1. Introduction
The GEYA GYHO9 Manual Transfer Switch (MTS) is designed to manually transfer power between a main power source and an alternate (standby) power source. This device is crucial for ensuring continuous power supply to a load during utility failures by allowing the user to switch to a backup power source. When installed correctly, the GYHO9 MTS provides a reliable and straightforward method for managing power transfer.
This manual provides essential information for the safe and effective installation, operation, and maintenance of your GYHO9 Manual Transfer Switch.
2. Safety Information
- Installation and maintenance should only be performed by qualified personnel.
- Always disconnect all power sources before working on the switch or associated wiring.
- Ensure proper grounding to prevent electrical shock.
- Verify all connections are secure and tightened to the specified torque.
- Do not operate the switch if it appears damaged or malfunctioning.
3. Product Features
- Manual Transfer: Allows for manual switching between main and standby power sources.
- Indicator Lights: Clearly marked power positions with indicator lights (Red, Green, Yellow) to show the active power source.
- Label Window: Integrated window for easy and clear labeling of power sources.
- Din Rail Mounting: Designed for easy installation on a standard Din Rail.
- Poles: Available in 1P, 2P, 3P, and 4P configurations.
- Rated Current: Available in 63A and 125A versions.

4. Setup and Installation
4.1 Mounting
The GYHO9 MTS is designed for Din Rail mounting. Ensure the Din Rail is securely fastened within an appropriate enclosure, such as a distribution box, to protect the switch from environmental factors and accidental contact.
4.2 Wiring Connections
Refer to the circuit diagrams below for correct wiring based on the number of poles (1P, 2P, 3P, 4P) of your GYHO9 MTS. Always ensure that the main power source and standby power source are clearly identified and connected to their respective terminals.

4.3 Cable Size
Ensure that the correct cable sizes are used for your installation to prevent overheating and ensure safe operation.
- For 63A models: Maximum cable size is 10mm².
- For 100A and 125A models: Maximum cable size is 50mm².
4.4 Dimensions
Consider the physical dimensions of the switch for proper enclosure selection and installation planning.


5. Operating Instructions
The GYHO9 MTS features a knob with three distinct positions for power transfer:
- Position '1': Main Power ON. The load is connected to the main power source. The indicator window will show Red.
- Position 'O': OFF. Both main and standby power sources are disconnected from the load. The indicator window will show Green.
- Position '2': Standby Power ON. The load is connected to the standby (alternate) power source. The indicator window will show Yellow.
To transfer power:
- If currently on Main Power (Position '1'), rotate the knob to Position 'O' (OFF) to disconnect the main power.
- Wait a few moments to ensure all power is dissipated.
- Rotate the knob to Position '2' (Standby Power ON) to connect the load to the standby power source.
- To switch back to Main Power, reverse the process: '2' -> 'O' -> '1'.

6. Maintenance
The GEYA GYHO9 MTS is designed for durability with a mechanical life of 10,000 cycles. Regular maintenance is minimal but important for ensuring long-term reliability:
- Visual Inspection: Periodically inspect the switch for any signs of physical damage, discoloration, or loose connections.
- Terminal Tightness: Ensure all wiring terminals remain tight. Loose connections can lead to overheating and potential hazards.
- Cleanliness: Keep the switch free from dust, dirt, and moisture. Use a dry, soft cloth for cleaning. Do not use abrasive cleaners or solvents.
- Operational Check: Occasionally cycle the switch through its positions (1-O-2) to ensure smooth operation and proper indicator light function.
7. Troubleshooting
If you encounter issues with your GYHO9 MTS, consider the following basic troubleshooting steps:
- No Power to Load:
- Check if the switch is in the correct 'ON' position (1 or 2).
- Verify that the main or standby power source is active and supplying power.
- Inspect all wiring connections for tightness and proper contact.
- Check upstream circuit breakers or fuses for trips.
- Indicator Lights Not Working:
- Ensure the switch is receiving power.
- If power is present and lights are still off, the indicator mechanism may be faulty.
- Difficulty in Switching:
- Do not force the knob. Ensure there are no obstructions.
- If the mechanism feels stiff, it might require professional inspection.
If the problem persists after performing these checks, contact a qualified electrician or GEYA customer support for assistance.
8. Specifications
| Attribute | Specification |
|---|---|
| Brand Name | GEYA |
| Model Number | GYHO9 MTS |
| Type | Mini Circuit breaker, Manual Transfer Isolating Switch |
| Rated Voltage Ue | AC220/400V (220/380V) |
| Rated Current | 63A, 125A |
| Poles | 1P, 2P, 3P, 4P |
| Rated Frequency | 50/60Hz |
| Standard | IEC/EN60947-3 |
| Mounting | Din Rail |
| Mechanical Life | 10000 Cycles |
| Cable Size 63A | Max 10mm² |
| Cable Size 100A 125A | Max 50mm² |
| Certification | CE |
| Origin | Mainland China |
| Is Smart Device | No |
| High-concerned chemical | None |
| New Design | with Indicator Red Green Yellow Color |
9. User Tips
- Professional Installation: For safety and optimal performance, it is highly recommended to have the GYHO9 MTS installed by a certified electrician.
- Clear Labeling: Utilize the label window feature to clearly mark your main and standby power sources. This helps prevent confusion during operation, especially in emergency situations.
- Regular Checks: Periodically test your standby power source and the transfer switch operation to ensure readiness for power outages.
- Enclosure Protection: Always install the switch within a suitable electrical enclosure to protect it from dust, moisture, and physical damage, extending its lifespan.
10. Warranty and Support
For warranty information, technical support, or any product-related inquiries, please contact GEYA customer service or your authorized dealer. Ensure you have your product model number and purchase details available when contacting support.
GEYA Contact Information:
- Website: www.geya.net
- Email: cassie@cngeya.com
- Phone: +86 13968799499
- Address: Wenzhou Bridge Industrial Zone, Beibaixiang Town, Wenzhou City, Zhejiang Province, China