PowMr POW-HVM6200W-48V

Contents

PowMr 6.2KW Hybrid Solar Inverter User Manual

Model: POW-HVM6200W-48V

PowMr Hybrid Solar Inverter with key features highlighted

Image: PowMr Hybrid Solar Inverter, showcasing its 230VAC, 6.2KW 48V, 120A MPPT charge current, 60-450VDC PV array voltage range, and 8000W max PV input power.

1. Product Overview

This multi-function inverter/charger combines the functions of an inverter, solar charger, and battery charger to provide uninterruptible power support. It features a comprehensive LCD display for user-configurable settings and easy operation.

Front, side, and rear views of the PowMr Hybrid Solar Inverter

Image: Various views of the PowMr Hybrid Solar Inverter, including front, side, and rear panels, highlighting connection ports and display.

1.1. Components

The inverter's front panel features an LCD display, status indicators, and function buttons. The rear panel includes various connection ports and a power switch.

Diagram of Hybrid Power System connections

Image: Hybrid Power System diagram showing connections between solar panels, inverter, battery, utility/generator, and home appliances. Max VOC: 500V DC, PV Array MPPT Voltage Range: 60-450V DC, Max. PV Array Power: 8000W, Max Charging current: 120A.

  1. LCD display
  2. Status indicator
  3. Charging indicator
  4. Fault indicator
  5. Function buttons
  6. Second out
  7. Main out
  8. AC input
  9. RS232 communication port
  10. Grounding
  11. RS485 communication port
  12. Battery input
  13. Power on/off switch
  14. PV input

2. Setup and Installation

2.1. Unpacking and Inspection

Before installation, carefully inspect the unit for any damage. The package should contain:

  • The inverter unit x 1
  • User manual x 1

2.2. Preparation

Before connecting any wiring, remove the bottom cover by unscrewing the two screws as shown in the product diagrams.

2.3. Mounting the Unit

Consider the following points when selecting an installation location:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install at eye level for easy LCD display reading.
  • Ambient temperature should be between 0°C and 55°C for optimal operation.
  • Adhere to vertical wall mounting.
  • Ensure sufficient space (at least 20cm on sides, 50cm above/below) for heat dissipation and wiring access.

CAUTION: Suitable for mounting on concrete or other non-combustible surfaces only.

2.4. Battery Connection

CAUTION: For safety and compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. Over-current protection is required even if a disconnect device is not used.

WARNING: All wiring must be performed by qualified personnel. Use appropriate cables and terminals to reduce injury risk.

Recommended Battery Cable & Terminal Size:

ModelMaximum AmperageBattery CapacityWire SizeCable mm²Terminal Size L(mm)Terminal Size W(mm)Terminal Size D(mm)Torque Value
6.2KVA137A200AH2AWG3835166.52~3 Nm

Connection Steps:

  1. Create battery positive and negative cables according to specifications.
  2. Connect all battery packs as required.
  3. Insert battery cables into the inverter's battery connector, ensuring bolts are tightened to 2-3 Nm. Verify correct polarity at both the battery and inverter/charger.

WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.

CAUTION: Do not place anything between the flat part of the inverter terminal; overheating may occur.

CAUTION: Do not apply anti-oxidant substance on terminals before connecting tightly.

CAUTION: Before final DC connection, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).

2.5. AC Input/Output Connection

CAUTION: Install a separate AC breaker (recommended 50A) between the inverter and AC input power source. Do not mis-connect input and output connectors.

WARNING: All wiring must be performed by qualified personnel. Use appropriate cable for AC input connection.

Suggested Cable Requirement for AC Wires:

ModelGaugeTorque Value
6.2KVA8 AWG1.4~1.6 Nm

Connection Steps:

  1. Before connecting, open the DC protector or disconnector.
  2. Remove 10mm insulation from six conductors. Shorten phase L and neutral conductor N by 3mm.
  3. Insert AC input wires according to polarities (Ground, LINE, Neutral) and tighten terminal screws. Connect PE protective conductor first.
  4. Insert AC output wires according to polarities and tighten terminal screws. Connect PE protective conductor first.
  5. The inverter has dual output (main out-L/N, second out-L/N). The second output can be configured via LCD program 43.

Remarks on Dual Output:

  • Main output handles heavy loads (air-conditioners, heaters, motors).
  • Second output handles light loads (lights, computers, fans).
  • The cutoff point of the second output is typically lower than the main output to maintain power for light loads.

CAUTION: Ensure AC wires are connected with correct polarity to avoid utility short-circuiting in parallel operation.

CAUTION: Appliances like air conditioners require 2-3 minutes to restart. If power fluctuates, it can damage appliances. Check if your appliance has a time-delay function.

2.6. PV Connection

CAUTION: Install a DC circuit breaker between the inverter and PV modules.

