Power
| Parameter | Specification (6KW) |
|---|---|
| Full Load | 6000W |
| Maximum Main Load | 6000W |
| Maximum Second Load (battery model) | 4200W |
| Main Load Cut off Voltage | 50Vdc |
| Main Load Return Voltage | 54Vdc |
8.4 Charge Mode Specifications
Utility Charging Mode:
| Parameter | Specification (6KW) |
|---|---|
| Charging Algorithm | 3-Step |
| AC Charging Current (Max) | 135A |
| Bulk Charging Voltage (Flooded Battery) | 58.4Vdc |
| Bulk Charging Voltage (AGM / Gel Battery) | 56.4Vdc |
| Floating Charging Voltage | 54.0Vdc |
MPPT Solar Charging Mode:
| Parameter | Specification (6KW) |
|---|---|
| Max. PV Array Power (PV1 Channel) | 4500W |
| Max. PV Array Power (PV2 Channel) | 4500W |
| Max. PV Array Power (PV3 Channel) | 4500W |
| Max. PV Current (PV1 Channel) | 18A |
| Max. PV Current (PV2 Channel) | 18A |
| Max. PV Current (PV3 Channel) | 18A |
| Nominal PV Voltage | 360Vdc |
| PV Array MPPT Voltage Range | 50Vdc~500Vdc |
| Max. PV Array Open Circuit Voltage | 520Vdc |
| Max Charging Current (AC charger plus solar charger) | 135Amp |
8.5 Grid-Tie Operation
| Parameter | Specification (6KW) |
|---|---|
| Nominal Output Voltage | 220/230/240Vac |
| Feed-in Grid Voltage Range | 170Vac~260Vac |
| Feed-in Grid Frequency Range | 45Hz~65Hz |
| Nominal Output Current | 26.5A |
| Power Factor Range | >0.99 |
| Maximum Conversion Efficiency (DC/AC) | 98% |
8.6 General Specifications
| Parameter | Specification |
|---|---|
| Safety Certification | CE |
| Operating Temperature Range | -10°C ~ 50°C |
| Storage temperature | -15°C ~ 60°C |
| Humidity | 5% to 95% Relative Humidity (Non-condensing) |
| Size | 520x490x238mm |
| Weight | 25 kg |
9. Troubleshooting
This section provides solutions for common issues you might encounter with your inverter.
| Fault Code | Fault Event | Explanation/Possible cause | What to do |
|---|---|---|---|
| 01 | Fan Lock. | Fan is locked when inverter is on. | Replace the fan. |
| 02 | Over Temp. | The temperature exceeds the protection point. | Check if the air flow is blocked or if ambient temperature is too high. |
| 03 | Bat Vol High. | Battery voltage is too high. | Refer to battery specifications. |
| 05 | Output Short. | Output short-circuited. | Check wiring and remove abnormal load. |
| 06 | Output Vol High. | Output voltage is too high. | Check wiring and remove abnormal load. |
| 07 | Over Load. | Overload (if alarm is overloaded over three times, the machine will not start again.) | Reduce the connected load by switching off some equipment. |
| 08 | Bus Vol Over. | Bus voltage is over. | Reduce the connected load. Return to repair center. |
| 12 | Soft Start Fail. | Soft start failed. | Return to repair center. |
| 15 | Internal SCI Fail. | Internal communication fault. | Return to repair center. |
| 17 | LLC Fault. | LLC short-circuit. | Return to repair center. |
| 18 | BMS Error. | Lithium communication fault. | Return to repair center. |
| 19 | PV current over. | PV current is over. | Return to repair center. |
| 21 | GFCI Fault. | Leakage current fault. | Return to repair center. |
| 23 | PV ISO Fault. | PV isolation resistance is too low. | Return to repair center. |
| 25 | RELAY Check Fault. | Relay self-check failed. | Return to repair center. |
| 51 | Over Current. | Over current or surge. | Restart the unit. If the error happens again, return to repair center. |
| 52 | Bus Vol Under. | Bus voltage is too low. | Restart the unit. If the error happens again, return to repair center. |
| 53 | Inv Soft Fail. | Inverter soft start failed. | Restart the unit. If the error happens again, return to repair center. |
| 55 | Load DC Vol Over. | Over DC voltage in AC output. | Restart the unit. If the error happens again, return to repair center. |
| 57 | Current Hall Fault. | Current sensor failed. | Return to repair center. |
| 58 | Output Vol Under. | Output voltage is too low. | Reduce the connected load. Return to repair center. |
| 59 | PV Vol Over. | PV voltage is over limitation. | Restart the unit. If the error happens again, return to repair center. |
| 60 | Parallel Neg Power. | Parallel failure. | Return to repair center. |
| 71 | Parallel Version Diff. | Parallel version is inconsistent. | Update all inverter firmware to the same version. Check CPU versions. Contact installer if problem persists. |
| 75 | Parallel Setting Fault. | Parallel Settings are inconsistent. | Return to repair center. |
| 80 | Parallel CAN Loss. | Parallel communication failure. | Check communication cables and restart inverter. Contact installer if problem persists. |
| 81 | Host Line Loss. | Host signal Loss. | If the problem remains, contact your installer. |
| 82 | Syn phase Loss. | Synchronization signal Loss. | If the problem remains, contact your installer. |
| 86 | Parallel Mode Diff. | Parallel mode is incorrect. | Switch off inverter and check LCD setting "Parallel Mode". Ensure no 3P-PhaseA/B/C for single phase, and no "Parallel" for three-phase. Contact installer if problem persists. |
| 99 | Other Fault. | Other fault. | Return to repair center. |
10. User Tips
- Battery Compatibility: Ensure your chosen battery type is compatible with the inverter. Some users have reported issues with specific battery brands like Pylontech, so verify compatibility before purchase.
- Firmware Updates: Regularly check for and apply firmware updates to ensure optimal performance and resolve potential issues, especially in parallel configurations.
- Professional Installation: Due to the complexity and high voltage involved, it is highly recommended to have the inverter installed by qualified personnel.
11. Warranty and Support
For any technical assistance, warranty claims, or further inquiries, please contact PowMr customer support.
- Company: SHENZHEN HEHEJIN INDUSTRIAL CO.,LTD
- Tel/Fax: +86755-28219903
- Email: support@powmr.com
- Web: www.powmr.com
- Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China
A detailed user manual in PDF format is available for download. You can access it via this link: PowMr Hybrid Inverter User Manual (PDF).