PowMr POW-HVM1K-12V

Contents

PowMr 1KW EU Hybrid Solar Inverter User Manual

Model: POW-HVM1K-12V

1. Introduction

This manual provides detailed instructions for the assembly, installation, operation, and troubleshooting of the PowMr 1KW EU Hybrid Solar Inverter. Please read this manual carefully before installation and operation, and keep it for future reference.

The PowMr POW-HVM1K-12V is a multi-function inverter/charger that combines the functions of an inverter, solar charger, and battery charger. It is designed to provide uninterruptible power support in a compact size. The comprehensive LCD display allows for user-configurable settings such as battery charging current, AC/solar charger priority, and acceptable input voltage ranges for various applications.

Key Features:

  • Pure sine wave inverter output.
  • Configurable input voltage range for home appliances and personal computers via LCD settings.
  • Configurable battery charging current based on applications via LCD settings.
  • Configurable AC/Solar Charger priority via LCD settings.
  • Compatible with mains voltage or generator power.
  • Auto restart function when AC power recovers.
  • Multiple protections: Overload, over temperature, and short circuit protection.
  • Smart battery charger design for optimized battery performance.
  • Cold start function.
  • Supports connection to lithium batteries.
PowMr 1KW Hybrid Solar Inverter with key specifications
The PowMr 1KW Hybrid Solar Inverter highlighting its 1000W pure sine wave output, 20-150VDC MPPT voltage range, and 80A maximum charging current.
Hybrid Power System Diagram
Diagram illustrating a typical hybrid power system setup, including PV panels, generator, utility, battery, and home appliances connected to the solar inverter charger.
Charging and Output Modes
Visual representation of the four charging modes (Solar First, Utility First, Solar and Utility, Only Solar) and three load output working modes (Utility First, Solar First, SBU First).
Multi-Protection Functions
Overview of the inverter's multi-protection functions, including CE certification, overload protection, surge protection, battery temperature monitoring, low voltage protection, high voltage protection, and MPPT controller.

2. Setup (Installation)

Proper installation is crucial for the safe and efficient operation of your inverter. Please follow these guidelines carefully.

2.1 Unpacking and Inspection

Upon receiving the unit, inspect the package for any damage. The package should contain:

  • The inverter unit x 1
  • User manual x 1
  • U-terminal x 2
Video demonstrating the unboxing of the PowMr 1KW Hybrid Solar Inverter, showing the contents of the package including the inverter, U-shaped terminals, and user manual.

2.2 Mounting the Unit

Consider the following points when selecting an installation location:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install the inverter at eye level for easy reading of the LCD display.
  • Ensure proper air circulation: allow a clearance of approximately 20 cm to the sides and 50 cm above and below the unit.
  • The ambient temperature should be between 0°C and 55°C for optimal operation.
  • The recommended installation position is vertically on the wall.
  • Keep other objects and surfaces clear as shown in diagrams to ensure sufficient heat dissipation and space for wiring.

The unit is suitable for mounting on concrete or other non-combustible surfaces only. Use M4 or M5 screws for mounting.

2.3 Battery Connection

WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.

CAUTION: To reduce the risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other battery types may burst, causing personal injury and damage.

For safety and compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. Use appropriate cable sizes for battery connection to ensure system safety and efficient operation.

Recommended Battery Cable Size:

Model Wire Size Cable (mm²) Torque Value (max)
1.0KW 12V 1 x 6AWG 14 5 Nm

Battery Connection Steps:

  1. Remove 18 mm of insulation sleeve for positive and negative conductors.
  2. Attach bootlace ferrules to the ends of positive and negative wires using a proper crimping tool.
  3. Connect all battery packs as shown in the diagram below.
  4. Insert the battery wires flatly into the inverter's battery connectors. Ensure bolts are tightened to 2 Nm in a clockwise direction. Verify correct polarity at both the battery and inverter/charger.
Inverter connected to a battery
The inverter connected to a battery, illustrating the battery terminals and proper wiring.