WARNING: All wiring must be performed by qualified personnel. Use appropriate cable for PV module connection.

Recommended PV Cable & Terminal Size:

ModelTypical AmperageCable SizeTorque
6.2KVA27A12 AWG1.4~1.6 Nm

PV Module Selection:

  • Open circuit Voltage (Voc) of PV modules must not exceed the inverter's max. PV array open circuit voltage.
  • Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.

Solar Charging Mode Specifications:

INVERTER MODEL6.2KVA
Max. PV Array Open Circuit Voltage500DC
PV Array MPPT Voltage Range60VDC~500VDC
Max. PV INPUT CURRENT27A

PV Module Wire Connection Steps:

  1. Remove 6mm insulation for positive and negative conductors.
  2. Check correct polarity of connection cable from PV modules and PV input connectors. Connect positive pole (+) to positive pole (+) and negative pole (-) to negative pole (-).
  3. Ensure wires are securely connected.

2.7. Final Assembly

After connecting all wirings, reattach the bottom cover by screwing in the two screws.

3. Operation

3.1. Power ON/OFF

Once the unit is properly installed and batteries are connected, press the On/Off switch (located on the bottom of the case) to turn on the unit.

3.2. Operation and Display Panel

The front panel features an LCD display, three LED indicators, and four function keys to show operating status and input/output power information.

LED Indicators:

LED IndicatorColorStatusMessages
AC/INVGreenSolid OnOutput is powered by utility in Line mode.
FlashingOutput is powered by battery or PV in battery mode.
CHGGreenSolid OnBattery is fully charged.
FlashingBattery is charging.
FAULTRedSolid OnFault occurs in the inverter.
FlashingWarning condition occurs in the inverter.

Function Keys:

Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

3.3. LCD Setting

Press and hold the ENTER button for 3 seconds to enter setting mode. Use UP/DOWN to select programs and ENTER to confirm or ESC to exit.

LCD display showing configurable settings

Image: LCD display of the inverter, showing configurable settings for AC/Solar charger priority, battery charging current, and input voltage range.

The LCD settings allow configuration of various parameters, including:

  • Program 01: Output source priority
    • Utility first (default): Utility powers loads first.
    • Solar first: Solar energy powers loads first.
    • SBU priority: Solar first, then battery, then utility.
    • SUB priority: Solar first, then utility, then battery.
  • Program 02: Maximum charging current (60A default)
  • Program 03: AC input voltage range (Appliances default: 90-280VAC; UPS: 170-280VAC; Generator: 170-280VAC)
  • Program 05: Battery type (AGM default, Flooded, User-Defined, Lithium)
  • Program 06: Auto restart when overload occurs (Restart enable default)
  • Program 07: Auto restart when over temperature occurs (Restart enable default)
  • Program 08: Output voltage (230V default)
  • Program 09: Output frequency (50Hz default)
  • Program 10: Auto bypass (manual default)
  • Program 11: Maximum utility charging current (30A default)
  • Program 12: Setting voltage or SOC percentage back to utility source (46.0V default for 48V model)
  • Program 13: Setting voltage or SOC percentage back to battery mode (Battery fully charged default)
  • Program 16: Charger source priority (Solar and Utility default)
  • Program 18: Buzzer mode (Mode4 default: sounds on fault)
  • Program 19: Auto return to default display screen (screen default)
  • Program 20: Backlight control (Backlight on default)
  • Program 23: Overload bypass (Bypass enable default)
  • Program 25: Modbus ID Setting Range (001 default)
  • Program 26: Bulk charging voltage (C.V voltage) (Default 56.4V, range 48.0V to 62.0V)
  • Program 27: Floating charging voltage (Default 54.0V, range 48.0V to program 26 value)
  • Program 29: Setting cut off voltage point or SOC percentage on the second output (OP2) (Default 42.0V)
  • Program 31: Setting cut off voltage point or SOC percentage on the Main output (OP1)
  • Program 32: Bulk charging time (C.V stage) (Automatically default)
  • Program 33: Battery equalization (Battery equalization disable default)
  • Program 34: Battery equalization voltage (Default 58.4V)
  • Program 35: Battery equalized time (60min default)
  • Program 36: Battery equalized timeout (120min default)
  • Program 37: Equalization interval (30 days default)
  • Program 39: Equalization activated immediately (Disable default)
  • Program 41: Automatic activation for lithium battery (Disable automatic activation default)
  • Program 42: Manual activation for lithium battery (Default: disable activation)
  • Program 43: Setting the second output (OP2) function (Turn on default)
  • Program 46: Maximum discharge current protection (Default 100A)
  • Program 47: Setting the OP2 overload warning point (50% default)

3.4. Charging & Output Modes

Four charging modes and three load output working modes

Image: Diagram illustrating four charging modes (Solar first, Utility first, Solar and Utility, Only Solar) and three load output working modes (Utility first, Solar first, SBU first).

