About This Manual
This manual provides comprehensive instructions for the assembly, installation, operation, and troubleshooting of your POWLAND Hybrid Solar Inverter/Charger. Please read it carefully before proceeding with installation or operation and retain it for future reference. It includes safety guidelines, installation procedures, operational details, and technical specifications.
Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Refer service or repair to a qualified service center. Incorrect re-assembly may result in electric shock or fire.
- To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not eliminate this risk.
- CAUTION: Only qualified personnel can install this device with a battery.
- NEVER charge a frozen battery.
- For optimum operation, follow required specifications for appropriate cable size.
- Exercise extreme caution when working with metal tools on or around batteries to prevent sparks or short circuits.
- Strictly follow installation procedures when disconnecting AC or DC terminals.
- Fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS: This inverter/charger must be connected to a permanent grounded wiring system. Comply with local requirements and regulations.
- NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors persist after troubleshooting, contact your local dealer or service center.
Product Overview
Features
- Pure sine wave inverter
- Inverter running without battery
- Built-in MPPT solar controller
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible with mains voltage or generator power
- Auto restart while AC is recovering
- Overload/ Over temperature/ short circuit protection
- Smart battery charger design for optimized battery performance
- Cold start function
Basic System Architecture
The inverter/charger is designed for a complete running system, typically including a generator or utility, and optional PV modules. Consult your system integrator for specific architectural needs.

Product Components

- LCD display
- Status indicator
- Charging indicator
- Fault indicator
- Function buttons
- Power on/off switch
- Battery negative/positive outlet hole
- Parallel communication port (only for parallel model)
- RS232 communication port (RJ45)
- RS485 communication port (RJ45)
- RS232 communication port (DB9)
- Dry contact port
- PV1 input
- PV2 input
- AC input
- Grounding point
- Main output
- Second output
Note: RS232 communication port (DB9) and RS232 communication port (RJ45) cannot be used simultaneously; only one can be used at a time.
LCD Display Overview

Installation
Unpacking and Inspection
Before installation, carefully inspect the unit for any damage. The package should contain:
- The unit x 1
- User manual x 1
- PV connector x 4
- Battery fuse x 1 (Only 11K model)
Preparation
Before connecting any wirings, remove the bottom cover by unscrewing the four screws.
Mounting the Unit
Consider the following points when selecting an installation location:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install at eye level for easy LCD display readability.
- Ambient temperature should be between 0°C and 55°C for optimal operation.
- Recommended installation position is vertically adhered to the wall.
- Ensure sufficient clearance (as shown in the diagram) for heat dissipation and wire removal.
WARNING: Suitable for mounting on concrete or other non-combustible surfaces only.

Battery Connection
CAUTION:
- Install a separate DC over-current protector or disconnect device between the battery and inverter.
- All wiring must be performed by qualified personnel.
- Use appropriate cable for battery connection to ensure system safety and efficient operation.
Recommended battery cable and terminal size:
| Model | Maximum Amperage | Battery Capacity | Wire Size | Cable mm² | Terminal Size (mm) L x W x D | Torque Value |
|---|---|---|---|---|---|---|
| 8.5KVA | 180A | 400AH | 4AWG*2 | 25 | 37 x 22 x 8.4 | 10~12 Nm |
| 11.0KVA | 220A | 600AH | 2AWG*2 | 38 | 37 x 22 x 8.4 | 10~12 Nm |
Steps for battery connection:
- Prepare positive and negative cables based on recommended terminal size.
- Connect all battery packs as units require, using recommended battery capacity.
- Insert battery cables flatly into the inverter's battery connector. Ensure bolts are tightened with a torque of 10-12Nm. Verify correct polarity at both the battery and inverter/charger, and ensure battery cables are tightly screwed.

AC Input/Output Connection
CAUTION:
- Install a separate AC breaker between the inverter and AC input power source. Recommended AC breaker spec is 63A.
- There are two terminal blocks with “IN” and “OUT” markings. Do not mis-connect input and output connectors.
- All wiring must be performed by qualified personnel.
- Use appropriate cable for AC input connection.
Suggested cable requirement for AC wires:
| Model | Gauge | Torque Value |
|---|---|---|
| All Models | 6 AWG | 1.2~1.4Nm |
Steps for AC input/output connection:
- Before making AC input/output connections, ensure the DC protector or disconnector is open.
- Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3mm.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the screws. Connect PE protective conductor (yellow-green) first.
- Insert AC output wires according to polarities indicated on the terminal block and tighten the screws. Connect PE protective conductor (yellow-green) first.

