Contents

POWLAND Hybrid Solar Inverter/Charger

Model: SMG-III-11KW-Wifi

Brand: POWLAND

About This Manual

This manual provides comprehensive instructions for the assembly, installation, operation, and troubleshooting of your POWLAND Hybrid Solar Inverter/Charger. Please read it carefully before proceeding with installation or operation and retain it for future reference. It includes safety guidelines, installation procedures, operational details, and technical specifications.

Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Refer service or repair to a qualified service center. Incorrect re-assembly may result in electric shock or fire.
  4. To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not eliminate this risk.
  5. CAUTION: Only qualified personnel can install this device with a battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation, follow required specifications for appropriate cable size.
  8. Exercise extreme caution when working with metal tools on or around batteries to prevent sparks or short circuits.
  9. Strictly follow installation procedures when disconnecting AC or DC terminals.
  10. Fuse is provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS: This inverter/charger must be connected to a permanent grounded wiring system. Comply with local requirements and regulations.
  12. NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors persist after troubleshooting, contact your local dealer or service center.

Product Overview

Features

  • Pure sine wave inverter
  • Inverter running without battery
  • Built-in MPPT solar controller
  • Configurable input voltage range for home appliances and personal computers via LCD setting
  • Configurable battery charging current based on applications via LCD setting
  • Configurable AC/Solar Charger priority via LCD setting
  • Compatible with mains voltage or generator power
  • Auto restart while AC is recovering
  • Overload/ Over temperature/ short circuit protection
  • Smart battery charger design for optimized battery performance
  • Cold start function

Basic System Architecture

The inverter/charger is designed for a complete running system, typically including a generator or utility, and optional PV modules. Consult your system integrator for specific architectural needs.

Figure 1 Hybrid Power System Diagram
Figure 1: Hybrid Power System Diagram. This diagram illustrates the connections between solar power, generator/utility, the hybrid solar inverter, external battery packs, and home appliances.

Product Components

Inverter Front and Rear Panel Overview
Inverter Front and Rear Panel Overview. The image shows the LCD display, status indicators, function buttons, and various ports including AC input/output, PV input, communication ports (RS232, RS485, BMS), and battery connections.
  1. LCD display
  2. Status indicator
  3. Charging indicator
  4. Fault indicator
  5. Function buttons
  6. Power on/off switch
  7. Battery negative/positive outlet hole
  8. Parallel communication port (only for parallel model)
  9. RS232 communication port (RJ45)
  10. RS485 communication port (RJ45)
  11. RS232 communication port (DB9)
  12. Dry contact port
  13. PV1 input
  14. PV2 input
  15. AC input
  16. Grounding point
  17. Main output
  18. Second output

Note: RS232 communication port (DB9) and RS232 communication port (RJ45) cannot be used simultaneously; only one can be used at a time.

LCD Display Overview

Detailed LCD Display Interface
Detailed LCD Display Interface. This image highlights the various icons and indicators on the LCD screen, providing real-time information about the inverter's status, input/output, battery, and PV.

Installation

Unpacking and Inspection

Before installation, carefully inspect the unit for any damage. The package should contain:

  • The unit x 1
  • User manual x 1
  • PV connector x 4
  • Battery fuse x 1 (Only 11K model)

Preparation

Before connecting any wirings, remove the bottom cover by unscrewing the four screws.

Mounting the Unit

Consider the following points when selecting an installation location:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install at eye level for easy LCD display readability.
  • Ambient temperature should be between 0°C and 55°C for optimal operation.
  • Recommended installation position is vertically adhered to the wall.
  • Ensure sufficient clearance (as shown in the diagram) for heat dissipation and wire removal.

WARNING: Suitable for mounting on concrete or other non-combustible surfaces only.

Inverter Mounting Dimensions
Inverter Mounting Dimensions. The diagram shows recommended clearances of 20cm on sides and 50cm above/below for proper ventilation.

