EASUN POWER SMG 6.2KP

EASUN POWER 6.2KW Hybrid Solar Inverter

Model: SMG 6.2KP

User Manual

1. Introduction

1.1 Purpose

This manual describes the assembly, installation, operation, and troubleshooting of the EASUN POWER 6.2KW Hybrid Solar Inverter. Please read this manual carefully before installation and operation, and keep it for future reference.

1.2 Scope

This manual provides safety and installation guidelines, as well as information on tools and wiring for the inverter.

1.3 Features

  • Pure sine wave inverter
  • Inverter running without battery
  • Built-in MPPT solar controller
  • Configurable input voltage range for home appliances and personal computers via LCD setting
  • Configurable battery charging current based on applications via LCD setting
  • Configurable AC/Solar Charger priority via LCD setting
  • Compatible with mains voltage or generator power
  • Auto restart while AC is recovering
  • Overload/Over temperature/short circuit protection
  • Smart battery charger design for optimized battery performance
  • Cold start function

1.4 Basic System Architecture

The following illustration shows a basic application for this inverter/charger. A complete running system includes a generator or utility, and optionally, PV modules.

System Diagram showing solar panels, inverter, battery, generator/utility, and home appliances
Figure 1: Hybrid Power System Diagram. This diagram illustrates how solar power, a generator or utility, and external battery packs connect to the hybrid solar inverter to power home appliances.
Video: Unboxing and overview of the EASUN POWER 6.2KW Hybrid Solar Inverter, highlighting its features like the 120A MPPT controller and parallel operation capability.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce the risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION: Only qualified personnel can install this device with a battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow the required specifications to select appropriate cable sizes. It is very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Refer to the INSTALLATION section of this manual for details.
  10. Fuses are provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  12. NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to a local dealer or service center for maintenance.

3. Product Overview

The EASUN POWER 6.2KW Hybrid Solar Inverter is an all-in-one off-grid inverter with a built-in 120A MPPT controller and pure sine wave output. It supports parallel operation for up to 9 units.

Front view of the EASUN POWER 6.2KW Hybrid Solar Inverter with key specifications listed: 6.2KW 48V 230VAC, 120A Max. Charge Current, 6500W Max. PV Array Power, 500VDC Max PV Array Voltage, 96% Peak Efficiency.
Figure 2: Front view of the Hybrid Solar Inverter, highlighting its core specifications.
Rear view of the Hybrid Solar Inverter with labeled ports: 1. AC input, 2. AC output, 3. RS232 communication port, 4. PV input, 5. RS485 communication port, 6. Battery input, 7. Grounding, 8. Parallel communication port (only for parallel model), 9. Power on/off switch.
Figure 3: Rear panel connections and controls of the Hybrid Solar Inverter.

The inverter features an LCD display, status indicator, charging indicator, and fault indicator. Function buttons allow for navigation and setting adjustments.

4. Installation

4.1 Unpacking and Inspection

Before installation, inspect the unit. Ensure nothing inside the package is damaged. The package should contain the unit (x1) and the user manual (x1).

4.2 Preparation

Before connecting any wiring, remove the bottom cover by unscrewing the two screws.

4.3 Mounting the Unit

Consider the following points when selecting where to install the inverter:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level for easy LCD display readability.
  • The ambient temperature should be between 0°C and 55°C for optimal operation.
  • The recommended installation position is vertically on the wall.
  • Ensure sufficient heat dissipation and space for wiring by maintaining at least 20cm clearance on the sides and 50cm above/below the unit.
Mounting diagram showing clearances: 20cm on sides, 50cm above and below the inverter.
Figure 4: Recommended mounting clearances for proper ventilation.

4.4 Battery Connection

CAUTION: For safety and compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. All wiring must be performed by qualified personnel. Use appropriate cable sizes for battery connection.

Battery connection diagram showing four 12V batteries connected in series to form a 48VDC system, connected to the inverter.
Figure 5: 48VDC Battery Connection Diagram.