CAUTION: Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).

2.4 AC Input/Output Connection

CAUTION: Before connecting to the AC input power source, install a separate AC breaker between the inverter and the AC input power source. This ensures the inverter can be securely disconnected for maintenance and is protected from overcurrent. The recommended AC breaker specification is 20A for the 1.0KW model.

CAUTION: There are two terminal blocks marked "IN" and "OUT". Do NOT mis-connect input and output connectors.

WARNING: All wiring must be performed by qualified personnel. Use appropriate cable for AC input connection to reduce risk of injury.

Suggested Cable Requirement for AC Wires:

Model Gauge Torque Value
1.0KW 12V 14 AWG 2 Nm

AC Input/Output Connection Steps:

  1. Before making AC input/output connections, ensure the DC protector or disconnector is open.
  2. Remove 10 mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3 mm.
  3. Insert AC input wires according to the polarities indicated on the terminal block and tighten the terminal screws. Connect the PE protective conductor first.
  4. Insert AC output wires according to the polarities indicated on the terminal block and tighten the terminal screws.

WARNING: Ensure the AC power source is disconnected before attempting to hardwire it to the unit.

2.5 PV Connection

CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.

WARNING: Use appropriate cable for PV module connection to reduce risk of injury.

Suggested Cable Requirement for PV Module Connection:

Model Wire Size Torque Value (max)
1.0KW 12V 1x12AWG 2 Nm

PV Module Selection Considerations:

  • Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter (150Vdc).
  • Open circuit Voltage (Voc) of PV modules should be higher than the minimum battery voltage.

PV Array MPPT Voltage Range: 20-150Vdc

PV Module Connection Steps:

  1. Remove 10 mm of insulation sleeve for positive and negative conductors.
  2. Attach bootlace ferrules to the ends of positive and negative wires using a proper crimping tool.
  3. Check correct polarity of wire connection from PV modules and PV input connectors. Connect positive pole (+) to positive (+) and negative pole (-) to negative (-).

2.6 Final Assembly

After connecting all wirings (battery, AC input/output, PV), replace the bottom cover by screwing in the four screws.

3. Operating

3.1 Power ON/OFF

Once the unit is properly installed and batteries are connected, press the On/Off switch (located on the button of the case) to turn on the unit.

3.2 Operation and Display Panel

The operation and display panel is located on the front of the inverter. It includes three indicators, four function keys, and an LCD display to show operating status and input/output power information.

Inverter Product Overview with Labeled Parts
Detailed view of the inverter with labeled components: 1. LCD Display, 2. Status Indicator, 3. Charging Indicator, 4. Fault Indicator, 5. Function Buttons, 6. Power On/Off Switch, 7. AC Input, 8. AC Output, 9. PV Input, 10. Battery Input, 11. Circuit Breaker, 12. Output Receptacles.

3.3 LCD Display Icons and Indicators

The LCD display provides visual feedback on the inverter's status. The LED indicators and their meanings are:

Indicator Color State Message
AC/INV Green Solid On Output is powered by utility in Line mode.
Flashing Output is powered by battery or PV in battery mode.
CHG Green Solid On Battery is fully charged.
Flashing Battery is charging.
FAULT Red Solid On Fault occurs in the inverter.
Flashing Warning condition occurs in the inverter.

3.4 LCD Setting Programs

To enter setting mode, press and hold the ENTER button for 3 seconds. Use the "UP" or "DOWN" buttons to select programs, and "ENTER" to confirm or "ESC" to exit.