4. Maintenance

4.1. Battery Equalization

The equalization function reverses the buildup of negative chemical effects like stratification and sulfation, which can reduce battery capacity. It is recommended to equalize the battery periodically.

How to Apply Equalization Function:

Enable battery equalization in LCD setting program 33. Then, apply by either:

  • Setting equalization interval in program 37.
  • Activating equalization immediately in program 39.

When to Equalize:

In float stage, when the set equalization interval is reached or equalization is actively initiated, the controller enters the Equalize stage.

Equalize Charging Time and Timeout:

During the Equalize stage, the controller charges the battery until it reaches the equalization voltage. Constant-voltage regulation maintains this voltage until the set battery equalized time is reached. If the battery voltage is still below the equalization voltage when the timeout expires, the charge controller will stop equalization and return to the float stage.

4.2. Setting for Lithium Battery

If using a lithium battery, ensure it is a compatible model. Two connectors are on the lithium battery: RS485 port of BMS and power cable.

Lithium Battery Connection Steps:

  1. Assemble battery terminals based on recommended cable and terminal size (same as Lead-acid).
  2. Connect the RS485 port of the battery to the BMS (RS485) communication port of the inverter.

Lithium Battery Communication and Setting:

If using a lithium battery, connect the BMS communication cable between the battery and the inverter. This cable transmits information for:

  • Re-configuring charging voltage, charging current, and battery discharge cut-off voltage.
  • Inverter starting or stopping charging based on battery status.

Ensure the lithium battery RS485 port connects pin-to-pin to the inverter. The inverter's RS485 port pin assignment is:

Pin numberRS485 Port
PIN1RS485-B
PIN2RS485-A
PIN7RS485-A
PIN8RS485-B

LCD Setting for Lithium Battery:

  1. Select program 05 as lithium battery type.
  2. Confirm program 12/13/29/31/41/42 settings.

If communication is successful, the LCD will show a 'Li' icon and display information like max charging voltage/current, and battery SOC (%).

Setting for PYLON US2000 Lithium Battery:

Dip Switch 1 'ON' for baud rate 9600. Dip switches 2, 3, and 4 on the master battery set the group address.

Setting for Lithium Battery Without Communication:

If communication is not used, obtain battery BMS specifications (Max charging voltage, Max charging current, Discharging protection voltage) and manually set:

  1. Battery type as 'USE' (user-defined) in program 05.
  2. C.V voltage as Max charging voltage of BMS - 0.5V.
  3. Floating charging voltage as C.V voltage.
  4. Low DC cut-off voltage as discharging protection voltage of BMS + 2V.
  5. Max charging current less than the BMS's max charging current.
  6. Voltage point back to utility source (program 12) must be ≥ Low DC cut-off voltage + 1V.

5. Troubleshooting

5.1. Fault Reference Code

The inverter displays fault codes to indicate specific issues:

Fault CodeFault EventIcon on
01Over temperature of inverter module01
02Over temperature of DCDC module02
03Battery voltage is too high03
04Over temperature of PV module04
05Output short circuited.05
06Output voltage is too high.06
07Overload time out07
08Bus voltage is too high08
09Bus soft start failed09
10PV over current10
11PV over voltage11
12DCDC over current12
13Over current or surge13
14Bus voltage is too low14
15Inverter failed (Self-checking)15
18Op current offset is too high18
19Inverter current offset is too high19
20DC/DC current offset is too high20
21PV current offset is too high21
22Output voltage is too low22
23Inverter negative power23

5.2. Warning Indicator

The inverter displays warning codes and audible alarms for various conditions:

Warning CodeWarning EventAudible AlarmIcon flashing
02Temperature is too HighBeep three times every second02
04Low batteryBeep once every second04
07OverloadBeep once every 0.5 second07
10Output power deratingBeep twice every 3 seconds10
14Fan blockedNone14
15PV energy is lowBeep twice every 3 seconds15
19Lithium Battery communication is failedBeep once every 0.5 second19
21Lithium Battery over currentNone21
22OP2 is overloadNone22
E9Battery equalizationNoneE9
hPBattery is not connectedNonehP