Battery Connection

CAUTION:

  • Install a separate DC over-current protector or disconnect device between the battery and inverter.
  • All wiring must be performed by qualified personnel.
  • Use appropriate cable for battery connection to ensure system safety and efficient operation.

Recommended battery cable and terminal size:

ModelMaximum AmperageBattery CapacityWire SizeCable mm²Terminal Size (mm) L x W x DTorque Value
8.5KVA180A400AH4AWG*22537 x 22 x 8.410~12 Nm
11.0KVA220A600AH2AWG*23837 x 22 x 8.410~12 Nm

Steps for battery connection:

  1. Prepare positive and negative cables based on recommended terminal size.
  2. Connect all battery packs as units require, using recommended battery capacity.
  3. Insert battery cables flatly into the inverter's battery connector. Ensure bolts are tightened with a torque of 10-12Nm. Verify correct polarity at both the battery and inverter/charger, and ensure battery cables are tightly screwed.
Battery Connection Diagram
Battery Connection Diagram. This diagram illustrates how to connect 24V batteries in series to form a 48V system for the 12KW model.

AC Input/Output Connection

CAUTION:

  • Install a separate AC breaker between the inverter and AC input power source. Recommended AC breaker spec is 63A.
  • There are two terminal blocks with “IN” and “OUT” markings. Do not mis-connect input and output connectors.
  • All wiring must be performed by qualified personnel.
  • Use appropriate cable for AC input connection.

Suggested cable requirement for AC wires:

ModelGaugeTorque Value
All Models6 AWG1.2~1.4Nm

Steps for AC input/output connection:

  1. Before making AC input/output connections, ensure the DC protector or disconnector is open.
  2. Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3mm.
  3. Insert AC input wires according to polarities indicated on the terminal block and tighten the screws. Connect PE protective conductor (yellow-green) first.
  4. Insert AC output wires according to polarities indicated on the terminal block and tighten the screws. Connect PE protective conductor (yellow-green) first.
AC Input/Output Wiring Diagram
AC Input/Output Wiring Diagram. This diagram shows the correct connection of AC input and output wires, including ground, line, and neutral.

CAUTION: Ensure AC wires are connected with correct polarity. Incorrect connection may cause utility short-circuits in dual output operation.

CAUTION: Appliances like air conditioners require a 2-3 minute restart delay. If the inverter experiences short power outages, it may damage connected appliances. Verify if your air conditioner has a time-delay function.

PV Connection

CAUTION:

  • Install a separate DC circuit breaker between the inverter and PV modules.
  • All wiring must be performed by qualified personnel.
  • Use appropriate cable for PV module connection.

PV Module Selection Parameters:

  • Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
  • Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.

Solar Charging Mode Specifications:

INVERTER MODEL8.5KVA11.0KVA
Max. PV Array Open Circuit Voltage500VDC
PV Array MPPT Voltage Range60VDC~500VDC
Max. PV INPUT CURRENT18A*2

Recommended module configurations (e.g., for 450Wp and 550Wp PV modules) are detailed in the full PDF manual.

Solar System Connection Diagram
Solar System Connection Diagram. This diagram shows the overall connection of the hybrid solar inverter to solar panels, battery, and loads, including AC input and output.
Solar Photovoltaic Panel Wiring Method
Solar Photovoltaic Panel Wiring Method. This image illustrates how to wire solar panels in series to increase voltage and in parallel to increase current, with recommended PV cable dimensions.

PV Module Wire Connection Steps:

  1. Remove insulation sleeve 10mm for positive and negative conductors.
  2. Check correct polarity of connection cable from PV modules and PV input connectors. Connect positive pole (+) to positive pole (+) of PV input connector, and negative pole (-) to negative pole (-) of PV input connector.
  3. Ensure wires are securely connected.

Final Assembly

After connecting all wirings, replace the bottom cover by screwing the four screws back into place.

Operation

Power ON/OFF

Once the unit is properly installed and batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

Operation and Display Panel

The operation and display panel on the front of the inverter includes three indicators, four function keys, and an LCD display, providing operating status and input/output power information.