Key settings include:

  • Program 00: Exit Setting Mode (Options: Escape, One-button restore setting options)
  • Program 01: Output Source Priority (Options: Utility first, Solar first, SBU priority, MKS priority)
  • Program 02: Maximum Charging Current (Configures total charging current for solar and utility chargers, max 80A MPPT)
  • Program 03: AC Input Voltage Range (Options: Appliances (90-280VAC), UPS (170-280VAC))
  • Program 05: Battery Type (Options: AGM, Flooded, User-Defined)
  • Program 06: Auto Restart When Overload Occurs (Options: Restart disable, Restart enable)
  • Program 07: Auto Restart When Over Temperature Occurs (Options: Restart disable, Restart enable)
  • Program 09: Output Frequency (Options: 50Hz, 60Hz)
  • Program 10: Output Voltage (Options: 220V, 230V, 240V)
  • Program 11: Maximum Utility Charging Current (Max 40A)
  • Program 12: Setting Voltage Point Back to Utility Source (When selecting "MKS priority")
  • Program 13: Setting Voltage Point Back to Battery Mode (When selecting "MKS priority")
  • Program 14: Maximum Battery Discharge Current (When selecting "SBU priority", max 40A)
  • Program 25: Record Fault Code (Options: Record enable, Record disable)
  • Program 26: Bulk Charging Voltage (C.V voltage) (Default 14.1V for 12V system)
  • Program 27: Floating Charging Voltage (Default 13.5V for 12V system)
  • Program 29: Low DC Cut-off Voltage (Default 10.0V for 12V system)
  • Program 30: Battery Equalization (Options: Battery equalization, Battery equalization disable)
  • Program 31: Battery Equalization Voltage (Default 14.6V for 12V system)
  • Program 33: Battery Equalized Time (Default 60min)
  • Program 34: Battery Equalized Timeout (Default 120min)
  • Program 35: Equalization Interval (Default 30 days)
  • Program 36: Equalization Activated Immediately (Options: Enable, Disable)

4. Maintenance

4.1 Clearance and Maintenance for Anti-Dust Kit (Optional)

The inverter comes with an anti-dust kit installed from the factory. This kit helps prevent dust from entering the inverter and enhances product reliability in harsh environments. The inverter automatically detects this kit and adjusts its internal thermal sensor for temperature regulation.

Maintenance Steps:

  1. Remove the screws securing the dustproof case.
  2. Carefully remove the dustproof case and take out the air filter foam.
  3. Clean the air filter foam and the dustproof case.
  4. After cleaning, re-assemble the dust-kit back onto the inverter.

NOTICE: The anti-dust kit should be cleaned from dust every one month.

5. Troubleshooting

This section provides information on fault codes and warning indicators to help diagnose and resolve common issues.

5.1 Fault Reference Code

Fault Code Fault Event Icon on
01 Fan is locked when inverter is off. 01
02 Over temperature 02
03 Battery voltage is too high 03
04 Battery voltage is too low 04
05 Output short circuited or over temperature is detected by internal converter components. 05
06 Output voltage is too high. 06
07 Overload time out 07
08 Bus voltage is too high 08
09 Bus soft start failed 09
51 Over current or surge 51
52 Bus voltage is too low 52
53 Inverter soft start failed 53
55 Over DC voltage in AC output 55
57 Current sensor failed 57
58 Output voltage is too low 58
59 PV voltage is over limitation 59

5.2 Warning Indicator

Warning Code Warning Event Audible Alarm Icon Flashing
01 Fan is locked when inverter is on. Beep three times every second 01
03 Battery is over-charged Beep once every second 03
04 Low battery Beep once every second 04
07 Overload Beep once every 0.5 second 07
10 Output power derating Beep twice every 3 seconds 10
15 PV energy is low. Beep twice every 3 seconds 15
E9 Battery equalization None E9

If errors persist after following the troubleshooting table, please contact your local dealer or service center for maintenance. Only qualified service personnel should service this device.

6. Specifications

Detailed technical specifications for the PowMr 1KW EU Hybrid Solar Inverter (POW-HVM1K-12V).