CAUTION: Ensure AC wires are connected with correct polarity. Incorrect connection may cause utility short-circuits in dual output operation.
CAUTION: Appliances like air conditioners require a 2-3 minute restart delay. If the inverter experiences short power outages, it may damage connected appliances. Verify if your air conditioner has a time-delay function.
PV Connection
CAUTION:
- Install a separate DC circuit breaker between the inverter and PV modules.
- All wiring must be performed by qualified personnel.
- Use appropriate cable for PV module connection.
PV Module Selection Parameters:
- Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
Solar Charging Mode Specifications:
| INVERTER MODEL | 8.5KVA | 11.0KVA |
|---|---|---|
| Max. PV Array Open Circuit Voltage | 500VDC | |
| PV Array MPPT Voltage Range | 60VDC~500VDC | |
| Max. PV INPUT CURRENT | 18A*2 | |
Recommended module configurations (e.g., for 450Wp and 550Wp PV modules) are detailed in the full PDF manual.


PV Module Wire Connection Steps:
- Remove insulation sleeve 10mm for positive and negative conductors.
- Check correct polarity of connection cable from PV modules and PV input connectors. Connect positive pole (+) to positive pole (+) of PV input connector, and negative pole (-) to negative pole (-) of PV input connector.
- Ensure wires are securely connected.
Final Assembly
After connecting all wirings, replace the bottom cover by screwing the four screws back into place.
Operation
Power ON/OFF
Once the unit is properly installed and batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.
Operation and Display Panel
The operation and display panel on the front of the inverter includes three indicators, four function keys, and an LCD display, providing operating status and input/output power information.
| LED Indicator | Color | Messages |
|---|---|---|
| AC / INV | Green | Solid On: Output is powered by utility in Line mode. Flashing: Output is powered by battery or PV in battery mode. |
| CHG | Green | Solid On: Battery is fully charged. Flashing: Battery is charging. |
| FAULT | Red | Solid On: Fault occurs in the inverter. Flashing: Warning condition occurs in the inverter. |
| Function Keys | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
LCD Setting
- Press and hold the ENTER button for 3 seconds to enter setting groups mode.
- Use the UP or DOWN button to select setting groups (F0/F1/F2/F3/F4). Press ENTER to confirm or ESC to exit.
- Press ENTER to confirm selection groups or ESC to return to selection groups or exit.
Detailed settings for F0 (General Parameters), F1 (AC Output Parameters), F2 (Battery Parameters), F3 (Time Parameters), and F4 (System Parameters) are available in the full PDF manual.
Battery Equalization
The equalization function helps reverse negative chemical effects like stratification and remove sulfate crystals, optimizing battery capacity and lifespan. It is recommended to equalize batteries periodically.
How to Apply Equalization Function
- Enable battery equalization in monitoring LCD setting program 17 of F2.
- Apply the function by either: setting equalization interval in program 21 of F2, or activating equalization immediately in program 22 of F2.
When to Equalize
In the float stage, when the set equalization interval is reached or equalization is activated immediately, the controller will enter the Equalize stage.

Equalize Charging Time and Timeout
During the Equalize stage, the controller supplies power to charge the battery until it reaches the battery equalization voltage. Constant-voltage regulation maintains this voltage. The battery remains in Equalize stage until the set equalized time is reached.

Setting for Lithium Battery
Lithium Battery Connection
If using a lithium battery, ensure it is a compatible model. There are two connectors on the lithium battery: RS485 port of BMS and power cable.
Steps for lithium battery connection:
- Assemble battery terminals based on recommended battery cable and terminal size (same as Lead-acid batteries).
- Connect the RS485 port of the battery to the BMS (RS485) communication port of the inverter.
Lithium Battery Communication and Setting
Connect the BMS communication cable between the lithium battery and the inverter. This cable transmits information and signals, including:
- Re-configuring charging voltage, charging current, and battery discharge cut-off voltage according to lithium battery parameters.
- Inverter starting or stopping charging based on lithium battery status.
Ensure the lithium battery RS485 port connects to the inverter's RS485 port pin-to-pin. The communication cable is included in the package.