LED IndicatorColorMessages
AC / INVGreenSolid On: Output is powered by utility in Line mode.
Flashing: Output is powered by battery or PV in battery mode.
CHGGreenSolid On: Battery is fully charged.
Flashing: Battery is charging.
FAULTRedSolid On: Fault occurs in the inverter.
Flashing: Warning condition occurs in the inverter.
Function KeysDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

LCD Setting

  1. Press and hold the ENTER button for 3 seconds to enter setting groups mode.
  2. Use the UP or DOWN button to select setting groups (F0/F1/F2/F3/F4). Press ENTER to confirm or ESC to exit.
  3. Press ENTER to confirm selection groups or ESC to return to selection groups or exit.

Detailed settings for F0 (General Parameters), F1 (AC Output Parameters), F2 (Battery Parameters), F3 (Time Parameters), and F4 (System Parameters) are available in the full PDF manual.

Battery Equalization

The equalization function helps reverse negative chemical effects like stratification and remove sulfate crystals, optimizing battery capacity and lifespan. It is recommended to equalize batteries periodically.

How to Apply Equalization Function

  1. Enable battery equalization in monitoring LCD setting program 17 of F2.
  2. Apply the function by either: setting equalization interval in program 21 of F2, or activating equalization immediately in program 22 of F2.

When to Equalize

In the float stage, when the set equalization interval is reached or equalization is activated immediately, the controller will enter the Equalize stage.

Battery Equalization Voltage Stages
Battery Equalization Voltage Stages. This chart illustrates the Bulk, Absorption, Float, and Equalize voltage stages during battery charging.

Equalize Charging Time and Timeout

During the Equalize stage, the controller supplies power to charge the battery until it reaches the battery equalization voltage. Constant-voltage regulation maintains this voltage. The battery remains in Equalize stage until the set equalized time is reached.

Battery Equalization Charging Timeout
Battery Equalization Charging Timeout. This chart shows how the Equalize stage extends if the battery voltage doesn't reach the target within the set time, eventually returning to float stage if timeout is exceeded.

Setting for Lithium Battery

Lithium Battery Connection

If using a lithium battery, ensure it is a compatible model. There are two connectors on the lithium battery: RS485 port of BMS and power cable.

Steps for lithium battery connection:

  1. Assemble battery terminals based on recommended battery cable and terminal size (same as Lead-acid batteries).
  2. Connect the RS485 port of the battery to the BMS (RS485) communication port of the inverter.

Lithium Battery Communication and Setting

Connect the BMS communication cable between the lithium battery and the inverter. This cable transmits information and signals, including:

  • Re-configuring charging voltage, charging current, and battery discharge cut-off voltage according to lithium battery parameters.
  • Inverter starting or stopping charging based on lithium battery status.

Ensure the lithium battery RS485 port connects to the inverter's RS485 port pin-to-pin. The communication cable is included in the package.

RS485 Port Pin Assignment
RS485 Port Pin Assignment. This diagram shows the pinout for the RS485 communication port on the inverter.

Setting for Lithium Battery Without Communication

If using a lithium battery without communication, follow these steps to prevent BMS protection issues:

  1. Set battery type as "LIB" in program 01 of F2.
  2. Set C.V voltage as Max charging voltage of BMS - 0.5V in program 03 of F2.
  3. Set floating charging voltage as C.V voltage in program 03 of F2.
  4. Set Low DC cut-off voltage ≥ discharging protection voltage of BMS + 3V.
  5. Set Max charging current in program 09 of F2, ensuring it is less than the Max charging current of BMS.
  6. Set voltage point back to utility source when selecting "SBU priority" in program 05 of F2. The setting value must be ≥ Low DC cut-off voltage + 2V, otherwise the inverter will warn of low battery voltage.

Remark: It is recommended to complete these settings without turning on the inverter (no output). After setting, restart the inverter.