Recommended Battery Cable Specifications:

ModelMaximum AmperageBattery CapacityWire SizeCable mm²Torque Value
6.2KVA137A200AH2AWG382~3 Nm

Follow these steps:

  1. For 6.2KVA, make positive and negative cables based on recommended terminal size.
  2. Connect all battery packs as units require. It's suggested to use recommended battery capacity.
  3. Insert battery cable flatly into the battery connector of the inverter and ensure bolts are tightened with a torque of 2-3Nm. Verify correct polarity.

4.5 AC Input/Output Connection

CAUTION: Install a separate AC breaker (50A recommended) between the inverter and the AC input power source. This ensures secure disconnection during maintenance and over-current protection. There are two terminal blocks marked 'IN' and 'OUT'; do not mis-connect them.

Schematic diagram of AC input and output wiring connections for the inverter.
Figure 6: AC Input/Output Wiring Diagram.

Suggested Cable Requirement for AC Wires:

ModelGaugeTorque Value
6.2KVA8 AWG1.4~1.6Nm

Follow these steps:

  1. Before making AC input/output connections, open the DC protector or disconnector.
  2. Remove 10mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor by 3mm.
  3. Insert AC input wires according to polarities (Ground, Line, Neutral) and tighten screws.
  4. Insert AC output wires according to polarities (Ground, Line, Neutral) and tighten screws.
  5. Ensure all wires are securely connected.

4.6 PV Connection

CAUTION: Install a DC circuit breaker between the inverter and PV modules. All wiring must be performed by qualified personnel. Use appropriate cable sizes for PV module connection.

PV module wire connection diagram showing positive and negative connections to the inverter.
Figure 7: PV Module Wire Connection Diagram.

Recommended PV Cable Specifications:

ModelTypical AmperageCable SizeTorque
6.2KVA27A10 AWG1.4~1.6 Nm

PV Module Selection Parameters:

  1. Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter (500VDC for 6.2KVA).
  2. Open circuit Voltage (Voc) of PV modules should be higher than the minimum battery voltage.

4.7 Final Assembly

After connecting all wirings, replace the bottom cover by screwing the two screws back into place.

5. Operation

5.1 Power ON/OFF

Once the unit is properly installed and batteries are connected, press the On/Off switch (located on the bottom of the case) to turn on the unit.

5.2 Operation and Display Panel

The front panel of the inverter features an LCD display, three indicators (AC/INV, CHG, FAULT), and four function keys (ESC, UP, DOWN, ENTER) to show operating status and input/output power information.

LED Indicators:

LED IndicatorColorMessages
AC / INVGreenSolid On: Output is powered by utility in Line mode.
Flashing: Output is powered by battery or PV in battery mode.
CHGGreenSolid On: Battery is fully charged.
Flashing: Battery is charging.
FAULTRedSolid On: Fault occurs in the inverter.
Flashing: Warning condition occurs in the inverter.

Function Keys:

Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

5.3 LCD Display Icons

The LCD display information can be switched by pressing the 'UP' or 'DOWN' key. It shows various parameters like input voltage, frequency, PV voltage, charging current, battery voltage, output voltage, load percentage, and more.

Input Source Information:

IconFunction description
ACIndicates the AC input.
PVIndicates the PV input.
INPUTBATTIndicates input voltage, input frequency, PV voltage, battery voltage and charger current.

Configuration Program and Fault Information:

IconFunction description
88Indicates the setting programs.
8.8Indicates the warning and fault codes.
Warning: 8.8 flashing with warning code.Warning: Flashing with warning code.
Fault: 8.8 lighting with fault code.Fault: Lighting with fault code.

Output Information:

IconFunction description
OUTPUTBATTLOADIndicates output voltage, output frequency, load percent, load in VA, load in Watt and discharging current.

Battery Information:

IconFunction description
CHARGINGIndicates battery level by 0-24%, 25-49%, 50-74% and 75-100% in battery mode and charging status in line mode.