5.3. Troubleshooting Table

ProblemLCD/LED/BuzzerExplanation / Possible causeWhat to do
Unit shuts down automatically during startup process.LCD/LEDs and buzzer active for 3 seconds then off.Battery voltage is too lowRe-charge battery. Replace battery.
No response after power on.No indication.1. Battery voltage is far too low.
2. Battery polarity is connected reversed.
1. Check if batteries and wiring are connected well. Re-charge battery. Replace battery.
Input voltage displayed as 0 on LCD, green LED flashing.Input protector is trippedCheck if AC breaker is tripped and AC wiring is connected well.
Mains exist but unit works in battery mode.Green LED is flashing.Insufficient quality of AC power (Shore or Generator)1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct (UPS→Appliance).
Green LED is flashing.Set "Solar First" as the priority of output source.Change output source priority to Utility first.
When unit is turned on, internal relay switched on and off repeatedly.LCD display and LEDs are flashingBattery is disconnected.Check if battery wires are connected well.
Buzzer continuously and red LED is on.Fault code 07Overload error. Inverter is overload 110% and time is up.Reduce connected load by switching off some equipment.
Fault code 05Output short circuited.Check if wiring is connected well and remove abnormal load.
Fault code 02Internal temperature of inverter component is over 100°C.Check whether air flow of unit is blocked or ambient temperature is too high.
Fault code 03Battery is over-charged.Return to repair center.
Battery voltage is too high.Check if spec and quantity of batteries meet requirements.
Fault code 06/22Output abnormal (Inverter voltage below 190Vac or higher than 260Vac)1. Reduce connected load.
Return to repair center.
Fault code 08/09/15Internal components failed.Return to repair center.
Fault code 13Over current or surge.Restart unit, if error happens again, return to repair center.
Fault code 14Bus voltage is too low.If wires connected well, return to repair center.
Another fault codeIf wires connected well, return to repair center.

6. Specifications

Product label with model number and detailed specifications

Image: Product label for model POW-HVM6.2K-48V-E, showing rated power, AC charger mode, and PV input specifications.

6.1. General Specifications

ParameterValue
INVERTER MODEL6.2KVA
Operating Temperature Range-10°C to 55°C
Storage temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension(D×W×H), mm423×344×112
Net Weight, kg8.2
CertificationCE
Is Smart DeviceYes

6.2. Line Mode Specifications

ParameterValue
INVERTER MODEL6.2KVA
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS); 90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS); 100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionBattery mode: Electronic Circuits
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)

6.3. Inverter Mode Specifications

ParameterValue
INVERTER MODEL6.2KVA
Rated Output Power6.2KVA/6.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency50Hz or 60Hz
Peak Efficiency94%
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage48Vdc
Cold Start Voltage46.0Vdc
No Load Power Consumption<55W
Low DC Warning Voltage (AGM/Flooded)@load < 20%: 44.0Vdc
@20% ≤ load < 50%: 42.8Vdc
@load ≥ 50%: 40.4Vdc
Low DC Warning Return Voltage (AGM/Flooded)@load < 20%: 46.0Vdc
@20% ≤ load < 50%: 44.8Vdc
@load ≥ 50%: 42.4Vdc
Low DC Cut-off Voltage (AGM/Flooded)@load < 20%: 42.0Vdc
@20% ≤ load < 50%: 40.8Vdc
@load ≥ 50%: 38.4Vdc

6.4. Charge Mode Specifications

ParameterValue
INVERTER MODEL6.2KVA
Max Charging Current (PV+AC)120Amp
Max Charging Current (AC)80Amp
Bulk Charging Voltage (Flooded Battery)58.4Vdc
Bulk Charging Voltage (AGM / Gel Battery)56.4Vdc
Floating Charging Voltage54Vdc
Overcharge Protection63Vdc
Charging Algorithm3-Step
Rated Power (Solar Input)6500W
Max. PV Array Open Circuit Voltage (Solar Input)500Vdc
PV Array MPPT Voltage Range (Solar Input)60Vdc~500Vdc
Max. Input Current (Solar Input)27A
Max. Charging Current (PV)120A

7. Warranty and Support

7.1. Warranty Information

This product comes with a 12-month warranty from the date of purchase.

7.2. Contact Information

For technical support or warranty claims, please contact PowMr:

  • Tel/Fax: +86 755-28219903
  • Email: support@powmr.com
  • Web: www.powmr.com
  • Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China

You can also refer to the official user manual PDF for more detailed information: View User Manual (PDF)

8. User Tips

  • Initial Inspection: Upon receiving your inverter, carefully inspect the packaging and contents for any signs of damage. Ensure all components are present before proceeding with installation.
  • Professional Installation: Given the complexity of solar inverter systems and high voltages involved, it is highly recommended to have the installation performed by qualified personnel.
  • Battery Compatibility: Pay close attention to battery type settings in the LCD menu, especially for lithium batteries, to ensure proper charging and discharge cycles.
  • Monitoring: Consider utilizing the optional WIFI remote monitoring feature for convenient oversight of your system's performance.

9. Product Video

Watch this official video for a visual overview of the PowMr Hybrid Solar Inverter:

Video: An official product video demonstrating the features and functionality of the PowMr 6.2KW Hybrid Solar Inverter.