Parallel Installation Guide

Instruction

This inverter supports parallel operation in two modes:

  1. Parallel operation in single phase with up to 6 units. Maximum supported output power is 8.5KW-8.5KVA/11KW-11KVA *6pcs.
  2. Maximum 6 units can work together to support three-phase equipment. 4 units support one phase maximum.

Note: If this unit is bundled with a parallel cable, it defaults to supporting parallel operation.

Package Contents (Parallel Kit)

The parallel kit includes a parallel communication cable.

Mounting the Unit (Parallel)

For proper air circulation and heat dissipation, allow a clearance of approximately 20 cm to the sides and 50 cm above and below each unit. Ensure all units are installed at the same level.

Wiring Connection (Parallel)

NOTICE: It is required to connect to the battery for parallel operation.

Ensure all battery cables are of the same length to prevent voltage differences that could hinder parallel operation. Use a connector or bus-bar to join battery cables, then connect to the battery terminal. The cable size from the joint to the battery should be X times the cable size for a single unit, where X is the number of inverters in parallel.

Recommended breaker specification for battery for each inverter:

Model1 unit*
8.5KVA200A/60VDC
11.0KVA250A/60VDC

*If using only one breaker for the entire system, its rating should be X times the current of 1 unit, where X is the number of inverters in parallel.

CAUTION: Install breakers at the battery and AC input sides to ensure secure disconnection and over-current protection.

WARNING! All inverters must share the same battery bank; otherwise, they will enter fault mode.

Communicating with Battery BMS in Parallel System

  1. Only common battery installation is supported.
  2. Use an RJ45 cable to connect any one of the inverters to the lithium battery.
  3. Set the battery type of this inverter to "Li 2" in LCD program 01(F2). Other inverters should retain the default "AGM" value.

Note: Ensure only one inverter is connected via RJ45 cable and set as Lithium in LCD program 01(F2).

Parallel Operation in Single Phase

Two Inverters in Parallel Power Connection
Two Inverters in Parallel Power Connection. This diagram shows the power and communication connections for two inverters operating in parallel in a single-phase setup.
Three Inverters in Parallel Power Connection
Three Inverters in Parallel Power Connection. This diagram shows the power and communication connections for three inverters operating in parallel in a single-phase setup.
More Than Four Inverters in Parallel Power Connection
More Than Four Inverters in Parallel Power Connection. This diagram illustrates the power and communication connections for a system with more than four inverters in parallel.

Support 3-Phase Equipment

3-Phase Equipment Power Connection
3-Phase Equipment Power Connection. This diagram shows how to connect one inverter per phase (P1, P2, P3) for 3-phase equipment support.

PV Connection (Parallel)

CAUTION: Each inverter should connect to PV modules separately.

Commissioning

Parallel in Single/Three Phase

  1. Step 1: Check correct wire connections and ensure all breakers in the Line wires of the load side are open, and all Neutral wires of each unit are connected.
  2. Step 2: Turn on each unit and set “PAL” or “3Px” in LCD setting program 02(F1) of each unit. Then shut down all units.

    Note: It is necessary to turn off each unit (keep power on) when setting the LCD program. Otherwise, the setting cannot be programmed.

  3. Step 3: Turn on each unit.

    Note: Master and slave units are randomly defined. If it is a master, the icon P flashes; if it is a slave unit, the icon P is normally on.

  4. Step 4: Switch on all AC breakers of Line wires in AC input. It is best to have all inverters connect to utility at the same time. If AC connection is detected, they will work normally.
  5. Step 5: If there is no more fault alarm, the parallel system is completely installed.
  6. Step 6: Switch on all breakers of Line wires in the load side. The system will then start to provide power to the load.

Troubleshooting

This section provides common fault codes, warning events, and their corresponding solutions.