Load Information:

IconFunction description
OVER LOADIndicates overload.
Load LevelIndicates the load level by 0-24%, 25-49%, 50-74% and 75-100%.

Mode Operation Information:

IconFunction description
MainsIndicates unit connects to the mains.
PV PanelIndicates unit connects to the PV panel.
BYPASSIndicates load is supplied by utility power.
Utility ChargerIndicates the utility charger circuit is working.
DC/AC InverterIndicates the DC/AC inverter circuit is working.

Mute Operation:

IconFunction description
MuteIndicates unit alarm is disabled.

5.4 LCD Setting

After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use 'UP' or 'DOWN' to select programs, then 'ENTER' to confirm or 'ESC' to exit.

Refer to pages 17-24 of the User Manual PDF for detailed LCD setting programs and options.

5.5 Operating Mode Description

The inverter operates in various modes, including Line Mode, Battery Mode, Standby Mode, Power Saving Mode, and Fault Mode. Each mode has specific behaviors regarding power source, charging, and output.

Refer to pages 28-30 of the User Manual PDF for detailed operating mode descriptions and diagrams.

6. Battery Equalization

The equalization function helps reverse the buildup of negative chemical effects like stratification and removes sulfate crystals, which can reduce battery capacity if left unchecked. It is recommended to equalize the battery periodically.

6.1 How to Apply Equalization Function

Enable the battery equalization function in monitoring LCD setting program 33. Then, apply this function by either:

  1. Setting the equalization interval in program 37.
  2. Activating equalization immediately in program 39.

6.2 When to Equalize

In float stage, when the setting equalization interval is reached, or equalization is actively initiated, the controller will enter the Equalize stage.

6.3 Equalize Charging Time and Timeout

In the Equalize stage, the controller charges the battery until its voltage reaches the battery equalization voltage. Constant-voltage regulation then maintains this voltage. The battery remains in the Equalize stage until the set equalized time is reached. If the battery voltage does not rise to the equalization voltage point within the set time, the charge controller will extend the time until it does. If the voltage is still low after the extended timeout, the controller will stop equalization and return to the float stage.

7. Setting for Lithium Battery

If using a lithium battery with the inverter, ensure it is a compatible model. Lithium batteries have two connectors: an RS485 port for the BMS and a power cable.

7.1 Lithium Battery Connection

  1. Assemble battery terminals based on recommended battery cable and terminal size (similar to lead-acid battery connections).
  2. Connect the RS485 port of the battery to the BMS (RS485) communication port of the inverter.
Diagram showing the RS485 connection between a lithium battery and the inverter.
Figure 8: Lithium Battery RS485 Communication Port Connection.

7.2 Lithium Battery Communication and Setting

Ensure the BMS communication cable is connected between the battery and the inverter. This cable transmits information and signals, allowing the inverter to:

  • Re-configure charging voltage, charging current, and battery discharge cut-off voltage based on lithium battery parameters.
  • Start or stop charging according to the lithium battery status.

Make sure the lithium battery RS485 port connects to the inverter with a Pin-to-Pin connection. The communication cable is included in the package.

Inverter RS485 Port Pin Assignment:

Pin numberRS485 Port
PIN1RS485-B
PIN2RS485-A
PIN7RS485-A
PIN8RS485-B

After connecting, you need to finish and confirm some settings:

  1. Set battery type as 'USE' (user-defined) in LCD program 05.
  2. Set C.V voltage as Max charging voltage of BMS - 0.5V.
  3. Set floating charging voltage.
  4. Set Low DC cut-off voltage ≥ discharging protection voltage of BMS + 2V.
  5. Set Max charging current (must be less than the Max charging current of BMS).
  6. Set voltage point back to utility source when selecting 'SBU priority' or 'Solar first' in program 01.

Refer to pages 35-39 of the User Manual PDF for detailed lithium battery settings.

8. Specifications

Detailed specifications for the EASUN POWER 6.2KW Hybrid Solar Inverter are provided in the tables below.