6.1 Line Mode Specifications

Parameter 1.0KW-12V
Input Voltage Waveform Sinusoidal (utility or generator)
Nominal Input Voltage 230Vac
Low Loss Voltage (UPS) 170Vac±10V
Low Loss Voltage (Appliances) 90Vac±10V
Low Loss Return Voltage (UPS) 180Vac±10V
Low Loss Return Voltage (Appliances) 100Vac±10V
High Loss Voltage 280Vac±10V
High Loss Return Voltage 270Vac±10V
Max AC Input Voltage 300Vac
Nominal Input Frequency 50Hz/60Hz (Auto detection)
Low Loss Frequency 40±1Hz
Low Loss Return Frequency 42±1Hz
High Loss Frequency 65±1Hz
High Loss Return Frequency 63±1Hz
Output Short Circuit Protection Circuit Breaker
Efficiency (Line Mode) >95% (Rated R load, battery full charged)
Transfer Time 10ms

6.2 Inverter Mode Specifications

Parameter 1.0KW-12V
Rated Output Power 1000VA/1000W
Output Voltage Waveform Pure Sine Wave
Output Voltage Regulation 230Vac±5%
Output Frequency 50Hz
Peak Efficiency 94%
Overload Protection 3s @ >150% load; 5s @ 100% ~ 150% load
Surge Capacity 2 * rated power for 5 seconds
Nominal DC Input Voltage 12Vdc
Cold Start Voltage 11.5Vdc
Low DC Warning Voltage (<50% load) 11.25Vdc
Low DC Warning Voltage (≥50% load) 11.0Vdc
Low DC Warning Return Voltage (<50% load) 11.75Vdc
Low DC Warning Return Voltage (≥50% load) 11.5Vdc
Low DC Cut-off Voltage (<50% load) 10.75Vdc
Low DC Cut-off Voltage (≥50% load) 10.5Vdc
High DC Recovery Voltage 15.5Vdc
High DC Cut-off Voltage 16.0Vdc
No Load Power Consumption <28W

6.3 Charge Mode Specifications

Parameter 1.0KW-12V
Charging Algorithm 3-Step
AC Charging Current (Max) 40Amp (@Vin=230Vac)
Bulk Charging Voltage (Flooded Battery) 14.6V
Bulk Charging Voltage (AGM/Gel Battery) 14.1V
Floating Charging Voltage 13.5Vdc
Max. PV Array Power 600W
PV Array MPPT Voltage Range 20~150Vdc
Max. PV Array Open Circuit Voltage 150Vdc
Max Solar Charging Current 40Amp
Max (AC+Solar) Charging Current 80Amp

6.4 General Specifications

Parameter 1.0KW-12V
Safety Certification CE
Operating Temperature Range -10°C to 50°C
Storage Temperature -15°C ~ 60°C
Humidity 5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm 286x240x91
Net Weight, kg 3.2 kg

For a complete list of specifications, please refer to the official user manual PDF: PowMr Solar Inverter Charger User Manual (PDF)

7. Warranty and Support

For technical support, warranty claims, or service, please contact PowMr directly using the information below:

  • Tel/Fax: +86755-28219903
  • Email: support@powmr.com
  • Website: www.powmr.com
  • Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China

8. User Tips

Based on user feedback and common questions, here are some helpful tips for using your PowMr Hybrid Solar Inverter:

  • Fan Noise: Some users have noted the fan can be loud and run continuously. Ensure the inverter is installed in a well-ventilated area, and consider its placement if noise is a concern.
  • Idle Power Consumption: Monitor the inverter's idle power consumption. While specifications indicate <28W, some users have observed higher idle draw (e.g., 60W). This is important for small setups where every watt counts.
  • Load Management: The inverter is rated for 1000W. Exceeding this limit, even temporarily (e.g., 900W), may trigger warning beeps or overload protection. Always ensure your connected appliances do not exceed the inverter's rated power.
  • Common Applications: This inverter is suitable for powering essential home appliances like refrigerators, desk lamps, and charging laptops, making it ideal for off-grid or backup power solutions.