Fault CodeSituation / Fault Event DescriptionSolution
E0Host data loss1. Check if communication cables are connected well and restart the inverter.
2. If the problem remains, contact your installer.
E1Synchronization data loss1. Check if communication cables are connected well and restart the inverter.
2. If the problem remains, contact your installer.
E2Incompatible battery type1. Check the battery type setting to ensure that only the device connected to the BMS in the system is one of Li1 or Li2 or Li3.
2. If the problem remains, contact your installer.
E3Firmware version inconsistent1. Update all inverter firmware to the same version.
2. Check the version of each inverter via LCD setting and make sure the CPU versions are same. If not, contact your installer to provide the firmware to update.
3. After updating, if the problem remains, contact your installer.
Warning CodeSituation / Warning Event DescriptionSolution
0ECAN communication loss1. Check if communication cables are connected well and restart the inverter.
2. If the problem remains, contact your installer.
1EAC output mode setting is different.1. Switch off the inverter and check LCD setting program 02(F1).
2. For parallel system in single phase, make sure “PAL” is set on program 02(F1).
3. If the problem remains, contact your installer.
2EThe battery voltage of each inverter is not the same.1. Make sure all inverters share same groups of batteries together.
2. Remove all loads and disconnect AC input and PV input. Then, check battery voltage of all inverters. If the values from all inverters are close, check if all battery cables are the same length and same material type. Otherwise, contact your installer to provide SOP to calibrate battery voltage of each inverter.
3. If the problem remains, contact your installer.

Specifications

Table 1 Line Mode Specifications

INVERTER MODEL8.5KVA11.0KVA
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS); 90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS); 100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionBattery mode: Electronic Circuits
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)

Table 2 Inverter Mode Specifications

INVERTER MODEL8.5KVA11.0KVA
Rated Output Power8.5KVA/8.5KW11.0KVA/11.0KW
Parallel CapabilityYES, 6unitsYES, 6units
Dual output functionYes
Max.main output power8.5KVA/8.5KW11.0KVA/11.0KW
Max.second output power5.0KVA/5.0KW5.5KVA/5.5KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency60Hz or 50Hz
Peak Efficiency94%
Overload Protection5.5s@≥140% load; 10.5s@100%~140% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage48Vdc
Cold Start Voltage46.0Vdc
Low DC Warning Voltage (Just for AGM and Flooded)@load < 20%: 44.0Vdc; @20% ≤ load < 50%: 42.8Vdc; @load ≥ 50%: 40.4Vdc
Low DC Warning Return Voltage (Just for AGM and Flooded)@load < 20%: 46.0Vdc; @20% ≤ load < 50%: 44.8Vdc; @load ≥ 50%: 42.4Vdc
Low DC Cut-off Voltage (Just for AGM and Flooded)When OP2 is allowed: OP1: 45.2Vdc, OP2: 42.0Vdc; When OP2 is forbidden: OP1: 45.2Vdc

Table 3 Charge Mode Specifications (Utility Charging Mode)

INVERTER MODEL8.5KVA11.0KVA
Charging Current (Max) (AC+PV)140Amp160Amp
AC Charging Current (Max)120Amp (@VI/P=230Vac)
Bulk Charging Voltage (Flooded Battery)58.4Vdc
Bulk Charging Voltage (AGM / Gel Battery)56.4Vdc
Floating Charging Voltage54Vdc
Overcharge Protection63Vdc
Charging Algorithm3-Step

Table 4 General Specifications

INVERTER MODEL8.5KVA11.0KVA
Safety CertificationCE
Operating Temperature Range-10°C to 55°C
Storage temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension(D*W*H), mm540x403x122
Net Weight, kg14.414.8

User Tips

  • Ease of Installation: Users have noted that the product is versatile and powerful, with straightforward installation. Following the manual's instructions carefully should lead to immediate operation.
  • Packaging: The product typically arrives in sturdy packaging, ensuring safe delivery.

Warranty & Support

For warranty information, technical support, or service inquiries, please contact your authorized POWLAND dealer or service center. Refer to your purchase documentation for specific warranty terms and conditions.