8.1 Table 1 Line Mode Specifications

INVERTER MODEL6.2KVA
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS)
90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS);
100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionLine mode: Circuit Breaker
Battery mode: Electronic Circuits
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS);
20ms typical (Appliances)
Output power derating:When AC input voltage drops to 95V or 170V depending on models, the output power will be derated.

8.2 Table 2 Inverter Mode Specifications

INVERTER MODEL6.2KVA
Rated Output Power6.2KVA/6.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency60Hz or 50Hz
Peak Efficiency94%
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage48Vdc
Cold Start Voltage46.0Vdc
Low DC Warning Voltage@load < 20%: 44.0Vdc
@20% ≤ load < 50%: 42.8Vdc
@load ≥ 50%: 40.4Vdc
Low DC Warning Return Voltage@load < 20%: 46.0Vdc
@20% ≤ load < 50%: 44.8Vdc
@load ≥ 50%: 42.4Vdc
Low DC Cut-off Voltage@load < 20%: 42.0Vdc
@20% ≤ load < 50%: 40.8Vdc
@load ≥ 50%: 38.4Vdc

8.3 Table 3 Charge Mode Specifications

Utility Charging Mode6.2KVA
Max Charging Current (PV+AC)120Amp (@ VI/P=230Vac)
MaxCharging Current (AC)80Amp (@ VI/P=230Vac)
Bulk Charging Voltage (Flooded Battery)58.4Vdc
Bulk Charging Voltage (AGM / Gel Battery)56.4Vdc
Floating Charging Voltage54Vdc
Overcharge Protection63Vdc
Charging Algorithm3-Step
Solar Input
Rated Power6500W
Max. PV Array Open Circuit Voltage500Vdc
PV Array MPPT Voltage Range60Vdc~450Vdc
Max. Input Current27A
MaxCharging Current(PV)120A

8.4 Table 4 General Specifications

INVERTER MODEL6.2KVA
Safety CertificationCE
Operating Temperature Range-10°C to 55°C
Storage temperature-15°C ~ 60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Net Weight, kg12
Ingress Protection ratingIP21

9. Troubleshooting

This section provides guidance for common issues. For persistent problems, contact a qualified service person.

9.1 Fault Reference Code

Fault CodeFault Event
01Over temperature of inverter module
02Over temperature of DCDC module
03Battery voltage is too high
04Over temperature of PV module
05Output short circuited.
06Output voltage is too high.
07Overload time out
08Bus voltage is too high
09Bus soft start failed
10PV over current
11PV over voltage
12DCDC over current
13Over current or surge
14Bus voltage is too low
15Inverter failed (Self-checking)
16Over DC voltage in AC output
17Reserved
18Op current offset is too high
19Inverter current offset is too high
20DC/DC current offset is too high
21PV current offset is too high
22Output voltage is too low
23Inverter negative power

9.2 Warning Indicator

Warning CodeWarning EventAudible Alarm
02Temperature is too HighBeep three times every second
04Low batteryBeep once every second
07OverloadBeep once every 0.5 second
10Output power deratingBeep twice every 3 seconds
15PV energy is lowBeep twice every 3 seconds
19Lithium Battery communication is failedBeep once every 0.5 second
20Battery low and it isn't up to the setting value of program 13Beep twice every 3 seconds
E9Battery equalizationNone
bPBattery is not connectedNone