Setting for Lithium Battery Without Communication
If using a lithium battery without communication, follow these steps to prevent BMS protection issues:
- Set battery type as "LIB" in program 01 of F2.
- Set C.V voltage as Max charging voltage of BMS - 0.5V in program 03 of F2.
- Set floating charging voltage as C.V voltage in program 03 of F2.
- Set Low DC cut-off voltage ≥ discharging protection voltage of BMS + 3V.
- Set Max charging current in program 09 of F2, ensuring it is less than the Max charging current of BMS.
- Set voltage point back to utility source when selecting "SBU priority" in program 05 of F2. The setting value must be ≥ Low DC cut-off voltage + 2V, otherwise the inverter will warn of low battery voltage.
Remark: It is recommended to complete these settings without turning on the inverter (no output). After setting, restart the inverter.
Parallel Installation Guide
Instruction
This inverter supports parallel operation in two modes:
- Parallel operation in single phase with up to 6 units. Maximum supported output power is 8.5KW-8.5KVA/11KW-11KVA *6pcs.
- Maximum 6 units can work together to support three-phase equipment. 4 units support one phase maximum.
Note: If this unit is bundled with a parallel cable, it defaults to supporting parallel operation.
Package Contents (Parallel Kit)
The parallel kit includes a parallel communication cable.
Mounting the Unit (Parallel)
For proper air circulation and heat dissipation, allow a clearance of approximately 20 cm to the sides and 50 cm above and below each unit. Ensure all units are installed at the same level.
Wiring Connection (Parallel)
NOTICE: It is required to connect to the battery for parallel operation.
Ensure all battery cables are of the same length to prevent voltage differences that could hinder parallel operation. Use a connector or bus-bar to join battery cables, then connect to the battery terminal. The cable size from the joint to the battery should be X times the cable size for a single unit, where X is the number of inverters in parallel.
Recommended breaker specification for battery for each inverter:
| Model | 1 unit* |
|---|---|
| 8.5KVA | 200A/60VDC |
| 11.0KVA | 250A/60VDC |
*If using only one breaker for the entire system, its rating should be X times the current of 1 unit, where X is the number of inverters in parallel.
CAUTION: Install breakers at the battery and AC input sides to ensure secure disconnection and over-current protection.
WARNING! All inverters must share the same battery bank; otherwise, they will enter fault mode.
Communicating with Battery BMS in Parallel System
- Only common battery installation is supported.
- Use an RJ45 cable to connect any one of the inverters to the lithium battery.
- Set the battery type of this inverter to "Li 2" in LCD program 01(F2). Other inverters should retain the default "AGM" value.
Note: Ensure only one inverter is connected via RJ45 cable and set as Lithium in LCD program 01(F2).
Parallel Operation in Single Phase