9.3 General Troubleshooting

ProblemExplanation / Possible causeWhat to do
Unit shuts down automatically during startup process.The battery voltage is too low.1. Re-charge battery.
2. Replace battery.
No response after power on.1. The battery voltage is far too low.
2. Battery polarity is connected reversed.
3. Input protector is tripped.
1. Check if batteries and the wiring are connected well.
2. Re-charge battery.
3. Replace battery.
4. Check if AC breaker is tripped and AC wiring is connected well.
Mains exist but the unit works in battery mode.1. Insufficient quality of AC power (Shore or Generator).
2. Set "Solar First" as the priority of output source.
1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct (UPS→Appliance).
3. Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly.Battery is disconnected.Check if battery wires are connected well.
Buzzer beeps continuously and red LED is on.1. Overload error. The inverter is overloaded 110% and time is up.
2. Output short circuited.
3. Internal temperature of inverter component is over 100°C.
4. Battery is over-charged.
5. The battery voltage is too high.
6. Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac).
7. Internal components failed.
8. Over current or surge.
9. Bus voltage is too low.
10. Output voltage is unbalanced.
1. Reduce the connected load by switching off some equipment.
2. Check if wiring is connected well and remove abnormal load.
3. Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
4. Please contact the seller and provide a video or pictures of the malfunction.
5. Check if spec and quantity of batteries are meet requirements.
6. Restart the unit, if the error happens again, Please contact the seller and provide a video or pictures of the malfunction.

10. Parallel Installation Guide

This inverter supports parallel operation in two different modes:

  1. Parallel operation in single phase with up to 12 units.
  2. Maximum 12 units working together to support three-phase equipment (10 units maximum per phase).

10.1 Package Contents

In the parallel kit, you will find a parallel communication cable.

10.2 Mounting the Unit for Parallel Operation

When installing multiple units, ensure proper air circulation to dissipate heat. Allow a clearance of approximately 20 cm to the sides and 50 cm above and below each unit. Install each unit at the same level.

Mounting diagram for multiple inverters in parallel, showing required clearances.
Figure 9: Mounting multiple inverters for parallel operation.

10.3 Wiring Connection for Parallel Operation

NOTICE: It is required to connect to the battery for parallel operation. Ensure all battery cables are of the same length to prevent voltage differences.

Recommended Battery Cable and Terminal Size for Each Inverter:

ModelWire SizeCable mm²Torque Value
6.2KVA2AWG382~3 Nm

Recommended AC Input and Output Cable Size for Each Inverter:

ModelAWG no.Torque
6.2KVA8 AWG1.4~1.6Nm

You need to connect the cables of each inverter together using a connector or bus-bar. The cable size from the joint to the battery should be X times the cable size for a single unit, where X is the number of inverters in parallel. The same principle applies to AC input and output.

CAUTION: Install breakers at the battery and AC input side. The recommended breaker specification for the battery for each inverter is 100A/60VDC. If using only one breaker for the whole system, its rating should be X times the current of one unit.

10.4 Parallel Operation in Single Phase

Two Inverters in Parallel:

Wiring diagram for two inverters operating in parallel in a single phase system.
Figure 10: Power and Communication Connections for Two Inverters in Parallel.

Four Inverters in Parallel:

Wiring diagram for four inverters operating in parallel in a single phase system.
Figure 11: Power and Communication Connections for Four Inverters in Parallel.

Six Inverters in Parallel:

Wiring diagram for six inverters operating in parallel in a single phase system.
Figure 12: Power and Communication Connections for Six Inverters in Parallel (Nmax=12 units).

10.5 Support 3-Phase Equipment

The inverter can support 3-phase equipment. It is possible to pick up to 10 inverters on any phase, with a maximum of 12 units total (N=N1+N2+N3).

One Inverter in Each Phase:

Wiring diagram for one inverter in each of three phases (P1, P2, P3) for 3-phase equipment support.
Figure 13: Power and Communication Connections for One Inverter in Each Phase.

N1max=N2max=9 units in two phases and one inverter for the one phase (N3=1):

Wiring diagram for a 3-phase system with an unequal distribution of inverters per phase, specifically N1max=N2max=9 units and N3=1 unit.
Figure 14: Power and Communication Connections for Unequal Inverter Distribution in 3-Phase.

10.6 PV Connection for Parallel Operation

Each inverter should connect to PV modules separately.

PV connection diagram for multiple inverters in a parallel system, showing each inverter connected to its own PV array.
Figure 15: PV Connection for Parallel Inverters.