Support 3-Phase Equipment

PV Connection (Parallel)
CAUTION: Each inverter should connect to PV modules separately.
Commissioning
Parallel in Single/Three Phase
- Step 1: Check correct wire connections and ensure all breakers in the Line wires of the load side are open, and all Neutral wires of each unit are connected.
- Step 2: Turn on each unit and set “PAL” or “3Px” in LCD setting program 02(F1) of each unit. Then shut down all units.
Note: It is necessary to turn off each unit (keep power on) when setting the LCD program. Otherwise, the setting cannot be programmed.
- Step 3: Turn on each unit.
Note: Master and slave units are randomly defined. If it is a master, the icon P flashes; if it is a slave unit, the icon P is normally on.
- Step 4: Switch on all AC breakers of Line wires in AC input. It is best to have all inverters connect to utility at the same time. If AC connection is detected, they will work normally.
- Step 5: If there is no more fault alarm, the parallel system is completely installed.
- Step 6: Switch on all breakers of Line wires in the load side. The system will then start to provide power to the load.
Troubleshooting
This section provides common fault codes, warning events, and their corresponding solutions.
| Fault Code | Situation / Fault Event Description | Solution |
|---|---|---|
| E0 | Host data loss | 1. Check if communication cables are connected well and restart the inverter. 2. If the problem remains, contact your installer. |
| E1 | Synchronization data loss | 1. Check if communication cables are connected well and restart the inverter. 2. If the problem remains, contact your installer. |
| E2 | Incompatible battery type | 1. Check the battery type setting to ensure that only the device connected to the BMS in the system is one of Li1 or Li2 or Li3. 2. If the problem remains, contact your installer. |
| E3 | Firmware version inconsistent | 1. Update all inverter firmware to the same version. 2. Check the version of each inverter via LCD setting and make sure the CPU versions are same. If not, contact your installer to provide the firmware to update. 3. After updating, if the problem remains, contact your installer. |
| Warning Code | Situation / Warning Event Description | Solution |
|---|---|---|
| 0E | CAN communication loss | 1. Check if communication cables are connected well and restart the inverter. 2. If the problem remains, contact your installer. |
| 1E | AC output mode setting is different. | 1. Switch off the inverter and check LCD setting program 02(F1). 2. For parallel system in single phase, make sure “PAL” is set on program 02(F1). 3. If the problem remains, contact your installer. |
| 2E | The battery voltage of each inverter is not the same. | 1. Make sure all inverters share same groups of batteries together. 2. Remove all loads and disconnect AC input and PV input. Then, check battery voltage of all inverters. If the values from all inverters are close, check if all battery cables are the same length and same material type. Otherwise, contact your installer to provide SOP to calibrate battery voltage of each inverter. 3. If the problem remains, contact your installer. |
Specifications
Table 1 Line Mode Specifications
| INVERTER MODEL | 8.5KVA | 11.0KVA |
|---|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) | |
| Nominal Input Voltage | 230Vac | |
| Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) | |
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) | |
| High Loss Voltage | 280Vac±7V | |
| High Loss Return Voltage | 270Vac±7V | |
| Max AC Input Voltage | 300Vac | |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | |
| Low Loss Frequency | 40±1Hz | |
| Low Loss Return Frequency | 42±1Hz | |
| High Loss Frequency | 65±1Hz | |
| High Loss Return Frequency | 63±1Hz | |
| Output Short Circuit Protection | Battery mode: Electronic Circuits | |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | |
Table 2 Inverter Mode Specifications
| INVERTER MODEL | 8.5KVA | 11.0KVA |
|---|---|---|
| Rated Output Power | 8.5KVA/8.5KW | 11.0KVA/11.0KW |
| Parallel Capability | YES, 6units | YES, 6units |
| Dual output function | Yes | |
| Max.main output power | 8.5KVA/8.5KW | 11.0KVA/11.0KW |
| Max.second output power | 5.0KVA/5.0KW | 5.5KVA/5.5KW |
| Output Voltage Waveform | Pure Sine Wave | |
| Output Voltage Regulation | 230Vac±5% | |
| Output Frequency | 60Hz or 50Hz | |
| Peak Efficiency | 94% | |
| Overload Protection | 5.5s@≥140% load; 10.5s@100%~140% load | |
| Surge Capacity | 2* rated power for 5 seconds | |
| Nominal DC Input Voltage | 48Vdc | |
| Cold Start Voltage | 46.0Vdc | |
| Low DC Warning Voltage (Just for AGM and Flooded) | @load < 20%: 44.0Vdc; @20% ≤ load < 50%: 42.8Vdc; @load ≥ 50%: 40.4Vdc | |
| Low DC Warning Return Voltage (Just for AGM and Flooded) | @load < 20%: 46.0Vdc; @20% ≤ load < 50%: 44.8Vdc; @load ≥ 50%: 42.4Vdc | |
| Low DC Cut-off Voltage (Just for AGM and Flooded) | When OP2 is allowed: OP1: 45.2Vdc, OP2: 42.0Vdc; When OP2 is forbidden: OP1: 45.2Vdc | |
Table 3 Charge Mode Specifications (Utility Charging Mode)
| INVERTER MODEL | 8.5KVA | 11.0KVA |
|---|---|---|
| Charging Current (Max) (AC+PV) | 140Amp | 160Amp |
| AC Charging Current (Max) | 120Amp (@VI/P=230Vac) | |
| Bulk Charging Voltage (Flooded Battery) | 58.4Vdc | |
| Bulk Charging Voltage (AGM / Gel Battery) | 56.4Vdc | |
| Floating Charging Voltage | 54Vdc | |
| Overcharge Protection | 63Vdc | |
| Charging Algorithm | 3-Step | |
Table 4 General Specifications
| INVERTER MODEL | 8.5KVA | 11.0KVA |
|---|---|---|
| Safety Certification | CE | |
| Operating Temperature Range | -10°C to 55°C | |
| Storage temperature | -15°C~60°C | |
| Humidity | 5% to 95% Relative Humidity (Non-condensing) | |
| Dimension(D*W*H), mm | 540x403x122 | |
| Net Weight, kg | 14.4 | 14.8 |
User Tips
- Ease of Installation: Users have noted that the product is versatile and powerful, with straightforward installation. Following the manual's instructions carefully should lead to immediate operation.
- Packaging: The product typically arrives in sturdy packaging, ensuring safe delivery.
Warranty & Support
For warranty information, technical support, or service inquiries, please contact your authorized POWLAND dealer or service center. Refer to your purchase documentation for specific warranty terms and conditions.
A complete user manual in PDF format is available here for detailed reference.