10.7 LCD Setting and Display for Parallel Operation

Refer to pages 53-54 of the User Manual PDF for detailed LCD settings specific to parallel operation.

10.8 Commissioning for Parallel Operation

Parallel in Single Phase:

  1. Step 1: Check for correct wire connections. Ensure all breakers in Line wires of the load side are open and all Neutral wires of each unit are connected together.
  2. Step 2: Turn on each unit and set "PAL" in LCD setting program 28 of each unit. Then shut down all units. (Note: It's necessary to turn off the switch when setting the LCD program. Otherwise, the setting cannot be programmed.)
  3. Step 3: Turn on each unit. Master and slave units are randomly defined. If it is a master, the 'P' icon blinks; if it is a slave, the 'P' icon is normally on.
  4. Step 4: Switch on all AC breakers of Line wires in AC input. It's best to connect all inverters to utility at the same time. If AC connection is detected, they will work normally.
  5. Step 5: If there is no more fault alarm, the parallel system is completely installed.
  6. Step 6: Switch on all breakers of Line wires in the load side. The system will start to provide power to the load.

10.9 Troubleshooting for Parallel Operation

Refer to page 55 of the User Manual PDF for troubleshooting specific to parallel installations, including issues like host loss, synchronization loss, incompatible battery type, and firmware version inconsistencies.

11. User Tips

  • Always ensure all wiring connections are secure and follow polarity guidelines to prevent damage and ensure safe operation.
  • For optimal performance and longevity, regularly check the battery equalization status and perform equalization as needed, especially for lead-acid batteries.
  • When connecting to a generator, ensure the generator provides stable power to avoid inverter instability.
  • If using lithium batteries, ensure proper communication between the battery's BMS and the inverter for correct charging and discharge management.

12. Frequently Asked Questions

Q: Is there a warranty for the product?
A: For warranty information, please refer to the official product documentation or contact the seller directly.

13. Warranty and Support

For detailed warranty terms, conditions, and support information, please refer to the complete User Manual (PDF) provided by the manufacturer. If you encounter any issues not covered in this manual or require technical assistance, please contact EASUN POWER customer support or your local dealer.

Related Documents - SMG 6.2KP

Preview EASUN ISolar SMG Series 6.2KW Hybrid Solar Inverter - Technical Specifications
Detailed technical specifications for the EASUN ISolar SMG Series 6.2KW hybrid solar inverter, including features, input/output parameters, battery specifications, and environmental data. Supports PV 60-500Vdc and 220/230Vac output.
Preview Easun Power ISolar SMG II 6.2KP Hybrid Solar Inverter/Charger User Manual
Comprehensive user manual for the Easun Power ISolar SMG II 6.2KP (6.2KVA 230Vac) hybrid solar inverter/charger, covering installation, operation, specifications, and troubleshooting for reliable power solutions.
Preview EASUN POWER 6.2KVA Hybrid Solar Inverter/Charger User Manual
User manual for the EASUN POWER 6.2KVA Hybrid Solar Inverter/Charger. Covers installation, operation, safety, and troubleshooting for this MPPT solar charger and battery backup system.
Preview EASUN POWER Hybrid Solar Inverter/Charger 8.5KVA/11.0KVA User Manual
Detailed user manual for EASUN POWER Hybrid Solar Inverter/Charger models 8.5KVA and 11.0KVA (230Vac). This guide covers installation, operation, safety protocols, key features, technical specifications, and troubleshooting for efficient solar energy management.
Preview Easun Hybrid Inverter User Manual: 3.6KW, 4.2KW, 6.2KW Models
Comprehensive user manual for Easun Hybrid Inverters (3.6KW, 4.2KW, 6.2KW). Covers installation, operation, safety instructions, specifications, and troubleshooting for efficient solar power system management.
Preview EASUN POWER Hybrid Solar Inverter/Charger User Manual
This user manual provides comprehensive instructions for the EASUN POWER Hybrid Solar Inverter/Charger, covering installation, operation, specifications, troubleshooting, and battery management.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.